algodue ELETTRONICA RS485 Modbus Communication Module User Manual
USER MANUAL
Subject to change without prior notice
PICTURE/ABBILDEN
WARNING! Device installation and use must be carried out only by qualified professional staff. Switch off the voltage before device installation.
CABLE STRIPPING LENGTH
For the module terminal connection, cable stripping length must be 5 mm. Use a blade screwdriver with 0.8×3.5 mm size, fastening torque
- Refer to picture B.
OVERVIEW
Refer to picture C:
- Terminals to be jumpered for termination resistor (RT) enabling
- RS485 connection terminals
- Optical COM port
- SET DEFAULT key
- Power supply LED
- Communication LED
- Power supply terminals
CONNECTIONS
A serial converter is required between PC and the RS485 network to adapt RS232/USB port to network. If there are more than 32 modules to be connected, insert a signal repeater. Each repeater can manage up to 32 modules. For the connection among the different modules, use a cable with a twisted pair and a third wire. The type of connection shown in picture D uses the third conductor to ensure that all the devices on the network have the same reference level and improve the reliability of communication. When there are strong electromagnetic disturbances, which may affect communication, a shielded cable should be used. The module is integrated with a termination resistor ( RT ) which can be enabled by jumpering the relevant terminals (1-2). The termination resistance must be installed on the PC and enabled on the last module connected along the line. Thanks to these resistances, the reflected signal along the line is reduced. The maximum recommended distance for a connection is 1200 m at 9600 bps. For longer distances, lower baud rates or low-attenuation cables or signal repeaters are needed. After making RS485 connections, combine each RS485 module with a single meter: place them side by side, perfectly lined up, with module optical port facing the meter optical port. RS485 parameters can be changed directly on the combined meter or by sending the proper MODBUS protocol commands to the module.
LEDS FUNCTIONALITY
Two LEDs are available on the module front panel to provide power supply and communication status:
__**LED COLOUR** | __**SIGNALLING** | MEANING |
---|
__**POWER SUPPLY LED **
– | __Power OFF| The module is OFF
GREEN
|
Always ON
| The module is ON
__**COMMUNICATION LED **
– | __Power OFF| The module is OFF
G REEN| Slow blink
__(2 s OFF time)
| RS485 communication=OK Meter communication=OK
R ED| Fast blink
(1 s OFF time)
| RS485 communication=fault/missing Meter communication=OK
R ED| A lways ON| M eter communication=fault/missing
GREEN/RED| Alternating colours for 5 s| SET DEFAULT procedure in progress
SET DEFAULT FUNCTION
SET DEFAULT function allows to restore on the module default settings (e.g. in
case of MODBUS address forgotten).
To restore default settings, keep SET DEFAULT key pressed for at least 5 s,
communication LED will blink green/red for 5 s. At the end of SET DEFAULT
procedure, communication LED will be red continuously indicating to release
the key.
Default settings:
RS485 communication speed = 19200 bps RS485 mode = 8N1 (RTU mode)
Modbus address = 01
TECHNICAL FEATURES
Data in compliance with EIA RS485 standard.