0486 Power Monitor
0486 Power Monitor
Power Monitor for LogiCO2 Safety System.
Important!
Retain this instruction manual for future reference: Please read these
instructions carefully prior to start-up and use. Failure to follow any of
these instructions could void product warranties. LogiCO2 assumes no
responsibility for claims arising out of improper or careless use or handling
of it’s products.
Technical specifications
Power supply
– Safety System: | 24V DC |
---|---|
– Batteries: | 2 x AAA Alkaline 1,5V batteries* |
Battery control internal: | Once per hour |
Low power trig point: | 18V |
No power trig point: | Approx 3V |
Wiring connections: | RJ 45 |
Acoustic signal-strength: | ~80 dBa (1m) |
Operating temperature range: | 0 to +45°C (32 to |
+113°F). Only for indoor use.
Overvoltage:| Category II
Pollution degree:| II
Dimensions (LxWxD):| 90 x 161 x 38 mm / 3.5” x 6.3” x 1.5”
Ingress protection:| IP54
Function
The Power Monitor is a surveillance unit which ensures that the personnel are
alerted in case there is a power failure that puts the LogiCO2 Safety System
out of function. It has a built-in buzzer and place for two AAA alkaline
batteries (batteries not included). If there is a power failure the Power
Monitor makes an alarm. The Power Monitor alarm will buzz for at least 12
hours.
If the LogiCO2 Safety System is powered via a UPS power back-up, it is
recommended to install a Power Monitor that monitors the UPS-function. In case
the UPS´s batteries run out, the Power Monitor will give an alarm informing
that the LogiCO2 Safety System is out of function.
The three LEDs show the current status:
LED | Information |
---|---|
Green LED | The safety system has power |
Red LED | 1. Continuous beep and LED-light: No power to the safety system |
2. Double beep and LED-flash every other second: Safety system power below
18V
Yellow LED| eep and LED-flash every five seconds: Poor batteries in the Power
Monitor, replace the batteries.
Installation
Install the Power Monitor as far out in the LogiCO2 Safe System as possible.
The Power Monitor can detect a system power failure on both the red and blue
cables of the Safety System.
Mount the Power Monitor in a suitable location where it is easily seen and
heard. Do not cover the Power Monitor.
Remove the cover by unscrewing the five Phillips-screws.
Use a splitter and connect the Power Monitor to the Safety Systems red or blue
cabling (red/blue RJ45 connectors). Install two high performance AAA Alkaline
batteries (i.e. Duracell Ultra or GP Ultra) in the Power Monitor within 30
seconds after connecting it to the LogiCO2 Safety System being monitored. If
no batteries are installed within 30 seconds, the Power Monitor will activate
a “low battery” alarm.
30 seconds after the Power Monitor has been connected to the LogiCO2 Safety
System, the Power Monitor checks the battery status. After that, the battery
check is done once every hour.
Start-up
How to start-up Power Monitor in order to avoid activating the buzzer during the start-up:
- Mount the Power Monitor in a suitable location.
- Remove the cover by unscrewing the five Phillips-screws.
- Disconnect the red cable installed in the Power Monitor.
- Use a splitter and connect the Power Monitor in the Safety Systems red or blue cabling. See Fig. 1 and Fig. 2.
- Install one new AAA battery.
- Reconnect the red cable in the Power Monitor.
- Install the other new AAA battery within 30 seconds after reconnection of the red cable.
- Reassemble the cover and screws in this order, see Fig. 3.
Fig. 1, Power Monitor connected on the red cables of the Safety System
Fig. 2, Power Monitor connected on the blue cables of the Safety System
Replace batteries
How to replace poor batteries in order to avoid activating the buzzer during the exchange:
- Remove the cover by unscrewing the five Phillips-screws.
- Remove the AAA batteries.
- Disconnect the red cable installed in the Power Monitor.
- Install one new AAA battery.
- Reconnect the red cable.
- Install the other new AAA battery within 30 seconds after reconnection of the red cable.
- Reassemble the cover and screws in this order, see Fig. 3.
Fig. 3, If the cover of the Power Monitor needs to be removed, please observe the following order of screw reassambling.
Manufactured by:
LogiCO2 International AB
Box 9097
SE-400 92 Gothenburg, Sweden
E-mail: info@logico2.com
Web: www.logico2.com
© 2023-05-17 R2.0 LogiCO2 HFE1163 EN
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>