Power Solid KR-RM Series UPS
- June 10, 2024
- POWER SOLID
Table of Contents
Power Solid KR-RM Series
KR-RM Series (10kVA-40kVA) UPS
Thank you for choosing the KR-RM series Uninterruptible Power System (UPS) product. This manual provides detailed information on the product, including its features, performance, appearance, structure, working principles, installation, operation, and maintenance. Please save the manual after reading it for future reference.
Suitable Models
- KR10kVA-RM
- KR15kVA-RM
- KR20kVA-RM
- KR30kVA-RM
- KR40kVA-RM
Symbol Conventions
The manual uses safety symbols to prompt users to comply with safety matters during installation, operation, and maintenance. The safety symbol meanings are as follows:
Symbol | Description |
---|---|
! | Alerts you to a high-risk hazard that could result in serious |
injury or death if not avoided.
!!| Alerts you to a medium or low-risk hazard that could result in
moderate or minor injury if not avoided.
!| Alerts you to a potentially hazardous situation that could
result in equipment damage, data loss, performance deterioration,
or unanticipated results if not avoided.
i| Anti-static prompting.
*| Be careful electric shock prompting.
TIP| Provides a tip that may help you solve a problem or save
time.
NOTE| Provides additional information to emphasize or supplement
important points in the main text.
Product Standard
Q/ZZKJ 007
Change History
Changes between document issues are cumulative. The latest document issue
contains all the changes made in earlier issues.
Issue 001 (2020-06-20) – First issue.
Contents
- 1 Safety Description
- 1.2 Operation and Maintenance Requirements
- 1.3 Environment Requirements
- 2 Overview
- 2.2 Work Principle
- 2.2.1 Work Principle Diagram
- 2.2.2 Work Mode
- 2.3 Optionals
- 2.3.1 Distribution Module
- 2.3.2 Battery Box
Product Usage Instructions
To use the KR-RM series UPS product, follow the instructions provided in the manual, including:
- Read the safety description and comply with the safety symbols during installation, operation, and maintenance.
- Ensure the product is installed and maintained in the required environment.
- Choose the suitable model based on your power requirements.
- Refer to the work principle diagram to understand how the product works.
- Select the work mode that suits your needs. Consider the optional distribution module and battery box for additional functionality.
KR-RM Series (10kVA-40kVA) UPS User Manual
Foreword
Foreword
Summaries
Thank you for choosing the Uninterruptible Power System (hereinafter referred
to as the “UPS”) product! This document gives a description of the KR-RM
series UPS, including the features, performance, appearance, structure,
working principles, installation, operation and maintenance.etc. Please save
the manual after reading, in order to consult in the future.
The figures in this manual are just for reference, for details please see the actual product.
Suitable Model
KR10kVA-RM, KR15kVA-RM, KR20kVA-RM KR30kVA-RM, KR40kVA-RM
Symbol Conventions
The manual quotes the safety symbols, these symbols used to prompt users to comply with safety matters during installation, operation and maintenance. Safety symbol meaning as follows.
Symbol
Description
Alerts you to a high risk hazard that could, if not avoided, result in serious
injury or death.
Alerts you to a medium or low risk hazard that could, if not avoided, result
in moderate or minor injury.
Alerts you to a potentially hazardous situation that could, if not avoided,
result in equipment damage, data loss, performance deterioration, or
unanticipated results.
i
Foreword
KR-RM Series (10kVA-40kVA) UPS User Manual
Symbol
Description
Anti-static prompting.
Be care electric shock prompting.
Provides a tip that may help you solve a problem or save time.
Provides additional information to emphasize or supplement important points in
the main text.
Product standard: Q/ZZKJ 007
Change History
Changes between document issues are cumulative. The latest document issue
contains all the changes made in earlier issues.
Issue 001 (2020-06-20)
First issue.
ii
KR-RM Series (10kVA-40kVA) UPS User Manual
KR-RM Series (10kVA-40kVA) UPS User Manual
1 Safety Description
1 Safety Description
This chapter introduces the safety announcements. Prior to performing any work
on the UPS, please read the user manual carefully to avoid human injury and
device damage by irregular operations.
1.1 Safety Announcements
This section introduces the safety announcements that must be complied with
and pay special attention while installing, using, maintenance and other
relative operations.
Before operating, please read the announcements and operation instructions in
this section carefully to avoid accident. The DANGER, WARNING, CAUTION, etc.
in the manual are not all the safety announcements that you must abide by,
they are just the supplements for the safety announcements during operating.
Our Company does not undertake the responsibility caused by violating common
safety operation requirements or the safety standard of design, manufacture
and use.
1.1.1 Safety Instructions
There exists high temperature and high voltage inside the UPS. During using,
please strictly comply with all warnings and operation instruments on the UPS
and in the user manual.
1
1 Safety Description
KR-RM Series (10kVA-40kVA) UPS User Manual
The UPS is class C3 device. If it is used in residential purpose, it may cause
wireless interference. User should take actions to avoid the interference. No
liquid or other objects are allowed to enter the UPS. UPS must be well
grounded. In case of fire, please use dry power fire extinguisher. If using
liquid fire extinguisher, it may
cause electric shock.
1.1.2 Use Announcements for Battery
Please use specified battery. Non-specified battery will damage the UPS. Only
authorized professional can replace battery. Do not wear conductive objects,
such as
watches, bracelets and rings during operating. Wear rubber shoes and gloves
and use tools with insulated handle. Don’t put tools or other conductive
objects on the battery. It is prohibited to short the positive pole and
negative pole of the battery or connect them reversely, which is to avoid fire
or electric shock. Before connecting or disconnecting the battery terminals,
disconnect charger first. The battery must be with the same type, model and
manufacturer. Battery should be kept away from fire source or other electrical
equipments that may easily cause spark to avoid human injury. Don’t open or
destroy the battery. The electrolyte in the battery includes some dangerous
objects, such as strong acid, which will be harmful to skin and eyes. If it is
careless to touch the electrolyte, clean it by a lot of water immediately and
then check it in the hospital. The waste battery should be disposed according
to the local regulations.
2
KR-RM Series (10kVA-40kVA) UPS User Manual
1.1.3 Anti-Static Protection
1 Safety Description
The static generated by human bodies may damage the electrostatic-sensitive
components on PCB. Before touching the sensitive component, please wear anti-
static rings and well connect the other end of the anti-static rings to
ground.
1.2 Operation and Maintenance Requirements
Only authorized professionals are allowed to open the UPS chassis, or it may
cause electric shock and the caused UPS fault is out of the guarantee range.
If UPS needs to be moved, rewired or maintained, disconnect all electrical
connection, such as AC power, battery power, etc. to isolate power input. Do
not do any work on the UPS until it is powered off completely(10min).
Otherwise, the output may exist electricity, which may cause electric shock.
When dismantling fan, do not put fingers or tools into the rotating fan to
avoid device damage or human injury.
1.3 Environment Requirements
Do not put the UPS in the environment where has inflammable, explosive gas or
smog, do not do any operation in this environment.
Do not use the UPS in the place where has direct sunshine, rain or wet. The
normal work temperature of UPS is -540, relative humidity: 0%-95%, with no
condensation (recommended work temperature is 20~25, humidity is about 50%).
Put the UPS in the flat floor without vibration and the vertical gradient is
less than 5°. Keep
good ventilation around the UPS. The clearance between the rear or the side of
UPS and adjacent devices or wall should be at least 300mm500mm. Poor
ventilation will rise temperature inside
3
1 Safety Description
KR-RM Series (10kVA-40kVA) UPS User Manual
UPS, which will reduce the service life of inner components and even affect
the life span of the UPS.
The UPS must be used below 2000m. If the altitude exceeds 2000m, it needs to
decrease the rated power according to IEC62040-32011 to use.
4
KR-RM Series (10kVA-40kVA) UPS User Manual
Overview
2 Overview
This chapter mainly introduces the UPS’s model meaning, features, structure, work principle, etc.
2.1 Product Intro
KR-RM series UPS is whole high frequency, pure online, double-conversion,
smart product. The system is perfect power security for file server,
enterprise server, center server, micro-computer, concentrator, telecom
system, data center and others that require high quality power protection.
They are widely used in many key business areas, such as post, finance,
network, stock, railway, etc.
2.1.1 Model Meaning
KR kVA – RM
Figure2-1 Model meaning
Can be used in rack-mounting
Output power
When it is 30, that means the output power of the UPS is 30kVA; When it is 40,
that means the output power of the UPS is 40kVA; And so on.
KR series online UPS
1. Three-phase input three-phase output (three in three out) is 33 mode UPS,
three-phase input single-phase output (three in one out) is 31 mode UPS.
2. KR(10kVA-20kVA)-RM UPS supports 33 mode, 31mode and 11mode.
3. KR(30kVA-40kVA)-RM UPS supports 33 mode and 31mode.
4. KR(10kVA-40kVA)-RM UPS is a standard single machine model, which can be
upgraded to a parallel machine model by selecting and matching machine kits.
5
2 Overview
KR-RM Series (10kVA-40kVA) UPS User Manual
2.1.2 Features
Completely digitalized smart control
KR (10kVA-20kVA)-RM UPS support three-in and three-out mode UPS, three-in and
one-out mode UPS, one-in and one-out mode UPS. KR (30kVA-40kVA)-RM UPS support
three-in and three-out mode UPS, three-in and one-out mode UPS. The UPS can
monitor the grid frequency (50Hz/60Hz) and self-adapt the frequency. The
output voltage can be set to 208V/220V/230V/240V, which makes the use more
flexible.
Energy conservation and high efficiency
Adopts three-level inverter technology and PFC control technology, the output
voltage wave is perfect and the whole efficiency can be 96%, the input power
factor is greater than 0.99, which greatly improves the use ratio of electric
energy and reduces the load of power grid.
Smart fan speed control
The fan speed is adjusted automatically in accordance with the load status,
which prolong fan life and reduce noise.
ECO energy conservation mode design
The UPS is designed with ECO energy conservation mode. When the grid is good,
if the UPS operating in this mode, the bypass prior to output, and the
efficiency can be 99%.When the bypass voltage or frequency out of normal range
and cannot satisfy the user’s power supply requirement, it will switch to
inverter output, which guarantee the reliability of power supply and also,
save energy.
Low mains input voltage
Adopt the independent rapid detection technology. When output load is small,
even the battery voltage is 80V, which is the mains low limit, the battery
still doesn’t discharge. Therefore, in the mains mode, all output power gets
from the grid, which is to ensure the battery in 100% energy storage status,
and at the same time, reduce the battery discharge times and prolong the
service life.
Tower-mounting and rack-mounting
User can select tower-mounting or rack-mounting the UPS according to use
space, the LCD also can display corresponding direction on the basis of
placement mode.
6
KR-RM Series (10kVA-40kVA) UPS User Manual
2.1.3 Appearance
2 Overview
Figure2-2 Appearance
Operation panel
Figure2-3 Operation panel
Table2-1 Illustration for operation panel
No. Name
Illustration
Illustration for operation panel
1 LCD display
Shows the working status and system setting.
” ” page up button
2 and power off LED Short press ” ” button, the LCD will enter previous page
or
previous option. indicator
3 ” ” function button Short press ” ” button to confirm the command of the
current
7
2 Overview
KR-RM Series (10kVA-40kVA) UPS User Manual
No. Name and breathing light
Illustration
LCD page. Long press ” ” button for 3s, will entry the parameter and
function setting page. When UPS is on, ” ” button will be in a cycle of light
up to
fade out.
” ” page up button
4 and power on LED Short press ” ” button, the LCD will enter next setting
page.
indicator
Combination buttons operation instructions
5 Power off
Press the ” ” and ” ” button at the same time, the UPS off and the corresponding indicate LED is on.
6 Power on
Press the ” ” and ” ” button at the same time, the UPS on and the corresponding indicate LED is on.
Rear panel
KR(10kVA-20kVA)-RM
Figure2-4 Rear panel of KR(10kVA-20kVA)-RM
1. The wiring terminal of 33 mode and 31 mode have a little different. For
the detail of the wiring terminal of each mode please see 3.4.1 Wiring
Operation.
2. The intelligent slot is optional: Built-in SNMP card, RS485+dry contact
card and communication protocol transfer card.
KR(30kVA-40kVA)-RM
8
KR-RM Series (10kVA-40kVA) UPS User Manual
2 Overview
Figure2-5 Rear panel of KR(30kVA-40kVA)-RM
1. The wiring terminal of 33 mode and 31 mode have a little different. For
the detail of the wiring terminal of each mode please see 3.4.1 Wiring
Operation.
2. The intelligent slot is optional: Built-in SNMP card, RS485+dry contact
card and communication protocol transfer card.
3. If the BMD and EPO detection function won’t be used, please short the port
by equipped 4P terminal. When the function needs to be used, dismantle the
short wire of BMD or EPO port and connect it with corresponding status signal
input of maintenance bypass breaker or EPO.
Only when the bypass maintain switch state detection (BMD) and EPO port are
all shorted respectively, the UPS can work normally. If BMD port is
disconnected, the UPS will turn to bypass power supply, and at the same time,
the LCD shows BMD fault. Once the port recovers short connection, the fault
will be removed automatically. If the EPO port is disconnected, the UPS will
shut down all inverter and bypass output and at the same time, the LCD shows
EPO fault. The UPS needs to be power down completely and short connect the EPO
port, the fault will be removed automatically.
2.1.4 Fittings Illustration
KR(10kVA-20kVA)-RM KR-RM series (10kVA-20kVA) UPS and distribution module has
4 kinds of copper bar, as shown in Table2-2. Users can connect the copper bar
to the corresponding wiring arrangement after UPS or distribution module
according to their needs, and set them to 33 mode or 31 mode.
9
2 Overview
Table2-2 Copper bar illustration Copper bar No. Illustration
KR-RM Series (10kVA-40kVA) UPS User Manual
Sketch map
1#
2PIN copper bar
2#
2PIN copper bar
3#
3PIN copper bar
4#
3PIN copper bar
The installation position of the UPS main and power distribution module is as shown in Figure2-6, Figure2-7.
Figure2-6 Installation 33 mode copper bar position of KR(10kVA-20kVA)-RM UPS 10
KR-RM Series (10kVA-40kVA) UPS User Manual
2 Overview
Figure2-7 Installation 31 mode copper bar position of KR(10kVA-20kVA)-RM UPS
KR(30kVA-40kVA)-RM
KR-RM series (30kVA-40kVA) UPS and distribution module has 2 kinds of copper
bar, as shown in Table2-3. Connect the wiring terminal of the UPS or
distribution module with the copper bar according to needs. The copper bar for
short connect with the three phase bypass input terminal and three phase
output terminal only for 31 mode UPS.
Table2-3 Copper bar illustration Copper bar No. Illustration
Sketch map
1#
3PIN copper bar
2#
3PIN copper bar
The installation position of the UPS main and power distribution module is as shown inFigure2-8, Figure2-9.
11
2 Overview
KR-RM Series (10kVA-40kVA) UPS User Manual
Figure2-8 Installation 31 mode copper bar position of KR(30kVA-40kVA)-RM UPS
Figure2-9 Copper bar 2# installation position of 31 mode power distribution
module
2.2 Work Principle
2.2.1 Work Principle Diagram
Work principle diagram of the UPS is as shown in Figure2-10.
12
KR-RM Series (10kVA-40kVA) UPS User Manual
Maintenance bypass
Bypass input
Bypass static switch
2 Overview
Mains input
Rectification
/PFC AC
DC
Inverter
DC AC
Output
Battery input
DC DC
Charger
Figure2-10 Work principle diagram
The KR-RM series UPS includes rectification/PFC, inverter, charger, bypass
static switch etc function module, the input power includes mains input,
bypass input, battery input, the output mode includes inverter output, bypass
output and maintenance bypass output (if equipped).
When mains normal, the rectifier starts and the charger charges the battery at
the same time. When UPS off, if bypass normal, the system turns to bypass
output; when UPS on, the mains boosts by rectification/PFC and output DC bus
voltage, and then go through inverter and output pure sine-wave AC power, the
output turns to inverter output to load from bypass output (if equipped).
When mains abnormal, the battery voltage boosts by rectification/PFC and
output DC bus voltage, and then go through inverter and output pure sine-wave
AC power to load. When mains recover normal, the UPS turns to mains mode from
battery mode automatically.
2.2.2 Work Mode
There are 5 work modes of the UPS: normal mains power supply mode, battery
inverter mode, bypass power supply mode, ECO power supply mode and maintenance
bypass power supply mode. The maintenance bypass power supply mode can only
suitable for install the UPS series fitting with distribution module.
Normal mains power supply mode
When mains power normal, the UPS works in mains inverter status and charge the
battery at the same time. The work mode is as shown in Figure2-11.
13
2 Overview
Bypass input
Bypass static switch
KR-RM Series (10kVA-40kVA) UPS User Manual
Mains input
Rectification
/PFC AC
DC
Inverter
DC AC
Output
Battery input
DC DC
Charger
Figure2-11 Normal mains power supply mode (the thick solid line stands for the energy flow direction)
Battery inverter mode
When mains abnormal, the rectifier will transfer to battery input immediately, boost the battery voltage and then maintain the voltage of DC bus voltage to guarantee the inverter output continuous. As shown in Figure2-12.
Bypass input
Bypass static switch
Mains input
Rectification
/PFC AC
DC
Inverter DC
AC
Output
Battery input
DC DC
Charger
Figure2-12 Battery inverter mode (the thick solid line stands for the energy flow direction)
Before the battery stop discharging, if the mains recover normal, the rectifier will transfer to mains input automatically and charge the battery at the same time. That is to say, the UPS recover normal mains power supply mode. If the mains always abnormal and the battery is running up, the UPS will send sound and light alarm and stop working till battery low-voltage point. At that time, the buzzer long beeps to alarm, the power for load powers down. Under the circumstance of mains power outage completely, the UPS will shut down about 1min later automatically and close the power of the UPS to avoid the battery discharge slimly, thus to protect the service life of battery. Once the mains recovers, the UPS will start automatically and turn to normal mains power supply mode.
14
KR-RM Series (10kVA-40kVA) UPS User Manual
2 Overview
Bypass power supply mode
Under the circumstance of bypass voltage normal, when UPS off or fault (such as inverter output overload, over-current surge or IGBT over-temperature etc) while UPS on, the UPS will output by bypass. When UPS on and the fault removed, it will turn to inverter output again. If the same fault occurs more than 5 times in a short time, the UPS protects and output by bypass until power off manually or power down and remove the fault, restart the UPS and then it will recover normal work.
