Read me

When you use BJ193-X series Digital Meter, be sure to carefully read this user manual, and be able to fully understand the implications, the correct guidance of operations in accordance with user manual, which will help you make better use BJ193 series Multifunction Power Meter, and help to solve the various problems at the scene.

  1. Before the meter turning on the power supply, be sure that the power supply within the provisions of the instrument;
  2. When installation, the current input terminal must non-open, voltage input terminals must Non-short circuit;
  3. Communication terminal (RS232 or RS485) is strictly prohibited to impose high pressure;
  4. Be sure the instrument wiring consistent with the internal system settings;
  5. When communicating with the PC, instrument communication parameters must be consistent with the PC.
  • Symbol Please read carefully before using this user manual
  • Please save this document

SUMMARIZE

BJ193-X series Digital Meter is used for power quality monitoring, factory automation and building automation.

These series can measure the power parameters in power grid:

Current, Reactive power,
Voltage, Apparent power,
Frequency, Energy,
Active power, Power factor,

It can replace many of a traditional analog measurement instruments, improve system accuracy and reliability.

SPECIFICATIONS

  1. Reference standard
    Basic electricity: GB/T13850-1998 (IEC688-1992)
    Active power : GB/T17215-2002 (IEC61036:2000)
    Reactive power : GB/T17882-1999 (IEC61268:1995)

  2. Accuracy standards
    Parameter| Accuracy| Three phase
    ---|---|---
    Active Power| 0.5%fs| W
    Reactive Power| 0.5%fs| Var
    Power Factor| 0.5%fs| PF

  3. Input
    Voltage: Rated 100/400V
    Current: Rated 5A (optional 1A)
    Frequency: 45-65Hz

  4. Load
    Voltage: <0.5VA / phase (rated 220V)
    Current: <0.5VA / phase (rated 5A)

  5. Overload
    Current: 2 times rated continuous; 10 seconds for 10 times the rated
    Voltage: 2 times the rated continuous; 10 seconds for 600V

  6. Dielectric strength
    IEC 688 / IEC 255-3 (1989)
    2kV AC RMS 1 minute, between input / output / case / power supply

  7. EMC Test
    | standard| Test voltage
    ---|---|---
    Electrostatic discharge immunity test:| IEC-61000-4-2
    level 4| 8KV
    Electrical fast transient burst immunity test| IEC61000-4-4
    level 3| Input 1kV; Power supply 2kV
    Surge (Shock) immunity test| IEC61000-4-5
    level 4| common mode test voltage 4kV

  8. Work environment
    Temperature: -20℃ ~ +60℃ (-4℉ ~ 140℉)
    Humidity: RH 20%~95%(No condensation)

  9. Protection
    Panel: IP40

  10. Storage Conditions
    Temperature: -25℃~+70℃(-13℉ ~ 158℉)
    Humidity: RH 20%~95%

  11. Power Supply
    AC /DC 80-270V

  12. Dimensions
    L × W × H =96x96x71mm (3.78×3.78×2.80 inch)

  13. Installation hole size
    L × W =(91+0.8)mm×(91+0.8)mm [(3.58+0.032)inch x (3.58+0.032)inch]

INSTALLATION AND START-UP

The manual you hold in your hands contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions. The instrument must not be powered and used until its definitive assembly on the cabinet’s door.

Whether the instrument is not used as manufacturer’s specifications, the protection of the instrument can be damaged.

When any protection failure is suspected to exist (for example, it presents external visible damages),the instrument must be immediately powered off. In this case contact a qualified service representative.

Installation

Mounting

Instrument is to be mounted on panel (cut-out 91+0.8 x 91+0.8 mm). All connections keep inside the cabinet.

Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. Therefore, the instrument must not be used until this is completely installed.
Installation And Start-up

Notes:

Auxiliary power:

BJ193X Series Power Meter with universal (AC / DC) power input, if not for a special statement, we provide the 220VAC/DC or 110VAC/DC power interface for standard products Instruments limit work power supply : AC / DC :80-270V, please ensure that the auxiliary power can match for BJ193-X series meter to prevent damage to the product.

