Remote I/O Module System Configuration List
Part No. | Specification | Description |
---|---|---|
GFGW-RM01N | Modbus TCP-to-Modbus RTU/ASCII, 4 Ports | Gateway |
GFMS-RM01S | Master Modbus RTU, 1 Port | Main Controller |
GFDI-RM01N | Digital Input 16 Channel | Digital Input |
GFDO-RM01N | Digital Output 16 Channel / 0.5A | Digital Output |
GFPS-0202 | Power 24V / 48W | Power Supply |
GFPS-0303 | Power 5V / 20W | Power Supply |
0170-0101 | 8 pin RJ45 female connector/RS-485 Interface | Interface Module |
Product Description
I. The interface module can convert the gateway’s RS485 port into a RJ45
connection.
II. The main controller is in charge of the management and dynamic
configuration of I/O parameters and so on.
III. The power module and interface module are standard for remote I/Os and
users can choose the model or brand they prefer.
Schneider TM241 Connection Setup
This section details how to connect a gateway to Schneider TM241. For detailed information regarding , please refer to theSeries Product Manual
i-Designer Program Setup
I. Make sure that the module is powered and connected to the gateway module using an Ethernet cable
II. Click to launch the software
III. Select “M Series Module Configuration” IV. Click on the
“Setting Module” icon V. Enter the “Setting Module” page for
M-seriesVI. Select the mode type based on the
connected moduleVII. Click on “Connect”VIII. Gateway Module IP SettingsNote: The IP
address must be in the same domain as the controller equipment
IX. Gateway Module Operational Modes Note:
Set Group 1 as Slave and set the gateway to use the first set of RS485 port to
connect to the main controller(GFMS-RM01N)
Schneider TM241 Hardware Connections
This section details how to use the SoMachine program to connect TM241
and
I. Modbus TCP connects with the gateway via the Ethernet cable going through
the Ethernet port on the TM241
Schneider TM241 Connection Setup
I. Launch SoMachine and click on “指令” on the right side of the program
- Click on “Ethernet_1 (EthernetNetwork)”
- Under “fixed IP Address”, set up the controller’s IP Address and Subnet Mask
- Right-click on “Ethernet_1 (Ethernet Network)” and then click on “Add Device…”
- In “Protocol Managers”, click to add a new “Industrial Ethernet Manager”
II. Add New Devices
- Right-click on “Industrial Ethernet Manager” and then select “Add Device…”
- Under “Modbus TCP Slaves”, click to add a new “Generic Modbus TCP Slave”
III. Set up gateway IP address
- Select “Generic Modbus TCP Slave”
- Select “Modbus TCP Slave Configuration” and set up the gateway IP address under “Slave IP Address”
IV. Reading Register Setup
- Select “Modbus TCP Channel Configuration”
- Select “Add Channel…”
- Set up the Master ID under “Unit ID”
- Under “Function Code”, select “Read Holding Registers (Function Code 03)”
- In the “Offset” field, enter “4096” for the read register’s IP address
- In the “Length” field, set up the data amount for reading
V. Write Register Setup
- Select “Add Channel…”
- Set up the Master ID under “Unit ID””
- Under “Function Code”, select “Write Multiple Registers (Function Code 16)”
- In the “Offset” field, enter “8192” for the Write register’s IP address
- In the “Length” field, set up the data amount for writing
VI. Command Address Mapping
- Select “Modbus TCP Slave I/O Mapping”
- Enter the I/O mapping name in “Input”
- Enter the I/O mapping name in “Output”
Notes:
※ ’s first GFDI-RM01N has the register address at 1000(HEX)
converted to (DEC) with the starting address at 4096
※ ’s first GFDO-RM01N has the register address at 2000(HEX)
converted to (DEC) with the starting address at 8192
VII. Sample Program
Control with one GFDI-RM01N and one GFDO-RM01N
When the first point of DI has received a signal and is triggered, the first
point of DO will output a signal as it is connected