SJE RHOMBUS 9500054M IFS Single Phase Duplex Owner’s Manual
- June 11, 2024
- SJE RHOMBUS
Table of Contents
INSTALLER FRIENDLY SERIES® (IFS)
SINGLE PHASE DUPLEX
Demand Dose or Timed Dose, Float or C-Level™ Sensor Controlled System for
Pump Control and System Monitoring
The Next Generation IFS duplex control panel utilizes an innovative circuit
board design enclosed in a touch-safe housing to control two 120/208/240V
single phase pumps in water and sewage applications. These newly redesigned
IFS panels feature an easy-to use color LCD interface located on the inner
door for programming and system monitoring. The panel configuration can be
easily converted in the field to either a timed dose or demand dose through
the LCD interface. Available with the EZconnex®
float system.
The panel can easily be changed in the field to utilize either floats or the
patented C-Level™ sensor for continuous level monitoring. The C-Level™ sensor
senses the level in the tank and sends a signal to the panel. Pump activation
levels can be adjusted by using the LCD interface. C-Level™ CL40 sensor
operating range is 3-39.9 inches (7.6- 101.3 cm). C-Level™ CL100 operating
range is 3-99.5 inches (7.6-252.7 cm). The C-Level™ Sensor features a five
year limited warranty.
LCD INTERFACE FEATURES
- Full color graphics and menu navigation encoder for easy setup
- Touch safe housing
- Pump Hand/Off/Auto Control selectable via menu navigation
- C-Level™ Sensor or Float operation selectable via menu navigation
- Demand or Timed Dose operation selectable via menu navigation
- Tank Level Indication and setpoint monitoring at-a-glance
- Lead pump is easily identified by a graphic ring around the current lead pump regardless of control mode (timed dose or demand)
- Displays remaining time in each active ON or OFF Timed Dose mode, as well as at-a-glance ON or OFF time elapsed graphic around lead pump
- RJ45 communication connector
- Flashing function for alarm beacon and horn (configurable)
- Manual alarm reset (configurable)
COMPONENTS
-
Enclosure measures 12 x 10 x 6 inches (30.48 x 24.4 x 15.24) NEMA 4X (ultraviolet stabilized thermoplastic, padlockable with integral mounting flanges, drip shield, heavy duty cover latches, and stainless steel ¼ turn set screw; for outdoor or indoor use)
-
Red Alarm Beacon provides 360° visual check of alarm condition
-
Circuit breakers provides pump power disconnect and branch circuit protection included as standard on all panels
-
C-Level™ Sensor and float connection terminal blocks
-
Controller Features:
a. Incoming Control/Alarm Power terminal blocks
b. Control/Alarm Power/System Status green LED indicators illuminate if control/alarm power is present and controller is operating
c. Controller status green LED indicators for: Power/Active, Float Input Status, Pump Run, C-Level Active
d. Normally open auxiliary alarm contacts included as standard
e. Control Power On/Off switch
f. Green LED Pump Run indicators illuminate when pump is called to run*
g. Control panel able to operate if LCD interface fails or is disconnected
h. Touch safe housing -
Alarm Horn provides audible warning of alarm condition (not shown)
-
Exterior Alarm Test/Silence push button allows horn and light to be tested and horn to be silenced in an alarm condition; alarm automatically resets once alarm condition is cleared (not shown)
-
Modbus Port (RJ45) for future expansion – eg. seal fail modules, remote monitoring, valve control, In-Site® , logging, etc. (not shown)
*In fault condition, LED indicators will be red.
Note: Added options, voltage, and amp range selected may change enclosure size and enclosure features, and component layout.
Note: Schematic/Wiring Diagram and Pump Specification Label are located inside the panel.
INSTALLER FRIENDLY SERIES® SINGLE PHASE DUPLEX – Demand or timed dose float controlled system for pump control and system monitoring.
NOTE: Pump down applications only. Industry practices suggest that a secondary device, such as a float switch, be used for redundant activation of the high level alarm and pump shut off when using the C-Level™ sensor.
| OPTIONS| DESCRIPTION
---|---|---
| 1J| Duo Alarm Inputs
| 3E| High Water Alarm Float (must also select Option 17) Only Available with
Float Switch Application = C
| 4D| Redundant Off Float (must also select Option 17) Only Available with
Float Switch Application = C
✓| 6A| Auxiliary Alarm Contact, Form C included as standard)
✓| SAC| Display Board – Includes: ETM Counter; Events (Cycles) Counter; Alarm
Counter, and Override Counter (Timed Dose Only) (included as standard)
✓| 10E| Lockable Latch – NEMA 4X (included as standard)
| 1OF| Lightning Arrestor (must also select Option 15A)
| 10K| Anti-condensation Heater (must also select Option 15A)
| 11 C| Additional NEMA 1 Remote Alarm Panel
| 11D| Additional NEMA 4X Remote Alarm Panel
| 15A| Control/Alarm Circuit Breaker
| 16A| 10′ Cord in Lieu of 20′ Cord (per Float)
| 16B| 15′ Cord in Lieu of 20′ Cord (per Float)
| 16C| 30′ Cord in Lieu of 20′ Cord (per Float)
| 16D| 40′ Cord in Lieu of 20′ Cord (per Float)
| 17C| Sensor Float3 / Internally Weighted (per Float) – Mercury
---|---|---
| 17D| Sensor Float3 / Externally Weighted (per Float) – Mercury
| 17G| SJE MilliAmpMaster” / Pipe Clamp (per Float) – Mechanical
| 17H| SJE MilliAmpMaster” / Externally Weighted (per Float) – Mechanical
| 17J| Sensor Float3 / Pipe Clamp (per Float) – Mercury
| 19 F| Additional 4th Float (Timer Override or Lag) Only Available with Float
Switch Application : H
| 24E| C-Level- CL40 Sensor with 4′ Vent Tube and 20′ Cord
| 24 F| C-Lever CL40 Sensor with 4′ Vent Tube and 40′ Cord
| 24G| C-Level’ CL40 Sensor with 8′ Vent Tube and 20′ Cord
| 24H| C-Level’ CL40 Sensor with 8′ Vent Tube and 40′ Cord
| 24X| No C-Lever CL40 Sensor
| 29A| Clever CL100 Sensor with 10′ Vent Tube and 20′ Cord
| 29B| Clever CL100 Sensor with 10′ Vent Tube and 40′ Cord
| 29X| No C-Lever CL100 Sensor
| 33D ■| EZconnexe® 3-Port, 25′, with 10′ Floats (3) / Pipe Clamp
| 33E ■| EZconnexe® 3-Port, 50′, with 10′ Floats (3) / Pipe Clamp
| 33G ■| EZconnexe® 3-Port, 25′, with 20′ Floats (3) / Pipe Clamp
| 33H U| EZconnext® 3-Port, 50′, with 20′ Floats (3) / Pipe Clamp
| 35D ■| EZconnext® 4-Port, 25′, with 10′ Floats (4) / Pipe Clamp
| 35E ■| EZconnexe® 4-Port, 50′, with 10′ Floats (4) / Pipe Clamp
| 35G ■| EZconnexe® 4-Port, 25′, with 20′ Floats (4) / Pipe Clamp
| 35H U| EZconnex® 4-Port, 50′, with 20′ Floats (4) / Pipe Clamp
EZconnex® mechanically-activated, narrow angle float switches with quick release connections