algodue FCA3000 Flexible Clamps Adapter User Manual
- June 12, 2024
- algodue
Table of Contents
algodue FCA3000 Flexible Clamps Adapter
Product Information
- Product Name: FCA3000 Flexible Clamps Adapter
- Model Number: Ed1401
- Manual Languages: English (p.2), Italiano (p.14)
- Manual Version: 1MAIFCA300004 16/05/2006
- Description: The FCA3000 is a flexible clamps adapter that provides installation, configuration, and usage information for the main instrument functions. The manual is intended for qualified technicians who have the necessary skills and knowledge to ensure safety while working with electric current.
Product Usage Instructions
- Graphic Symbols: Pay attention to the operational dangers highlighted by graphic symbols in both the manual and on the device.
- Preliminary Checks: Perform preliminary checks before installation.
- Installation:
- Environmental Requirements: Ensure that the environment in which the instrument is installed meets the specified features. Avoid exposing the instrument to direct sunlight.
- Mounting: Use a screwdriver as a lever on the plastic hook on the base of the instrument to mount it on a DIN EN 50022 rail.
- Safety Measures: Take the following safety measures:
- DANGER! Be cautious of voltage exceeding 1kV on the terminals.
- WARNING! Electrical connections should only be made by skilled technicians who are aware of the risks associated with voltage presence. Before connecting, check the conductor wires, power supply values, installation environment, accessibility of terminals after connection, compliance with wiring standards, installation of isolator and over-current device, correct polarity connections, and secure fixation of connectors.
- Connections: Make instrument connections using the indicated connectors. Ensure the instrument is switched OFF before making any connection. Check the power supply voltage corresponds to the specified range (80-260 VAC or 19-60VDC).
INTRODUCTION
This manual provides information on the installation, configuration and use of
the main instrument functions. The manual is not intended for general use, but
for qualified technicians.
This term indicates a professional and skilled technician, authorized to act
in accordance with the safety standards relating to the dangers posed by
electric current.
This person must also have basic first aid training and be in possession of
suitable Personal Protective Equipment.
WARNING!
It is strictly forbidden for anyone who does not fulfill the above-mentioned
requirements to install or use the instrument.
The instrument complies with the European Union directives in force, as well
as with the technical standards implementing these requirements, as certified
by the CE mark on the device and on this Manual.
Using the meter for purposes other than intended ones, understood by the
manual content, is strictly forbidden. The information herein contained shall
not be shared with third parties. Any duplication of this manual, either
partial or total, not authorized in writing by the Manufacturer and obtained
by photocopying, duplicating or using any other electronic means, violates the
terms of copyright and is punishable by law.
Any brands quoted in the publication belong to the legitimate registered
owners.
NOTE
This manual describes the use of the main instrument functions.
GRAPHIC SYMBOLS
Some instructions in the manual and on the device are highlighted by graphic symbols to draw the reader’s attention to the operational dangers. The following graphic symbols are used:
-
DANGER!
This warning indicates the possible presence of voltage exceeding 1kV on the marked terminals (even if for short periods). -
WARNING!
This warning indicates the possible occurrence of an event which may cause a serious accident or considerable damage to the device if suitable precau- tionary countermeasures are not taken. -
ATTENTION!
This warning indicates the possible occurrence of an event which may cause a light accident or damage to the device if suitable precautionary counter- measures are not taken. -
NOTE
This warning indicates important information which must be read carefully.
DESCRIPTION
FCA3000 is a three-phase converter with DC outputs (current or voltage), which
convert the value measured by a Rogowski coil into true RMS value.
FCA3000 has 3 inputs channels suitable for 3 transducers; the 4 outputs are
dedicated one for each transducer, the fourth gives the sum of the 3 current
values.
These outputs can be used with any kind of indicating device such as
voltmeter, oscilloscope, data logger, SCADA systems, protection systems,
metering equipments, etc.
FCA3000 can be used both with rigid and flexible transducers.
PRELIMINARY CHECKS
NOTE
At the opening the box, check that the instrument has not been damaged during
transport.
If the instrument appears to be damaged, contact the aftersales service.
The box contains:
- the instrument
- the user’s manual
INSTALLATION
NOTE
The equipment complies with the 89/366/EEC, 73/23/EEC standards and following
amendments. However, if not properly installed, it may generate a magnetic
field and radio interference. This is why compliance with EMC standards on
electromagnetic compatibility is essential.
ENVIRONMENTAL REQUIREMENTS
The environment in which the instrument is installed must satisfy the
following features:
- No vibrations
- Indoor area
- Operating temperature between -10°C and +50°C Storage temperature between -25°C and +60°C
- Max humidity 75% (no condensation) altitude up to 2000m
NOTE
The instrument must not be exposed to sun rays.
MOUNTING
Fastening to DIN EN 50022 rail is provided for the instrument.
To mount it on the DIN rail, you simply need to use a screw driver as a lever
on the plastic hook on the base of the instrument itself. This operation will
allow to fi t the instrument on the DIN rail.
SAFETY MEASURES
DANGER!
This warning means that a voltage exceeding 1kV (even if for short periods)
may be present on the terminals.
WARNING!
Electrical instrument connections must be carried out only by skilled
technicians who are aware of the risks involved to the presence of voltage.
Before connecting, check the following:
- the conductor wires are not powered
- the power supply corresponds to the values on the instrument label
- the instrument has been installed in a vibration-free environment a suitable temperature (see section 5.1)
- the terminals are no longer accessible after being connected
- the wiring is carried out in accordance with the standards in force in the country where the instrument is to be installed
- an isolator and an over-current device (e.g. fuse) are installed between the instrument power supply and the electrical system
- the connections are made respecting the polarities
- the connectors are fixed in such a way that they cannot be accidentally disconnected
CONNECTIONS
The instrument connections are carried out through the following connectors, as indicated in the picture:
Pict. 7.1 – Connections
- a 3-pin female connector (power supply)
- a 6-pin female connector (inputs)
- a 8-pin female connector (outputs)
WARNING!
Before making any connection, check if the instrument is switched OFF.
POWER SUPPLY
WARNING! Before connecting the power supply, check if it corresponds to the
plated voltage value (80-260 VAC or 19-60VDC).
The instrument does not have a protection fuse on the power supply, therefore
the installer must protect it with a current backer and an overcurrent
protection device (315mA delayed fuse, T type).
ANALOG INPUTS
The analog inputs allow the connection of 100 mV/kA signal Rogowski coils with
3000A full scale. On request, the input value can be customized to allow the
connection of rigid or flexible Rogowski coils with full scale different from
3000A. Each one of the 3 inputs has 2 terminals; the ground is common to all
the outputs.
ANALOG OUTPUTS
Two different analog outputs types are available: on DC current (standard
version), or on DC voltage (on request). Each one of the 4 inputs has 2
terminals; the ground is common to all the outputs (see picture 7.3).
WARNING!
In case of analog output on DC current, the maximum value of delivered voltage
is 10V, therefore the load must never exceed 300 Ohm.
WARNING!
In case of analog output on DC voltage, the internal resistance is 500 Ohm,
therefore the load must never be lower than 100 kOhm.
The maximum output value of 20mA (in case of analog output on DC current), and
of 10 VDC (in case of analog output on DC voltage), on the SUM output,
corresponds to the sum of the 3 clamps full scale (e.g.: 3000A clamps, SUM
f.s.=9000A).
The instrument is calibrated for the declared accuracy; if a further full
scale regulation is necessary, remove the instrument panel, using a
screwdriver (see picture 7.2), and operate on the trimmer located inside the
instrument (see picture 7.4, OUT 1, 2, 3, SUM).
Pict. 7.2 – Front panel opening
DC Current
DC Voltage
Pict. 7.3 – Analog outputs diagram
In case of instrument with 4-20 mA output (only on request), the 4 mA output can be regulated operating on the trimmer located inside the instrument (see picture 7.4, O 1, 2, 3, SUM).
Pict. 7.4 – Trimmer
RESPONSE TIME
The waveform shows the relevant output variation and an input variation from 0 to 40% of the signal and vice versa. The horizontal scale is 50 msec for each column.
TECHNICAL FEATURES
POWER SUPPLY
- Rated voltage (Vn) 80-260 VAC (45 – 65 Hz) 19-60 VDC (on request)
- Maximum repetitive voltage 265 VDC
- Consumption 3VA max
MEASUREMENTS
-
Inputs 100 mV/kA flexible coils with 3000 A fullscale.
On request, the input value can be customized to allow the connection of rigid or flexible Rogowski coils with fullscale different from 3000 A. -
Outputs 0-20 mA 4-20 mA (on request) 0-10 VDC (on request)
-
Response time 150 ms (standard value), programmable
-
Accuracy ±1% reading ±0.3% fullscale
CONDIZIONI AMBIENTALI
- Operating temperature From -10°C to +50°C
- Storage temperature From -25°C to +60°C
- Operating humidity Max 75% non condensing
If the instrument was stored at temperature lower than 0°, it is necessary to wait 1 hour of warm up before switched ON (to avoid condensing).
MECHANICAL FEATURES
- Material NORYL UL 94 V-0 autoextinguish, grey plastic enclosure (RAL 7035)
- Protection degree IP51 (front panel); IP20 (terminals)
- Connections A 3-pin female connector (power supply)
- A 6-pin female connector (inputs)
- A 8-pin female connector (ouputs)
- Size 160 x 90 x 51 (mm)
- Weight 250g. approximately
WARNING – The manufacturer declines all liability for any damage to people or properly caused by incorrect use of this product. Subject to change without prior notice.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>