PSi1500VA#12VT Power Solid Inverter User Manual
- June 10, 2024
- POWER SOLID
Table of Contents
PSi1500VA#12VT Power Solid Inverter
IMPORTANT SAFETY INSTRUCTIONS
SAFETY INSTRUCTIONS
General
Please familiarize yourself with the safety features and instructions by first reading the documentation supplied with this product before using the equipment.This product has been designed and tested in accordance with international standards.The equipment must be used exclusively for the purpose for which it was designed .
WARNING
ELECTRIC SHOCK HAZARD.
The product is used in conjunction with a permanent energy source(battery).lnput and/or output terminals may still be dangerously energized,even when the equipment is switched off.Always switch off the AC supply and the battery before carrying out maintenance or servicing the product.
The product has no internal user-serviceable components.Do not remove the front plate or operate the product if any panels have been removed.Only Qualified personnel must undertake all servicing.
Never use the product in around where there is a risk of gas or dust explosions.(before using) Consult the battery manufacture’ s to confirm the products if can be used with the battery.Always comply with the battery manufacturer’s safety instructions.
Installation
Read the installation instructions in the installation manual before installing the equipment.
This is a Safety Class I product (supplied with a protective grounding terminal).Uninterruptible protective grounding must be provided at the AC input and/or output terminals.Alternatively the grounding point located externally on the product may be used.Whenever it is likely that the grounding protection has been damaged,the product must be turned off and secured against unintended operation.
Ensure that the DC and AC input cables are fused and fitted with circuit breakers.Never replace a safety component with a different type. Always consult the manual to determine the correct component.
Before applying power,ensure that the available power source matches the required specification of the product as described in the manual.
Ensure that the equipment is used under the correct ambient conditions.Never operate the product in a wet or dusty environment. Ensure there is adequate free space for ventilation around the product and check that the ventilation vents are not blocked.
Ensure that the required system voltage does not exceed the product’s capacity.
Transport and Storage
Ensure that the mains power and battery leads have been disconnected before storing or transporting the product.
No liability can be accepted for any transport damage if the equipment is shipped in non-original packaging.
Store the product in a dry environment;the storage temperature must be between-20°C and 60°C.
Consult the battery manufacturer’s manual in respect of transport, storage,charging,recharging and disposal of the battery.
DESCRIPTION
Fig. 1 : rear plate
- 0utput seat
- 0utput seat
- Fuse(Recoverable over current protector)
- lnput seat
Fig 2: LCD Screen
- Power button
- AC In LED
- Inverter LED
- Charge LED
- Alarm LED
- Confirm Key
- Page Down Key
- Page UP Key
- Escape Key
- Indicator Screen
Fig 3: Power Button
1 ……………………. Saver Mode
2 ……………………. Off Mode
3 ……………………. On Mode
OPERATION
AC In
When power button is switched to”on”,the product is fully functional.
The inverter will come into operation and the green LED “AC ln”will light up.
Inverter Mode
In the event of a grid failure,or generator power being disconnected, the unit switches to inverter mode and takes over supply to the connected loads.This happens so fast (less than 10 milliseconds) that computers and other electronic equipment will continue to operate without disruption.The green LED light of “Inverter” indicates on the LCD panel
Charging Mode
In the event of restoration of grid,or generator power,the Inverter commences charging.The”AC ln”green LED light comes up,and the orange”Charge”light starts blinking.When the batteries are fully charged,the blinking orange light changes to Solid Orange.
Alarm Mode
In the event of high battery discharge,and its gets close to the battery cutoff level,the red”Alarm”light starts showing,and it is accompanied with a beeping sound,this continues until the units gets to the battery voltage cutoff level and its powers down automatically,except there is a restoration of grid supply in which case it changes back to gharging mode.
Bypass Functionality:
When the power control button is switched to “OFF”,and there is a grid or
generator supply,the inverter supplies output to the load and also charges.
When the power control button is switched to”OFF”,and there is no grid or
generator supply,the inverter supplies does not supply output to the load.
Saver Mode
When the power control button is switched to”SAVER”,and there is no supply of grid,the inverter’s AC output will not be supplied until a load greater than 15 watts is connected to the inverter. It automatically detects the connected load every 15 seconds.
