systemair 24808 EC-BASIC-CO2 and Temperature Controller Instructions
- June 4, 2024
- systemair
Table of Contents
systemair 24808 EC-BASIC-CO2 and Temperature Controller
Description
- Simple to install, connect and set up
- 50/60HZ mains option
- Can be used with all 220V single phase and 380V three phase EC fans
- Built in sensors
- Conforms to CE standards EN 60730-1, EN 61000-6-3, EN 61000-6-1
- Demand control made simple
The controller compares room temperature with an adjustable set point (knob) and regulates a 0..10 V proportional integral INTERNAL 1 SIGNAL in direct or reverse action based on jumper JP1 setting:
JP1 closed 1-2 = heating (reverse action)
JP1 closed 2-3 = cooling (direct action)
The controller compares also CO2 with an adjustable set point (SW3) and regulates a 0..10 V proportional INTERNAL 2 SIGNAL in direct action.
The output signal applied to a ventilator is the maximum between INTERNAL 1 SIGNAL and INTERNAL 2 SIGNAL.
The range for temperature knob set point is from 5 to 30°C
Technical parameters
Other
Weight| 0,15 kg
Default group
Frequency| 50/60 Hz
Power consumption| 1,5 W
Temperature range| -20-50 °C
CO2 measurement range| 0-2000 PPM
Dimensions
Accessories
Documentation
IMO_EC-BASIC_EN_SV_rev3.pdf (1,42MB)
24808_Declaration of Conformity_EN.pdf (127,33kB)
Wiring
Name: EC-BASIC-CO2 AND TEMPERATURE | Item no.: 24808
Document type: Product card | Document date: 2019-08-01 | Generated