**Thermozone®Portier**
Ambient, no heat
3 3–13,5kW Electrical heat
Lengths: 1 and 1,5 meter
Thermozone ®Portier
Air curtains for installation heights up to 2,5 meters
Application
Portier is an exclusive air curtain in brushed stainless steel intended for
entrances with high demands in respect of design. The air curtain is available
in two different lengths that can be combined to cover entrances of different
sizes.
Comfort
Portier creates an air barrier, which prevents cold draughts and ensures
comfortable heating inside the door. An adjustable air blower grille makes it
possible to direct the air for an optimal air curtain effect. The air curtain
can also contribute to the heating of the premises when the door is closed.
Operation and economy
Thanks to Thermozone Technology, Portier saves energy. The air barrier reduces
energy losses through the door opening and the energy consumption of the air
curtain is also low. With an air curtain as a heat source, it produces heat in
the area where it is most needed, and as a result, the rest of the premises
can be covered with less output. Easy installation and maintenance minimize
the cost and the risk of errors.
Design
Portier has a unique symmetrical design in brushed stainless steel with a
black grille and ends. Color-coordinated housing is available as a special
order.
Product specifications
- Low sound level
- Simple suspension using fixing nuts on the upper side for installation with wall brackets, suspension kit or wire/threaded rod
- Adjustable exhaust grille makes it possible to direct the air for an optimum air curtain effect
- Optimized airflow with Thermozone technology
- Housing in brushed stainless steel. Colour outlet grille and ends: black, RAL 9005. Colour coordinated as special order
Air velocity profile
Technical specifications
Thermozone Portier A, without heat 1
Type| Output| Airflow| Sound level| Voltage| Amperage| Length|
Weight
---|---|---|---|---|---|---|---
| [kW]| [m 3 /h]| **[dB(A)]* 1| [V]| [A]|
[mm]**|
[kg]
PS210A| 0| 1000/1300| 44/54| 230V~| 0,45| 1020| 14
PS215A| 0| 1300/2000| 46/56| 230V~| 0,55| 1530| 20
Thermozone Portier E, electrically heated 3
Type| Output steps| Airflow| Sound level| Voltage| Amperage| Length|
Weight
---|---|---|---|---|---|---|---
| [kW]| [m 3 /h]| **[dB(A)]* 1| [V]| [A]|
[mm]**|
[kg]
PS210E03| 0/1,5/3| 950/1200| 44/50| 230V~/400V3N~2| 13,4/4,8| 1020| 17
PS210E06| 0/3/6| 950/1200| 44/50| 400V3N~2| 9,2| 1020| 17
PS210E09| 0/4,5/9| 950/1200| 44/50| 400V3N~2| 13,5| 1020| 17
PS215E09| 0/4,5/9| 1200/1900| 39/50| 400V3N~2| 13,5| 1530| 24
PS215E14| 0/6,7/13,5| 1200/1900| 39/50| 400V3~ + 230V~| 20,0| 1530| 24
- Conditions: The distance to the unit is 5 meters. Directional factor: 2. Equivalent absorption area: 200 m
- Alternative 400 V3~ + 230 V~ (operating supply) if the current is greater than 16 A. This applies when connecting several units.
Protection class: IP21.
CE is compliant.
Dimensions
Design and specifications are subject to change without notice.
Mounting and connection
Mounting
The units may only be installed horizontally over a doorway with the air
stream directed downwards. Distance from the exhaust to combustible materials
must be at least 50 mm. Portier is prepared with four M6 threaded holes on
the upper side of the air curtain. Wall mounting kit P2WB is available for
wall mounting. Suspension kit ADPK1 and suspension brackets ADPF1 are
available for ceiling installation. Portier can also be suspended using
cables/wires or threaded rods. See the next page for all the
mounting alternatives.
To achieve the optimum air curtain effect, the unit must extend the full width
of the door opening and as close to the opening as possible. For the
protection of wider doorways, several units can be mounted next to each other.
To achieve the optimum air curtain effect, they should be mounted as close to
each other as possible. Using joining kit P2JK (fig. 2) a complete unified air
curtain can be created.
Connection
The connection should be made with a type EKK, EKLK or corresponding cable via
knockouts in the upper side of the unit. The terminal block is equipped for a
max 16 mm 2cable, and the terminal block is for a max of 2.5 mm2. Normally,
the power and operating voltage are supplied separately. For smaller units,
the supply can be common, see wiring diagrams.
Installation options
Wall mounting kit P2WB (accessory)
Suspension kit ADPK1 (accessory)
Suspension brackets ADPF1 (accessory)![FRICO PS210E09 Thermozone Portier
- Suspension brackets ADPF1](https://manuals.plus/wp-content/uploads/2022/09 /FRICO-PS210E09-Thermozone-Portier-Suspension-brackets-ADPF1.png)
Control options
Ambient 1
Level 1
Airflow is controlled manually
Control kit:
– CB20, control box, controls the airflow in 2 steps.
Electrical 3
Level 1
Airflow is regulated manually. The room thermostat controls the heat output in
2 steps.
Control kit :
- CB22, control box, controls the airflow in 2 steps and heat output in 2 steps
- RTI2, 2-step room thermostat (option KRT2800)
Level 2
Airflow and heat output are controlled automatically based on the opening of
the door and the room temperature. When the door is open the fan runs at high
speed, when the door closes the fan will continue to run at high speed for the
desired time (2s–10 min.) set on MDC. When the door is closed the fan runs on
low speed if there is a need for heating, if not the fan is switched off.
The room thermostat controls the heat output. E.g. the thermostat is set at 23
°C and the difference between the stages is 4 °C. The thermostat will activate
below 19 °C when the door is closed. When the door opens, the thermostat will
activate below 23 °C and normally the heat is switched on.
Control kit:
- CB22, control box, controls the airflow in 2 steps and heat output in 2 steps
- MDC, door contact with time delay
- RTI2, 2-step room thermostat (option KRT2800)
Level 3
Airflow and heat output are controlled automatically based on the opening of
the door, outdoor temperature, and room temperature.
The system is based on an advanced microprocessing regulator in an attractive
design. All parameters are preprogrammed for easy and quick installation.
Control kit:
- ADEA, regulator (complete with outdoor sensor, built-in room sensor, and door contact).
- ADEAEB, control board, for external mounting.
Read more about the operation and usage of ADEA in the chapter on Controls and accessories.
For further options, see the section on thermostats and controls or contact Frisco.
Wiring diagrams
Ambient control options
Level 1
Electrical control options
Level 1
Wiring diagrams
Electrical control options
Level 2
Wiring diagrams
Electrical control options
Level 3
| MDCDC, magnetic door contact
---|---
| ADEAR, regulator with a display unit and built-in room sensor
| ADEAOS, outdoor sensor
| ADEAIS, external room sensor
| ADEAEB, external control board