HAMPTON GC60-2 Freestanding Cast Iron Pellet Stove Instruction Manual
- June 12, 2024
- HAMPTON
Table of Contents
GC60-2 Freestanding Cast Iron Pellet Stove
Product Information:
The Hampton GC60-2 Cast Pellet Stove is a freestanding cast iron
pellet stove designed to provide heat in a room. It is important to
read the entire manual before installation and use to ensure proper
usage and avoid any potential risks. The stove is manufactured by
FPI Fireplace Products International, Ltd., located in Delta, BC,
Canada.
The stove has been tested and certified for safety. Improper
installation, adjustment, alteration, service, or maintenance can
cause injury, property damage, or loss of life. It is recommended
to consult an authorized installer or service agency for
installation and service.
It is essential to follow the installation instructions provided
in the manual and consult with local building and fire officials or
authorities to comply with restrictions and inspection requirements
in your area. Failure to install the stove correctly may result in
a house fire.
Fire extinguishers should be available in a central location
known to all household members. Smoke detectors and carbon monoxide
detectors should be installed and maintained in the room where the
stove is placed. In case of an alarm, address the cause of the
alarm but do not deactivate the detectors. You may choose to
relocate the smoke detection device within the room but do not
remove them from the room.
This wood heater requires periodic inspection and repair to
ensure proper operation. It is against federal regulations to
operate the wood heater in a manner inconsistent with the
instructions provided in the manual. The manufacturer has set a
minimum low burn rate that should not be altered.
Product Usage Instructions:
-
Read the entire user manual and technical manual before
installation and use. -
Consult with building or fire officials to understand
restrictions and installation inspection requirements in your
area. -
Ensure the stove is properly installed according to the
provided instructions. -
Contact an authorized installer or service agency for
installation and service. -
Keep a fire extinguisher in a central location known to all
household members. -
Install and maintain smoke detectors and carbon monoxide
detectors in the room containing the stove. -
If the alarm sounds, address the cause but do not deactivate
the detectors. -
If needed, relocate the smoke detection device within the room
but do not remove them from the room. -
Periodically inspect and repair the wood heater for proper
operation. -
Do not operate the wood heater in a manner inconsistent with
the instructions provided in the manual. -
Do not alter the manufacturer’s set minimum low burn rate.
Greenfire® GC60-2
TECHNICAL MANUAL
Freestanding Cast Iron Pellet Stove
French Manual: https://bit.ly/3bzMqj0 Manuel en Français : https://bit.ly/3bzMqj0
PLEASE READ THIS ENTIRE MANUAL BEFORE INSTALLATION AND USE OF THIS PELLET- BURNING ROOM HEATER. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE, BODILY INJURY OR EVEN DEATH.
Contact your building or fire officials about restrictions and installation inspection requirements in your area.
WARNING:
FOR YOUR SAFETY:
Do not store or use gasoline or other flammable Improperinstallation,adjustment,alteration,service vapoursandliquidsinthevicinityofthisoranyother or maintenance can cause injury, property damage, appliance. or loss of life. Refer to this manual. For assistance or
additional information consult an authorized Installation and service must be performed by an
installer or service agency.
authorized installer or service agency.
Tested by:
IMPORTANT: SAVE THESE INSTRUCTIONS
920-585
FPI FIREPLACE PRODUCTS INTERNATIONAL, LTD. 6988 Venture St., Delta, BC, Canada V4G 1H4
09.22.22
Safety Note: If this stove is not properly installed, a house fire may result.
For your safety, follow the installation instructions, contact local building,
fire officials, or authority having jurisdiction about restrictions and
installation inspection requirements in your area.
The authority having jurisdiction should be consulted before installation to
determine the need to obtain a permit.
Emissions and Efficiency: This manual describes the installation and operation
of the Regency GC60-2 pellet heater. This heater is U.S. ENVIRONMENTAL
PROTECTION AGENCY certified to comply with 2020 particulate emission
standards. Under specific test condition this heater has been shown to deliver
heat at rates raging from: 7,817 – 38,437 Btu/hr Efficiency: 78% HHV (PFS
TECO 21-703) When using optional top vent adaptor kit (GC60-920) and 4” to
6” flue adaptor (4PVP-X6). See instruction manual for further information.
FIRE EXTINGUISHER AND SMOKE DETECTION: All home with a pellet burning stove
should have at least one fire extinguisher in a central location known to all
the household. Smoke detectors and carbon monoxide detectors should be
installed maintained in the room containing the stove. If it sounds the alarm,
correct the cause but do not deactivate. You may choose to relocate the smoke
the smoke detection device within the room; DO NOT REMOVE THE SMOKE OR CARBON
MONOXIDE DETECTORS FROM THE ROOM.
WARNING: This wood heater needs periodic inspection and repair for proper
operation. It is against federal regulation to operate this wood heater in a
manner inconsistent with operating instructions in this manual. WARNING: This
wood heater has a manufacturer set minimum low burn rate that must not be
altered. It is against federal regulations to alter this setting or other wise
operate this wood heater in a manner inconsistent with operating instructions
in this manual.
2
Hampton GC60-2 Cast Pellet Stove Technical Manual
Table of Contents
Safety Warnings & Recommendations………………………………………………………………………………….4
Specifications…………………………………………………………………………………………………………………6
Rating Label & Location………………………………………………………………………………………………7
Dimensions………………………………………………………………………………………………………………7
Specifications……………………………………………………………………………………………………………7 Installation
……………………………………………………………………………………………………………………8 Deciding Where to Locate your
Pellet Appliance………………………………………………………………..8 Removing Pellet Stove From
Pallet…………………………………………………………………………………8 Clearances to
Combustibles………………………………………………………………………………………….9 Leveling Leg
Adjustment……………………………………………………………………………………………..9 Thermostat
Installation………………………………………………………………………………………………9 Vent Termination
Requirements…………………………………………………………………………………….10 Outside Fresh Air
Connection………………………………………………………………………………………11 Exhaust And Fresh Air Intake
Locations…………………………………………………………………………11 Mobile Home
Installation……………………………………………………………………………………………12 Corner Through Wall
Installation………………………………………………………………………………….12 Horizontal Exhaust Through Wall
Installation………………………………………………………………….13 Recommended – Through Wall With
Vertical Rise and Horizontal Termination Installation………….15 Through Concrete
Wall With Vertical Rise Installations………………………………………………………15 Outside Vertical
Installations……………………………………………………………………………………….16 Inside Vertical
Installations…………………………………………………………………………………………17 Hearth Mount
Installation…………………………………………………………………………………………..18 Top Vent Adaptor Kit & 4”
(102 mm) to 6” (152 mm) Flue Adaptor (Approved for Vertical Installations
only)…………………………………………………………………………………………………….19 Slider/Damper Set-
Up………………………………………………………………………………………………..20 Troubleshooting
……………………………………………………………………………………………………………21 Wiring
Diagram……………………………………………………………………………………………………………..24 Parts
List……………………………………………………………………………………………………………………..25 Parts Diagram –
Components……………………………………………………………………………………………27 Parts Diagram –
Cast………………………………………………………………………………………………………28
Warranty……………………………………………………………………………………………………………………..30
Hampton GC60-2 Cast Pellet Stove Technical Manual
3
Safety Warnings & Recommendations
This manual is designed for the technician in conjunction with the owner’s manual.
Please read this entire Technical Manual before installing or operating your
Hampton Pellet Stove. Failure to follow these instructions may result in
property damage, bodily injury or even death. Any unauthorized modification of
the appliance or use of replacement parts not recommended by the manufacturer
is prohibited. All national and local regulations shall be complied with when
operating this appliance.
Caution: Do not connect to any air distribution duct or system.
Warning: Never place wood, paper, furniture, drapes or other combustible
materials within 48″ (122cm) of the front of the unit, 12″ (30.5cm) from each
side, and 4″ (10cm) from the back of the unit. Do not let children or pets
touch it when it is hot.
To prevent the possibility of a fire, ensure that the appliance is properly
installed by adhering to the installation instructions. An Hampton dealer will
be happy to assist you in obtaining information with regards to your local
building codes and installation restrictions.
FIRE EXTINGUISHER AND SMOKE DETECTION: All homes with a pellet burning stove
should have at least one fire extinguisher in a central location known to all
in the household. Smoke detectors should be installed and maintained in the
room containing the stove. If it sounds the alarm, correct the cause but do
not deactivate. You may choose to relocate the smoke detection devise within
the room; DO NOT REMOVE THE SMOKE DETECTOR FROM THE ROOM.
CHIMNEY OR RUN AWAY FIRE (SOOT/CREASOTE): Call local fire department (or dial
911). Close the draft fully. Extinguish the fire in the burn pot liner with a
cup of water and close the door. Examine the flue pipes, chimney, attic, and
roof of the house, to see if any part has become hot enough to catch fire. If
necessary, spray with fire extinguisher or water from the garden hose.
IMPORTANT: Do not operate the stove again until you are certain the chimney
and its lining have not been damaged. Check daily for creasote build-up until
experience shows how often you need to clean to be safe.
OPERATION: The door and ash drawer must be kept closed when the unit is in
operation to prevent fume spillage and for proper and safe operation of the
pellet stove. Also ensure all gaskets on the door are checked and replaced
when necessary. Unit hot while in operation. Keep children, clothing and
furniture away. Contact may cause skin burns.
CAUTION: When operating during adverse weather, if the unit exhibits dramatic
changes in combustion stop using the unit immediately.
FUEL: This stove is designed and approved to only burn wood pellets of any
quality, corn, wheat, barley, and grass. Dirty fuel will adversely affect the
operation and performance of the unit and may void the warranty. Check with
your dealer for fuel recommendations. THE USE OF CORDWOOD IS PROHIBITED BY
LAW. Do not burn garbage or flammable fluids such as gasoline, naptha or
engine oil.
SOOT/CREASOTE: Operation of the stove with insufficient combustion air will
result in the formation of soot/ creasote which will collect on the glass, the
heat exchanger, the exhaust vent system, and may stain the outside of the
house. Frequently check your stove and and adjust the combustion air trim
and/or if necessary adjust the slider/damper as needed to ensure proper
combustion. See: “Slider/damper Setting”.
CLEANING: There will be some build up of fly ash and small amounts of creosote
in the exhaust. This will vary due to the ash content of the fuel used and the
operation of the stove. It is advisable to inspect and clean the exhaust vent
semi-annually or every two tons of pellets. The appliance, flue gas connector
and the chimney flue require regular cleaning. Check them for blockage prior
to re-lighting after a prolonged shut down period. If a significant layer of
creasote has accumulated in the flue (3mm or more) it should be removed to
reduce the risk of a chimney fire.
ASHES: Disposed ashes should be placed in a metal container with a tight
fitting lid. The closed container of ashes should be on a non-combustible
surface, well away from all combustible materials pending final disposal. If
the ashes are disposed of by burial in soil or otherwise locally dispensed,
they should be retained in the closed container until all cinders have
thoroughly cooled.
4
Hampton GC60-2 Cast Pellet Stove Technical Manual
Safety Warnings & Recommendations
ELECTRICAL: The use of a surge protected power bar is highly recommended. The
unit must be grounded. The grounded electrical cord should be connected to a
standard 110-120 volts (4.2 Amps), 60 hertz electrical outlet and also must be
accessible. If this power cord should become damaged, a replacement power cord
must be purchased from the manufacturer or a qualified Hampton dealer. Be
careful that the electrical cord is not trapped under the appliance and that
it is clear of any hot surfaces or sharp edges. This unit’s maximum power
requirement is 504 watts.
When installing the stove in a mobile home, it must be electrically grounded
to the steel chassis of the home and bolted to the floor.
GLASS: Do not abuse the glass by striking or slamming the door. Do not attempt
to operate the stove with broken glass. The stove uses ceramic glass.
Replacement glass must be purchased from an Hampton dealer. Do not attempt to
open the door and clean the glass while the unit is in operation or if glass
is hot. To clean the glass, use a soft cotton cloth and mild window cleaner,
gas or wood stove glass cleaner, or take a damp paper towel and dip into the
fly ash. This is a very mild abrasive and will not damage the glass. Do not
use polishing compounds or abrasive cleaners.
KEEP ASH PAN FREE OF RAW FUEL. DO NOT PLACE UNBURNED OR NEW PELLET FUEL IN ASH
PAN. A fire in the ash pan may occur.
INSTALLATION: Contact your local building or fire official to obtain a permit
and any information on installation restrictions and inspection requirements
for your area.
Be sure to maintain the structural integrity of your home when passing a vent
through walls, ceilings, or roofs, and all construction meets local building
codes. It is recommended that the unit be secured into its position in order
to avoid any displacement. This appliance must be installed on a floor with an
adequate load bearing capacity, if existing construction doesn’t meet load
capacity, suitable measures (e.g. load distributing plate) must be taken to
achieve it.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
FRESH AIR: This unit uses large quantities of air for combustion; outside
Fresh Air connection is strongly recommended. Fresh Air must be connected to
all units installed in Mobile and “Air Tight Homes” (R2000) or where required
by local codes.
Consider all large air moving devices or any other appliance which may compete
for fresh air when installing the unit and provide room air accordingly. NOTE:
Extractor fans when operating in the same room or space as the appliance may
cause problems. Limited air for combustion may result in poor performance,
smoking and other side effects of poor combustion.
The stove’s exhaust system works with negative combustion chamber pressure and
a slightly positive chimney pressure. It is very important to ensure that the
exhaust system be sealed and airtight. The ash pan and viewing door must be
locked securely for proper and safe operation of the pellet stove.
Do not burn with insufficient combustion air. A periodic check is recommended
to ensure proper combustion air is admitted to the combustion chamber. Setting
the proper combustion air is achieved by adjusting the slider damper located
on the left side of the stove.
Soot or creosote may accumulate when the stove is operated under incorrect
conditions such as a rich burn (black tipped, lazy orange flames).
If you have any questions with regards to your stove or the above-mentioned
information, please feel free to contact your local dealer for further
clarification and comments.
SINCE REGENCY FIREPLACE PRODUCTS LTD. HAS NO CONTROL OVER THE INSTALLATION OF
YOUR STOVE,REGENCY FIREPLACE PRODUCTS LTD. GRANTS NO WARRANTY IMPLIED OR
STATED FOR THE INSTALLATION OR MAINTENANCE OF YOUR STOVE. THEREFORE, REGENCY
FIREPLACE PRODUCTS LTD. ASSUMES NO RESPONSIBILITY FOR ANY CONSEQUENTIAL
DAMAGE(S). SAVE THIS INSTRUCTION MANUAL FOR FUTURE REFERENCE.
Hampton GC60-2 Cast Pellet Stove Technical Manual
5
Hampton GC60-2 Cast Pellet Stove Technical Manual
To Start Stove: Select fuel type mode; PREMIUM PELLETS for superior quality pellet fuel,
584
DO NOT REMOVE THIS LABEL / NE RETIREZ PAS CETTE ÉTIQUETTE REGULAR PELLETS for all grades of wood pellets & MULTIFUEL for all other fuels. Press the
ON / OFF button. A small handful of pellets in the burn pot liner will speed up ignition.
Serial No. / No. De Serié:
Installed as a freestanding stove – conventional or mobile home – To Operate Stove: MANUAL MODE: When a fire has been established the stove settings are adjustable. /
Model / Modèle: GC60-2
Minimum Clearances to Combustible Material / Installé comme poêle HIGH/LOW MODE: (Requires a thermostat) When the thermostat calls for heat the stove settings are
autoportant – conventionnel ou mobile – dégagement minimum par
adjustable. When the thermostat contacts open, the HEAT LEVEL and Fans will drop down to the LOW setting
Listed Room Heater, Pelletized Fuel Type (Appareil de chauffage à granules certifié)
rapport aux matériaux combustibles
until the thermostat contacts close again. / AUTO/OFF MODE: (Requires a thermostat) When the thermostat
Input rating when using (Le chauffage d’énergie avec):
contacts close, the unit will light automatically. Once up to temperature the stove settings are adjustable. When
Wood Pellets/Corn (Boulettes de bois/lMaïs) – 55,000BTU (16.1KW*hr)
A = Sidewall to Unit / Du mur de côté à l’appareil: 9 in / 230mm the thermostat contacts open, the stove will drop down to the LOW settings for 30 minutes. If within the 30 min
Wheat/Barley (Blé/l’Orge) – 53,000BTU (15.5KW*hr)
B = Backwall to Unit / Du mur de derrière à l’appareil: 3 in. / 76 mm the thermostat contacts close, the HEAT LEVEL will return to previous MANUAL setting or if the thermostat
Suitable For Mobile Home Installation (Accepté pour l’installation dans une maison mobile, test)
C = Corner to Unit / Du coin à l’appareil:
3 in. / 76 mm contacts remain open the stove begin its shutdown routine and it will restart when the thermostat closes.
Solid Fuel Room Heaters / Identifie Comme Un Foyer A Combustible Solide: ULC S627 & ORD 1482
D = The unit must be installed with a minimum of 6″(152 mm) of
This pellet appliance has been tested and listed for use in manufactured homes in accordance with Oregon floor protection in front of and to the sides of the door opening.
To Turn Off Stove: MANUAL and HI / LOW mode: Press the ON / OFF button AUTO / OFF mode: Turn the thermostat down or off.
Administrative rules 814-23-900 through 814-23-909.Install and use only in accordance with the The pedestal base can be manufacturer’s installation and operating instructions. Contact local building or fire officials about adjusted to the forward position
Backwall
Pour démarrer le poêle: Choisir le mode pour le carburant ; PREMIUM PELLETS pour le carburant de boulette de qualité de superior, REGULAR PELLET pour tous degrés de boulettes de bois & MULTIFUEL pour tous
restrictions and installation inspection in your area. Do not connect this unit to a chimney flue serving to satisfy this requirement. The
another appliance. See local building code and manufacturer’s instructions for precautions required for unit can be installed on a hard,
passing a chimney through a combustible wall or ceiling. ELECTRICAL RATING: 120 Volts, 60Hz, 4.2 stable combustible surface. (D –
Amps. Route Cord Away From Heater.
L’unité doit être installée avec
For use with pelletized solid fuels – wood, corn, wheat, & barley only. Operate only with viewing door and protection de plancher devant et
A
ash removal door closed. Only replace glass with ceramic glass. Components required for installation: a au bord de la porte ouvrant
4inch (100 mm) listed PL or L vent, complete with components.
avec au moins 6″ (152 mm). La base de piédestal peut être
autres carburants. Appuyer sur le bouton “ON/OFF”. Une petite poignée de boulettes dans le pot de brûlure
B
hâtera l’allumage.
C
Pour faire fonctionner le poêle : MODE MANUEL : Lorsque le feu est bien établi, les réglages peuvent être
ajustés. / MODE “HIGH/LOW” : (Nécessite un thermostat) Lorsque le thermostat requière de la chaleur, les
réglages peuvent être ajustés. Lorsque les contacts du thermostat ouvrent, le réglage du niveau de chaleur et
les ventilateurs s’ajusteront au réglage ” bas ” jusqu’à ce que les contacts du thermostat se referment. / MODE
“AUTO/OFF” : (Nécessite un thermostat) Lorsque les contacts du thermostat ferment, le poêle s’allumera
automatiquement. Lorsque la température adéquate est atteinte, les réglages peuvent être ajustés. Lorsque les
Cet appareil a été testé et certifié pour utilisation dans les maisons mobiles en accord avec les “Règles adaptée à la position à Administratives de l’Oregon 814-23-900 à 814-23-909”. Installez et utilisez cet appareil seulement selon les satisfaire cette condition.
contacts du thermostat ouvrent, le poêle s’ajustera aux réglages “LOW” pendant 30 minutes. Si les contacts du
D
thermostat sont fermés pendant ces 30 minutes, le réglage de niveau de chaleur retournera en réglages
instructions d’installation et d’opération du fabricant. Contactez les autorités locales de votre quartier L’unité peut être installée sur un
Floor Protection
“MANUEL” ou si les contacts du thermostat restent ouverts, le poêle entamera le processus d’arrêt et il vouloir
concernant les restrictions et les inspections d’installation. Consultez les codes de bâtiment locaux et les dur, la surface combustible
redémarrer lorsque les contacts du thermostat refermer.
instructions du fabricant pour les précautions à prendre lorsque une cheminée doit être installée au travers stable.)
Pour éteindre le poêle : MODE MANUEL ET ” HIGH/LOW ” : Appuyer sur le bouton “ON/OFF”.
un mur ou un plafond combustible. CLASSEMENT ÉLECTRIQUE : 120 Volts, 60 Hz, 4.2 Amps. Placez le
MODE “AUTO / OFF” : Régler le thermostat à la baisse ou éteignez le.
This wood heater needs periodic inspection and repair for proper operation.
Consult the owner’s manual for further information. It is against federal
regulations to operate this wood heater in a manner inconsistent with the
operating instructions in the owner’s manual. U.S.
to comply with 2020 particulate emission
heater has been shown to have a particulate emission level of 1.9 g/hr.
Ce poêle à granulés besoins inspection périodique et la réparation pour un
fonctionnement correct. Consultez le manuel d’owners pour plus d’informations. Il est contre les règlements manière incompatible avec les instructions de fonctionnement dans le manuel d’owner
s. Ce poêle répond aux normes limites d’émission de l’Environmental
Protection Agency des États-Unis
poêle a été montré pour avoir un niveau d’émission de particules de 1.9 g / h.
Safety Decal
This is a copy of the safety label that accompanies each GC60-2. We have
printed a copy of the contents here for your reference. On the GC60-2 the
safety label is located on the underside of the hopper lid. See next page for
location.
Sidewall
câble électrique loin de la chaleur. Utilisation avec granules – le bois, le maïs, le blé, & l’orge seulement. Utiliser seulement lorsque les portes avants et la porte du réceptacle de cendre sont fermées. Si une ou
CAUTION:
ATTENTION:
des vitres devaient être remplacées, utilisez seulement du verre céramique. Les composantes requises pour l’installation sont un évent PL ou L certifié de 4in/100mm avec ses composantes.
DATE OF MANUFACTURE / DATE DE FABRICATION:
J F M AMJ J A S O N D
2022 2023 2024
HOT WHILE IN OPERATION. DO NOT TOUCH. KEEP CHILDREN,
CLOTHING AND FURNITURE AWAY. CONTACT MAY CAUSE BURNS. SEE NAMEPLATE AND
INSTRUCTIONS.
L’APPAREIL EST CHAUD LORSQU’IL FONCTIONNE. NE PAS TOUCHER. GARDER LES ENFANTS, LES VÊTEMENTS ET LES MEUBLES ÉLOIGNÉS DE L’APPAREIL EN MARCHE. UN CONTACT AVEC CELUI-CI POURRAIT RÉSULTER EN DES BRÛLURES. VEUILLEZ VOIR LA PLAQUE DU FABRICANT ET LES INSTRUCTIONS.
PFS TECO
C#4001609
REPORT
Certified for use in Canda & USA. Refer to
21-703
MANUFACTURED FOR /
Intertek’s Directory of Building Products for detailed information / Certifié pour installation au
FABRIQUE POUR:
Canada et aux Etats-Unis.Reportez-vous au répertoire des produits de construction d’Intertek
FPI Fireplace Products International Ltd.
pour des informations détaillées.
DELTA, BC CANADA GC60-00
920-570
6
Specifications
rating label & location:
Lift the cast top off the stove and place to one side. On the back of the
pellet stove there will be two flat head screws that hold the hopper lid shut.
Remove both screws. Once both screws have been removed open the hopper lid.
The serial number will be on the underside of the hopper lid as illustrated
below.
Hampton GC60-2 Cast Pellet Stove Technical Manual
7
dimenSionS: 4″ Exhaust
Specifications
23″ (584mm)
3″ Fresh Air Intake
28-1/2″ (724mm)
29-1/2″ (749mm)
28-12″ (724mm)
31-1/2″ (800mm)
4″ Exhaust
SpecificationS:
29″ (737mm)
18-3/4″ (476mm)
Figure 2: Dimensions of GC60-2.
Input rating when using: Wood Pellets/Corn – 55,000BTU (16.1KW·hr) & Wheat/Barley – 53,000BTU (15.5KW·hr).
Table 1: GC60-2 Specifications
Description
Fuel type
Residential Pellet Heater
6mm (¼”) dia. Pellets – wood, corn, wheat, & barley*
Voltage 110 – 120 V
Current 4.2 Amps
Max Power 504 Watts
Frequency 60 Hz
Hopper Capacity up to 60 lb (36.3 Kg)
Consumption on Low 1.5 lb/hr (0.68 Kg/hr)*
Testing Standard
Weight (with full hopper)
Consumption on High
ASTM 1509-04
504 lb (229 Kg)
6.5 lb/hr (2.95 Kg/hr)*
*Note: Consumption will vary with the type and quality of pellets / fuel used.
8
Hampton GC60-2 Cast Pellet Stove Technical Manual
Installation
deciding Where to locate your pellet appliance:
1. Do not install the stove in a bedroom or room where people sleep in. 2.
Locate the stove in a large and open room that is centrally located in the
house. This will optimize
heat circulation. 3. Check clearances to combustibles and for the least amount
of interference to house framing, plumbing,
wiring, etc. 4. You can vent the stove with approved pipe through an exterior
wall behind the unit or pass it through
the ceiling and roof. The stove can connect to an existing masonry or metal
chimney (must be lined if the chimney is over 6″ (15 cm) diameter, or over 28
inches² (180 cm²) cross sectional area). 5. This unit must not be installed
directly onto carpet. If it is to be installed on a carpeted area, a solid
surface (metal or approved hearth pad) must be installed between the unit and
the carpet. 6. This unit uses large quantities of air for combustion; outside
Fresh Air connection is strongly recommended. Fresh Air must be connected to
all units installed in Mobile and “Air Tight Homes” (R2000) or where required
by local codes. 7. Do not obtain combustion air from an attic, garage or any
unventilated space. Combustion air may be obtained from a ventilated
crawlspace. 8. The power cord is 8 feet (2.43 m) long and may require a
grounded extension cord to reach the nearest electrical outlet.
removing pellet Stove from pallet:
REPLACE THESE SCREWS AFTER REMOVING FROM PALLET. (2 EACH SIDE)
1. Remove the two (2) screws that hold the brackets to the pallet on either
side of the unit.
2. Remove the two (2) 5/16″ hex head screws that hold the brackets to the
units.
Figure 3: Screws to take out to remove stove from pallet
Hampton GC60-2 Cast Pellet Stove Technical Manual
9
Installation
clearanceS to combuStibleS:
Back Wall
3″ (76mm)
Adjacent Wall
3″ (76mm)
Side Wall
9″ (229mm)
Figure 4: GC60-2 Clearance to Combustibles
These dimensions are minimum clearances but it is recommended that you ensure sufficient room for servicing, routine cleaning and maintenance.
Side wall to unit Back wall to unit Corner to unit Ceiling height
9 inches 3 inches 3 inches 60 inches
(229 mm) (76 mm) (76 mm) (152 mm)
Alcove Maximum Depth 36 inches (914 mm) Alcove Minimum Width 48 inches (1219 mm) Alcove Minimum Height 60 inches (1524 mm)
In the USA, the unit must be installed with a
minimum of 6″ (152 mm) of floor protection in front of and to the sides of the
door opening.
In Canada, the unit must be installed with a
minimum of 8″ (203 mm) of floor protection in front of and to the sides of the
door opening.
leveling leg adjuStment: The leveling legs should be adjusted for the unit to to sit level and not rock if installed on uneven flooring. 1. Turn levelling legs until they are at the required heights. 2. Tighten the nut to hold the leveling leg in position.
thermoStat inStallation:
Figure 5: Thermostat wire placement
1. Install the wall thermostat (millivolt rated thermostat recommended, or a
12/24 Volt rated thermostat set to millivolts) in a location that is not to
close too the unit but will effectively heat the desired area.
2. Connect the Thermostat using a 2 x 18 gauge wire from the unit to the
thermostat.
If the heat in the room becomes to great, the high limit switch may turn the
stove off and the switch will have to be manually reset. The switch is found
below the firebox top on the hopper’s right surface.
10
Hampton GC60-2 Cast Pellet Stove Technical Manual
Installation
vent termination requirementS:
IT IS RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER.
Table 2: Use in conjunction with Figure 6 for allowable exterior vent termination locations.
Letter A B
C
D E F G H
I J
K L
Minimum Clearance
Description
24 in (61 cm)
Above grass, top of plants, wood, or any other combustible materials.
48 in (122 cm)
Beside/below any door or window that may be opened. (18″ (46 cm) if outside fresh air installed.)
12 in (30 cm)
Above any door or window that may be opened. (9″ (23 cm) if outside fresh air installed.)
24 in (61 cm)
To any adjacent building, fences and protruding parts of the structure.
24 in (61 cm)
Below any eave or roof overhang
12 in (30 cm)
To outside corner.
12 in (30 cm)
To inside corner, combustible wall (vertical and horizontal terminations).
3 ft (91 cm) within a height of 15 ft (4.5 m) above the meter/regulator assembly
To each side of center line extended above natural gas or propane meter/ regulator assembly or mechanical vent.
3 ft (91 cm)
From any forced air intake of other appliance
12 in (30 cm)
Clearance to non-mechanical air supply inlet to building, or the combustion air inlet to any appliance.
24 in (61 cm)
Clearance above roof line for vertical terminations.
7 ft (2.13 m)
Clearance above paved sidewalk or paved driveway located on public property.
1. Do not terminate the vent in any enclosed or semi-enclosed areas such
G K
as a carport, garage,
attic, crawlspace, narrow
E
walkway, closely fenced area, under a sundeck
D
F
Opens
B
Opens
C
G
G
or porch, or any location that can build up a
B
A
I
Opens
L
concentration of fumes such as stairwells, covered
Termination Cap Air Supply Inlet
G Gas Meter
H
Restriction Zone
(Termination not allowed)
breezeway, etc. 2. Vent surfaces can become
Figure 6: Use in conjunction with Table 2 for allowable exterior vent termination locations.
hot enough to cause burns if touched by children. Non-combustible shielding or guards may be required.
3. Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe be installed outside when the appliance is vented directly through a wall, to create some natural draft to prevent the possibility of smoke or odor during appliance shut down or power failure. This will keep exhaust from causing a nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest and preferred venting method is to extend the vent through the roof vertically.
4. Distance from the bottom of the termination and grade is 12″ (30 cm) minimum. This is conditional upon the plants and nature of grade surface. The exhaust gases are hot enough to ignite grass, plants and shrubs located in the vicinity of termination. The grade surface must not be lawn.
5. If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior of the house might occur. Since these factors are beyond the control of Regency Fireplace Products, we grant no guarantee against such incidents.
6. Horizontal terminations must extend at least 12″ (30 cm) away from the building.
NOTE: Venting terminals shall not be recessed into walls or siding.
Hampton GC60-2 Cast Pellet Stove Technical Manual
11
Installation
outSide freSh air connection:
This Heater must have adequate air for proper combustion in the room that it is installed.
A Fresh-air intake is strongly recommended for all installations. Failure to install intake air may
result in improper combustion as well as the unit smoking during power failures.
The inlet to the intake must be below and a minimum of 12″ (30cm) away from
the unit exhaust outlet.
Outside fresh air is mandatory when installing this unit in airtight homes and
mobile homes.
Outside Wall
When connecting to an outside fresh air source, do not use plastic or combustible pipe. A 3″ minimum (76 mm) ID (inside diameter) steel, aluminum or copper pipe or ducting should be used. The inlet must have a screen installed. It is recommended, when you are installing a fresh air system, to keep the number of bends in the pipe to a minimum.
3″ ID (76 mm)
Optional Elbow
Figure 7: Outside Air Connection
exhauSt and freSh air intake locationS:
This unit uses a 4″ exhaust vent.
EXHAUST: Base of unit to center of flue
14-1/2″ (368 mm) Center of unit to center of flue
6-1/2″ (162 mm)
FRESH AIR INTAKE.
Base of unit to center of intake
11″
(279 mm)
Center of unit to center of intake
4-7/8″ (126 mm)
14-1/2″ 11″
9-1/4″
4-7/8″
6-1/2″
7-3/4″
Figure 8: GC60-2 Inlet and Outlet Location
12
Hampton GC60-2 Cast Pellet Stove Technical Manual
Installation
mobile home inStallation: Secure the heater to the floor using the four (4)
holes in the pedestal.
Ensure the unit is electrically grounded to the chassis of your
home (permanently).
Do not install in a room people sleep in.
Outside fresh air is mandatory. Secure outside air connections
directly to fresh air intake pipe
and secure with three (3) screws
evenly spaced.
All specified components must be used. Do not use any
components other than what’s
specified.
Optional Hearth Pad Flooring
Steel Frame
1/4″Lag Bolts Securely Fastened
Ground Wire Directly to Metal Chassis
Figure 9: Mobile home installation.
CAUTION: THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL AND
CEILING/ROOF MUST BE MAINTAINED.
corner through Wall inStallation:
Wall thimble manufactured by pellet vent manufacturer
3″Fresh Air Intake
3″ (76mm)
3″ (76mm)
Figure 10: Corner Installation.
Hampton GC60-2 Cast Pellet Stove Technical Manual
13
Installation
horizontal exhauSt through Wall inStallation:
Vent installation: install vent at clearances specified by the vent
manufacturer. A chimney connector shall not pass through an attic or roof
space, closet or similar concealed spaces, or a floor, or ceiling. Where
passage through a wall or partition of combustible construction is desired,
the installation must conform to CAN/CSA-B365 Installation Code for Solid-
Fuel-Burning Appliances and Equipment and with all local regulations,
including those referring to regional and national. Only use venting of L or
PL type or corn certified venting if corn will be burned as a fuel with an
inside diameter of 4 inches (100 mm). All joints in the exhaust venting system
must be fastened with at least three (3) screws. 1. Place the appliance 15″
(37.5 cm) away from the wall. If the stove will be installed on a hearth pad,
set the unit on it. 2. Locate the center of the exhaust pipe on the stove.
Extend that line to the wall. Once you have located
the center point on the wall, refer to pellet vent manufacturer installation
instructions for correct hole size and clearance to combustibles. 3. Install
the wall thimble as per the instructions written on the thimble. Maintain an
effective vapour barrier in accordance with local building codes. 4. Install a
length of vent pipe into the wall thimble. Try not to have joints inside the
thimble. The pipe should install easily into the thimble. 5. Connect the
exhaust vent pipe to the exhaust pipe on the stove. Seal the connection with
high temperature silicone. 6. Install the fresh air intake (see Outside Fresh
Air COnneCtiOn). 7. Push the stove straight back, leaving a minimum of 3″ (7.6
cm) clearance from the back of the stove to the wall. Refer to Vent
Manufacturers’ instructions if sealant is required.
