DAUDIN GFGW-RM01N Remote I/O Module System User Manual

June 11, 2024
DAUDIN

DAUDIN logo 2

and Schneider PLC
Modbus TCP
Connection Operating Manual

DAUDIN GFGW-RM01N Remote I O Module System

2302EN
V2.0.0

 Remote I/O Module System Configuration List

Part No. Specification Description
GFGW-RM01N Modbus TCP-to-Modbus RTU/ASCII, 4 Ports Gateway
GFMS-RM01S Master Modbus RTU, 1 Port Main Controller
GFDI-RM01N Digital Input 16 Channel Digital Input
GFDO-RM01N Digital Output 16 Channel / 0.5A Digital Output
GFPS-0202 Power 24V / 48W Power Supply
GFPS-0303 Power 5V / 20W Power Supply
0170-0101 8 pin RJ45 female connector/RS-485 Interface Interface Module
Product Description

I. The interface module can convert the gateway’s RS485 port into a RJ45 connection.
II. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
III. The power module and interface module are standard for remote I/Os and users can choose the model or brand they prefer.

Schneider TM241 Connection Setup

This section details how to connect a gateway to Schneider TM241. For detailed information regarding DAUDIN logo 2, please refer to theDAUDIN logo
2Series Product Manual

 i-Designer Program Setup

I. Make sure that the module is powered and connected to the gateway module using an Ethernet cable

DAUDIN GFGW-RM01N Remote I O Module System - Ethernet
cable

II. Click to launch the software

III. Select “M Series Module Configuration” DAUDIN GFGW-RM01N Remote I O
Module System - software 1IV. Click on the “Setting Module” icon DAUDIN GFGW-RM01N Remote I O Module System - software
2V. Enter the “Setting Module” page for M-seriesDAUDIN GFGW-RM01N Remote I O Module System - software
3VI. Select the mode type based on the connected moduleDAUDIN GFGW-RM01N Remote I O Module System - software
4VII. Click on “Connect”DAUDIN GFGW-
RM01N Remote I O Module System - software 5VIII. Gateway Module IP SettingsDAUDIN GFGW-RM01N Remote I O
Module System - software 6Note: The IP address must be in the same domain as the controller equipment
IX. Gateway Module Operational ModesDAUDIN GFGW-RM01N Remote I O Module
System - software 7 Note:
Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller(GFMS-RM01N)

Schneider TM241 Hardware Connections

This section details how to use the SoMachine program to connect TM241 andDAUDIN logo 2
I. Modbus TCP connects with the gateway via the Ethernet cable going through the Ethernet port on the TM241

Schneider TM241 Connection Setup

I. Launch SoMachine and click on “指令” on the right side of the programDAUDIN
GFGW-RM01N Remote I O Module System - software 8

  1. Click on “Ethernet_1 (EthernetNetwork)”
  2. Under “fixed IP Address”, set up the controller’s IP Address and Subnet Mask
  3. Right-click on “Ethernet_1 (Ethernet Network)” and then click on “Add Device…”
  4. In “Protocol Managers”, click to add a new “Industrial Ethernet Manager”

II. Add New DevicesDAUDIN GFGW-RM01N Remote I O Module System - software
9

  1. Right-click on “Industrial Ethernet Manager” and then select “Add Device…”
  2. Under “Modbus TCP Slaves”, click to add a new “Generic Modbus TCP Slave”

III. Set up gateway IP address DAUDIN GFGW-RM01N Remote I O Module System -
software 10

  1. Select “Generic Modbus TCP Slave”
  2. Select “Modbus TCP Slave Configuration” and set up the gateway IP address under “Slave IP Address”

IV. Reading Register Setup DAUDIN GFGW-RM01N Remote I O Module System -
software 11

  1. Select “Modbus TCP Channel Configuration”
  2. Select “Add Channel…”
  3. Set up the Master ID under “Unit ID”
  4. Under “Function Code”, select “Read Holding Registers (Function Code 03)”
  5. In the “Offset” field, enter “4096” for the read register’s IP address
  6. In the “Length” field, set up the data amount for reading

V. Write Register SetupDAUDIN GFGW-RM01N Remote I O Module System -
software 12

  1. Select “Add Channel…”
  2. Set up the Master ID under “Unit ID””
  3. Under “Function Code”, select “Write Multiple Registers (Function Code 16)”
  4. In the “Offset” field, enter “8192” for the Write register’s IP address
  5. In the “Length” field, set up the data amount for writing

VI. Command Address MappingDAUDIN GFGW-RM01N Remote I O Module System -
software 13

  1. Select “Modbus TCP Slave I/O Mapping”
  2. Enter the I/O mapping name in “Input”
  3. Enter the I/O mapping name in “Output”

Notes:
DAUDIN logo 2 ’s first GFDI-RM01N has the register address at 1000(HEX) converted to (DEC) with the starting address at 4096
DAUDIN logo 2 ’s first GFDO-RM01N has the register address at 2000(HEX) converted to (DEC) with the starting address at 8192
VII. Sample Program
Control with one GFDI-RM01N and one GFDO-RM01N
When the first point of DI has received a signal and is triggered, the first point of DO will output a signal as it is connected DAUDIN GFGW-RM01N Remote
I O Module System - software 14DAUDIN logo 2