Tab.I
MODE | BUTTON | NOAC SUPPLY | AC SUPPLY |
---|---|---|---|
SAVER | I | ≤ 15W LOAD.NO O/P | CHARGING,O/P |
≥ 15w LOAD,O/P
ON| II| INVERTER| CHARGING,O/P
OFF| 0| NO O/P| CHARGING,O/P
DIP SWITCH| FUNCTION| UP| DOWN
---|---|---|---
SW1| BATTERY LOW CUT OFF POINT| 10.5V/21V| 10V/20V
SW2| INPUT VOLTAGE RANGE| 154-265 /83-132 VAC| 185-265/96-132VAC
SW3| BATTERY CHARGER CURRENT| 100%| 50%
Setting Mode
Press “ ” and “ ” buttons together.LCD will show “Password:00000” ,it enter
into setting mode,the pass word is: 12345,use “ ” button, and “ ” button to
input password, finishing input.choose “ ” ,then press “lmml” to confirm pass
word.
After confirm pass word,enter into “System Settings” ,and press ” ” ,it will
show ” ◄ ” ,use “ ” or ” ” buttons to move ” ◄ ” to setting items,then press “
” ,then you can use “ ” or “ ” buttons to setting.After finish setting, pis
choose ” Yes ” at confirm page.
Setting Items | Parameters | Remarks |
---|---|---|
Input Range | UPS | 180~265/96~132VAC |
INV | 155~265/83~132VAC | |
Input Priority | UTI | AC supply power to load when AC is normal,battery supply |
power load when AC is off
SBU| Battery supply power to load,it will change to AC when battery low
voltage
CHA Utility| A| Increase or decrease charging current
CHA Solar| A| Changing solar charging current(with solar controller type)
Floate CHA| (13-14)*N
(N isseries battery qty)
| Battery floating voltage setting depends on different batteries
Bulk CHA| (14-14.6)*N
(N isseries battery qty)
| Battery strong charging setting depends on different batteries
Low Cut-Off| (9.5-11.0)N| Setting battery protection cut-off voltage
SOL TO AC| (11-12.5)N| when choose ” SBU” priority,setting voltage return to
AC supply
Inverter output| 210~240V
/105~120V
| Setting output voltage
Output Freq| 50Hz/60Hz| Setting output frequency
AC CHK Speed| Fast| AC sensitivity setting:Fast,Median,Slow
Median
SLOW
Fault Restart| NO| No restart if short circuit or over load
Yes| Restart 3times if short circuit or over load
Backlight| Normal| Backlight will off after 60s
ON/Off| Setting backlight lighting or close
Factory| Yes| Factory setting parameters
NO| User can change parameters
INSTALLATION
WARNING
A qualified electrician should install this product.
Locating and Mounting the Inverter
The product must be installed in a dry and well-ventilated area,as close as possible to the batteries.There should be a clear space of at least 10cm around the appliance for cooling.
Excessively high ambient temperature will result in the following:
- Reduced service life.
- Reduced charging current.
- Reduced peak capacity,or shutdown of the inverter.
Never mount the appliance directly above the batteries. The product is
suitable for wall mounting.For mounting see Fig.1.
The appliance can be mounted horizontally as well as vertically;vertical
mounting is preferable.The vertical position offers optimum cooling. The
interior of the product must remain accessible after installation. Try and
keep the distance between the product and the battery to a minimum in order to
minimize cable voltage losses.
For safety purposes,this product should be installed in a heat-resistant
environment if it is used with equipment where a substantial amount of power
is to be converted.You should prevent the presence of e.g. chemicals,synthetic
components,curtains or other textiles,etc.,in the immediate vicinity.
AC Wiring
This is a Safety Class I product (supplied with a protective grounding terminal).Uninterruptible protective grounding must be provided at the AC input and/or output terminals and/or chassis grounding point located externally on the product
AC Wiring should be connected in the following order:
- AC INPUT (Source)
- AC OUTPUT (Load)
AC Input: The inverter comes installed with Input protection circuit
breaker.This should be switched off before the cable is installed. Remove the
AC wiring compartment cover to gain access to the AC terminal strip inside.
Run the three conductors AC INPUT (source) wiring into the wiring
compartment.Connect the AC INPUT ground wire first to the ground terminal
(ground symbol with circle around it),and then connect the AC.
INPUT line (L) and neutral wire (N) to the corresponding AC input
terminals.