GGCC606-02
REFER TO VENT MANUFACTURER’S INSTRUCTIONS FOR CLEARANCES AND SEALING
REQUIREMENTS.
4″(100mm) Exhaust
4″(100mm) Pellet Vent Pipe
3″(80mm) Intake 4″(100mm) Pellet Vent Wall Thimble Figure 11: Straight through wall Installation.
45 Elbow with Screen or Termination Cap
14
Hampton GC60-2 Cast Pellet Stove Technical Manual
Installation
8. The pipe must extend at least 12″ (30 cm) away from the building. If
necessary, bring another length of pipe to the outside of the home to connect
to the first section. Do not forget to place high temperature silicone around
the pipe that passes through the thimble if required by vent manufacturer.
9. Install a vertical pipe, or if all requirements for direct venting are
met, install vent termination. The stainless steel cap termination
manufactured by the vent manufacturer is recommended. However, when the vent
terminates several feet above ground level and there are no trees, plants,
etc. within several feet, a 45° elbow can be used as termination. The elbow
must be turned down to prevent rain from entering.
NOTE: · It is recommended that horizontal through wall installations have 3 to
5 feet (91 to 152 cm) of vertical
pipe in the system to help naturally draft the unit in the event of extreme
weather or a power outage. · Some horizontal through wall installations may
require a “T” and 3 to 5 feet (91 to 152 cm) of vertical
pipe outside the building to help draft the unit. This may be required if a
proper burn cannot be maintained, after the stove has been tested and the
airflow set. This is due to the back pressure in the exhaust caused by airflow
around the structure. · Follow vent manufacturer guidelines for installation,
clearance to combustibles, and sealing of venting. High temp Sealant must be
used when connecting vent pipe to the unit’s starter pipe. Improper seals at
the vent joints may cause combustion by-products to leak into the room where
installed – seal as required by vent manufacturer.
Wall Framing
Horizontal Frame for Thimble
Termination Cap or 45 Elbow with screen
4″ Vent Pipe Wall Thimble
Figure 12: Straight through Wall Installation – Side View
Hampton GC60-2 Cast Pellet Stove Technical Manual
15
Installation
recommended – through Wall With vertical riSe and horizontal termination
inStallation:
A 45° down elbow with a screen may be used in place of the termination cap (or stainless steel termination hood).
Elbow with Screen or Termination Cap
4″ 90
Wall framing
Clean out Tee Horizontal frame for thimble
4′ MAX
Wall Strap
Vertical section of 4″ vent pipe
Wall Strap
Wall Thimble Figure 13: Venting horizontally with rise.
through concrete Wall With vertical riSe inStallationS:
Installation to use if there is a concrete or retaining wall in line with
exhaust vent on pellet stove.
A 45° down elbow with a screen may be used in place of the termination cap (or
stainless steel termination hood).
The termination must be 12 inches (30 cm) from the outside wall and 12 inches
(30 cm) above the ground.
Horizontal frame for thimble
4″ 90 Elbow
Wall Thimble
4″ 45 Elbow with screen or Termination Cap
Vertical section of 4″ pipe
Wall Framing
Clean Out Tee
Concrete Wall Figure 14: Venting with concrete wall behind unit .
16
Hampton GC60-2 Cast Pellet Stove Technical Manual
Installation
outSide vertical inStallationS:
To accomplish an outside vertical pipe installation, follow the “hOrizOntAl
exhAust thrOugh WAll instAllAtiOns” section and then finish it by performing
the following (refer to Figure 15).
1. Install a tee with clean out on the outside of the house. 2. Install PL
vent upward from the tee. Make sure that you install support brackets to keep
the vent
straight and secure. All joints in the exhaust venting system must be fastened
with at least three (3) screws. 3. Install ceiling thimble and secure the
flashing as you go through the roof. 4. Ensure that the rain cap is a minimum
of 24″ (61 cm) above the roof.
Rain Cap
MIN 24″ (610mm)
3″MIN Clearance (75mm)
All around
Storm Collar Flashing
Wall Strap
Horizontal Frame for Thimble
4′ (1220mm) MAX
3″(76mm) MIN.
Clean Out Tee Wall Thimble
Figure 15: Outside Vertical Installation.
Hampton GC60-2 Cast Pellet Stove Technical Manual
17
Installation
inSide vertical inStallationS:
1. Place the unit on the hearth pad if a hearth pad is to be used (or on
solid material if installed on a carpeted surface) and space the unit in a
manner so when the pellet vent is installed vertically, it will meet the
minimum clearance from a combustible wall stated by the vent manufacturer.
2. Install the tee with clean out. 3. Install the pellet vent upward from
tee. When you reach the ceiling, make sure that the vent goes
through a ceiling fire stop. Keep attic insulation away from the vent pipe &
maintain an effective vapor barrier. All joints in the exhaust venting system
must be fastened with at least three (3) screws. Refer to vent manufacturer
for distance to combustibles & follow the vent manufacturer’s instructions on
sealing. 4. Finally, extend the pellet vent to go through the roof flashing.
5. Ensure that the rain cap is a minimum of 24″ (61 cm) above the roof. 6.
Install the fresh air system.
Rain Cap (ensure cap is at least 3ft (91cm) above the roof at the lowest point
Roof Flashing
Roof Rafter
Fire Stop with Support Collar
Ceiling Joist
2 ft (61 cm)
Vertical Vent Pipe
Clean Out Tee with Pipe Adapter
NOTE: All vent sections must maintain the clearances to combustibles set out
by the vent manufacturer.
Figure 16: Inside Vertical Installation.
18
Hampton GC60-2 Cast Pellet Stove Technical Manual
hearth mount inStallation:
Installation
Damper Removed or Fastened Open Mantel Minimum (8″) 200mm from top of stove
Clean-out tee
Min (6″) 150mm
Fresh-air intake should com from chimney. If holes
already exist fresh-air intake can be taken through back of the fireplace or
through the ash dump.
Masonry Fireplace
Floor Protection
Combustible Floor
Figure 17: Hearth Mount – Side View.
1. Lock fireplace damper in the open position.
2. Install flexible stainless steel liner or listed pellet vent to the top of
the chimney. All joints in the exhaust venting system must be fastened with at
least three (3) screws.
3. Install a sealing plate at the top of the chimney.
4. Connect a rain cap and flex adapter to the chimney liner/pipe.
5. Connect a clean-out tee or a 90° elbow to the liner/pipe.
6. Install tee onto stove.
Rain Cap
Seal Plate
Existing Masonary Flue Vent Pipe (single wall stainless flex pipe or PL vent)
Flexible Vent Connector (Use this 5 ft section of pipe to vent past fireplace
damper or smoke shelf)
Fireplace Damper Location Clean Out Tee Existing Fireplace
Hampton GC60-2 Cast Pellet Stove Technical Manual
Figure 18: Hearth Mount – Over View. 19
Top Vent Adaptor Kit & 4″ (102 mm) to 6″ (152 mm) Flue Adaptor (approved for
vertical installations only)
4PVP-X6
4” (102 mm) pipe lengths to class A chimney
GC60-920
*In order to achieve the maximum rated efficiency of 78% HHV purchase of a top vent adaptor kit (GC60-920) is required. Use the sheet metal screws provided to attach the kit to the rear of the unit as shown. Please see kit instruction manual for more detailed installation instructions. The stove must also be connected to a 6″ (152 mm) Class A flue (where permitted) using the 4″ (102 mm) to 6″ (152 mm) Flue Adaptor (4PVP-X6). See separate instruction manual for complete details.
Note: Part # 6DVL-ADT Simpson Duravent DVL adaptor would also be required to
connect the 4″ (102 mm) – 6″ (152 mm) increaser to class A chimney when going
through the wall or ceiling when using Simpson Duravent Duraplus/Duratech
chimney systems. Not required with DuraTech Premium or DuraTech Canada. DTC
ceiling supports feature a built-in flue extension which eliminates the need
for this Simpson Duravent DVL adaptor.
20
Hampton GC60-2 Cast Pellet Stove Technical Manual
Installation
Slider/damper Set-up: This is used to regulate the airflow through the pellet
stove and has been set at the factory.
Convection Fan
Removable Plate & Exhaust Sensor location
Slider Damper
Slider Damper Set Screw with 5/16″ Hex Head
Combustion Blower
Note: The side panel, & back grill are removed for clarity.
Figure 19: Slider/Damper Plate in Unit.
Figure 20: Efficient Flame.
This unit is designed to operate within a negative pressure range that may only be adjusted by a qualified technician. This can be measured using a Magnahelic pressure gauge once the unit has been running on heat level 5 setting after one hour of burn time. This adjustment is necessary for varying venting configurations. The reading can be taken from the ” hole located on the right side of the Ash Box.
The Combustion Trim, Feed Trim and Fuel Type Functions can be used to
compensate for varying fuel qualities. Refer to the Owners Manual for circuit
board operation.
If, after long periods of burning, the fire builds up or there is a build up
of clinkers, this would be a sign that the fuel quality is poor – this
requires more air.
The easiest way to make sure that an efficient flame is achieved is to
understand the characteristics of the fire. · A tall, lazy flame with dark
orange tips requires more air. · A short, brisk flame, like a blowtorch, has
too much air . · If the flame is in the middle of these two characteristics
with a bright yellow/orange, active flame with no black tips
then the air is set for proper operation, refer to Figure 20.
SPECIAL NOTES: Fuel quality is a major factor in how the stove will operate.
If the fuel has a high moisture content or ash content the fire will be less
efficient and has a higher possibility of the fire building up and creating
clinkers (hard ash build-up).
Hampton GC60-2 Cast Pellet Stove Technical Manual
21
Troubleshooting
DO NOT: Service the stove with wet hands. The stove is an electrical
appliance, which may pose a shock hazard
if handled improperly. Only qualified technicians should deal with possible
internal electrical failures. Do not remove from the firebox any screws
without penetrating oil lubrication.
WHAT TO DO IF: 1. The stove will not start. 2. The stove will not operate when
hot. 3. The exhaust blower will not function normally. 4. Light # 3 on Heat
output bar flashing. 5. Auger light flashes but auger motor does not turn at
all. 6. The 200 °F (93 °C) high limit temperature sensor has tripped. 7. The
convection blower will not function normally. 8. Ignitor- the Fuel will not
light. 9. Control settings (Heat Level) has no effect on the fire. 10. The
stove keeps going out. 11 The agitator does not turn.
*NOTE: All troubleshooting procedures should be carried out by qualified technicians or installers.
1. The stove will not start. · Check the line fuse to see if it has blown. ·
Make sure the stove is plugged in and the wall outlet is supplying power. · If
the Control Board has been placed in the ON /OFF thermostat mode, then turn
the thermostat up
to call for heat. · Ensure the burn pot liner is correctly placed in the burn
pot · Check the Heat Level Indicator. – If the # 3 light is flashing (unit may
be out of fuel) · Check the Door and Ash Pan door – THEY MUST BE CLOSED TIGHT.
· See section 8 “The Fuel will not light”. · Check the fuse on the circuit
board. · If the unit still does not start, contact your local service dealer
for service.
2. The stove will not operate when hot. · Check the Heat Level Indicator if a
fire is not detected or if the fire has gone out the #3 light will flash
because the Exhaust Temperature Sensor’s contacts have opened. · Check the
hopper for fuel. · Incorrect air damper/combustion air trim setting.
Excessive air may consume the fire too quickly before the next drop of fuel,
leaving completely unburned fuel in the burn pot liner. Insufficient air may
cause the vacuum switch to open or will cause build up, further restricting
the air flow through the Burn Pot Liner. This in turn will cause the fuel to
burn cold and very slowly. Fuel may build up and smother the fire. In this
case clean the burn pot. NOTE: The unit may require a change to the vent
system or installation of fresh air to correct Air to Fuel ratio problems if
unable to achieve proper damper setting. · Combustion Blower failure. – The
Combustion Blower is not turning fast enough to generate the proper vacuum in
the fire box. Visual Check is the blower motor turning. See section #3 – The
Exhaust Blower will not function normally. · Poor Quality Fuel Insufficient
energy in the fuel to produce enough heat to keep the stove burning
22
Hampton GC60-2 Cast Pellet Stove Technical Manual
Troubleshooting
· Exhaust Temperature Sensor failure. Bypass sensor located on Exhaust Blower,
if stove now operates properly, the unit may require cleaning or a new sensor.
Contact your local dealer for service.
· Check the agitator to make sure it is turning properly
3. The exhaust motor will not function normally. · Check the line fuse to see
if it has blown. · Open the access panels; check all connections against the
wiring diagram. · Check the Exhaust Blower voltage across the blower motor
wires (>=115V on #5 setting and >= 75V
on #1 setting). Replace the Circuit Board if the Voltage reading is less
than 75 V. with a line voltage of >115 V AC. · Clean all exhaust passages and
venting. · Check and, if necessary, replace capacitor.
4. Light # 2 on heat output bar flashing (indicates loss of vacuum) check the
following: · Make sure the ash pan is closed and sealed · Make sure unit and
venting is clear of fly ash · Check the vacuum switch · Check all wires and
connections · Check hose from vacuum switch to hose barb · Check hose barb
that connects hose to back of unit · Check combustion blower fuse · Confirm
combustion blower voltage to determine that it is working properly
5. Light # 3 on Heat output bar flashing (The Exhaust Temp. Switch contacts
have opened.) · Stove ran out of fuel – check fuel level in the hopper. · See
sections #2 – Stove will not operate when hot, #3 – The Exhaust motor will not
function normally,
and #5 – Unit is on but auger does not turn at all for more suggestions. ·
Severe negative pressure in area where unit is installed – Check the operation
by opening a window,
does this solve the problem? If it does, install fresh air intake to unit or
room. Venting system may require vertical section to move termination into a
low pressure zone. · To reset Circuit Board after a trouble code – push the
ON/OFF button.
6. Unit is on but auger motor does not turn at all. · Check the line fuse to
see if it has blown. · Check the Door and Ash Pan door – THEY MUST BE CLOSED
TIGHT. · If the Auger gear box does not turn but the motor’s armature does try
to spin, then the auger is
jammed. Try to break apart jam by poking at the jam through the drop tube. If
this fails then empty the hopper and remove the Auger Cover Remember to re-
seal the cover after installation · Auger stopped running. Pinch, break or
blockage in Vacuum Hose – Check hose for pinch points or damage, replace or
re-route as required. Blow out Vacuum Hose and intake pipe. · Damage to wires
between Circuit Board and Vacuum Switch and Auger Motor – Inspect wires and
connectors. · Vacuum Switch failure – Bypass the vacuum switch, if this
corrects the problem check for above problems before replacing the Vacuum
Switch. · Blocked exhaust / venting system – Have stove and venting cleaned
and inspected. · Check Vacuum levels at the Vacuum Switch, with a Magnahelic
Gauge (readings must be above .07″ W.C. on low fire).
Hampton GC60-2 Cast Pellet Stove Technical Manual
23
Troubleshooting
7. Light # 4 on Heat output bar flashing The 200 °F ( 93 °C) high limit
temperature sensor has tripped.
· Reset sensor and determine cause. Was it Convection Blower failure or
Circuit board control problems?
· Hopper lid has been left open for longer than two minutes.
8. The convection blower will not function normally. · Check the line fuse to
see if it has blown. · Clean all grill openings at the back and below unit . ·
Check the Voltage across the blower wires, It should adjust with the heat
output settings. If not
contact your local dealer for service.
9. Ignitor – the pellets will not light. · Check the line fuse to see if it
has blown. NOTE: The ignitor should be bright orange in color. · Everything
else in the stove operates but the ignitor will not light the pellets. · Make
sure the burn pot liner is up tight and square to the ignitor · Check to see
if the exhaust blower is operating. If not, contact your local dealer for
service.
10. Control settings (Heat Level) has no effect on the fire. · Check position
of the Thermostat slide switch on the Circuit Board. · If there is no control
of the Heat Level button, make sure the thermostat is calling for heat. · Call
your local dealer for service.
11. The stove keeps going out. If the stove goes out and leaves fresh
unburned fuel in the burn pot liner, the fire is going out before the stove
shuts off. · Trim the combustion air down to decrease the magnahelic pressure.
· Turn the Heat Level up slightly (poor quality fuels will require slightly
higher settings). · Set the auger trim up one setting
If the stove goes out and there are partially burned pellets left in the burn
pot liner, the stove has shut down due to a lack of air, exhaust temperature,
or power failure. · Trim the combustion air to a higher setting to increase
the magnahelic pressure inside the stove. · Check to see if the stove needs a
more complete cleaning. · Turn the Heat Level up slightly (poor quality fuel
will require slightly higher settings). · Jump the exhaust temperature sensor,
if this fixes the problem then replace the white 120 °F ( 49
°C) sensor · Did the power go out? · Contact your local Dealer for service.
12. The agitator does not turn. · Ensure unit has finished start-up. · Ensure
agitator is locked into the drive shaft properly and is not jammed. · Check
drive chain assembly and gear motor for damage. · Check the agitator motor is
functioning properly.
24
Hampton GC60-2 Cast Pellet Stove Technical Manual
Red
Combustion
Blue
Blower Blue
Black
Wiring Diagram
Black Black
Blue White
2µF Capacitor
Brown Brown
Exhaust Temperature Sensor
120V Ground
Plug
Red White
Air Pump
Green Ground
Red White
Ignitor
5 Amp 2 Amp 2 Amp 2 Amp 2 Amp
Thermostat
Ground
Black White Green
Black
Connect Thermostat Here
Red Yellow Purple
Blue Brown Brown White
Grey Grey
Orange Orange
Hampton GC60-2 Cast Pellet Stove Technical Manual
White Blue/Yellow
Agitator Motor
White Yellow
Auger Motor
6 µF Capacitor Brown
Purple
Blue
White
Convection Blower
Grey Grey
Orange
Vacuum Switch
High Limit Temperature Switch
Orange
Hopper Switch
25
Parts List
ITEM # not shown not shown not shown not shown not shown not shown not shown
not shown not shown not shown not shown not shown not shown not shown not
shown not shown not shown not shown not shown not shown not shown not shown
not shown not shown not shown not shown
1 2 3 4 5 6 7 8 9 10 11
DESCRIPTION Log Set (optional) 120 CERAMIC EXHAUST TEMP SENSOR WINDOW CHANNEL TAPE 72″ 5/8″ DOOR GASKET 7′ PED & ASHPAN GASKET 10′ PELLET MECHANICAL & ELEC FASTERNER BAG BURN POT SCRAPER TOOL DOMESTIC POWER CORD HEYCO STRAIN RELIEF PELLET SERVICE TOOL KIT MAGNAHELIC GAUGE (TESTING UNIT) PELLET STOVE CLEANING BRUSH PELLET STOVE THERMOSTAT DOOR & ASH DOOR GASKET 9/16 FIRM (10′) W/JOINING TAPE(2) GLASS RETAINER LATCH BOLT & ROLLERS C/W NUT 2 AMP SMALL FUSE 4 AMP SMALL FUSE IGNITOR ADJ AUGER FEED COVER KIT (N/C) PRE NOV 2010 COMBUSTION BLOWER MOUNTING GASKET C-10859 MAGNET 0.5″ X 0.25″ (NEO 45) CONVECTION FAN CAPACITOR CERAMIC REFRACTORY BRICK LINER KIT HEAT EXCHANGER SCRAPER ROD GC60 OWNERS MANUAL GC60 TECHNICAL MANUAL AUGER WITH PADDLES VACUUM SWITCH LOW PRESURE AUGER STOPS (CLEAR RUBBER) AUGER PLATE AND BUSHING (ASSEMBLY) BURN POT STAINLESS STEEL CAST AGITATOR W/ COUPLER AGITATOR DRIVE SHAFT W/SPROCKET MOTOR DRIVE SPROCKET 1/4″ SPRING PIN AIR PUMP AGITATOR BUSHING LEFT SIDE
PART # GC60-930 GF55-009 GF55-018 GF55-019 GF55-020 GF55-021 GF55-023 GF55-025 GF55-026 GF55-031 GF55-035 GF55-048 GC60-001 GC60-019 GC60-025 GC60-031 GC60-032 GC60-033 GC60-034 GC60-035 GC60-036 GC60-039 GC60-044 GC60-047 GC60-053 GC60-054 GC60-002 GC60-003 GC60-004 GC60-005 GC60-006 GC60-007 GC60-008 GC60-009 GC60-010 GC60-011 GC60-012
26
Hampton GC60-2 Cast Pellet Stove Technical Manual
GC60-2 Parts List
ITEM # 12 14 15 15A 16 17 18 19 20 21 22 23 24 25 26 27 31 32 33 39 40 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 66
DESCRIPTION AUGER BRASS BUSHINGS (2) FIRE GRATE AGITATOR DRIVE BRACKET AGITATOR DRIVE BRACKET ASSEMBLY C/W HARDWARE SS BURN POT LINER 4″ EXHAUST STARTER TUBE C/W GASKET AIR DEFLECTOR HOPPER SWITCH EXHAUST MOTOR CAPACITOR C/W STRAP AUGER MOTOR 2 RPM EXHAUST STARTER TUBE GASKET ONLY DRIVE CHAIN CONVECTION FAN 80MM SILICONE HOSE (BLACK) (AIR PUMP) FS COMBUSTION BLOWER CW HOUSING /MOUNT/ GASKET FIREBOX LOWER GC60 CONTROL PANEL WITH DECAL DAUGHTER BOARD MOTHER BOARD ASH PAN GLASS DOOR COMPLETE AUGER TUBE COVER IGNITOR ASSEMBLY HINGE BRACKET (INNER) EXHAUST CHANNEL CW SENSOR BAFFLE WIRING HARNESS MOTHERBOARD MOUNTING PANEL CAST FRONT MOUNTING BRACKETS (SET OF 2) MAGNET LATCH (SET OF 2) 5/8″ I.D. AUGER COLLAR W/SCREW AUGER MOTOR 1 RPM 200 HIGH LIMIT SENSOR MANUAL RESET SILICONE HOSE (ORANGE) (VACUUM SWITCH) FIREBOX CLEANING PORT COVERS CAST FLUTED FIREBOX LINER
Hampton GC60-2 Cast Pellet Stove Technical Manual
PART # GF55-045 GC60-013 GC60-067 GC60-068 GC60-289 GC60-040 GC60-290 GC60-016
GC60-017 GC60-018 GC60-042 GC60-020 GC60-037 GC60-021 GC60-043 GC60-045
GC60-055 GC60-022 GC60-023 GC60-046 GC60-024 GC60-026 GC60-027 GC60-028
GC60-029 GC60-048 GC60-049 GC60-030 GC60-050 GC60-052 GC60-051 GF55-047
GF55-001 GF55-011 GF55-013 GC60-038 GC60-041
27
GC60-2 Parts Diagram – Components
22 26 20 21
54 40
19
48
1
52 2
55
53 23
12
3 6 9
4 18
31 50 45
17
46
24 11 42
39 51
14
27
5
43
16
10 25
32
33
44
47
15
8
56 7
49
28
Hampton GC60-2 Cast Pellet Stove Technical Manual
Parts Diagram – CAST
ITEM # 57 58 59 60 61 62 63 64 65 67 N/S N/S
DESCRIPTION GC60 CAST FRONT – CHARCOAL GC60 CAST TOP – CHARCOAL GC60 CAST HOPPER LID – CHARCOAL GC60 CAST LEG – CHARCOAL GC60 CAST SIDE LEFT – CHARCOAL GC60 CAST SIDE RIGHT – CHARCOAL GC60 CAST LEG LIP LEFT – CHARCOAL GC60 CAST LEG LIP RIGHT – CHARCOAL GC60 CAST ASH DOOR – CHARCOAL TOP VENT ADAPTOR 4” (102 MM) TO 6” (152 MM) FLUE INCREASER DVL ADAPTOR
PART # GC60-201 GC60-211 GC60-221 GC60-231 GC60-241 GC60-251 GC60-261 GC60-271 GC60-281 GC60-920 4PVP-X6 6DVL-ADT
59 61
63
67
58 57 62
64 60
65
66
Hampton GC60-2 Cast Pellet Stove Technical Manual
29
WARRANTY
Limited Lifetime Warranty FPI Fireplace Products International Ltd. (for
Canadian customers) and Fireplace Products U.S., Inc. (for U.S. customers)
(collectively referred to herein as “FPI”) extends this Limited Lifetime
Warranty to the original purchaser of this appliance provided the product
remains in the original place of installation. The items covered by this
limited warranty and the period of such coverage is set forth in the table
below.
Some conditions apply (see below).
The policy is not transferable, amendable or negotiable under any
circumstances.
Pellet Products Warranty Coverage for Components and labor is as follows:
Firebox/Heat exchanger Surrounds, castings, door assembly. Burn Pot, Log sets,
Firebox panels, Ceramic Glass ( Thermal Breakage) Pedestals, legs Burn Pot
Liner Agitator Auger Motor, Combustion blower, Convection blower Wiring, all
switches, Wiring harness, Power cords Circuit boards, Circuit board ribbon
cable Vacuum switch, Ignitor, Air pump, Temperature sensors, Wall thermostat
Auger Circuit Board Decals Hopper Rails/ Baffle
Component Coverage 7 years
2 years
Labour Coverage (Years)
2 2 2 2 2 2 2 2
2
2
2
2
2
Conditions: Warranty protects against defect in manufacture or FPI factory assembled components only, unless herein specified otherwise.
Any part(s) found to be defective during the warranty period as outlined above will be repaired or replaced at FPI’s option through an accredited distributor, dealer or pre-approved and assigned agent provided that the defective part is returned to the distributor, dealer or agent for inspection if requested by FPI. Alternatively, FPI may at its own discretion fully discharge all of its obligations under the warranty by refunding the verified purchase price of the product to the original purchaser. The purchase price must be confirmed by the original Bill of Sale.
The authorized selling dealer, or an alternative authorized FPI dealer if pre- approved by FPI, is responsible for all in-field diagnosis and service work related to all warranty claims. FPI is not responsible for results or costs of workmanship of unauthorized FPI dealers or agents in the negligence of their service work.
At all times FPI reserves the right to inspect reported complaints on location in the field claimed to be defective prior to processing or authorizing of any claim. Failure to allow this upon request will void the warranty.
All warranty claims must be submitted by the dealer servicing the claim, including a copy of the Bill of Sale (proof of purchase by you). All claims must be complete and provide full details as requested by FPI to receive consideration for evaluation. Incomplete claims may be rejected.
30
Hampton GC60-2 Cast Pellet Stove Technical Manual
WARRANTY
Replacement units are limited to one per warranty term. Airtube and baffle
replacements are limited to one replacement per term.
Unit must be installed according to all manufacturers’ instructions as per the
manual.
All Local and National required codes must be met.
The installer is responsible to ensure the unit is operating as designed at
the time of installation.
The original purchaser is responsible for annual maintenance of the unit, as
outlined in the owner’s manual. As outlined below, the warranty may be voided
due to problems caused by lack of maintenance.
Repair/replacement parts purchased by the consumer from FPI after the original
coverage has expired on the unit will carry a 90 day warranty, valid with a
receipt only. Any item shown to be defective will be repaired or replaced at
our discretion. No labor coverage is included with these parts
Exclusions:
This Limited Lifetime Warranty does not extend to paint, rust or corrosion of
any kind due to a lack of maintenance or improper venting, combustion air
provision, corrosive chemicals (i.e. chlorine, salt, air, etc.), inner panels,
door or glass gasketing, or any other additional factory fitted gasketing.
Malfunction, damage or performance based issues as a result of environmental
conditions, location, chemical damages, downdrafts, installation error,
installation by an unqualified installer, incorrect chimney components
(including but not limited to cap size or type), operator error, abuse,
misuse, use of improper fuels (plastics, garbage, solvents, cardboard, coal or
coal products, oil based products, waxed cartons, compressed premanufactured
logs), lack of regular maintenance and upkeep, acts of God, weather related
problems from hurricanes, tornados, earthquakes, floods, lightning
strikes/bolts or acts of terrorism or war, which result in malfunction of the
appliance are not covered under the terms of this Limited Lifetime Warranty.
FPI has no obligation to enhance or modify any unit once manufactured (i.e. as
products evolve, field modifications or upgrades will not be performed on
existing appliances).
This warranty does not cover dealer travel costs for diagnostic or service
work. All labor rates paid to authorized dealers are subsidized, pre-
determined rates. Dealers may charge homeowner for travel and additional time
beyond their subsidy.
Any unit showing signs of neglect or misuse will not be covered under the
terms of this warranty policy and may void this warranty. This includes units
with rusted or corroded fireboxes which have not been reported as rusted or
corroded within three (3) months of installation/purchase.
Units which show evidence of being operated while damaged, or with problems
known to the purchaser and causing further damages will void this warranty.
Units where the serial no. has been altered, deleted, removed or made
illegible will void this warranty.
Minor movement, expansion and contraction of the steel is normal and is not
covered under the terms of this warranty.
FPI is not liable for the removal or replacement of facings or finishing in
order to repair or replace any appliance in the field.
Freight damages for products or parts are not covered under the terms of the
warranty.
Products made or provided by other manufacturers and used in conjunction with
the FPI appliance without prior authorization from FPI may void this warranty.
Hampton GC60-2 Cast Pellet Stove Technical Manual
31
WARRANTY
Limitations of Liability:
The original purchaser’s exclusive remedy under this warranty, and FPI’s sole
obligation under this warranty, express or implied, in contract or in tort,
shall be limited to replacement, repair, or refund, as outlined above. IN NO
EVENT WILL FPI BE LIABLE UNDER THIS WARRANTY FOR ANY INCIDENTAL OR
CONSEQUENTIAL COMMERCIAL DAMAGES OR DAMAGES TO PROPERTY. TO THE EXTENT
PERMITTED BY APPLICABLE LAW, FPI MAKES NO EXPRESS WARRANTIES OTHER THAN THE
WARRANTY SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO
DURATION OF THE EXPRESSED WARRANTY SPECIFIED ABOVE. IF IMPLIED WARRANTIES
CANNOT BE DISCLAIMED, THEN SUCH WARRANTIES ARE LIMITED IN DURATION TO THE
DURATION OF THIS WARRANTY.
Some U.S. states do not allow limitations on how long an implied warranty lasts, or allow exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you.
Customers located outside the U.S. should consult their local, provincial or national legal codes for additional terms which may be applicable to this warranty.
How to Obtain Warranty Service:
Customers should contact the authorized selling dealer to obtain warranty
service. In the event the authorized selling dealer is unable to provide
warranty service, please contact FPI by mail at the address listed below.
Please include a brief description of the problem and your address, email and
telephone contact information. A representative will contact you to make
arrangements for an inspection and/or warranty service.
Canadian Warrantor:
U.S. Warrantor:
FPI Fireplace Products International Ltd. 6988 Venture St. Delta, British Columbia Canada, V4G 1H4
Fireplace Products U.S., Inc. PO Box 2189 PMB 125 Blaine, WA United States, 98231
Or contact the Regency Customer Care Centre at 1-800-442-7432 (phone) / 604-946-4349 (fax)
Product Registration and Customer Support:
Thank you for choosing a Regency Fireplace. Regency strives to be a world
leader in the design, manufacture, and marketing of hearth products. To
provide the best support for your product, we request that you complete a
product registration form at http://www.regency-fire.com/Customer-Care
/Warranty-Registration.aspx within ninety (90) days of purchase.
32
Hampton GC60-2 Cast Pellet Stove Technical Manual
WARRANTY
Product Registration and Customer Support:
Thank you for choosing a Regency Fireplace. Regency strives to be a world
leader in the design, manufacture, and marketing of hearth products. To
provide the best support for your product, we request that you complete a
product registration form found on our Web Site under Customer Care within
ninety (90) days of purchase.
For purchases made in CANADA or the UNITED STATES: http://www.regency-fire.com
/Customer-Care/Warranty-Registration.aspx
For purchases made in AUSTRALIA: http://www.regency-fire.com.au/Customer-Care
/Warranty-Registration.aspx
You may also complete the warranty registration form below to register your
Regency Fireplace Product and mail and/or fax it back to us, and we will
register the warranty for you. It is important you provide us with all the
information below in order for us to serve you better.
Warranty Registration Form (or Register online immediately at the above Web
Site):
Warranty Details Serial Number (required): Purchase Date (required) (mm/dd/yyyy): Product Details Product Model (required): Dealer Details Dealer Name (required): Dealer Address: Dealer Phone #: Installer: Date Installed (mm/dd/yyyy): Your Contact Details (required) Name: Address: Phone: Email:
For purchases made in CANADA:
FPI Fireplace Products International Ltd. 6988 Venture St. Delta, British
Columbia Canada, V4G 1H4
Phone: 604-946-5155 Fax:
1-866-393-2806
For purchases made in the UNITED STATES:
Fireplace Products US, Inc. PO Box 2189 PMB 125 Blaine, WA United States,
98231
For purchases made in AUSTRALIA:
Fireplace Products Australia Pty Ltd 99 Colemans Road Dandenong South, Vic.
3175 Australia
Phone: 604-946-5155 Fax: 1-866-393-2806
Phone: +61 3 9799 7277 Fax: +61 3 9799 7822
For fireplace care and tips and answers to most common questions please visit our Customer Care section on our Web Site. Please feel free to contact your selling dealer if you have any questions about your Regency product.
Hampton GC60-2 Cast Pellet Stove Technical Manual
33
WARRANTY
34
Hampton GC60-2 Cast Pellet Stove Technical Manual
Hampton GC60-2 Cast Pellet Stove Technical Manual
35
Installer: Please complete the following information
Dealer Name & Address:__
____ Installer:
Phone #:
___ Date Installed:
__ Serial
:____
Regency, Hampton and Greenfire are registered and / or proprietary trademarks of FPI Fireplace Products International Ltd.
© Copyright 2022, FPI Fireplace Products International Ltd. All rights reserved.
Printed in Canada
References
- Warranty Registration | Register Your Unit Today | Regency
- Warranty Registration | Register Your Unit Today | Regency
- bit.ly/3bzMqj0