Bypass input
Bypass static switch
Mains input
Rectification
/PFC AC
DC
Inverter
DC AC
Output
Battery input
DC DC
Charger
Figure2-13 Bypass power supply mode (the thick solid line stands for the energy flow direction)
ECO power supply mode (just suitable for single UPS)
At the ECO mode, when bypass voltage normal, the power for load is prior
supplied by bypass, when bypass voltage abnormal, the power for load turns to
inverter. ECO mode is an economic operation mode. For the load which does not
require high quality, user can select ECO mode to reduce the energy
consumption. At the ECO mode, the UPS efficiency can be 99%.
Maintenance bypass power supply mode (suitable for the system with
distribution module)
When the UPS needs to be maintained and the power supply for load cannot be
interrupted, user can shut down the inverter and make the UPS works in bypass
status, then switch on the maintenance bypass breaker and switch off the mains
input breaker and bypass input breaker, output breaker. During the
transforming of manual maintenance bypass, AC power is supplied for load by
maintenance bypass breaker. At this time, the inner UPS has no electricity,
maintainer can perform the maintenance safely.
15
2 Overview
Maintenance bypass
Bypass input
Bypass static switch
KR-RM Series (10kVA-40kVA) UPS User Manual
Mains input
Rectification
/PFC AC
DC
Inverter
DC AC
Output
Battery input
DC DC
Charger
Figure2-14 Maintenance bypass power supply mode (the thick solid line stands for the energy flow direction)
2.3 Optionals
KR-RM series UPS can equip distribution module or battery box according to
needs.
2.3.1 Distribution Module
Appearance
Figure2-15 Appearance of distribution module
Front panel of KR(10kVA-20kVA)-RM
The operation breakers of distribution module locate inside the front panel,
when operating, it needs to open the front panel fist. Open the front panel
way as shown in Figure2-16.
16
KR-RM Series (10kVA-40kVA) UPS User Manual
2 Overview
Figure2-16 Open the front panel of KR(10kVA -20kVA)-RM UPS
When install the front panel, insert the buttons at right side into the body,
and then insert the buttons at left side into the body.
Figure2-17 Distribution module illustration (dismantle front panel) of
KR(10kVA -20kVA)-RM UPS
Rear panel of KR(10kVA-20kVA)-RM
Figure2-18 Distribution module illustration (dismantle front panel) of
KR(10kVA -20kVA)-RM UPS 17
2 Overview
KR-RM Series (10kVA-40kVA) UPS User Manual
Front panel of KR(30kVA-40kVA)-RM
The operation breakers of distribution module locate inside the front panel,
when operating, it needs to dismantle the front panel fist. Open the front
panel way as shown in Figure2-19.
Figure2-19 Open the front panel of KR(30 kVA -40kVA)-RM UPS
When install the front panel, insert the buttons at right side into the body,
and then insert the buttons at left side into the body.
Figure2-20 Distribution module rear panel of KR(30 kVA -40kVA)-RM UPS
Operation method of maintenance bypass mode: dismantle the protection plate of
maintenance bypass breaker, the detection switch of maintenance bypass status
pop up automatically, the UPS close the inverter and turn to bypass to supply
power, then close the maintenance bypass breaker, turn off the AC input
breaker, bypass breaker and AC output breaker, at this time, the power for
load turns to maintenance bypass, the input and output of the UPS is
disconnected, the maintenance can be done. Recover inverter power supply from
maintenance bypass power supply: connect the wires of UPS and distribution
module (including bypass maintain detection signal wire), and then close the
AC input breaker, bypass breaker and AC output breaker, after the work power
of UPS normal and the LCD show bypass output voltage, turn off the maintenance
bypass breaker and lock the protection plate of maintenance bypass breaker,
finally, press the power on button to start the inverter to supply power.
18
KR-RM Series (10kVA-40kVA) UPS User Manual
Rear panel of KR(30kVA-40kVA)-RM
2 Overview
Figure2-21 Distribution module rear panel of KR(30kVA -40kVA)-RM UPS
2.3.2 Battery Box Appearance
Figure2-22 Appearance of battery box
Rear panel
Figure2-23 Rear panel of battery box 19
3 Installation
KR-RM Series (10kVA-40kVA) UPS User Manual
3 Installation
This chapter mainly introduces the installation of the UPS, including
unpacking and checking, cable selection, installation, electrical connection,
etc.
3.1 Unpacking and Checking
Unpack and check the UPS according to follows. Inspect the appearance for
shipping damage. If any shipping damage is found, report it to the
carrier immediately. Check the delivery list to see if the types of
accessories are complete and correct. If there is any
discrepancy, contact the distributor immediately.
3.2 Installation Preparation
3.2.1 Tools
Tools
20
KR-RM Series (10kVA-40kVA) UPS User Manual
Tools
3 Installation
3.2.2 Select Breaker & Wires
The selecting for AC input and output wire, DC input wire and corresponding
breakers needs to be judged by the UPS’ max. steady state phase current.
Table3-1 shows the max. steady state phase current of each work mode, Table3-2
shows the rated current of recommended breakers, Table3-3 shows the min.
recommended wire cross-sectional area. Select the wires and breakers according
to Table3-1, Table3-2, Table3-3.
Table3-1 UPS max. steady state phase current
type
10kVA
15kVA
20kVA
30kVA
40kVA
Mode type
33 31 11 33 31 11 33 31 11 33 31 33 31
AC input (A)
18 18 54 26 26 78 35 35 105 59 59 75 75
21
3 Installation
KR-RM Series (10kVA-40kVA) UPS User Manual
type
10kVA
15kVA
20kVA
30kVA
40kVA
Mode type
33 31 11 33 31 11 33 31 11 33 31 33 31
Bypass input (A) 15 46 46 23 68 68 31 91 91 45 136 61 182
DC input (A)
29 29 29 44 44 44 58 58 58 83 83 111 111
AC output (A) 15 46 46 23 68 68 30 91 91 45 136 61 182
3.2.3 Select Input Breaker
We suggest to add a breaker (we suggest to select the breaker with feedback double pole disconnection equipment) or distribution cabinet that matches the UPS power at the front of the UPS input to insulate the mains. Considering the UPS charge power and the impact current while power on, the selected breaker must be 1.5 to 2 times of UPS input max. current, and cannot with leakage protection, which is to avoid wrong action of breaker. The distribution box should be manufactured by professional company. The breaker of DC input should be select more than the 250V DC. The selection of breaker, please reference Table3-2.
Table3-2 Recommended input breaker list
type
10kVA
15kVA
20kVA
30kVA 40kVA
Mode type 33 31 11 33 31 11 33 31 11 33 31 33 31
32 32 63 50 50 100 63 63 125 100 100 100 100
AC input (A)
3P 3P 1P 3P 3P 1P 3P 3P 1P 3P 3P 3P *3P
Bypass input 32 63 63 50 100 100 63* 125 125 100 200 100 250
(A)
3P 1P 1P 3P 1P 1P 3P 1P 1P 3P 1P 3P 1P
50 50 50 63 63 63 80 80 80 125 125 175 175
DC input (A)
3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P *3P
32 63 63 50 100 100 63 125 125 100 200 100 250
AC output (A)
3P 1P 1P 3P 1P 1P 3P 1P 1P 3P 1P 3P *1P
3.2.4 Select Wires
For the wire cross-sectional area of AC input, output and battery please see the recommended value in Table3-3,Table3-4 and Table3-5. The cross-sectional area of the following cable is only for
22
KR-RM Series (10kVA-40kVA) UPS User Manual
Installation
reference when the user is connected wire for a length of about 5 meters. If the length of the lead wire exceeds 20 meters, the cross-sectional area of the conductor wire shall be increased.
For KR(10kVA-20kVA)-RM UPS is set to 31 mode or 11mode, since the UPS is
equipped with input and output three-phase connector, the bypass input and out
wires are recommended according to the single wire. When the UPS is set to 11
mode, the UPS is not equipped with the input and output three-phase connector,
thus the AC input wires are recommended according to the three wires. Please
notes that when the UPS is single phase input, the three firewires need to be
connected to the same phase of power input.
When KR(30kVA-40kVA)-RM UPS is set to 31 mode, bypass input and output wires
are recommended as single wire. When the cross-sectional area of single wire
is greater than 35mm2, it is recommended to connect two wires in parallel.
Table3-3 Recommended cross-sectional area of wire (unit: mm2, environment temperature: 25)
type
KR10kVA-RM
KR15kVA-RM
KR20kVA-RM
Mode type
33 31 11
33 31 11
33 31 11
AC input live wire 43 43 4*3
(U/V/W)
63 63 6*3
103 103 10*3
AC input neutral wire 4*1
(N)
101 101 6*1
161 161 101 161 16*1
Bypass input live wire 4*3
(U/V/W)
101 101 6*3
161 161 103 161 16*1
AC output live wire 4*3
(U/V/W)
101 101 6*3
161 161 103 161 16*1
AC output neutral wire 4*1
(N)
101 101 6*1
161 161 101 161 16*1
DC input (+/BATN/-) 63 63 63 103 103 103 103 103 10*3
Grounding wire (PE) 61 61 61 101 101 101 101 101 10*1
Table3-4 Recommended cross-sectional area of wire (unit: mm2, environment temperature: 25)
type
KR30kVA-RM
KR40kVA-RM
Mode type
33 mode 31 mode
33 mode 31 mode
AC input live wire (U/V/W)
16*3
16*3
16*3
16*3
23
3 Installation
KR-RM Series (10kVA-40kVA) UPS User Manual
type
KR30kVA-RM
Mode type
33 mode 31 mode
AC input neutral wire (N)
16*1
16*2 (parallel)
Bypass input live wire (U/V/W) 10*3
35*1
AC output live wire (U/V/W)
10*3
35*1
AC output neutral wire (N)
10*1
16*2 (parallel)
DC input (+/BATN/-)
16*3
16*3
Grounding wire (PE)
16*1
16*1
KR40kVA-RM 33 mode 31 mode
16*1
25*2 (parallel)
163 163
252 (parallel) 252 (parallel)
16*1
25*2 (parallel)
253 161
253 251
Table3-5 Contrast list between wires and wiring terminals
Wire cross-sectional area (unit: mm2)
Wiring terminal type Perforation
Straight cutting
4
RV3.5-6
/
6
RV5.5-6
/
10
RNBS8-6
E10-12
16
RNBS14-6
E16-12
25
RNBS22-6
E25-16
35
RNBS38-8
/
KR(10kVA-20kVA)-RM UPS
The wiring terminals of KR(10kVA-20kVA)-RM UPS recommend type as shown in Table3-1. If users have additional terminals required, please check dimensions to ensure proper selection according to Table3-7.
24
KR-RM Series (10kVA-40kVA) UPS User Manual
3 Installation
Figure3-1 Wiring terminal dimensions of KR(10 kVA-20kVA)-RM UPS
Table3-6 Dimensions limit of wiring terminal
Dimensions KR10kVA-RM
KR15kVA-RM
KR20kVA-RM
(unit: mm) 4
6
10
6
10
16 10
16
A
12.1
12.1
12.1
B
6.2
6.2
6.2
C
6.2
6.2
6.2
D
6.2
6.7 7.2 6.7 7.2 9.0 7.2 9.0
KR(30kVA-40kVA)-RM UPS
Wiring terminal dimensions of The wiring terminals of KR(30kVA-40kVA)-RM UPS recommend type as shown in Figure3-2. If users have additional terminals required, please check dimensions to ensure proper selection according to Table3-7.
Figure3-2 Wiring terminal dimensions of KR(30 kVA-40kVA)-RM UPS
Table3-7 Dimensions limit of wiring terminal
Dimensions (unit: mm) KR30kVA-RM
10
16
A
12.5
12.5
KR40kVA-RM
16
25
12.5
16.7
25
3 Installation
KR-RM Series (10kVA-40kVA) UPS User Manual
Dimensions (unit: mm) KR30kVA-RM
10
16
B
24
24
C
4.7±0.3
5.83±0.3
KR40kVA-RM
16
25
24 5.83±0.3
29.4 7.43±0.3
When the KR(30kVA-40kVA)-RM UPS is set to 31mode, the terminal (as shown in Figure3-3 )will be used, and it size requirements are shown in Table3-8.
Figure3-3 Wiring terminal dimensions
Table3-8 Dimensions limit of wiring terminal
Mode
KR(30kVA-40kVA)-RM
Dimensions (unit: mm) A B C D
25 12.2 6.15 / 11.5
35 15.4 8.3 8.4 13.3
The equipped wires by our company are all passed the national standard or UL
certification, the quality is perfect and meets the requirements of safety
standard. The cross-section area of the above cables is only a reference value
or users connecting 5 meters long. If the length of the cable exceeds 20
meters, the cross-section of the wires will be increased accordingly
3.3 Mechanical Installation
The installation for the UPS can be tower-mounting and rack-mounting, user can
select suitable installation way according to actual condition.
26
KR-RM Series (10kVA-40kVA) UPS User Manual
3 Installation
3.3.1 Tower-mounting
Single UPS installation
Step 1 Take out a pair of support base and 1U joint base, assemble them
together, as shown in Figure3-4, and lay them flat for the UPS tower base.
Figure3-4 Assemble support base Step 2 Put the UPS onto the assembled support base, as shown in Figure3-5.
Figure3-5 Install the UPS —-End
Install the UPS with battery box or distribution module
When equip battery box or distribution module, the installation procedure is
the same. In this section, we take the installation of one UPS and one
distribution module as an example to illustrate. Step 1 Take out a pair of
support base and other 1U joint bases, assemble them together, as shown in
Figure3-6.
27
3 Installation
KR-RM Series (10kVA-40kVA) UPS User Manual
Figure3-6 Assemble support base
When one optional added, 3 pieces of 1U joint base need to add, the assemble
way is the same.
Step 2 Put the UPS and distribution module onto the assembled support base, as
shown in Figure3-7.
Figure3-7 Install the UPS and distribution module Step 3 Take out the
combination parts and screws, and fasten them onto the top of the UPS and
distribution
module, as shown in Figure3-8.
28
KR-RM Series (10kVA-40kVA) UPS User Manual
3 Installation
Figure3-8 Install combination units
Every two adjacent devices need to be connected by two combination parts at
the top of the device, that is to say, every add one optional (distribution
module or battery box), it needs to install another 2 combination parts. —-End
3.3.2 Rack-mounting
KR-RM series UPS and the optional also can be installed in 19 inch standard
cabinet to use.
The rack-mounting procedure of UPS, battery box and distribution module is the
same, in this section, we take the UPS installation as an example to
illustrate.
Step 1 Fasten the two angle irons onto the two sides of the UPS by 4 sunk
screws M4×8, as shown in Figure3-9.
29
3 Installation
KR-RM Series (10kVA-40kVA) UPS User Manual
Figure3-9 Install angle iron
Do not transport the UPS, battery box or power distribution module by angle
iron. The front panel can be dismantled front, during transporting, do not
make it bear any force. The device needs to be transported by two or more
people. Step 2 Push the UPS into the cabinet, and fasten it by screws, as
shown in Figure3-10.
Figure3-10 Fasten the UPS
The battery box is heavy, when installing, the battery box must be installed
from bottom and down below the UPS. —-End
30
KR-RM Series (10kVA-40kVA) UPS User Manual
3.4 Electrical Connection
3 Installation
Before connecting, ensure that the external connected front breakers of mains, battery are all off. DO NOT connect wires with electricity.
While wiring, avoid making the power wire at the place where is easy to be
trod or tripped.
If there is an optional distribution module, the wiring of KR-RM series UPS
and distribution module (optional) shall be connected with the distribution
module wire first, and then the UPS wire.
3.4.1 Wiring Operation of KR(10kVA-20kVA)-RM UPS 33 mode
The input and output wiring of 33 mode UPS is as shown in Figure3-11.
Figure3-11 The 33 mode wiring of KR(10kVA-20kVA)-RM UPS 31
3 Installation
KR-RM Series (10kVA-40kVA) UPS User Manual
31 mode
The input and output wiring of 33 mode UPS is as shown in Figure3-12.
Figure3-12 The 31 mode wiring of KR(10kVA-20kVA)-RM UPS
3.4.2 Wiring Operation of KR(30kVA-40kVA)-RM UPS 33 mode
The input and output wiring of 33 mode UPS is as shown inFigure3-13. The
output and input have two N-terminal bar respectively, and they separate
parallel connection. The input and output single cable of the 33 mode can be
connected to one of the groups.
32
KR-RM Series (10kVA-40kVA) UPS User Manual
3 Installation
Figure3-13 The 33 mode wiring of KR(30kVA-40kVA)-RM UPS
31 mode
Take out a couple of copper bar 1#, connect them to the wiring terminal of
UPS. The wiring diagram of 31 mode UPS is as shown in Figure3-14. When the
wire output and the input N wire are in parallel of two cables, the two groups
of N-terminals are connected separately.
Figure3-14 The 31 mode wiring of KR(30kVA-40kVA)-RM UPS 33
3 Installation
3.4.3 Wiring Between UPS and Battery Box
KR-RM Series (10kVA-40kVA) UPS User Manual
DC battery switch must be provided between the battery and UPS.
User can select tower-mounting or rack-mounting the UPS according to use
space. Specific installation requirements are as follows:
Rack-mounting products: UPS installed in the bottom layer, distribution module
installed in the top layer for easy cable connection and operation.
Tower-mounting products: the distribution module is installed on the left side
of UPS to facilitate cable connection and operation. The battery box is on the
left side of distribution, as shown in Figure3-15.
Figure3-15 Tower-mounting
3.4.4 Wiring Between UPS and Battery Box of KR(10kVA-20kVA)-RM UPS
The wiring of parallel connected battery box and each mode UPS is the same, in
this section, we take KR20kVA-RM as an example to illustrate.
34
KR-RM Series (10kVA-40kVA) UPS User Manual
3 Installation
Figure3-16 Wiring diagram between UPS and two parallel connected battery boxes
Figure3-17 Wiring diagram between UPS and two sets parallel connected battery
boxes (each set has two battery boxes)
35
3 Installation
KR-RM Series (10kVA-40kVA) UPS User Manual
The wiring between UPS and parallel connected battery boxes must be connected
strictly according to Figure3-16,Figure3-17, avoid wrong connection or short
circuit.