AC Output: The inverter comes installed with Input protection circuit
breaker.This should be switched off before the cable is installed.
In a similar manner,connect the AC OUTPUT (load) wiring to the Inverter AC
output terminal as was done on the AC Input After wiring ,double check and
review all connections to make sure the wires are in the correct terminals and
the terminals are tight
To ensure the best performance from your inverter system.do not use old or
untested batteries.Batteries should be of the same size.type, rating.and age.
AC Safety Grounding: During the AC wiring installation.AC input and output
ground wires are connected to the inverter.The AC input ground wire must
connect to the incoming ground from your AC utility source. The AC output
ground wire should go to the grounding point for your loads (e.g.a
distribution panel ground bus).
DC Wiring
**WARNING**
DO NOT connect the DC wires from the battery bank to the inverter until:
- All AC wiring is complete,
- The correct DC and AC protection switches are OFF
- The correct DC voltage and polarity have been verified
Depending upon the type of batteries you use in the installation (6 or 12
VDC),the batteries must be wired in series,parallel,or series-parallel.
The interconnecting DC wires must be sized and rated exactly the same as those
that are used between the battery bank and the inverter.
To ensure the best performance from your inverter system.do not use old or
untested batteries.Batteries should be of the same size.type, rating,and age.
procedure
In order to fully utilize the full capacity of the product.batteries with sufficient capacity and battery cables with sufficient cross section should be used.
Proceed as follows to connect the battery cables:
WARNING
- Use an insulated box spanner in order to avoid shorting the battery.
- Avoid shorting the battery cables.
Connect the battery cables: the + (red) on the left and the-(black) on the
right.to the battery.Reverse polarity connection (+ to – and – to +) will
cause damage to the product.(Safety fuse inside the Inverter unit can be
damaged)
The DC overcurrent device (i.e.,fuse or circuit breaker) must be placed in the
positive (RED) DC cable line between the inverter’s positive DC terminal and
the battery’s positive terminal (RED);as close to the battery as possible.
A brief spark or arc may occur when connecting the battery cables to the
inverter DC terminals;this is normal and due to the inverter’s internal
capacitors being charged.
All wiring to the battery terminals should be checked periodically (once a
month) for proper tightening Secure the nuts tightly in order to reduce the
contact resistance as much as possible.
Be aware that over-tightening or misthreading the nuts on the DC terminals can
cause the bolts to strip and snap/break off.
DC Wiring Size
It is important to use the correct sized DC wire to achieve maximum efficiency
from the system and to reduce fire hazards associated with overheating.Always
keep your wire runs as short as practical to prevent low voltage shutdowns and
to keep the DC breaker from nuisance tripping (or open fuses) because of
increased current draw.
The correct minimum DC wiresize (and corresponding overcurrent device) is
required in order to reduce stress on the inverter.minimize voltage
drops,increase system efficiency and ensure the inverter’s ability to surge
heavy loads.
If the distance from the inverter to the battery bank is ~5 feet,use a minimum
DC wire size of #2 AWG (33.6 mm2).lf the distance between the inverter and the
battery is>5 feet.the DC wire will need to be increased.Longer distances cause
an increase in resistance,which affects the performance of the inverter.
Tab.Ill
Models| Minimum DC Wire Size(rating)| Maximum DC Fuse size|
DC Grounding wire size
---|---|---|---
PSi1500VA#12VT| 16/8/4mm2| 200/100/SOA| 2.5mm2
PSi2000VA#24VT| 25/10/6mm2| 250/120/60A| 2.5mm2
Parallel and Series Connection
12 volts Battery in Series
Difference between Series and Parallel connection
Batteries in Parallel Voltage remain the same Ah capacity doubles
Batteries in Series Voltage doubles Ah capacity stays the same
TROUBLESHOOTING
Proceed as follows for quick detection of common faults.DC loads must be
disconnected from the batteries and the AC loads must be disconnected from the
inverter before the inverter and/or battery charger is tested.
Consult your local dealer/repair center if the fault cannot be resolved.
Tab.V
Problem | Cause | Solution |
---|---|---|
The inverter fails to operate when switched on | Battery terminal not firm |
Tighten the battery terminals.
Continuous spark from the inverter terminal| Battery terminal reversal| Check
and connect the cable to the right terminal lead.
No output from inverter| Output cable terminals loosed| Open the casing and
connect the output cable terminals firm to the appropriate lead.
Inverter not charging battery| input power less than(<) 150 /83-96VAC| A step-
up stabilizer of rating higher than the inverter should be installed.
Continuous alarm when the inverter is loaded| Overloading condition| Check the
loads and disconnect heavier loads.
TECHNICAL DATASHEET
Model | PSi1500VA#12VT |
---|---|
Capacity (VA) | 1500VA |
Input Voltage (DC) | 12V |
Input Nominal Voltage | 220VAC |
Input Voltage Range | 154-265VAC (AC Mode);185-264VAC±3V (UPS Mode) |
Input Frequency | 50-60HZ Auto sensing |
Output Power Factor | 0.8 |
Output Rated Power | 1200W |
Output Frequency | 50/60HZ |
Output Waveform | Pure Sine Wave |
Output Transfer Time | <8ms |
Output Bypass Mode | Yes |
Output Saver Mode | Yes |
Output Efficiency | >98% |
Input Protection | Circuit Breaker |
Output Protection | Circuit Breaker |
Battery Type | AGM-Deep Cycle, Gel/Up to 500AH |
Battery AC Charging | 25A |
Battery Low Level | 10V or 10.5V |
LCD indicator status | AC input voltage, AC input frequency, PV voltage, PV |
current, Output Voltage, Output Frequency, Battery
voltage,
LED indicator status| AC Line In: Green/Inverter: Green/Charging:
Yellow/Alarm: Red
Protections| Over load, over temp, over charging, battery low, battery reverse
connects, high AC voltage etc.
Alarm LOW battery| Audible alarm-5 seconds beeping
Alarm Overload alarm| Audible alarm- continuous beeping
Alarm Fault| Audible alarm- continuous beeping
Environment
Temperate
| 0-40℃
Humidity| —10℃~90℃ Non condensing
Noise(dB)| >55dB
Size LWH(mm)| 430220185mm
Packaging| 560335250mm
Weight (kg)| 14.5
Capacity (VA)| 2000VA
Input Voltage (DC)| 24V
Input Nominal Voltage| 220VAC
Input Voltage Range| 154-265VAC (AC Mode);185-264VAC±3V (UPS Mode)
Input Frequency| 50-60HZ Auto sensing
Output Power Factor| 0.8
Output Rated Power| 1600W
Output Voltage| 220VAC
Output Frequency| 50/60HZ
Output Waveform| Pure Sine Wave
Output Transfer Time| <8ms
Output Bypass Mode| Yes
Output Saver Mode| Yes
Output Efficiency| >98%
Input Protection| Circuit Breaker
Output Protection| Circuit Breaker
Battery Type| AGM-Deep Cycle, Gel/Up to 500AH
Battery AC Charging| 18A
Battery Low Level| 20V or 21V
LCD indicator status| AC input voltage, AC input frequency, PV voltage, PV
current, Output Voltage, Output Frequency, Battery voltage,
LED indicator status| AC Line In: Green/Inverter: Green/Charging:
Yellow/Alarm: Red
Protections| Over load, over temp, over charging, battery low, battery reverse
connects, high AC voltage etc.
Alarm LOW battery| Audible alarm-5 seconds beeping
Alarm Overload alarm| Audible alarm- continuous beepingAudible alarm-
continuous beeping
Alarm Fault| Audible alarm- continuous beeping
Environment Temperature| 0-40℃
Humidity| —10℃~90℃ Non condensing
Noise(dB)| >55dB
Size LWH(mm)| 430220185mm
Packaging| 560335250mm
Weight (kg)| 17
Warranty scope
The following is not within the scope of warranty:
(a) Battery configured by user.
(b) Do not operate according to the user’s manual.resulting in damage to
the machine.
(c) Machanical damage due to natural disasters such as fire,flood, etc.
(d) Products beyond the warranty period, the implementation of paid
maintenance services
Trademarks
Other trademarks,registered trademarks,and product names are the property of
their respective owners and are used herein for identification purposes only.
Exclusion for Documentation
(A) Makes no warranty as to the accuracy,sufficiency or suitability of
any technical or other information provided in its manual or other
documentation.
(B) Assumes no responsibility or liability for losses,damages,cost or
expenses.whether special,direct,indirect,consequential or incidental, which
might arise out of the use of such information. The use of such information
will be entirely at the user’s risk.