A. Suggest install 1A fuse in the fire line side.
B. For the areas with poor power quality, suggest install lightning surge suppressor and rapid burst suppressor to prevent lightning strikes

Connection terminal and drawing for BJ193PQH (see label on the rear

part)

Terminal description

Installation And Start-up

  1. *Supply voltage input: 0 V
  2. *Supply voltage input:85~265 Va.c.
  3. Current A-phase – S1 input
  4. Current A-phase – S2 input
  5. Current B-phase – S1 input
  6. Current B-phase – S2 input
  7. Current C-phase – S1 input
  8. Current C-phase – S2 input
  9. Voltage A-phase input
  10. Voltage B-phase input
  11. Voltage C-phase input
  12. Neutral Voltage input

IMPORTANT REMARK!

If power = -0.01 is shown for any of the phases and voltage and current are not zero for this phase, check out following points:

  • Assure that A,B,C phases coincide in voltage and current.
  • Correct polarity? Reverse the current transformer placed at this phase.

Screen display

Panel diagram

Screen display

Display Summary
No. Display Explanation
1 Digital display module Three lines 4 digital LED show measurement power

data
2| Indicator of the data Unit| “K” means thousand; “M” means million
3| Enter key| For menu selection and confirmation
4
| Menu key| Used to open the menu and return to previous menu
5*| Up and Down key| Set the programming value

Note: Please see detail instructions of “*” items at “OPERATION MODE”

OPERATION MODE

The instrument has three displays. Every led will be on according to the parameter presently shown in screen.

When the 193PQH is powered up, the entire symbol will be on, and the meter starts to self- test.
After some seconds, the meter is ready for operation and shows one of the available screens.

Icon Parameters on display can be switched by pressing key or . LED shown on screen at any moment

When the key is pressed, the screen CURRENT values of each phase are now showing.
Pressing again the key , the screen will show the following parameters successively.
In setting menu, pressing key can move the setting cursor to left;
Pressing can enter the number 0 ~ 9.
This key named “SET” key, pressing it can open the programming menu and return to previous menu.
This key named “Enter” key, pressing this key you can exit it with saving any modification that you might have done, in menu operation press “Enter” key, and user can go to the next menu.

Note:

Press key or in normal standby status, and the meter will show different data in main screen:
In the menu set mode, when changes the parameter and exit setting, the meter will ask to
“SAVE”, press exit without saving press save and exit.

SETUP PROCEDURE

The SETUP procedure of the BJ193-X is performed by means of several SETUP options.
Once into the SETUP, use the keyboard to select different options and enter required variables:

Setup Procedure

Note:

The procedure above is for reference, not all series have the step 3 (communication preference), only the K series have this step. If you want the X series and D series have this function,

Menu are not specified in the manual would be invalid, do any modify will be no change. If doubt about the please contact the Technical Service. tech@cqbluejay.com

SAFETY CONSIDERATIONS

All installation specification described at the previous chapters named :
INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. This instrument is factory-shipped at proper operation condition.

MAINTENANCE

The 193X does not require any special maintenance. No adjustment, maintenance or repairing action should be done when the instrument open and powered on, should those actions are essential, high-qualified operators must perform them.

Before any adjustment, replacement, maintenance or repairing operation is carried out, the instrument must be disconnected from any power supply source.

When any protection failure is suspected to exist, the instrument must be immediately put our of service. The instrument’s design allows a quick replacement in case of any failure.

TECHNICAL SERVICE

For any inquiry about the instrument performance or whether any failure
happens, contact to Blue Jay’s technical service.
Blue Jay – After-sales service
E-mail : tech@cqbluejay.com

CUSTOMER SUPPORT

Tel: +0086-023-67628702
Email:tech@cqbluejay.com
www.cqbluejay.com
Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

BLUE JAY Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals