BLUE JAY BJ-QPAX Three Phase Power Transducer User Manual
- June 10, 2024
- BLUE JAY
Table of Contents
Three-Phase Transducer
BJ- QPAX / QPVX
User Manual
Version:1.3
Features
- AC Voltage Input: 110V,220V,380V optional
- AC Current Input: 0-5A, 5-10A, 0-10A optional
- Output: 0-5V,0-10V,4-20mA, 0-20mA optional
- RMS measurement and output
- 0.2 measurement accuracy
- 200ms response time
- 35mm Din rail mounting
- Support customized parameters
Technical parameters
Power Supply | AC/DC 85-265VAC/DC (..Customer specified) |
---|---|
Signal input | Current(QPAX): 0-1A / 0-5A(..Customer specified) Voltage(QPVX): |
0-100V / 0-400V(..Customer specified)
Output| DC 4 – 20 mA / 0-20mV / 0-5V / 0-10V
Accuracy| 5 ±0.5%
Accuracy drift| Annual Variation < 0.2%
Response time| 5 200 ms
Isolation| Input / output / power supply
Power consumption| DC —-. 3W, AC —-. 4VA
Case Material| ABS fireproof materials
Insulation Voltage| AC 2KV RMS / min
Weight| About 650g
Insulation Resistance| When DC 500V ,100 MO
Dimension| 120(L) X 110(W) X 75(H) mm
Installation| Fixed in a standard 35mm (1.38 inch) DIN rail or screwed on the
cabinet
Working Condition| 0 – 50C/ less than 95% RH (Non-condensing)
Storage Conditions| -20 – 70C/ less than 70% RH (Non-condensing)
Connection drawing
Current transducer
(1) Current C-phase output
(2) Current C-phase input
(3) Current B-phase output
(4) Current B-phase input
(5) Current A-phase output
(6) Current A-phase input| (16) C-phase output pin (-)
(17) C-phase output pin (+)
(18) B-phase output pin (-)
(19) B-phase output pin (+)
(20) A-phase output pin (-)
(21) A-phase output pin (+)
---|---
Voltage transducer
(1) Voltage C-phase output
(2) Voltage C-phase input
(3) Voltage B-phase output
(4) Voltage B-phase input
(5) Voltage A-phase output
(6) Voltage A-phase input| (16) C-phase output pin (-)
(17) C-phase output pin (+)
(18) B-phase output pin (-)
(19) B-phase output pin (+)
(20) A-phase output pin (-)
(21) A-phase output pin (+)
---|---
Power Supply : AC/DC 220V
Notes: Listed above picture is for reference!
Detail wiring instructions please refer to product label
Dimension
Notes
- Please confirm the parameter on the label match the order specification
- Confirm the power supply, input current and voltage
- Transducer can connect to the CT / PT secondary side
For any inquiry about the instrument performance or whether any failure
happens, contact to Blue Jay’s technical service.
Blue Jay – After-sales service
Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District ,
400020 Chongqing
Tel – + 0086 023 86850812
Fax – + 0086 023 67636974
E-mail : tech@cqbluejay.com
Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District,
Chongqing