EMERSON KHZ506LRL ZSI Scroll Condensing Units User Manual
- June 4, 2024
- Emerson
Table of Contents
EMERSON KHZ506LRL ZSI Scroll Condensing Units
Disclaimer
Thank you for purchasing the Emerson Copeland ZSI low Temperature Condensing
units. We trust that you will see this product meeting your refrigeration
needs efficiently and efficaciously.
Please read through the User Manual thoroughly to familiarize yourself with
the installation and commissioning process of this product and how to use it
optimally to suit your needs. Please do read the information given below
before proceeding with the rest of the manual. The Emerson Low temperature
refrigeration condensing units should only be installed by suitably qualified
and experienced refrigeration technicians. No responsibility can be accepted
for damage caused by inexperienced or inadequately trained site technicians or
improper system design. All instructions and procedures described in this
manual are based on good refrigeration trade practices as applicable to this
particular product. The installation contractor may prefer to use variations
to these recommendations. However, the methods described in this manual
represent the minimum requirements to avoid any subsequent warranty claims for
this equipment and its components. These instructions do not cover the
fundamentals of good electrical or refrigeration practice and are therefore
intended for use only by qualified and/or experienced personnel or technicians
certified by us. These instructions are general in nature for this family of
products and due to our policy of continuous improvement, some of the details
may not apply to the unit that you are installing. If in doubt, please consult
your local sales office, quoting unit model and serial number as shown on the
name plate. In case of ambiguity, the wiring diagram supplied with each unit
takes precedence over the diagram in this manual.
Important:
The information contained in this manual is critical to the correct operation and maintenance of the condensing unit and should be read by all persons responsible for the installation, commissioning and maintenance of this unit.
Icon Explanation
WARNING
This icon indicates instructions to avoid Personal injury and material damage.
This icon indicates operations with a danger of electric shock.
High voltage
Danger of burning or frost burn This icon indicates operations with a danger
of burning or frost burn.
Explosion hazard
This icon indicates operations with a danger of explosion.
CAUTION
This icon indicates instructions to avoid property damage and possible
personal injury.
IMPORTANT
This icon indicates instructions to avoid malfunction of the compressor
NOTE
This word indicates a recommendation for easier operation
Use personal safety equipment. Safety goggles, gloves, protective clothing, safety boots and hard hats should be worn where necessary.
Safety Instruction:
The equipment has been designed and manufactured to meet international safety
standards but, like any
mechanical/electrical equipment, care must be taken if you are to obtain the
best results.
- Service and maintenance of this unit, that is Electrical and Mechanical in nature should be carried out by technically trained and competent personnel. They should be familiar with Local Standards and Codes of Practice.
- When carrying out unit maintenance, ensure that the equipment is disconnected from the electrical power supply.
- Never Place the unit in flammable atmosphere. Do not bypass any Electrical and Product safety devices.
- Refrigerant used in this unit is classified under the COSHH regulations as an irritant, with set Occupational Exposure Levels (OEL) for consideration if installed in confined or poorly ventilated areas.
- Use personal protective equipment’s (PPE’s) while installation and commissioning the product at site.
- Under all Circumstances, any applicable local safety regulations requirement must be fulfilled.
- Ensure the proper earthing should be connected to condensing unit before starting the Unit.
- The condensing unit must only be used for its designed purposes with approved Refrigerants & lubrication oil, proper Electrical supply and within its scope of application.
- Do not start the unit until it is charged with refrigerant. Never charge the oxygen in the Unit/System
- Ensure that materials and wiring do not touch high temperature areas of the compressor & discharge line.
- Never install a system and leave it unattended when it has no charge, a holding charge, or with the service valves closed without electrically locking out the system.
- Under running condition, the compressor and the tubing can reach temperatures high enough to induce burns and in case of leak of refrigerant avoid eye contact.
- During maintenance, if Brazing or De-brazing process is required. Kindly ensure that there should not be any refrigerant & oil inside the system pipe or the brazing area.
- Company shall not be responsible for any kind of accidents occur at sites due lack of sense of responsibility, Mis-handling, Wrong practice of installation and not following the instructions as mentioned above.
- All the products are not released for use with caustic, poisonous or flammable substances
- Do not pressurize the unit above 300 PSI in ideal conditions with Nitrogen, dry air,& Refrigerant. Always use pressure regular valve while connecting to Nitrogen cylinder.
Receiving your unit
All units are shipped with a holding charge of dry nitrogen inside at a low but positive pressure. It is very important to check that this holding pressure exists at the time you receive each unit from us or our authorized representatives. Please inform us or our authorized representative if the holding charge is non-existent. Failure to do so could void the claim for other related system faults at a later period. Transit damage is essentially an insurance claim and is not covered under manufacturing defect. It is also advisable to inspect the rest of the unit for obvious physical damage and inform us or our authorized representative in case any is discovered.
Condensing Unit Handling Transport, Handling and Storage
- During transportation & storage, always keep the unit in vertical/upright position.
- Always move the CDU Boxes or pallet using shrink wrap packaging and all the boxes should be tighten properly with strapping tape. Because it may cause transit damage.
- Do not stack single boxes on top of each other without pallet in any case.
- Always move the units in fully closed container/Vehicle to avoid from rain.
- Handle the unit with care. The packaging allows the use of a forklift or pallet jack for handling. Use appropriate and safe handling equipment.
- It is recommended not to open the packaging before the unit is at final place for installation.
Features & Benefits:
Emerson Commercial and Residential Solutions is pleased to introduce the Copeland Scroll™ KHZXXXLRL condensing units for low temp applications. These condensing units are built with the ZSI scroll compressors with liquid injection and premium on-board CoreSense™ electronics features for diagnostics plus protection and come with a service door for ease of access and serviceability.
Some of the key features of this line-up of condensing units is as follows:
- Provides complete line-up of scroll CDUs (below 7.5 HP) for low temperature applications.
- Built with Copeland Scroll™ ZSI compressors for a silent and enhanced reliable operation.
- On-board CoreSense™ electronics unit for diagnostics and protection to assist contractors troubleshoot in the field.
- Uses Liquid Injection technology, controlled by CoreSense™ to protect the compressor from high discharge temperature.
- LED display alerts user of DLT sensor status and EXV operation enabling easier troubleshooting.
- Tropicalized for Indian climate to operate at higher ambient temperatures.
- Provides service door for ease of access & accessibility.
- Offering best life cycle cost solution to end users.
- Light weight and compactness, up to 20% weight reduction of equivalent semi-hermetic compressors Leading to Compact CDU Design.
- Optimized Condenser Design & Higher CFM for Elevated Ambient Conditions & Extreme Field Conditions.
- Hydrophilic blue fins condenser to prevent from corrosion.
- Large surface area coil ideally positioned to optimize air flow and heat transfer.
- Low Noise Fan for Quieter Fan Operation.
- Robust & Reliable components of construction.
CoreSense™ Electronics Module:
use the proven ZSI compressor range which features Liquid Injection Technology controlled by an intelligent electronics platform—the CoreSense™ Control Board. CoreSense™ regulates liquid injection by sensing the Discharge Line Temperature (DLT) to widen the operating envelope and enhance the product reliability. It also features LED display that alerts the user of sensor status and Electronic Expansion Valve (EEV) operation.
Function Descriptions:
The board will be used to turn the compressor on/off based on the demand signal from low pressure switch and thermostat. The board will control Liquid Injection through an EXV based on a temperature sensor placed on the discharge line.
Dipswitch Setting
- SW1 is used to control the liquid injection setpoint and cut out. Do not change settings and ensure that a replacement board is set correctly.
- SW2 and SW3 are not functional in ZSI CDU units
Dipswitch | Factory Setting |
---|---|
SW1 bit1 | OFF |
SW1 bit2 | OFF |
SW2 and SW3 | Not used |
Board Operation – EXV Testing
Button Function
Up| To operate EXV manually
Down
Reset| Resets the board
LED Display| Description
---|---
1
(YellowGreen)
| LED Blinking Pattern Indicates DLT Sensor Status
2(YellowGreen)| LED2 and LED3 Combination and Blinking Patterns Indicate EXV
Opening or Closing
3(Yellow Green)| LED2 and LED3 Blink Once When Entering or Exiting EXV Manual
Operation
4(Red)| LED4 Turns on as an Alarm when Triggered by any of the following:
- DLT overheat protection
- DLT sensor open circuit
- DLT sensor short circuit
Operation: Shift Between Auto Mode and Test Mode
- Push “Up” and “Down” together for 5 seconds to shift between Control Mode and Auto Mode
- LED2 and LED3 flashing together once means the shift is successful
Operate EXV Manually
- Short Push (< 2s) “Up” or “Down” to open or close EXV by one step
- Long Push “Up” and “Down” to open and close EXV rapidly
- LED2 will flash when EXV is opening and will remain on when EXV is fully open
- LED3 will flash when EXV is closing and will remain on when EXV reaches minimum opening
- Push “Up” and “Down” together for 5 seconds to revert to Auto Mode
- Board will automatically revert to Auto operation after 10 minutes from last manual button push
Diagnostic Function of the Board
LED1: Status Indicator of Discharge Line Temperature Sensor
LED4: Warning Signal
- Overheat Protection
- Sensor Failure, Circuit Open/Short
- Overheat Protection
- Sensor Failure, Circuit Open/Short
Standard Scope of Supply:
The following components are included in the KHZXXXLRL – E5EC6C condensing unit scope of supply:
Model| KHZ506| KHZ508| KHZ509| KHZ511| KHZ514|
KHZ515| KHZ518| KHZ521
---|---|---|---|---|---|---|---|---
Compressor with oil Sight glass| ✓| ✓| ✓| ✓| ✓|
✓| ✓| ✓
CoreSense along with EXV| ✓| ✓| ✓| ✓| ✓| ✓|
✓| ✓
Fan motor| ✓| ✓| ✓| ✓| ✓| ✓| ✓|
✓
Serviceable chassis| ✓| ✓| ✓| ✓| ✓| ✓|
✓| ✓
Blue fin coated condenser| ✓| ✓| ✓| ✓|
✓| ✓| ✓| ✓
Receiver with valve| ✓| ✓| ✓| ✓| ✓|
✓| ✓| ✓
Accumulator| ✓| ✓| ✓| ✓| ✓| ✓| ✓|
✓
Oil separator| ✓| ✓| ✓| ✓| ✓| ✓| ✓|
✓
Adjustable LP/HP switch| ✓| ✓| ✓| ✓| ✓|
✓| ✓| ✓
Liquid Line filter drier| ✓| ✓| ✓| ✓| ✓| ✓|
✓| ✓
Moisture Indicator| ✓| ✓| ✓| ✓| ✓| ✓|
✓| ✓
CDU service valves| ✓| ✓| ✓| ✓| ✓| ✓|
✓| ✓
Electrical Terminals| ✓| ✓| ✓| ✓| ✓| ✓|
✓| ✓
Crank Case Heater| ✓| ✓| ✓| ✓| ✓| ✓|
✓| ✓
Important Note – Above given Scope of supply comes with our Standard
designed Models. For any customized
requirement of additional accessories/system component, please contact our
Authorized WHS/Dealer or our
Regional Sales Manager
Physical Layout
Technical Specifications:
Refer Table 2 below for the dimension, weight & other mechanical details of
the product.
Always use AC-3 Category Contactor with above mentioned rating in table.
Refer below the operating envelope of the KHZXXXLRL CDU models
Installation
The condensing unit should be located in such a place to prevent any dirt,
plastic bag, leaves or papers from
covering the condenser and its fins. The unit must be installed without
restricting the airflow. A clogged condenser will increase the condensing
temperature, thus reduce the cooling capacity, and lead to a high-pressure
switch tripping. Clean the condenser fins on a regular basis.
Before Installation
- Check all the LOTO tags, Working Space, operative should have correct tools etc.
- Ensure the units received are the correct models for the intended application.
- Ensure the refrigerant, voltage and gauges are all suitable for the proposed application & unit.
- Check there is no damage to the units.
- Check that the proposed equipment locations are suitable and provide adequate support for the weight
of the units.
During Installation and Subsequent Maintenance
-
Installation and maintenance are to be performed only by qualified personnel who are familiar with
local codes and regulations and experienced with this type of equipment. -
As lifting equipment is required, ensure that it is suitable for purpose, certified and that the operators
are qualified to use it -
Safe working methods are identified, and operator have suitable PPE’s.
-
Ensure the working area has adequate ventilation during brazing procedures.
-
Disconnect and shut off power before installation or service of the equipment
-
Refrigerant release into the atmosphere is illegal. Proper evacuation, recovery, handling and leak
testing procedures must always be observed. -
Units must be earthed, and no maintenance work should be attempted prior to disconnecting the
electrical supply -
The electrical box/terminal covers, and fan guards must always remain fitted.
Note: All Compressors are delivered with sufficient oil for normal
operation. The optimum oil level or oil
return should be checked by operating the compressor until the system is
stable. It is not recommended
to top up Oil unnecessary. If required additional charge of oil for top-up or
oil change during
maintenance or in case of leakage. kindly use our qualified oil as per below
table recommended for
these Condensing units. Oil Level should not exceed 1/3rd of the Compressor
sight glass.
10
Oil & Refrigerant:
Qualified Refrigerant | R404A |
---|---|
Copeland® Brand Products Standard Oils |
Emkarate RL 32 3MAF
Servicing Oils| Emkarate RL 32 3MAF Mobil EAL Arctic 22 CC
Location and Fixing
-
The unit should always be installed in a location that ensures clean air flow. Both service access and
airflow have been considered in making these recommendations. -
Where multiple units are to be installed in the same location, the contractor needs to
consider each individual case carefully. -
Ideally, the unit should be mounted on a solid concrete slab with anti-vibration pads between unit
feet and concrete. -
Ensure that there is no obstruction to air flow into or out of the unit. Remove obstacles which
block air intake or discharge -
The location must be well ventilated, so the air can pass properly through condenser by
maintaining the proper condensation in the system.
Installation Clearance :
It is recommended to have a clearance of 500 mm between the condenser face and
adjacent wall or
unit, while a clearance of 500mm on remaining 3 sides and top for service and
free circulation
All Dimensions are in mm
Above instructions are recommended for Dual Fan CDU Units Also.
Refrigeration Piping Installation
All interconnecting pipes should be of refrigeration grade, clean, dehydrated
and must remain capped at
both ends until installation. Even during installation, if the system is left
for any reasonable period (say
two hours), pipes should be re- capped to prevent moisture and contaminants
from entering the system.
Do not assume that the service connection sizes on the unit (at the service
valves) are the correct size to
run your interconnecting refrigeration pipes. The service valve sizes have
been selected for convenience
of installation and in some cases (larger units) these may be considered too
small. However, for the very
short pipe run within our units, these service connection sizes are adequate.
The pipe should be sized to ensure optimum performance and good oil return.
The sizing must also take
into account the full capacity range through which this particular unit will
need to operate.
Pipe runs should be kept as short as possible, using the minimum number of
directional changes. Use
large radius bends and avoid trapping of oil and refrigerant. This is
particularly important for the suction
line. The suction line should ideally slope gently towards the unit.
Recommendation slope is
1/200~1/250. P traps, double risers and reduced pipe diameters may be required
for suction lines where
long vertical risers cannot be avoided. All pipes should be adequately
supported to prevent sagging
which can create oil traps.
The recommended pipe clamp support distance is shown in the table.
Tube Size | Max distance between 2 clamp support |
---|---|
12.7mm (1/2 inch) | 1.20 m |
16.0mm (5/8 inch) | 1.50 m |
22.0mm (7/8 inch) | 1.85 m |
28.5mm (1 1/8 inch) | 2.20 m |
Brazing Recommendations
Maintain a flow of oxygen-free nitrogen through the system at a very low-
pressure during brazing.
Nitrogen displaces the air and prevents the formation of copper oxides in the
system. If copper
oxidization is allowed to form, the copper oxide material can later be swept
through the system and
block screens such as those protecting capillary tubes, thermal expansion
valves, and accumulator oil
return holes. This minimizes any entry of contaminants and moisture.
- Remove the liquid line connection cap.
- Then remove the suction connection cap.
- Open both valves midway. Care should be taken to avoid the holding charge from releasing too quickly.
- Be sure tube fitting inner diameter and tube outer diameter are clean prior to assembly.
- Since both tubes are extended from the condensing unit housing, we recommend insulating the housing by using a wet cloth on the copper tubing.
- Recommended brazing materials: a copper / phosphorous or copper/ phosphorous / silver alloy rod should be used for joining copper to copper whereas to join dissimilar or ferric metals, use a silver alloy rod, either flux coated or with a separate.
- Use a double tip torch.
Start Up and Operation
Leak Check
The unit has been leaktested and QA approved from the factory. However, due to
handling and shipping
the entire refrigeration systemmust be tested for leaks. Failure to carry out
leak test can result to
undesirable system performance
Step-by-step:
- Open both the liquid and suction service valves.
- Ensure the solenoid valve is energized and open, if available.
- Pressurize the system to300 psig/21 Bar maximum with dry nitrogen.
- Allow dry nitrogen to reach all parts of the system.
- Check all joints and components using soap/bubble test or with an electronic leak detector.
- Wait for atleast an hour to ensure the system is holding the pressure and is found to beleaked proof, if the system loses any pressure over the course of 30 minutes to1 hour, then it is a sure indication that the system is leaking
If leak has been detected somewhere on the system, relief the pressure and
repair the leak. For an
effective installation, the system must be leak tight.
System Evacuation
Evacuating a refrigeration system serves two primary objectives: (1) remove
non-condensable and
(2) remove water vapor or dehydrate the system.
Air and moisture are detrimental to system operation. The successful long-term
operation of the system
depends on thoroughly conditioning them before charging with refrigerant and
the losses associated
with improper evacuation erodes system efficiency as well as costly for the
installers.
A 2-stage vacuum pump along with a micron gauge is recommended in performing
evacuation. The
quality of vacuum is not determined by time – a micron gauge must be used
since it is the only device
that accurately reads the vacuum pressure during the evacuation process.
REMINDER:
Do not use the system compressor as a vacuum pump and never operate the
compressor
while the system is in vacuum. Emerson Climate Technologies recommends Triple
Evacuation Process
(best practice) to be implemented on all our installations.
Note
that the following procedure is based upon achieving an actual system vacuum
standard and it is NOT TIMEDEPENDENT!
Step-by-step:
- Open both the liquid and suction service valves.
- Ensure the solenoid valve is energized and open, if available.
- Connect vacuum pump to the liquid and suction service valves.
- Start the vacuum pump and then open the service valves.
- Perform triple evacuation process as follows:
- Vacuum until a pressure of 500 microns is reached — at which time the vacuu should be broken with the refrigerant to be used in the system through a drier until the system pressure rises to 20 psig
- Repeat this vacuuming process again.
- Evacuate the entire system to 500 microns (minimum recommended). Evacuate the system below 500 microns may enhance the reliability of system
Refrigerant Charging
After ensuring the system is vacuumed properly and all valves are opened, only
then start the refrigerant
charging process
- Ensure that there is no power supply to the CDU unit. The Liquid Line solenoid needs to be kept open for the charging process, if available and this may require a temporary power feed to it.
- Connect the refrigerant cylinder to main service hose and purge line at the manifold end.
- Ensure correct orientation of the refrigerant cylinder.
- Follow cylinder labeling/instructions so that liquid refrigerant can be charged into the high side of the system using high-pressure side of the manifold.
- The refrigerant cylinder should be weighed at this point to be able to record the final refrigerant charge.
- Now open the liquid service valve (off the back seat). With a good vacuum in the system, system will in take 60- 70 of the refrigerant required in the system without running the compressor.
- The compressor can then be started, and the unit continued to be charged (with liquid refrigerant through the suction service valve). The quantity of charge should always be measured. See note.
- The system needs to be operated down to its design evaporating temperature before you can be sure the charge is correct. Check the liquid line sight glass for violent bubbles and the operating pressures.
In the event that the system is still short of refrigerant, repeat from step
7 onwards
Refrigerant charging is said to be complete when the operating temperature of
the system has been stable
for some time and the liquid line sight glass is clear ensuring Suction &
Discharge pressure, Superheat
and sub cooling.
Note:
Do not Charge the refrigerant by measuring the current drawn by compressor.
Pressure Cut Out Settings
Please ensure following setting for the cut outs for the safe operation of the unit:
Maximum | LP | Minimum | HP |
---|---|---|---|
Refrigerant | Condensing |
Temp.
| Cut Out| Cut In| Evaporating
Temp.
| Cut Out| Cut In
R404A| 60°C| 1.0 bar| 2.7 bar| -30°C| 29.6 bar| 24.1 bar
Refrigerant Charge
Refer to the table below for the approximate Refrigerant holding capacity of Condensing Unit
Model| Refrigerant Charge
(R404a) kg
---|---
KHZ506LRL-EX| 4.10
KHZ508LRL-EX| 4.10
KHZ509LRL-EX| 4.10
KHZ511LRL-EX| 4.10
KHZ514LRL-EX| 4.10
KHZ515LRL-EX| 4.10
KHZ518LRL-EX| 4.54
KHZ521LRL-EX| 4.54
Maintenance
Condenser Fins
-
Condenser fins become dirty over time as ambient air is induced to the condenser. Dirty coil surfaces
result in high condensing temperatures and poor unit performance. Regular cleaning is recommended
with frequency depending on the installation and the surrounding environment. As a general guide,
it is advisable to do this at least once every two months. -
Fins should be cleaned with proper cleaning agent. Before washing, a light brush downward (in the
direction of the fins) should be brushed to remove heavy deposits.
Electrical Connections
- Check tightness of electrical connections occasionally.
- Always ensure the below mentioned Electrical tips before starting the unit.
Routine Leak Test
- All joints should be checked for leaks during site visits. All joints should be leak tested once-a-year.
Condenser Fan(s) and Motor(s)
An annual inspection of these items is recommended. Fastenings may loosen, bearings may wear, and fans
may require cleaning of solid deposits which can cause imbalance.
WARNING:
TURN OFF OR DISCONNECT THE ELECTRICAL POWER SOURCE BEFORE CLEANING THE CONDENSER
Application Tips for Scroll Compressors/ Do’s & Don’ts:
General Tips:
-
Please do Vacuum break with pure liquid refrigerant charge on high side and top-up by liquid bleed
in suction -
Always ensure the LP/HP Setting before starting the compressor.
-
Don’t use refrigeration compressor for self-evacuation.
-
Never use the compressor to suck oil into the system.
-
Do not test compressor by closing suction valve.
-
Do not set low pressure switch below 1 bar.
-
Do not pump down below 1 bar.
-
To avoid the refrigerant flood back a Solenoid valve should be used in liquid line.
-
Don’t start the compressor when it is in vacuum.
-
Don’t operate the compressor in open air.
-
Don’t allow short- cycling of compressor.
-
Ensure the oil return in sight glass during running cycle.
-
Don’t allow air, moisture, contaminants to enter compressor.
-
Don’t charge refrigerant looking at compressor amperes
-
Do not bypass LP/HP controls
-
Reverse Rotation
Scroll compressors pump in one direction only Incorrect rotation can be identified by: -low current, noise, balanced suction and discharge pressure Correct by interchanging any two phases Short-term reverse rotation will not damage the compressor
Electrical Tips:
Kindly verify before any Electrical installation if the voltage, frequency and
phase of supply satisfy those
required of the unit. Ensure that Operative is following all safety guideline
& procedure as mentioned
above while performing Electrical Installation.
-
All wiring should be carefully checked & refer wiring diagram (attached inside of the electrical cabinet) to
complete unit control circuit. -
Do not handle high-voltage electrical wiring unless properly trained.
-
Check if the Voltage deviation of 10 % is within the specified range mentioned on unit name plate.
-
Do not by -pass any electrical safety equipment like MCCB, SPP, Contactor, Overload Relay, timer & other safety devices.
-
Use genuine specified electrical accessories for CDU/Compressor model recommended by Company.
-
Check the electrical connections if they are properly attached, secured and properly tightened.
-
Make sure all panels are secure and panel screws are properly tightened.
-
Check that the ampere draw doesn’t exceed the amperage specified on the nameplate.
-
Check the phase unbalance if there is a three-phase connection.
-
In single phase compressor. Check for neutral connection. It is better to connect Common ( C ) terminal
to the neutral supply. -
Check for proper Earthing/ground. Ensure each component is getting proper supply, no burnt/Chattering in Connection and is working as intended.
-
Do not bypass the crankcase heater connection and its operation sequence (low ambient/
During off cycle). -
If you do not fully understand how to install your product after reading the manufacturer’s instructions,
contact our local authorized dealer or technical team for help and do not attempt to install it yourself.
Electrical (Power) Connections
KEEP IN MIND
KHZ Condensing units uses 3-Phase Scroll compressors and can rotate in the
wrong
direction when starting. If this happens reverse any two phases (L1 & L3) and
start again. So, a Single
phase preventor must require. Always observe the rotation of 3 phase Scroll
Compressor by measuring
Current drawn, Compressor pumping and running sound.
Rotation direction of Scroll compressors
KEEP IN MIND
ZSI Low temperature Condensing units ‘uses 3-Phase Scroll compressors which
can only
compress in one rotational direction. Scroll Compressor can rotate in the
wrong direction when start
depending upon phasing of the power. Since there is a 50-50 chance of
connecting power in such a way
as to cause rotation in the reverse direction, So, a Single phase preventor
must require. Always observe
the rotation of 3 phase Scroll Compressor by measuring Current drawn,
Compressor pumping and
running sound.
Maximum Compressor Cycle & Minimum run time
KHZ or ZSI Scroll CDU units- Maximum permitted starts per hour is 10.
There is no minimum off time because Scroll compressors start unloaded even if
the system has
unbalanced pressures. It is recommended to set minimum 3 mins run time of
compressor after it comes
in operation for adequate oil return and if possible, we can set 3 mins off
time/Delay time of compressor
once the power supply is disconnected from circuit to avoid frequent on/off or
chattering in Electrical
components.
Note:
The components listed in this catalogue are not released for use with caustic,
poisonous or flammable
substances. Emerson Climate Technologies cannot be held responsible for any
damage caused by using these
substances.
Pressure -Temperature Chart
Temperature | Refrigerant |
---|---|
°F | °C |
3 | -16.1 |
4 | -15.6 |
5 | -15.0 |
6 | -14.4 |
7 | -13.9 |
8 | -13.3 |
9 | -12.8 |
10 | -12.2 |
11 | -11.7 |
12 | -11.1 |
13 | -10.6 |
14 | -10.0 |
15 | -9.4 |
16 | -8.9 |
17 | -8.3 |
18 | -7.8 |
19 | -7.2 |
20 | -6.7 |
21 | -6.1 |
22 | -5.6 |
23 | -5.0 |
24 | -4.4 |
25 | -3.9 |
26 | -3.9 |
27 | -2.8 |
28 | -2.2 |
Temperature | Refrigerant |
--- | --- |
°F | °C |
29 | 1.7 |
30 | -1.1 |
31 | -0.6 |
32 | 0.0 |
33 | 0.6 |
34 | 1.1 |
35 | 1.7 |
36 | 2.2 |
37 | 2.8 |
38 | 3.3 |
39 | 3.9 |
40 | 4.4 |
41 | 5.0 |
42 | 5.6 |
43 | 6.1 |
44 | 6.7 |
45 | 7.2 |
46 | 7.8 |
47 | 8.3 |
48 | 8.9 |
49 | 9.4 |
50 | 10.0 |
55 | 12.8 |
60 | 15.6 |
65 | 18.3 |
System Troubleshooting Guide:
Unit is not starting| • Power disconnected or loose connection
• Blown fuse / breaker tripped
• Thermostat out of calibration – set too high
• Contactor defective
• High pressure Switch open (if provided)
| • Check voltage at contactor in condensing unit
• Replace fuses / reset breaker
• Reset
• Check & replace if open
• Reset – see high pressure correction (high pressure control opens at 450 psig)
---|---|---
Outdoor fan on; Compressor off| • Run or start capacitor defective
• Start relay defective
• Loose wire & low Voltag
• Compressor stuck, grounded or open motor winding, open internal overload
| • Replace
• Replace
• Check for correct voltage at compressor – check and tighten all connections
• Wait at least 2 hours for overload to reset; if still open, Check the compressor & replace.
Too little cooling| ****
• Improperly sized unit
• Improper indoor airflow
• Incorrect refrigerant charge
• Air, non-condensable or moisture in system
| ****
• Recalculate load
• Check as per desired conditions
• Charge per procedure in installation manual
• Recover refrigerant, evacuate and recharge, replace filter drier
Compressor operates in short cycles| Incorrect voltage
• Defective overload protector
• Refrigerant undercharge
| • At compressor terminals, voltage must be +/- 10% of nameplate marking when unit is operating
• Replace – check for correct voltage
• Add refrigerant
High head pressure; Low suction pressure| • Restriction in liquid line, expansion device or filter drier
• Lack of sufficient indoor airflow
| • Remove or replace defective component
• Clean/check filters, registers, or evaporator coil that may cause a restriction.
High head pressure; Normal suction pressure
| ****
• Dirty outdoor coil
• Refrigerant overcharge
• Outdoor fan not running
• Air or non-condensable gas in system
| • Clean coil
• Correct system charge
• Repair or replace
• Recover refrigerant, evacuate and recharge
Low head pressure; High suction pressure| • Expansion device stuck in open position
• Defective compressor valves
| • Replace expansion device
• Replace compressor
Low suction pressure; Compressor cool; Ice on indoor coil| • Low indoor airflow
• Operating in very low Ambient
• Moisture in system
| • Increase speed of blower or reduce restriction – replace air filter
• Add low ambient kit
• Recover refrigerant – evacuate and recharge – replace filter drier
High suction pressure;
Or fluctuating head and suction pressures
| • Excessive load
• Defective compressor
• TXV hunting
| • Recheck load calculation
• Replace
• Check TXV bulb clamp – check air distribution on coil – replace TXV
| • Air or non-condensable gas in syste| • Recover refrigerant, evacuate and
recharge
---|---|---
Suction & Discharge pressure balanced
| • Compressor may loss pumping
• If Cooling achieve, Gauges may faulty
• Compressor may trip on IPRV
| • Replace
• Gauges Replace
• Check for high side restriction in the system
Unit /Compressor Draw high Amps| ****
• Run or start capacitor defective
• Start relay defective
• Loose wire
• Low Voltage or Voltage Fluctuation
• Moisture in the system
• Liquid Flood back in the compressor
• Any Contamination/ Oil Dilute
| ****
• Replace
• Replace
• Check for correct voltage at compressor – check and tighten all connections
• Recover refrigerant – evacuate and recharge
• replace filter drier
• Ensure proper load
• Check oil quality, replace with new oil & do the commissioning as per procedure
Compressor trip on IOLP| • Leakage in the System
• Compressor Stuck/JAM
• Compressor getting hot & Motor temperature Shooting – up
• Reverse rotation of compressor
| • Repair
• Replace
• Maintain proper suction superheat & check oil level/return to compressor
• Check voltage & connection of Comp. terminal
System Start-Up and Operational Check Sheet:
Client Details
Facility/Customer Name :|
Address :|
Contact Details :|
Installer :|
Installation Date :|
Condensing Unit Info
CDU Model :|
Serial Number :|
CDU Location :|
Indoor Unit Make/Model :|
System Details
Room/Case ID :|
Pipe Length (approx.) :|
OAT @ Start-Up/Check :|
PSI Leak Test :| PSIG
Duration :| Hours
System is Leak Tight :| Y / N
Triple Evacuation :| Y / N
Micron Gauge Reading
:
| microns
Total Evacuation :| PSIG @ # of Hrs
Refrigerant :|
Total Charge :| Kg.
Sight Glass Clear :| Y / N
Evap. Fans Running :| Y / N
Liquid Line Insulation :| Y / N
Sound and Vibration|
System Operation
COMP Voltage :| V
COMP Current :| A
Standing Pressure| PSIG/Bar
Suction Pressure :| PSIG/Bar
Liquid Line Pressure :| PSIG/Bar
COMP Suction Temp :| °C
COMP Disch. Temp :| °C
Liquid Line Temp :| °C
Compressor SH :| K
Subcooling :| K
Adjustable LP Setpoint :| PSIG
Design/Operating Temp:| °C
Actual Room/Case
Temp :
| °C
Documents / Resources
|
EMERSON KHZ506LRL ZSI Scroll Condensing
Units
[pdf] User Manual
KHZ506LRL, ZSI Scroll Condensing Units, KHZ506LRL ZSI Scroll Condensing Units,
Condensing Units, KHZ508LRL, KHZ509LRL, KHZ511LRL, KHZ514LRL, KHZ515LRL,
KHZ521LRL, KHZ518LRL
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>