3.4.5 Wiring Between UPS and Battery Box of KR(30kVA-40kVA)-RM UPS
The wiring of parallel connected battery box and each mode UPS is the same, in
this section, we take KR40kVA-RM as an example to illustrate.
Figure3-18 Wiring diagram between UPS and two sets parallel connected battery
boxes (each set has two battery boxes)
The wiring between UPS and parallel connected battery boxes must be connected
strictly according to Figure3-18, avoid wrong connection or short circuit.
36
KR-RM Series (10kVA-40kVA) UPS User Manual
3 Installation
Wiring of external batteries
If user needs to connect batteries externally, please connect the wires as follows.
This series UPS’s battery input adapt positive and negative battery group (each battery group default has 16 positive cell and 16 negative cell). Figure3-19 shows one wiring way: one battery cabinet has 32 cells and one 3P breaker, the external wiring includes BATT.+, BATT.- and battery neutral wire. The selection of battery wires and breaker specification please see Table3-2, Table3-3 and Table3-4.
NO.1
- –
NO.2
- –
NO.3
- –
……
NO.16
- –
BATT. +
Battery cabinet
NO.32
- –
NO.31
- –
NO.30
- –
……
NO.17
- –
BATT. N
UPS
BATT. –
Figure3-19 Wiring diagram of external batteries
3.4.6 Wiring Between UPS and Distribution Module of KR(10kVA-20kVA)-RM UPS
Wiring of each standard UPS and distribution module is shown in Figure3-20 and
Figure3-21.
33 mode
The supporting UPS and the distribution wire are connected one to one
according to the wire information.
37
3 Installation
KR-RM Series (10kVA-40kVA) UPS User Manual
Figure3-20 Wiring Between 33 mode UPS and Distribution Module of KR(10kVA-
20kVA)-RM UPS
31 mode
The copper bar from Table2-2 are short connect with 3P terminal bar of the
bypass and output. The supporting UPS and the distribution wire are connected
one to one according to the wire information.
Figure3-21 Wiring Between 31 mode UPS and Distribution Module of KR(10kVA-
20kVA)-RM UPS
Ensure that the wires are connected properly and firmly, and then install the
wiring protection plate to the device (the installation procedure is as
follows). 38
KR-RM Series (10kVA-40kVA) UPS User Manual
3 Installation
3.4.7 Wiring Between UPS and Distribution Module of KR(30kVA-40kVA)-RM UPS
Wiring of each standard UPS and distribution module is shown in Figure3-22 and
Figure3-23.
33 mode
The supporting UPS and the distribution wire are connected one to one
according to the wire information.
Figure3-22 Wiring Between 33 mode UPS and Distribution Module of KR(30kVA-
40kVA)-RM UPS
31 mode
The 2# copper bar from Table2-3 are short connect with 3 pin terminal bar of
the bypass and output. The supporting UPS and the distribution wire are
connected one to one according to the wire information.
39
3 Installation
KR-RM Series (10kVA-40kVA) UPS User Manual
Figure3-23 Wiring Between 31 mode UPS and Distribution Module of KR(30kVA-
40kVA)-RM UPS
Ensure that the wires are connected properly and firmly, and then install the
wiring protection plate to the device (the installation procedure is as
follows).
Install wiring plates
The wiring covers’ install procedure of each mode UPS and distribution module
is the same, in this section, we take KR40kVA-RM as an example to illustrate.
Step 1 Remove the flat-head screws from the protective cover before wiring, as
shown in Figure3-24.
Figure3-24 Remove the screws from the protective cover 40
KR-RM Series (10kVA-40kVA) UPS User Manual
Step 2 Remove the protective cover, as shown in Figure3-25.
3 Installation
Figure3-25 Remove the protective cover Step 3 Connect the wires in accordance with 3.4.1 Wiring Operation as shown in Figure3-26.
Figure3-26 Connect the wires Step 4 Reinstall the wiring row cover in the
corresponding position of the chassis, as shown inFigure3-27.
Figure3-27 Reinstall the wiring row cover 41
3 Installation Step 5 Fix with the flat head screws, as shown in Figure3-28.
KR-RM Series (10kVA-40kVA) UPS User Manual
Figure3-28 Fix with the flat head screws
—-End
3.4.8 Wiring of Parallel System
Step 1 Install the battery and UPS of parallel system separately according to
3.3 Mechanical Installation. Step 2 Connect the wires of input, output,
battery and grounding in parallel system on the basis of
Figure3-29, Figure3-30, Figure3-31 or Figure3-32. KR(10kVA-20kVA)-RM
42
KR-RM Series (10kVA-40kVA) UPS User Manual
UPS1
NBF 1
NBF 2
UPS2
NBF 3
NBF 4
3 Installation
Input N Input W
Ground Output W Output V Output U Output N Bypass W Bypass V Bypass U
NBF 5
NBF 6
NBF 7
NBF 8
Battery Battery N
Battery + Output N
Input W Input V Input U
Figure3-29 Diagram of 33 mode parallel system wiring of KR(10kVA-20kVA)-RM UPS
43
3 Installation
UPS1
NBF 1
NBF 2
KR-RM Series (10kVA-40kVA) UPS User Manual
UPS2
NBF 3
NBF 4
Ground Output Output N
NBF 5
NBF 6
NBF 7
NBF 8
Battery Battery N
Battery + Input N Input W Input V Input U
Figure3-30 Diagram of 31 mode parallel system wiring of KR(10kVA-20kVA)-RM UPS KR(30kVA-40kVA)-RM
44
KR-RM Series (10kVA-40kVA) UPS User Manual
UPS1
NBF 1
NBF 2
UPS2
NBF 3
NBF 4
3 Installation
Output N Output W Output V Output U Bypass W Bypass V Bypass U
NBF 5
NBF 6
NBF 7
NBF 8
Input N Input W Input V Input U Battery Battery N Battery +
Figure3-31 Diagram of 33 mode parallel system wiring of KR(30kVA-40kVA)-RM UPS
45
3 Installation
UPS1
NBF 1
NBF 2
KR-RM Series (10kVA-40kVA) UPS User Manual
UPS2
NBF 3
NBF 4
Output N Output N
Output W Output V Output U Bypass W Bypass V Bypass U
NBF 5
NBF 6
NBF 7
NBF 8
Input N Input N Input W Input V Input U Battery Battery N Battery +
Figure3-32 Diagram of 31 mode parallel system wiring of KR(30kVA-40kVA)-RM UPS
Step 3 Connect the parallel port of each unit in parallel by parallel wires,
as shown in Figure3-33.
Figure3-33 Wiring diagram of parallel wire 46
KR-RM Series (10kVA-40kVA) UPS User Manual
3 Installation
1. The wiring of parallel port of each mode UPS is the same, in above figure,
we take KR30kVA-RM as an example to illustrate.
2. The UPS parallel system requires the user to distribute power by himself.
1. The wiring and phase sequence of each unit in the parallel system must be
the same strictly, which is to ensure the bypass power of parallel system is
the same phase.
2. The parallel system of this series UPS can share battery groups, but the
battery amount of each UPS must be the same.
3. Connect the parallel ports of each unit in parallel by equipped shielding
communication wire. The two RJ45 parallel ports are the same, they are
redundancies and backup for each other to increase the reliability of the
system, once one of them is not connected, the UPS will send alarm prompting.
—-End
47
4 Screen Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
4 Screen Operation
This chapter mainly introduces the working parameters, working status and system settings of UPS screen.
4.1 Menu Hierarchy
The menu hierarchy of the screen is as shown in Figure4-1.
MAIN
System DateEnergy Flow DiagramDevice State
DETAIL
Grid BYP BAT REC INV UPSTEMP
GRID
Grid VGrid IGrid F
Monitor
BYP
BYP VBYP IBYP F
BAT
BAT VBAT IRemain TRemain CState
OUT
OUT VOUT IOUT FActive AppareLoadPF
DEVICE
PowerS/N.PFC VerINV VerHMI VerSystem VerID
Main Page
Parameter Set
BYP Para Set
V RangeF Range
BAT Para Set
CapNumCharge ILV ProtectEquCharVFloCharVTemp CompForceCHG
OUT Para Set
Rated VV AdjustRated F
Set Manage
Functon Set
Mode Set ECO Set BAT Test Else Set
Wire(3/3 3/1)ParaMod(Single/BSC/Expand/Redund) ECO EnV RangeF Range
BAT Test(StandardDepthTiming)TestTime Backup TOff No BYPSilenceAutoStartID
Log Manage Screen Set Permission Set
History Query DateTimeLangInstal(Rack/Tower/Auto)
ProbatProTimeDefault
Figure4-1 Menu hierarchy of the screen
The parameter values and other details in the pictures in this chapter are for illustration only. The actual parameters should be displayed on the LCD of the product.
48
KR-RM Series (10kVA-40kVA) UPS User Manual
4 Screen Operation
4.2 Power On for The First time
After power on, the system will enter the welcome page first. If the UPS is
started for the first time, the welcome page will stay 5s after entering the
password input page, as shown in Figure4-2.
