MGC LT-6741 Note Regarding MP Manual Stations Instructions

June 10, 2024
MGC

NOTE REGARDING MP MANUAL STATIONS

LT-6741 Note Regarding MP Manual Stations

Note: Forward this document to the programmer of the system.

When you add an MP (MGC Protocol) manual station in the Configurator, it is configured as class B by default. Single stage manual stations must be configured as class A. Follow the instructions below to configure a manual station as class A. (Instructions for the MGC-400 Configurator are on page 2.)

MGC-4000 Configurator

To add an MP (MGC Protocol) manual station, follow these steps:

  1.  In the Add Devices window, click the Device menu and select Dual Input (MIX4).
  2.  Click the Option menu, and select Class A for a single stage manual station and Class B for a two stage manual station.
  3.  Select Manual Pull in the Type menu.
  4. Click Add.MGC LT 6741 Note Regarding MP Manual Stations

For example, to add a single stage manual station, add Dual Input (MIX4) and select Class A in the Option menu.MGC LT 6741 Note Regarding MP Manual
Stations - Fig

To add a two stage manual station, add Dual Input (MIX4) and select Class B in the Option menu. The first input is the pull handle and the second input is the stage two key.MGC LT 6741 Note Regarding MP Manual Stations - Fig
1

Convert a Device to Class A

To convert a class B device to class A after you have added it, follow these steps.

  1.  Double-click Class B in the IptMethod column for the device.
  2. Select Class A in the menu that appears.MGC LT 6741 Note Regarding MP Manual Stations - Fig 2

To convert the device back to class B, select Class B in the IptMethod column.

MGC-400 Configurator

To add an MP (MGC Protocol) manual station, follow these steps.

  1.  Add a (MIX-404x) Dual InputA.
    The device appears as two entries, (MIX-404x)Dual InputA and (MIX-404x)Dual InputB. These entries represent a two stage manual station. The first input is the pull handle and the second input is the stage two key.
    MGC LT 6741 Note Regarding MP Manual Stations - Fig 3

  2. To convert this device to a single stage manual station, double-click in column F3 for the first entry, (MIX404x)Dual InputA.

  3. Select CA in the menu that appears.

MGC LT 6741 Note Regarding MP Manual Stations - Fig 4

The Configurator deletes (MIX-404x)Dual Input B automatically. The address that was used by (MIX404x) Dual Input B is free to be used by another device.

MGC LT 6741 Note Regarding MP Manual Stations - Fig 5

Mircom Group of Companies
http://www.mircomgroup.com
888-660-4655
905-660-4655

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals