Technical Specifications

Mains voltage <0.5W
Stand-by power 220~240VAC  50/60Hz
DALI Channel 1 Max. 25pcs devices, 50mA
DALI Channel 2 Max. 15pcs devices, 30mA
Warming-up Appr. 20s
Sensor principle PIR detection

Detection range (Max.)
HIR32| Installation Height : 6m
Detection Range (Ø) :9m
Detection range (Max.)

HIR32/R
Detection range (Max.)
HIR32/H
Detection range (Max.)

HIR32/RH| Installation Height : 6m
Detection Range(Ø): 10m
Installation height:15m (forklift)  12m (person)
Detection range (Ø):   24m
Installation height:20m (forklift)  12m (person)
Detection range (Ø):40m
Detection angle| 360°
Operation temperature| Ta: -20°C ~ +50°C
IP rating| IP20
EMC standard (EMC)| EN55015, EN61000
Safety standard (LVD)| EN60669, AS/NES60669
Certification| CB, CE , EMC, RCM

Installation

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
1

  1. Ceiling (drill hole 65mm)
  2. Carefully prise off the cable clamps.
  3. Make connections to the pluggable terminal blocks.
  4. Insert plug connectors and secure using the provided cable clamps, then clip terminal covers to the base.
  5. Fit detection blind (if required) and desired lens.
  6. Clip fascia to body.
  7. Bend back springs and insert into ceiling.

Functions

3.1 Daylight Harvest (Daylight Regulating)
Daylight sensor measures the available surrounding natural light, calculates how much electrical light is needed to reach the total lux expected. The demand is given to the LED driver by DALI signal, so as to deliver the needed amount of electric light.

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
2

3.2 Lux Off Function
The built-in daylight sensor can measure ambient natural light and switch off the fixture automatically whenever artificial light is not required (natural light lux level exceeds daylight threshold).
3.3 Dual DALI Output Control
Two channels of self-powered DALI output are available on HIR32 for connection of two groups of LED drivers. Please note that both channels share the same control settings sent from the occupancy sensor and photocell.

System Capacity DALI channel DALI Driver < 2mA

HIR32 includes 2 channels
total 80mA max. DALI PSU| DALI PSU Channel 1 (max 50mA)| 25 pcs
DALI PSU Channel 2 (max 30mA)| 15 pcs

3.4 Manual Override (Push Function)
Three push terminals (P1, P2, P3) are available on the HIR32 for end-users to switch on/off, change the light brightness, colour temperature of the two DALI channels temporarily. The settings will revert to daylight harvest mode after sensor time-out.

  • Long push on P1: adjust the hold-time light brightness of DALI channel 1; Short push (<1s) on P1: on/off function
  • Long push on P2: adjust the hold-time light brightness of DALI channel 2; Short push (<1s) on P2: on/off function
  • Long push on P3: cycles through colour tuning on both channels. (work with DT8 LED driver only) Short push (<1s) on P3: resume automatic daylight harvest mode .

Wire Preparation

Pluggable screw terminal. It is recommended to make connections to the terminal before fitting to the sensor.

  1. 200 metres (total) max. for 1mm² CSA (Ta = 50℃)
  2. 300 metres (total) max. for 1.5mm² CSA (Ta = 50℃)

Wiring Diagram

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
4

Description of the Button Functions (remote control HRC-11)

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
5

Permanent ON/OFF [ button 1] Press button 1, to select permanent ON or permanent OFF mode.

  • Press button 2/4 to to quit this mode.
    RESET[ button 2]
    Press button 2, all settings go back to default values as below:
    Hold-time 5min, Daylight sensor 100Lux, Stand-by time: 10min, Stand-by dimming level: 20%
    Test Mode[ button15 ]
    This button is for testing purpose only. The sensor goes to test mode (hold- time is 2s) after commissoning, meanwhile the stand-by period and daylight sensor are disabled.

  • This mode can be ended by pressing “reset”, or any button of “scene mode” and “hold-time”. The sensor settings are changed accordingly.
    Shift [ button3 ]
    Press button 3, the LED on the top left corner is on to indicate mode selection.
    All values / settings in RED are in valid for 20 seconds.
    Auto Mode [ button 4]
    Press button 4 to initiate automatic mode. The sensor starts working and all settings remain as before the light is switched ON/OFF.
    Semi-auto Mode [ button 3 & 4]

    1. Press button 3 Shift (the red LED is on for indication).
    2. Press button 4 to initiate semi-auto mode. The fixture is manually on by push-switch and automatically off in semi-auto mode.

Power output [ button 5] 5Press button 5, the light output shifts between 80% and 100%.
Note: the function of “Sensor off” and “Twilight” are disabled.
Brightness +/- [ button 6] Press button 6 to adjust the light brightness and color temperature between 10%~100%.
Scene prog. [ zone 7 ] (One-key-commissioning)

  1. Press button “Start” to program.
  2. Select the buttons in 8“Detection range”,9/10“Daylight threshold”,11 “Hold time”12,“Stand-by time”13,“Stand-by dimming level” to set all parameters.
  3. Press button 7 “Memory” to save all the settings programmed in the remote control.
  4. Press button 7 “Apply” to set the settings to each sensor unit(s).
    For example, to set detection range 100%, daylight threshold
    Disable, hold time 5min, stand-by time +∞, stand-by dimming level 30%, steps should be:
    Press button 7 Start, button 8 100%,10  Disable, Shift, 11 5min, 3 Shift, 12+∞ 13, 30%,7 Memory. By pointing to the sensor unit(s) and pressing 7Apply, all settings are passed on the sensor(s).