Figure4-2 password input page
Each series of the UPS is different, the Figure4-2 just for an example, the
actual displayed should be base on the LCD of the product.
User needs to input the password correctly before continuing to use it. Please
contact the local customer service, report the machine serial number on the
LCD, you can get the boot password. After entering the password, press the
function button shortly, if the power-on password is correct, then go to the
monitoring main page, if the password is wrong, the screen will have the word
“password error” display. Password match successfully after long-term
validity, subsequent use does not need to be entered again.
4.3 Main Page
After the UPS is powered on, it will enter the system monitoring main
interface-energy flow chart display page, as shown in Figure4-3.
49
4 Screen Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
Figure4-3 Main Page After entering the main interface, it is easy to monitor
the system. The meaning of the icons on the main interface is as follows:
System bypass icon. System rectification icon. System inverter icon.
System battery icon. The internal energy bar of the battery changes
accordingly depending on the current battery status and battery voltage.
System current date display. System current operating status display. Monitor
page number display. The working state and energy flow on the main interface
visually describe the operating state of the system and the operation of the
module.
4.4 System Working Status Display
The operating status of the system is: main power inverter output, battery
inverter output, ECO bypass output, maintenance bypass output. Interface
display for each working status as shown in Figure4-4 to Figure4-7.
50
KR-RM Series (10kVA-40kVA) UPS User Manual
Figure4-4 Main power Inverter Output Figure4-5 Battery Inverter Output
Figure4-6 ECO/Bypass output Figure4-7 Maintenance bypass output
4 Screen Operation 51
4 Screen Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
4.5 Monitoring Page
After the system automatically enters the monitoring page, the monitoring page in the lower right corner has page number display, according to the current set of different system, the total number of monitoring pages displayed is different. By pressing the up/down page button, you can turn on the monitoring page, and the monitoring page loop display, three-in and three-out page number and page loop order as shown in Figure4-8.
1.Energy Flow Diagram
2.Detail Page
3.Output Information
4.Output Power
5.Output Load Percent
9.Device Information
8.BAT Information
7.BYP Information
6.Grid Information
Figure4-8 three-in and three-out page number and page loop order
4.6 Setting Page
On the monitoring page, by long pressing function button for 3s, you can go to
the settings page. And the setting page structure diagram as shown in
Figure4-9. In the settings page, by short pressing the up/down page button,
you can realize the function of selecting up/down scrolling, and then with the
function button short press and short press function, you can realize the
setting function of the corresponding setting item. Besides, setting the lower
right corner of the page has a return button, by short pressing the up/down
page button and with the function button short press function, you can achieve
the function of returning to the previous page.
52
KR-RM Series (10kVA-40kVA) UPS User Manual
4 Screen Operation
Parameter Set
BYP Para Set BAT Para Set OUT Para Set
V RangeF Range CapNumCharge ILV ProtectEquCharVFloCharV
Rated VV AdjustRated F
Set Manage
Functon Set
Mode Set ECO Set BAT Test
Wire(3/3 3/1)ParaMod(Single/BSC/Expand/Redund) ECO EnV RangeF Range
BAT Test(StandardDepthTiming)TestTime
Log Manage
Else Set
Backup TOff No BYPSilenceAutoStartID History Query
Screen Set
DateTimeLangInstal(Rack/Tower/Auto)
Permission Set
Figure4-9 Setting page structure diagram
ProbatProTimeDefault
4.7 Management Setting
In any monitoring page by long pressing function button for 3s can enter the
settings management page, the page is mainly for the directory display
function, the page display includes: parameter set, function set, log manage,
screen set and permission set five items, as shown in Figure4-10. Each item
has a hollow box icon ” ” before it, and if the item is selected, the hollow
box icon becomes a solid box ” ” icon. You can select page content by pressing
the up/down page button. When you select the back button ” ” to the lower
right corner, the back button is selected and appears as a opposite color
status ” “.
Figure4-10 Set manage page After the page option selection is complete, short
press the function button to go to the corresponding next settings page. When
you select the back button ” ” in the settings management page and press the
function button shortly, the display takes you to the previous page.
53
4 Screen Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
4.7.1 Parameter Setting
In the settings management page, select the “Parameter Set” option, and short
press the function button shortly to enter the parameter settings page, which
is a second class page, mainly for the directory display function, the page
display includes: bypass parameter settings, battery parameter settings and
output parameter setting three, as shown in Figure4-11 and Figure4-12.
Figure4-11 Parameter setting page
Figure4-12 Details of parameter setting page By shortly pressing the up/down
page button to achieve the page option selection, the selected option in front
of the hollow box will become a solid box, at this time short press function
button can go to the corresponding next level of settings page. When you
select the back button at the lower right corner, the return button is
displayed as a opposite color state, and this time, short press function
54
KR-RM Series (10kVA-40kVA) UPS User Manual
4 Screen Operation
button can go to the previous level of the page, and the previews class
parameter settings page is the settings management page.
There are four next level pages on the parameter settings page, one bypass
parameter settings page, two battery parameter settings pages, and one output
parameter settings page. In the battery parameter page, you can select the
setting options by short pressing the up/down page turning button. After the
option selection is complete, such as selecting “number of sections”, you can
enter the setting of the number of sections by short pressing the function
button, the number of sections displayed “20” will flash, and this time, you
can set the section number minus/plus by pressing the up/down page turning
button. When the section number is adjusted to the value to be set, the
section number setting can be completed by the short function button.
4.7.2 Function Setting
In the Settings Management page, select the “Function Set” option, and short
press the function button to enter the function settings page, and it mainly
for the directory display function, the page display includes: mode set, ECO
set, battery test and else set four items, as shown in Figure4-13.
By shortly pressing the up/down page button to achieve the page option
selection, the selected option in front of the hollow box will become a solid
box, at this time short press function button can go to the corresponding next
level of settings page. When you select the back button in the lower right
corner, the return button is displayed as a opposite color state, at which
point the short press function button can go to the previous level of the
page, and the previews class function settings page is the settings management
page.
Figure4-13 Function setting page There are four next-level pages on the
function set page, and the page display includes: mode set, ECO set, battery
test and else set four items, as shown in Figure4-14. The following is to take
the battery test page as an example, explain the three-level page setting
method, the rest of the page setting method is the same, will not repeat the
story.
55
4 Screen Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
On the battery test page, you can select the options by short pressing the
up/down page button, and after selecting “Standard Test”, you can enter the
settings for the standard test by short pressing the function button, at which
point the standard test option “Off” flashes;
The on/off option switch can be performed for the standard test, and after
adjusting to the specific option, the standard test can be completed by short
pressing the function button.
Because the current three battery tests cannot be performed at the same time,
when one battery test is set to on, the options for the other two battery
tests automatically appear to be off. In addition, since the discharge time
setting is only available under the timing test conditions, when the timing
test is set to off, the discharge time item is not displayed.
Figure4-14 Details of function setting page
1. Battery test settings: Standard test is that UPS return to the
electrolytic inversion after turning to battery inverter for 10s at power-on
state, and the depth test is that UPS to go to battery inversion until the
battery discharges to the under-voltage alarm, and then returns to the main
power inverter.
2. Back-up time display settings: When there are other more accurate battery
remaining discharge time monitoring devices in the system, you can choose to
turn off the battery residual discharge time display function of the UPS
itself.
3. Call self-start setting: manual mode is that human shutdown needs to be
re-manual power edged to trigger the UPS self-start function after the power
generation, automatic mode is as long as the normal power generation UPS is
self-starting, under this condition UPS shutdown can only be manually shut
down when the battery is reversed, suitable for unattended applications.
56
KR-RM Series (10kVA-40kVA) UPS User Manual
4 Screen Operation
4.7.3 Screen Setting
In the Settings management page, select the “Screen Settings” option, and
short press the function button to enter the screen settings page, the page is
a three-level page, the page display includes: date settings, time settings,
language settings, display mode settings four items, as shown in Figure4-15.
The page option selection can be achieved by pressing the top/bottom page
button shortly, and the hollow box in front of the selected option becomes a
solid box. When you select the back button in the lower right corner, the back
button is displayed as a opposite color state, at which point the short press
function button can go to the next level of the page, and the previous level
page on the screen settings page is the settings management page.
Figure4-15 Screen set page
On the screen settings page, select “Date” and short press the settings button
will enter the date settings, where “2019” in the date will flash, and when
flashing, you can set the section number minus/plus by pressing the up/down
page turning button. After the section number is adjusted to the value to be
set, you can short press the function button to enter the month setting in the
date. When entering the month setting, the value “07” corresponding to the
month will flash, user can set the month number minus/plus by short pressing
the up/down page turning button when the month is flashing, short press
function button to enter the day setting in the date after adjusting the month
number to the corresponding number. The same is true, when entering the day
setting, the value “28” corresponding to the day will flash, user can set the
day number minus/plus by short pressing the up/down page turning button when
the day is flashing, short press function button to finish the date setting
after adjusting the day number to the corresponding number. The time setting,
language settings are the same as the date settings, and it will not be
repeated here. The installation method settings have three options: tower,
rack and automatic, and when set to Auto, the LCD screen automatically
switches the display mode based on the current UPS placement status (tower
type or rack type).
57
4 Screen Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
4.7.4 Permission Setting
In the Settings management page, select “Permission” option to enter the
password entry page first, as shown in Figure4-16.
Figure4-16 Password input page
By short pressing the up/down page button to achieve page option selection,
when selecting the lower right corner of the back button, the return button
will be displayed as a opposite color state, at this time short press function
button can enter the page to the previews level of the page, the password
input page on the previews level of the page for the settings management page.
In the password input page, short press function button can enter the password
settings, at this time the first password flickering from the left, by short
press the up/down page button can achieve the first bit password value
minus/plus operation, select the required value, then short press function
button into the second bit password settings. The second to sixth bit password
is set the same way, which is not repeated here. The password input range is
000000-999999.
After the sixth bit passwords is entered, press the function button shortly,
at which point if the password entered does not match the current system
password, the screen will display the word “password error”, and if the
password entered matches the current system password, the system will enter
the permission set page according to the current input password permission.
Figure4-17 Permission setting page 58
KR-RM Series (10kVA-40kVA) UPS User Manual
4 Screen Operation
The permission set page includes trial function and trial time two setting items, and the trial time will not be displayed until the trial function is turned on. By pressing the up/down page button and working with the function button’s short press operation, you can set the trial function and the trial time, the setting method is the same as the other settings mentioned above, and it is not repeated here.
1. The permission set is a restricted operation, if you need this operation,
you need to obtain the trial period password from the service provider;
2. The way for obtain the trial period password: After the service provider
agrees, report the series number on the password input page (as shown in
Figure4-16), then you can obtain the corresponding passwords.
59
5 Use and Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
5 Use and Operation
This chapter mainly describes the operation process, operation method, daily
maintenance and troubleshooting, etc.
5.1 Check Before Startup
Check if the wire connection is firm and the color of AC wires is in
accordance with the specification.
Check if UPS is grounded reliably. Check if the voltage between the neutral
wire and grounding wire is less than 5Vac. If the UPS equipped with remote
monitoring device, check if the wiring of the RS485 port is
correct. If it is long backup model, check if the wiring between UPS and
battery box is correct and
reliable. Check if the wiring is neat and the wire binding is in accordance
with the specification. Check if the installation and wiring are good for
transformation, expansion and maintenance in
future. Check that there is no short-circuit in the output of the UPS and the
load capacity isn’t beyond the
rated capacity of the UPS.
5.2 Startup Operation
Step 1 Switch on the external mains, bypass and battery switch. Step 2 Press
the ” ” and ” ” button on the front panel at the same time for 1s to start the
UPS. Step 3 About 10s later, if the UPS works steadily, start loads, such as
PC, etc.
60
KR-RM Series (10kVA-40kVA) UPS User Manual
5 Use and Operation
Start load according to “high power devicesmall power device”, which is to
avoid overload protection when starting high power device. —-End
5.3 Shutdown Operation
Step 1 Close load and keep the UPS running without load for about 10min to
exhaust heat. Step 2 Press ” ” and ” ” button on the front panel at the same
time for 1s to shut down the UPS. Step 3 Switch off the external battery,
bypass and mains switch.
—-End
5.4 Parallel System Operation
5.4.1 Start Parallel System
Before completely starting the parallel system, please do not start load, and
ensure that all switches of output distribution cabinet are off. The following
steps for start the parallel system: Step 1 Ensure that each unit of parallel
system is installed properly, start each unit of parallel system according to
the 5.2 Startup Operation one by one. Step 2 After each unit in parallel
system outputs by inverter, measure the inverter voltage of each paralleled
unit. The voltage difference between max. and min. voltage should be within
8V. Close the breaker of paralleled unit in parallel distribution cabinet,
measure the circulating current of parallel unit, and the current should be
less than 3A. When the voltage different larger than 8V, measure the output
voltage of the UPS and check if the output are all 220V, if the voltage
different larger than 15V, please report it to our company to
61
5 Use and Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
maintain it. In addition, once the circulating current of parallel unit too
large, it will lead to the inverter fault. If the circulating current larger
than 3A, please report it to our company to maintain it.
Step 3 Switch on the total output breaker of output distribution cabinet, each
output branch breaker, and then start the load one by one.
—-End
5.4.2 Shut Down Parallel System
Generally, it isn’t recommended to start or close parallel system frequently.
Step 1 Shut down all load. Step 2 Shut down parallel UPS one by one. Step 3
Switch off the related breakers of each unit (when daily use, the breakers can
be not closed).
—-End
5.4.3 Exit Parallel System Online
When one UPS in parallel system fault, it will exit from parallel system automatically with sound & light alarm. At that time, perform the operations shown in Figure5-1, the fault UPS will be exited from parallel system completely to achieve online hot maintenance or replacement.
Close the fault UPS according to shutdown procedures.
Switch off breaker in the distribution box, which connects with the faulty UPS.
Figure5-1 Exit parallel system online
When the parallel system works normally, it’s better not to exit the output
from parallel system before the unit closed, or the power system will be
abnormal.
5.4.4 Add New UPS into Parallel System Online
When it has to add one or more UPS into parallel system, perform the
operations shown in Figure5-2. When the added UPS works steadily, it will add
into parallel system automatically and achieve current- sharing.
62
KR-RM Series (10kVA-40kVA) UPS User Manual
5 Use and Operation
Install the added UPS completely
Switch on the breaker of the distribution box that connected with added UPS
Figure5-2 Add new UPS into parallel system
Start the added UPS according to the startup procedures successively
5.4.5 Redundance Function of Parallel System
When system adopts N+1 redundance design, the total output cannot larger than
N times of single unit’s rated power. When one paralleled unit fault, it can
put into use or exit parallel system and do not affect the operation of
system, which enhance the system reliability. When output exceed N times of
single unit’s rated power, the overload unit (exceeding N/(N+1) times of
single unit’s rated power) will send alarm. for example, for the backup system
with two UPS, once one UPS overload for 50% rated power, it will send overload
alarm.
5.5 Periodic Preventative Maintenance
To improve the efficiency and reliability of the UPS, perform the following
maintenance regularly: Clean the UPS by dry cloth regularly. Don’t use liquid
or spray cleaner. Before cleaning, shut
down the UPS. Check if the wiring of input and output is firmly and well
connected. Check the working status of cooling fans regularly. Prevent
sundries from blocking the air outlet.
If damaged, please replace it in time. Check the battery voltage and the
working status of UPS regularly to discover fault timely.
5.6 Battery Maintenance
The working life of battery is based on the environment temperature and
discharge times. Using battery in the high temperature for a long time or
discharging battery deeply will reduce the working life of battery.
When selecting battery box, please pay attention to following items: Charge
the battery for 10 hours before using. During charging, the UPS still can be
used, but if
power outage at the same time, the discharging time may be less than the
standard backup time. Generally, charge and discharge the battery once every 4
to 6 months. Discharge the battery till
under-voltage and power off and then charge it. In high temperature area,
charge and discharge the battery once every 2 months. The charging time for
the standard battery should be more than 10 hours every time.
63
5 Use and Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
If the UPS hasn’t been used for a long time, it is recommended to charge the
battery more than 10 hours every three months.
Generally, the working life of battery is 3 to 5 years. If battery is not so
good, replace it in time. The battery replacement should be performed by
authorized professional.
5.7 Troubleshooting
5.7.1 Common Fault
As shown in Table5-1, it only includes some common fault diagnosis. If any
doubt, contact the local office or distributor for details.
Table5-1 Troubleshooting
Fault phenomenon
Possible reason
The mains normal, after starting the UPS, it outputs normally, but it works in the battery mode and the buzzer beeps intermittently.
1. Check if the contactors and wiring terminals in the input circuit are in
good condition;
2. Check if the displayed input voltage amplitude or frequency of mains on
the LCD is beyond the allowable range of UPS;
3. Check if the mains input breaker is disconnected, if yes, please close the
breaker again.
After installing UPS, connecting with power will fuse the fuse or cause tripping operation.
The wiring of UPS input or output is short circuit.
After starting, the LCD display and output are normal. But once connecting with load, it will stop outputting immediately.
1. UPS is overload seriously or the output circuit is short-circuit. Please
reduce load to proper capacity or find the short-circuit reason. The common
reason is that the output changeover socket short-circuit or the input short-
circuit after UPS damage;
2. The load is not started according to “high power device small power
device”. Restart the UPS, and after the UPS works steadily, start high power
load first, and then start small power ones successively.
Buzzer long beeps, fault indicator lights on, UPS works
1. The output is overload. The load is too heavy and beyond the rated power of the UPS. Please reduce load or select a
64
KR-RM Series (10kVA-40kVA) UPS User Manual
5 Use and Operation
Fault phenomenon in bypass mode and inverter failure.
Possible reason
UPS with larger power capacity. If it is temporary bypass caused by impact of
load start and recovers automatically, it still is normal;
2. UPS over-temperature protection. Check if the air inlet and air outlet of
UPS is blocked or the working temperature of UPS is beyond the allowable
range.
Usually, UPS works normally. When power failure, it doesn’t transfer to battery mode or it transfers to battery mode and battery under-voltage protection soon.
1. Battery aging, the battery capacity loss. Please replace battery;
2. Battery charger fault. At ordinary time, the battery cannot be charged;
3. Battery wire doesn’t connect well or the terminals contact is bad.
When the load is PC, everything works normally. When power failure, UPS works normally, but the computer system halted.
The grounding connection is not so good. The floating voltage between the neutral wire and the grounding wire is too high.
Table5-2 Meaning of fault symbol and buzzer status
NO. LCD fault Buzzer status symbol
Meaning
1
EPO
Long beep
UPS has emergency protection (if equipped with EPO function), Bypass output and inverting output are all closed.
2
PhaseSet Err. Long beep
UPS system mode system settings and the actual wiring do not match the fault, please check the main power or bypass wiring, and make the actual system is consistent with the set mode system.
3
Maintenance Long beep
UPS maintenance bypass protection, inverted output closed, please check back board maintenance bypass detection port is shorted.
4
Output fault Long beep
The UPS output is faulty, detect the UPS output is
65
5 Use and Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
NO. LCD fault Buzzer status symbol
Meaning short or over load.
5
PhaPRA
Long beep
6
VolPRA
Long beep
7
FrePRA
Long beep
8
BypPRA
Long beep
9
ModPRA
Long beep
10 PowPRA
Long beep
11 NumPRA
Long beep
12 PRA
Long beep
13 StbPRA
Long beep
The UPS of the input and output mode in the parallel does not match the actual
system.
The UPS of the output voltage in the parallel does not match the actual
system.
The UPS of the frequency in the parallel does not match the actual system.
The UPS of the bypass voltage or frequency in the parallel does not match the
actual system.
The UPS parallel mode setting in the parallel system does not match the actual
system.
The UPS of the output power setting in the parallel does not match the actual
system.
The UPS of the battery number setting in the parallel does not match the
actual system.
The UPS of parameters setting in the parallel does not match the actual
system.
The UPS of short turn to bypass setting in the parallel does not match the
actual system.
14 Double Err. Long beep
Fall-off fault at both ends of the parallel wire.
15 Single Err. Slow beep
Fall-off fault at one ends of the parallel wire.
16 PWR 17 Fan fault
Long beep
UPS internal working power failure, if it cannot be automatically recovered, please report repair promptly.
Urgent beep (alarm once about every 0.2s)
Fan fault warning prompt, please check the fan for damage or blocking.
66
KR-RM Series (10kVA-40kVA) UPS User Manual
5 Use and Operation
NO. LCD fault Buzzer status symbol
Meaning
Slow beep (alarm The CAN communication of parallel system
18 CAN fault once about every abnormal, please check if the parallel wire is damaged
2.0s)
or there is only one UPS in parallel system works.
19 SCI fault
Long beep
UPS internal communication abnormal, if the continuous alarm cannot be restored, please report repair promptly.
The total output load of the UPS parallel system Slow beep (alarm
exceeds the full load of the single machine, check that 20 No Redund once
about every
the output load exceeds the requirements for 2.0s)
redundant backups.
Long beep
The mains power input phase sequence is abnormal, please check the main power input wiring.
21 Grid Err.
3 continuous alarms at 10s intervals
The main power input occur lack N fault, power down failure, overvoltage protection, under voltage protection, over-frequency fault, under-frequency fault, please check whether the main power input status is normal.
22 BYP Err.
Slow beep (alarm once about every 2.0s)
At mains status, the bypass voltage abnormal, frequency abnormal, phase sequence abnormal, or mode setting mismatches the wiring. Please check if the bypass breaker is closed, if the bypass phase sequence is normal, if the wiring way of bypass matches the system mode setting.
23 BAT Err.
Slow beep (alarm Battery has been pressure protection, charging fuse
once about every failure, over-pressure alarm fault, please check the
2.0s)
battery status is normal.
Urgent beep (alarm once about every 0.2s)
Battery wiring fault, charging short, under-voltage protection, under-voltage warning problem, please check the battery wiring and the current state is normal.
67
5 Use and Operation
KR-RM Series (10kVA-40kVA) UPS User Manual
NO. LCD fault Buzzer status symbol
Meaning
No buzzer warning The battery charging temperature is too high.
24 PFC Err.
Long beep
UPS rectifier fault.
25 INV Err.
Long beep
UPS inverter failure.
The buzzer alarm in the table above describes the phenomenon of UPS boot state and no beep ban when the buzzer is not set, the shutdown state or some abnormal phenomena when setting the buzzer ban will prompt the information in the LCD, but the buzzer alarm will not be issued.
68
KR-RM Series (10kVA-40kVA) UPS User Manual
6 Package, Transportation and Storage
6 Package, Transportation and Storage
6.1 Package
During packing, please pay attention to the place direction requirements. At
the side of the package, there is afraid of wet, handle with care, upward,
stack layer limit, etc. alarm marks. And also, the device model is printed on
the package. At front of the package, the device name is printed.
6.2 Transportation
During transporting, pay attention to the warning marks and avoid severe
impact on the package. Place the device according to the marked direction,
which is to avoid damage the component. Any inflammable, explosive, corrosive
object is not allowed to shipping with the device. While midway
transportation, do not put the device in the open air. The device cannot
suffer any rain, snow or liquid material or mechanical damage.
6.3 Storage
During storing, place the UPS according to the marked direction. The package
box should be far away from ground for 200mm, and keep at least 500mm from
wall, eat source, cold source, window or air inlet. Storage temperature: 0~40,
relative humidity is 20%80%.In the warehouse, any inflammable, explosive,
corrosive object or harmful gas is not allowed, and also, strong mechanical
shake, impact or magnetic field is forbidden. The storage period of these
requirements, generally, is 6 months. If the UPS is stored more than 6 months,
it is necessary to check again. If the UPS is stored for a long time, please
charge the battery every 3 months.
69
A Technical Specifications
KR-RM Series (10kVA-40kVA) UPS User Manual
A Technical Specifications
Model Index
KR10kVA-RM KR15kVA-RM KR20kVA-RM KR30kVA-RM KR40kVA-RM
Input mode
3W+ N+PE(can be set as 1W+ N+PE)
3W+ N+PE
When the input voltage in the range of 176280, the UPS can bear load of 100% rated
Voltage range power;
(Vac)
When the input voltage in the range of 80-176, the output of the UPS needs to decrease
rated power linearly to use
Frequency range (Hz)
40~70
Bypass synchronism
50/60±10% (50/60 self-adaption) track range (Hz)
Bypass input voltage range 208/220/230/240±20% (phase voltage) (default is 220) (Vac)
Input power 0.99 factor
Input THDI Resistive full load:3%; non-linear full load: 5%
Input
70
KR-RM Series (10kVA-40kVA) UPS User Manual
A Technical Specifications
Model Index
KR10kVA-RM KR15kVA-RM KR20kVA-RM KR30kVA-RM KR40kVA-RM
Battery voltage (Vdc)
±144~±240 (can be selected from ±12 cells ~±20 cells, default is ±16 cells, when the battery voltage is set from ±12 cells ~±15 cells, the output of the UPS decreases to 75% rated) (single battery voltage is 12Vdc)
Charge current 1~20 settable (default is 4A)
(A)
1~20 settable (default is 15A)
Output mode 3W+N+PE (can be set to 1W+N+PE)
Capacity 10/9
(kVA/kW)
15/13.5
20/18
30/27
40/36
L-N: 220/230/240 (default is 220) Voltage (Vac)
L-L: 380/400/415 (default is 380)
Frequency (Hz)
When mains normal, it tracks the bypass input frequency; When mains abnormal, it tracks the frequency of 50±0.1 or 60±0.1 (default is 50)
Wave form
Sine-wave
Voltage distortion
Resistive full load: 1%; non-linear full load:4%
Power factor 0.9 (when PF set to 1.0, the UPS can output long time)
Transfer time of bypass and Synchronization: 1ms; asynchronization: 10ms inverter (ms)
System efficiency
Up to 96%
Overload capacity
Inverter: <115: continue 115~130: 15min
Output
71
A Technical Specifications
KR-RM Series (10kVA-40kVA) UPS User Manual
Model Index
KR10kVA-RM KR15kVA-RM KR20kVA-RM KR30kVA-RM KR40kVA-RM
130~150: 1min 150%: 200ms Bypass: <130: continue 130~155: 1min 155%: 200ms
DC startup Equipped
function
Panel display LCD shows the running status of the UPS
Communicatio RS485
n port
Alarm function Alarm for battery low-voltage, mains abnormal, UPS fault, output overload, etc.
Protection function
Protection for battery under-voltage, overload, short-circuit, over- temperature, input over-voltage, communication abnormal, etc.
Noise (dB)
<55 (normal temperature)
Work temperature ()
-5 ~ 40
Relative humidity
0 ~ 95%, non-condensation
Size (W×D×
H) (mm3)
438×500×130
438×680×130
Weight (kg) 17.5
19
20
34
Specifications are subject to change without prior notice.
Others
72
KR-RM Series (10kVA-40kVA) UPS User Manual
B Acronyms and Abbreviations
B Acronyms and Abbreviations
A
AC
Alternating Current
B BMD
Bypass Maintain Detection
D
DC
Direct Current
E ECO EPO
Economic Operation Model Emergency Power Off
L LCD
Liquid Crystal Display
P
PE
Protective Earthing
73
B Acronyms and Abbreviations
R RS485
Recommend Standard485
S SNMP
Simple Network Management Protocol
U
UPS
Uninterruptible Power System
KR-RM Series (10kVA-40kVA) UPS User Manual
74