Detection range [ zone 8]
These two buttons are disabled.
Daylight threshold [ zone 9]
Press buttons in zone to set daylight sensor at 2Lux/ 10Lux /50Lux / 100Lux / 300Lux / 500Lux / Disable.
Note: To set daylight sensor at 100Lux / 300Lux / 500Lux, press 3 Shift button first.
Ambient daylight threshold [ button 10]

  1. Press button 3 Shift, the red LED starts to flash.
  2. Press button 10, the ambient lux level is sampled and set as the new daylight threshold / target Lux level.

Hold time [ zone 11]

Press buttons in zone 11 to set the hold time at 2s / 30s / 1min /5min / 10min / 15min / 20min / 30min.
Note:

  1. To set hold-time at 30s / 5min / 15min / 30min, press button 3 Shift at first.
  2. 2s is for test purpose only, stand-by period and daylight sensor settings are disabled in this mode.

*To exit from Test mode, press button 2 or any button in zone 11.
Stand-by time [ zone 12]

Press buttons in zone 12 to set the stand-by period at 0s / 10s /1min / 5min / 10min / 30min / 1h / +∞.
Note: “0s” means on/off control; “+∞” means bi-level control, 100% on when motion detected, and remains at the stand-by dimming level when no presence after hold-time.

Stand-by dimming level [ zone 13] Press buttons in zone 13 to set the stand-by dimming level at 10% /20% / 30% / 50%.
Note: the function of 24h/12h/4h/30s are disabled.
Dual tech & RF mode [ zone14 ]
All buttons in zone 14 are disabled.

Detection Pattern & Optional Accessories

1. HIR32 (Low-bay)

HIR32: Low-bay flat lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
7

Mount height Tangential (A) Radial (B)
2.5m max 50m²(Ø = 8m) max 13m² (Ø = 4m)
3m max 64m² (Ø = 9m) max 13m² (Ø = 4m)
4m max 38m² (Ø = 7m) max 13m²(Ø = 4m)
5m max 38m² (Ø = 7m) max 13m² (Ø = 4m)
6m max 38m² (Ø = 7m) max 13m² (Ø = 4m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
8

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
9

2. HIR32/R (Reinforced Low-bay)

HIR32/R: Low-bay convex lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
10

Mount height Tangential (A) Radial (B)
2.5m max 79m² (Ø = 10m) max 20m² (Ø = 5m)
3m max 79m² (Ø = 10m) max 20m² (Ø = 5m)
4m max 64m² (Ø = 9m) max 20m² (Ø = 5m)
5m max 50m² (Ø = 8m) max 20m² (Ø = 5m)
6m max 50m² (Ø = 8m) max 20m² (Ø = 5m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
11

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
12

3. HIR32/H (High-bay)

HIR32/H: High-bay lens detection pattern for forklift @ Ta = 20ºC
(Recommended ceiling mount installation height 10m-15m)

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
13

Mount height Tangential (A) Radial (B)
10m max 380m² (Ø = 22m) max 201m² (Ø = 16m)
11m max 452m² (Ø = 24m) max 201m² (Ø = 16m)
12m max 452m² (Ø = 24m) max 201m² (Ø = 16m)
13m max 452m² (Ø = 24m) max 177m² (Ø = 15m)
14m max 452m² (Ø = 24m) max 133m² (Ø = 13m)
15m max 452m² (Ø = 24m) max 113m² (Ø = 12m)

HIR32/H: High-bay lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-12m)

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
14

Mount height Tangential (A) Radial (B)
2.5m max 50m² (Ø = 8m) max 7m² (Ø = 3m)
6m max 104m² (Ø = 11.5m) max 7m² (Ø = 3m)
8m max 154m² (Ø = 14m) max 7m² (Ø = 3m)
10m max 227m² (Ø = 17m) max 7m² (Ø = 3m)
11m max 269m² (Ø = 18.5m) max 7m² (Ø = 3m)
12m max 314m² (Ø = 20m) max 7m² (Ø = 3m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
15

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
16

4. HIR32/RH (Reinforced High-bay with 3-Pyro)

HIR32/RH: Reinforced high-bay lens detection pattern for forklift @ Ta = 20ºC
(Recommended ceiling mount installation height 10m-15m)

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
17

Mount height Tangential (A) Radial (B)
10m max 346m² (Ø = 21m) max 177m² (Ø = 15m)
11m max 660m² (Ø = 29m) max 177m² (Ø = 15m)
12m  max 907m² (Ø = 34m) max 154m² (Ø = 14m)
13m max 962m² (Ø = 35m) max 154m² (Ø = 14m)
14m max 1075m² (Ø = 37m) max 113m² (Ø = 12m)
15m max 1256m 2 (Ø = 40m) max 113m 2 (Ø = 12m)
20m max 707m² (Ø = 30m) max 113m² (Ø = 12m)

HIR32/RH: Reinforced high-bay lens detection pattern for single person @ Ta = 20OC
(Recommended ceiling mount installation height 2.5m-12m)

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
18

Mount height Tangential (A) Radial (B)
2.5m max 38m² Ø = 7m) max 7m² (Ø = 3m)
6m max 154m² (Ø = 14m) max 7m² (Ø = 3m)
8m max 314m²(Ø = 20m) max 7m² (Ø = 3m)
10m max 531m² (Ø = 26m) max 13m² (Ø = 4m)
11m max 615m² (Ø = 28m) max 13m² (Ø = 4m)
12m max 707m² (Ø = 30m) max 13m² (Ø = 4m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK HIR32 Series Flush Mount PIR Motion Sensor - fig
19

Additional Information / Documents

  1. Regarding precautions for PIR sensor installation and operation, please kindly refer to www.hytronik.com/download>knowledge>PIRSensors – Precautions for Product Installation and Operation
  2. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download>knowledge>Hytronik Standard Guarantee Policy

HIR32-20210813-A0
www.HYTRONIK.COM

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals