Dik Geurts Kalle Wood Stove Instruction Manual
- June 11, 2024
- Dik Geurts
Table of Contents
Dik Geurts Kalle Wood Stove Instruction Manual
Please read and retain this document carefully
Introduction
As a manufacturer of fires, DRU Verwarming develops and produces products
according to the highest possible English quality, performance and safety
requirements. These woodburning Dik Geurts fires are provided with a CE mark
that is only awarded for fires complying with the essential requirements of
the European Construction Products Regulation, including requirements made of
safety, the environment and energy consumption.
An installation manual and user manual is supplied with the fire. An installer
must be certified and a competent professional in the field of woodburning
appliances.
The installation manual provides the information you need to install the fire
in such a way that it works properly and safely.
This manual covers installation of the fire and the applicable instructions.
You will also find the technical details of the fire.
The figures are annexed at the back of this booklet.
You must fully and carefully read the installation manual before using it to install the fire. If you have any questions or doubts always contact your supplier.
The user manual gives you the information you need to ensure that the
appliance works properly and safely.
Carefully read the user manual before starting to use the fire.
The manuals include the following indications to show important information:
Action to take
Tip! Suggestions and advice
Caution These instructions are required to prevent possible problems
during installation and/or use.
!CAUTION These instructions are required to prevent fire, personal injury
or other serious damage.
After delivery you must give the user manual and this installation manual to the user.
The user must safely keep the user manual and installation manual.
DECLARATION OF CONFORMITY
The undersigned, representative of:
Manufacturer:
DRU Verwarming BV
Postbus 1021
NL-6920 BA Duiven
Ratio 8, NL-6921 RW Duiven
hereby declares that the design and construction of the woodburning heating appliance supplied by DRU satisfies the essential requirements of the Construction Products Regulation and is produced and distributed according to the requirements of the Belgian Royal Decree of 12 October 2010 for the regulation of the minimum requirements of efficiency and emission levels of pollutants for solid fuel heating equipment.
The product properties/technical information is included in annex 1, Table 2 at the back of the manual. Internal company measures guarantee that the serial production fires satisfy the essential requirements of the applicable EC directives and their derivative standards.
This declaration is no longer valid if changes are made to the appliance without written permission from DRU.
Duiven, 23/03/2022
R.P. Zantinge, Managing director
SAFETY
General
CAUTION
- Carefully read this section about safety before you start installation or maintenance.
- Comply with the generally applicable conditions and the precautionary measures/safety instructions in this manual.
Regulations
Install the appliance according to the applicable European, national, local
and construction (installation) regulations.
In the Netherlands this includes the Building Decree
Precautions/safety instructions during installation
Carefully comply with the precautionary measures/safety regulations below:
- Only install and maintain the fire if you are a trained installer of woodburning appliances.
- Only install the fire in a space where the location, the technical construction and the activity in this space cannot involve any danger due to the burning of the fire.
- Depending on the type of suspension, install the fire on a floor, against a wall or on a ceiling with sufficient load bearing capacity.
- Take account of any combustible chimney beams above the fire. Remove them or apply sufficient non-combustible insulation material according to the construction regulations under European fire classification A1 EN 13501-1.
- If you find other combustible materials, apply sufficient non combustible insulation material according to the construction regulations under European fire classification A1 EN 13501 1.
- When installing a free-standing fire take account of the minimum required distance from the fire to a non-combustible wall. This distance amounts to 50 mm.
- Use heater piping material that at least suffices with regard to EN 1856 2 T600.
- When installing the fire and/or the flue pipes respect the minimum distance to combustible objects and materials (see Annex 1, Table 2 and the data plate at the front of this installation manual).
- Lay a protective floor plate if the floor is combustible (see section 5.7).
- Never cover a free-standing fire and/or pack it with an insulation blanket or any other material.
- Connect the fire to a suitable flue duct.
- Remove any stop valve or slide in the flue duct of the existing open hearth.
- Have the flue duct inspected and cleaned by a certified chimney sweeping company beforehand.
- Do not make any changes to the fire yourself.
- Only use original parts for replacement.
- Ensure sufficient ventilation in the installation space. Fit an extra air supply opening if necessary.
- Make sure that there is never underpressure in the installation space. If applicable, connect the outside air connection to immediately extract the combustion air to outside the home.
Extra information if you are installing an insert/built-in appliance:
- Use non-combustible and heat-resistant material according to European fire classification A1 EN 13501-1 for the chimney breast (including the upper face), the material in the chimney breast and the back wall against which the appliance is fitted. Plate material or stony materials can be used for this.
- Take adequate measures according to the construction regulations to prevent too high temperatures (>85 °C) of a wall behind the chimney breast, including the materials and/or objects behind the wall.
- Take account of the minimum required internal dimensions of the chimney breast.
- Convection heat can be extracted from the chimney breast by using ventilation grates.
- If applicable connect the convection opening with a flexible aluminium pipe and ventilation elements.
- These accessories can be ordered from your supplier.
- If applicable use heat-resistant electrical connections and fit them away from the appliance.
Unpacking
Follow the below points below when unpacking:
- Check the appliance with accessories for (transport) damage.
- Never install a damaged fire!
- If necessary contact your supplier.
!CAUTION Keep plastic bags away from children.
-
Annex 1, Table 1 mentions which parts you must have after unpacking.
-
For technical transport reasons the flame baffle plate is at the bottom of the fire with some appliances.
For fitting this flame baffle plate we refer to section 9 ‘Appliance-specific information’ as applicable. -
Transport may have caused parts to move around. Check the position of the baffle plate and inner lining plates.
-
Before installing check the operation of the air slide valve, door locking and any turning mechanism.
For the assembly/disassembly of these parts we refer to section 9 ‘Appliance- specific information’ as applicable. -
Remove any remaining blasting grit from the air slide valve.
-
If necessary contact your supplier.
Dispose of packaging in accordance with local regulations.
Installation
Read the manual carefully to ensure the correct and safe installation of the appliance.
Regulations
- Install the fire according to the applicable European, national, local and construction (installation) regulations.
- Follow the instructions as given in this manual.
- DRU Verwarming provides no guarantee to cover installation and maintenance of the fire and is not responsible for any resulting consequential damage.
Flue duct
The following requirements apply for the flue duct:
- The flue duct must be inspected by a specialist beforehand.
- The flue duct must be suitable for a woodburning appliance.
- The fire must be connected to a single, one-piece flue duct.
- The flue duct must be clean and leakproof.
- For the flue duct use material that at least suffices with regard to EN 1856-1 T450.
- For the fire pipe use material that at least suffices with regard to EN 1856-2 T600.
- The offset in the flue duct may be a maximum of 1.5 metres with a maximum angle of 45 degrees from the horizontal plane, providing the chimney draught is not too weak.
- With a rear fire connection the horizontal part of the flue duct may be a maximum of 500 mm.
- With a rear fire connection to a vertical flue duct a T-piece with soot bag must be used.
- The diameter of the flue duct must be at least equal to the diameter of the flue gas discharge pipe from the fire.
- The flue duct draught must be at least 12 Pascal.
- Fit a flue ventilator if the draught is too weak or if mechanical ventilation in the home causes underpressure in the installation space.
- A flue gas regulator must be used in a duct with a (too) strong draught (30 – 40 Pa). The draught can then be controlled. Your appliance can be fitted with a “restrictor cap” to slow any strong draughts (if applicable see section 9 ‘Appliance-specific information’).
- When fitting a flexible pipe always use a double-walled stainless steel design with a “smooth” interior.
- A rain cap must be fitted on top of the flue duct to limit rusting and damage to the interior lining of the fire due to moisture.
- The flue duct must be self-supporting and may not rest on the fire
Convection
When installing an appliance in a hollow chimney breast, it is necessary to create convection openings. If applicable, open the convection openings on the appliance, as described in chapter 9 ‘Appliance specific information’. If there are no convection openings on the appliance, you must create the required chimney breast aeration and de-aeration yourself. For this, you should assume a minimum chimney breast de-aeration of 200 cm2 (at the top side) and a minimum aeration of 200 cm2 (at the bottom side). Place the de- aeration at the top side at least 30 cm below the ceiling and at least 180 cm above the floor.
Appliances with fan(s)
Appliances that are made with one or more fans will heat a room more quickly
and increase comfort. As soon as the fan is switched on you will be able to
sense a pleasant, warm air flow. The fan can be set in various positions.
The air flow can leave the appliance both at the front and via the convection
openings. For more information on appliances with fans, we would like to refer
you to chapter 9 “Appliance specific information”.
Country-specific installation requirements
Install the appliance according to the applicable European, national, local
and construction (installation) regulations.
In the Netherlands this includes the Building Decree.
HETAS amendments
For supplementary information for the verification of Ecodesign Compliance
under the HETAS product approval scheme see appendix 3 if applicable.
Health and safety precautions
Special care must be taken when installing the stove such that the
requirements of the Health and Safety at Work Act are met.
Handling
Adequate facilities must be available for loading, unloading and site
handling.
Fire Cement
Some types of fire cement are caustic and should not be allowed to come into
contact with the skin. In case of contact wash immediately with plenty of
water.
Asbestos
This stove contains no asbestos. If there is a possibility of disturbing any
asbestos in the course of installation then please seek specialist guidance
and use appropriate protective equipment.
Metal Parts
When installing or servicing this stove care should be taken to avoid the
possibility of personal injury.
Note of references to the current UK regulations
In all cases the installation must comply with current Building Regulations,
Local Authority Byelaws and other specifications or regulations as they affect
the installation of the stove. It should be noted that the Building
Regulations requirements may be met by adopting the relevant recommendations
given in British Standards BS 8303, BS EN 15287-1:2007 as an alternative means
to achieve an equivalent level of performance to that obtained following the
guidance given in Approved Document J.
Please note that it is a legal requirement under England and Wales Building
Regulations that the installation of the stove is either carried out under
Local Authority Building Control approval or is installed by a Competent
Person registered with a Government approved Competent Persons Scheme. HETAS
Ltd operate such a Scheme and a listing of their Registered Competent Persons
can be found on their website at www.hetas.co.uk.
This stove must not be installed into a chimney that serves any other heating
appliance. More detailed advice about existing chimney usage.
Note
A chimney height of not less than 4.5 metres measured vertically from the
outlet of the stove to the top of the chimney should be satisfactory.
Alternatively the calculation procedure given in EN 13384-1 may be used as the
basis for deciding whether a particular chimney design will provide sufficient
draught.
The outlet from the chimney should be above the roof of the building in
accordance with the provisions of Building Regulations Approved Document J.
If installation is into an existing chimney then it must be sound and have no
cracks or other faults which might allow fumes into the house. Older
properties, especially, may have chimney faults or the cross section may be
too large i.e. more than 230 mm x 230 mm. Remedial action should be taken, if
required, seeking expert advice, if necessary. If it is found necessary to
line the chimney then a flue liner suitable for solid fuel must be used in
accordance with Building Regulations Approved Document J.
Any existing chimney must be clear of obstruction and have been swept clean
immediately before installation of the stove. If the stove is fitted in place
of an open fire then the chimney should be swept one month after installation
to clear any soot falls which may have occurred due to the difference in
combustion between the stove and the open fire. If there is no existing
chimney then any new system must be to the designation described above and in
accordance with Building Regulations Approved Document J.A single wall metal
fluepipe is suitable for connecting the stove to the chimney but is not
suitable for use as the complete chimney. The chimney and connecting fluepipe
must have a minimum diameter and its dimension should be not less than the
size of the outlet socket of the stove (see Annex 1, table 2).
Any bend in the chimney or connecting fluepipe should not exceed 45°. 90°
bends should not be used.
Combustible material should not be located where the heat dissipating through
the walls of fireplaces or flues could ignite it. Therefore when installing
the stove in the presence of combustible materials due account must be taken
of the guidance on the separation of combustible material given in Building
Regulations Approved Document J and also in these stove instructions.
If it is found that there is excessive draught in the chimney then a draught
stabiliser should be fitted. Fitting of a draught stabiliser will affect the
requirement for the permanent air supply into the room in which the stove is
fitted in accordance with Approved Document J (see also combustion air
supply).
Commissioning and handover
Ensure all parts are fitted in accordance with the instructions.
On completion of the installation allow a suitable period of time for any fire
cement and mortar to dry out, before lighting the stove. Once the stove is
under fire check all seals for soundness and check that the flue is
functioning correctly and that all products of combustion are vented safely to
atmosphere via the chimney terminal. On completion of the installation and
commissioning ensure that the operating instructions for the stove are left
with the customer. Ensure to advise the customer on the correct use of the
appliance and warn them to use only the recommended fuel for the stove.
Advise the user what to do should smoke or fumes be emitted from the stove.
The customer should be warned to use a fireguard to BS 8423:2002 (Replaces BS
6539) in the presence of children, aged and/or infirm persons.
Warning note on fume emission
Properly installed, operated and maintained this appliance will not emit fumes
into the dwelling.
Occasional fumes from de-ashing and re-fuelling may occur. However, persistent
fume emission is potentially dangerous and must not be tolerated. If fume
emission does persist, the following immediate actions should be taken:
a) Open doors and windows to ventilate room.
b) Let the fire out or eject and safely dispose of fuel from the appliance.
c) Check for flue or chimney blockage, and clean if required.
Do not attempt to relight the fire until the cause of the fume emission has
been identified and corrected. If necessary seek expert advice.
Extractor fan
There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit smoke and fumes into the room.
Permanent air vent
The stove requires a permanent and adequate air supply in order for it to
operate safely and efficiently.
In accordance with current Building Regulations the installer may have fitted
a permanent air supply vent into the room in which the stove is installed to
provide combustion air. This air vent should not under any circumstances be
shut off or sealed.
Chimney cleaning
The chimney should be swept at least twice a year. It is important that the flue connection and chimney are swept prior to lighting up after a prolonged shutdown period. If the stove is fitted in place of an open fire then the chimney will require sweeping after a month of continuous operation. This is a precaution to ensure that any “softer” deposits left from the open fire usage have not been loosened by the higher flue temperatures generated by the closed stove.
Periods of Prolonged Non-Use
If the stove is to be left unused for a prolonged period of time then it should be given a thorough clean to remove ash and unburned fuel residues. To enable a good flow of air through the appliance to reduce condensation and subsequent damage, leave the air controls fully open.
Use of fireguard
When using the stove in situations where children, aged and/or infirm persons are present a fireguard must be used to prevent accidental contact with the stove. The fireguard should be manufactured in accordance with BS 8423:2002 (Replaces BS 6539).
CO Alarm
Building regulations require that whenever a new or replacement fixed solid fuel or wood/biomass appliance is installed in a dwelling a carbon monoxide alarm must be fitted in the same room as the appliance. Further guidance on the installation of the carbon monoxide alarm is available in BS EN 50292:2002 and from the alarm manufacturer’s instructions. Provision of an alarm must not be considered a substitute for either installing the appliance correctly or ensuring regular servicing and maintenance of the appliance and chimney system.
Use of operating tools
Always use the operating tools provided when handling parts likely to be hot when the stove is in use.
Aerosol sprays
Do not use an aerosol spray on or near the stove when it is alight.
The Clean Air Act 1993 and Smoke Control Areas
Smoke Control Areas
Under the Clean Air Act local authorities may declare the whole or part of the district of the authority to be a smoke control area. It is an offence to emit smoke from a chimney of a building, from a furnace or from any fixed boiler if located in a designated smoke control area. It is also an offence to acquire an “unauthorised fuel” for use within a smoke control area unless it is used in an “exempt” appliance (“exempted” from the controls which generally apply in the smoke control area).
In England appliances are exempted by publication on a list by the Secretary of State in accordance with changes made to sections 20 and 21 of the Clean Air Act 1993 by section 15 of the Deregulation Act 2015. In Scotland appliances are exempted by publication on a list by Scottish Ministers under section 50 of the Regulatory Reform (Scotland) Act 2014. Similarly, In Northern Ireland appliances are exempted by publication on a list by the Department of Agriculture, Environment and Rural Affairs under Section 16 of the Environmental Better regulation Act (Northern Ireland) 2016. In Wales appliances are exempted by regulations made by Welsh Ministers.
Further information on the requirements of the Clean Air Act can be found
here: https://www.gov.uk/smoke-control-area-rules
Your local authority is responsible for implementing the Clean Air Act 1993
including designation and supervision
of smoke control areas and you can contact them for details of Clean Air Act
requirements.
Additional Operational Information:
Refuelling on to a low fire bed
If there is insufficient burning material in the firebed to light a new fuel charge, excessive smoke emission can occur. Refuelling must be carried out onto a sufficient quantity of glowing embers and ash that the new fuel charge will ignite in a reasonable period. If there are too few embers in the fire bed, add suitable kindling to prevent excessive smoke.
Fuel overloading
The maximum amount of fuel specified in this manual should not be exceeded, overloading can cause excess smoke.
Operation with door left open
Operation with the door open can cause excess smoke. The appliance must not be operated with the appliance door left open except as directed in the instructions.
Dampers left open
Operation with the air controls or appliance dampers open can cause excess smoke. The appliance must not be operated with air controls, appliance dampers or door left open except as directed in the instructions.
Exempt appliances
Exempt appliances are appliances (ovens, wood burners and stoves) which have
been exempted under the Clean Air Act 1993 or Clean Air (Northern Ireland)
Order 1981.
Appliances which are exempt for use in Smoke Control Areas:
https://smokecontrol.defra.gov.uk/appliances.php
Outside air connection (if applicable)
Some fires can be provided with an outside air connection. For an optimum operation of the appliance, the following should be taken into account in case of an outside air connection:
- The passage of the outside air connection and possibly the passage of a grate may not be smaller than the passage of the outside air connection on the fire.
- Make sure the maximum underpressure created in the combustion air supply pipe is 4 pascal. If a higher underpressure is created, the fire will not function properly and (hot) flue gases may flow back into the supply pipe.
- Prevent placing the outside air supply in an underpressure area on the outside of the house. If possible, place a supply pipe with T piece to 2 sides of the house.
- The combustion air supply pipe may not be placed higher than the bottom of the fire. This will prevent flue gases from flowing back.
- The combustion air pipe that is connected to the fire should be made of non combustible material.
- The fire will function properly with a flexible pipe with a maximum length of 11 metres and 4 bends. In case of a longer pipe or more bends, we recommend placing a pipe with a larger diameter (100-125mm).
- If a crawl space is properly aerated with open grates, it is allowed to retrieve combustion air from there. If there is no proper aeration in the crawl space, it is possible that harmful radon gases are drawn in. This is not allowed according to national regulations.
Further information on the outside air connection, if applicable, can be found in section 9 ‘Appliance specific information’.
Please note that HETAS product approval remains valid for the appliance only when installed with its air supply taken from the room of installation and the room is ventilated permanently to outside air as necessary in accordance with the guidelines given in Approved Document J. HETAS product approval is not valid for appliances fitted with an external air supply ducted directly to the appliance.
Installing the fire, general
Caution
- Do not make any changes to the fire yourself.
- Use clean fabric gloves and avoid fingerprints on the fire and flue pipes.
- Depending on the type of suspension, install the fire on a floor, against a wall or on a ceiling with sufficient load bearing capacity.
- Lay a fire-resistant floor plate if the floor is combustible. The floor plate in non-combustible material must extend at least 300 mm away from the fire and be at least 300 mm wider than the fire. Check these distances before installation on the basis of applicable national/local laws.
Tip!
A floor plate offers protection against smouldering ash and prevents the
soiling of a marble or flagstone floor, for example. We therefore also advise
using a fire-resistant floor plate when installing appliances on a wall or
ceiling.
-
Use the fire’s dimensional sketch to see which fire pipe diameter you need (see Annex 1, table 2).
-
Use a fire pipe that at least meets the requirements of standards as established in EN 1856-2 T600.
-
Install the flue pipes in such a way that a fire hazard can never originate.
-
When installing a free-standing fire take account of the minimum required distance from the fire to a non-combustible wall. This distance amounts to 50 mm.
-
When installing the fire and/or flue pipes respect the minimum distance to combustible objects and materials as shown in Annex 1, table 2.
-
Take adequate measures to avoid too high temperatures in any walls behind the chimney breast.
This also applies for materials and/or objects behind the wall. -
Respect the flue duct requirements as described in paragraph. 5.2.
For any appliance-specific instructions we refer to section 9 ‘Appliance specific information’.
CAUTION
If you are installing a built-in appliance take account of:
The minimum building-in dimensions according to Annex 1, Table 2.
Free-standing/design fires
Conversion from fire top connection to rear connection (if applicable).
The fire is supplied with a top connection for connecting the flue duct.
The top connection can be converted to a rear connection.
To do this proceed as follows (see Annex 2, Fig. 2):
- Take the flame baffle plate or baffle plates out of the fireplace (if applicable see section 9, ‘Appliance-specific information’).
- Your appliance can be provided with an extra steel restrictor cap (if applicable see section 9, ‘Appliance-specific information’). Remove this by sliding the restrictor cap forwards and taking it out of the rails. This restrictor cap is not replaced with a rear connection.
- Remove the fire’s convection back plate by undoing the bolts.
- Remove the push-through plate from the convection back plate.
- Remove the cover plate for the flue from the back wall of the fire by undoing the 2 or 3 nuts.
- Remove the flue ring from the top plate by undoing the nuts and/or bolts.
- Fit the flue ring on the back wall using the bolts and/or nuts.
- Fasten the convection back plate again with the bolts.
- Assemble the cover plate for the flue in the opening in the top plate using the nuts.
- Replace the flame baffle plate or baffle plates in the reverse order.
Installing a free-standing fire, general
A free-standing fire is installed as follows:
- Determine the fire location. The dimensions of the appliance are given in Annex 1, Table 2.
- For any appliance-specific instructions we refer to section 9 ‘Appliance specific information’.
- Make sure there are no combustible materials present.
- Lay the floor plate if applicable.
- Place the fire on a blanket or sheet of cardboard (to avoid damaging the floor) then put it in the desired place.
- Connect the fire to the flue duct. Follow the instructions of the supplier of the flue gas extraction system. Use heater piping material that at least suffices with regard to EN 1856-2 T600.
- Lift the fire a little if necessary so the blanket or cardboard can be removed.
- For completing installation we refer to paragraph 5.8.
Design fire installation
To install a design fire we refer to Section 9 ‘Appliance-specific information’.
Insert fires (existing and new situation)
With an existing chimney or chimney breast
To install an insert fire with an existing chimney or chimney breast proceed as follows:
-
Determine the fire location. The dimensions of the appliance are given in Annex 1, Table 2.
-
Leave a space of at least 10 mm between the fire and construction materials.
-
Check the size of the recess. If necessary the walls of the open hearth can be broken out a little. Make sure that the chimney top is still sufficiently supported.
-
If applicable make room for the connection of the convection openings (if applicable see section 9 ‘Appliance-specific information’) and section 5.3 ‘Convection’)) with a flexible aluminium pipe and ventilation elements (see section 5.4 ‘Appliances with fan(s)’. These accessories can be ordered from your supplier.
-
Be careful with the chimney breast plaster. Plaster beading makes the recess smaller.
-
Remove any existing valve from the open hearth or slide and clean the chimney top so all soot is removed.
-
Remove the fire door and disassemble the frame when it is supplied separately (see section 9 ‘Appliance-specific information’).
-
Carefully remove the inner lining plates (mark them), the baffle plate and (if present) the restrictor cap from the fire (if applicable see, section 9 ‘Appliance-specific information’).
-
Lay any bottom plate supplied where the fire is to be installed.
-
Turn the adjustable legs in with the hexagonal socket screwdriver supplied and check whether they are properly adjustable. There may still be some blasting grit present.
-
Make sure there is sufficient room under fire for the supply of combustion air when there is no outside air connection.
-
An outside air connection can be made (if applicable see section 9 ‘Appliance-specific information’).
-
Carefully slide the fire into the hole. Make sure that no damage is caused.
-
If applicable connect the convection opening ( see section 5.3 ‘Convection’) with the flexible aluminium pipe and ventilation elements (see section 5.4 ‘Appliances with fan(s))’.
-
The fire may never support the flue.
-
Make a good, airtight seal between the fire and the flue, possibly with a register plate and preferably with a fixed fire pipe or stainless steel double-walled flexible pipe that at least suffices with regard to standard EN 1856-2 T600.
-
If applicable, and depending on national regulations, the connection between the existing flue duct and the fire may be plugged with heat-resistant ceramic wool Proceed as follows:
-
Check whether the open hearth valve has been removed.
-
Remove the frame (if the frame is already fitted).
-
Remove the bottom plates and turn the fire as far as possible downwards with the adjustable legs to make space for the ceramic wool.
-
Fill any space behind the fire with fire-resistant insulation material so no dirt can get in.
-
Remove the flame baffle plate.
-
Apply the ceramic wool between the top side of the fire and the chimney for an airtight connection.
-
Turn the fire up again with the adjustable legs and check whether the ceramic wool seals properly.
-
Replace the flame baffle plate (see section 9 ‘Appliance-specific information’).
!Caution After the chimney has been swept always check that the connection is still airtight. -
A handy kit is available through your supplier for the direct connection of a stainless steel flexible pipe to the fire.
The use of a kit is, however, not required for all appliances (if applicable see section 9 ‘Appliance-specific information’). -
After the fire has been connected turn the adjustable legs with the Allen key supplied until the fire is in the desired position. Make sure that the combustion air supply is not blocked.
-
Replace the restrictor cap for the outflow, fit the inner lining plates in reverse order and place the baffle plate against the back wall and on the profiles (if applicable see section 9 ‘Appliance-specific information’).
-
Use a torch or a thin screwdriver to check that the secondary ventilation holes in the back wall are directly facing the recesses in the interior lining.
-
If applicable replace the frame around the fire (if applicable see section 9 ‘Appliance-specific information’).
In a new situation
To install an insert fire with a newly built chimney breast proceed as follows:
-
Determine the fire location. The dimensions are given in Annex 1, Table 2.
-
Place the fire on a floor with a sufficient load bearing capacity.
-
If applicable make a recess for an outside air connection (if applicable see section 9 ‘Appliance-specific information’).
-
Use non-combustible and heat-resistant material according to European fire classification A1 EN 13501-1 for the plate on the floor, chimney breast (including the upper face), the material in the chimney breast and the back wall against which the appliance is fitted. Plate material or stony materials can be used for this.
-
Leave a space of at least 10 mm between the fire and construction materials.
-
Be careful with the chimney breast plaster. Plaster beading makes the recess smaller.
-
Take account of the expansion of the fire. Keep the fire free of plasterwork.
-
If there is a combustible ceiling, place a fire-resistant plate with a 10 cm thick heat-insulating layer on top 30 cm below the ceiling in the chimney breast.
-
If are there combustible materials (e.g. wooden floor parts/beams etc.) below or behind the fire, sufficient non-combustible insulation material according to European fire classification A1 EN 13501-1 must be applied.
Comply with national regulations here. -
If there is a combustible wall build a 10 cm-thick fire-safe wall.
-
Build the base or elevation with heat resistant material.
-
Place the steel plate supplied in the place for the fire. If applicable make a recess in it for the outside air connection. Remove the fire door and disassemble the frame when it is supplied separately.
-
Remove the fire door and disassemble the frame when it is supplied separately (see section 9 ‘Appliance-specific information’).
-
Install the fire.
-
If applicable connect the outside air connection (see section 9 ‘Appliance-specific information’).
-
If applicable connect the convection opening (see section 5.3 ‘Convection’) with the flexible aluminium pipe and ventilation elements (see section 5.4 ‘Appliances with fan(s))’.
Keeps these elements at least 30 cm away from the ceiling. -
Use single-walled stainless steel flue pipes or stainless steel double walled flexible pipes that at least meet the requirements of standard EN 1856-2 T600.
-
The fire may never support the flue.
-
After the fire has been connected turn the adjustable legs with the Allen key supplied until the fire is in the desired position. Make sure that the combustion air supply is not blocked when doing this.
-
Replace the restrictor cap for the outflow, fit the inner lining plates in reverse order and place the baffle plate against the back wall and on the profiles (see section 9 ‘Appliance-specific information’).
-
Use a torch or a thin screwdriver to check that the secondary ventilation holes in the back wall are directly facing the recesses in the interior lining.
-
Replace the door and if applicable the frame around the fire (if applicable see section 9 ‘Appliance-specific information’).
-
Lay a fire-resistant floor plate for the fire if the floor is combustible. The floor plate of non-combustible material must extend at least 300 mm away from the fire and be at least 300 mm wider than the fire.
Built-in fires
-
Determine the place of the fire.
-
Slide the build-in frame into the desired position.
-
Use non-combustible and heat-resistant material according to European fire classification A1 EN 13501-1 for the plate on the floor, chimney breast (including the upper face), the material in the chimney breast and the back wall against which the appliance is fitted. Plate material or stony materials can be used for this.
-
If there is a combustible ceiling, place a fire-resistant plate with a 10 cm thick heat-insulating layer on top 30 cm below the ceiling in the chimney breast.
-
Place the fire level at the desired height and fix it with metal anchors.
-
Connect the flue duct to the fire ring.
-
Always connect any convection openings (see section 5.3 ‘Convection’) with heat-resistant flexible pipe and ventilation elements (see section 5.4 ‘Appliances wit fan(s)) to protect the plasterwork against high temperatures.
If the chimney breast is made of non-combustible materials (e.g. facing brickwork) this is not required. -
Make sure there is sufficient space under the fire for the supply of combustion air. When the outside air connection ring is not used, it must remain at least 20 mm free for sufficient combustion air.
-
If applicable connect the outside air connection (see section 9 ‘Appliance-specific information’).
-
The fire is not suitable to support a flue duct, it must be self-supporting.
-
Stony materials may absolutely not rest on the fire. For this use e.g. a brick lintel with ceramic felt.
-
Make sure that the opening in the chimney breast is 6 mm wider than the built-in frame.
-
The chimney breast may not be warmer than 90 degrees Celsius on the outside.
-
Lay a fire-resistant floor plate for the fire if the floor is combustible. The floor plate in non-combustible material must extend at least 300 mm away from the fire and be at least 300 mm wider than the fire.
Completing installation
- Check if grit, dust or other materials are left behind in the chimney breast (odours).
- Use clean fabric gloves and avoid fingerprints on the fire and flue pipes.
- Check whether the interior lining and the baffle plates are fitted properly in the fire (if applicable see section 9 ‘Appliance-specific information’). Correct the position of these plates if necessary.
- Check whether the holes of the secondary ventilation in the back plate are immediately facing the recesses in the interior lining.
- Clean the fire with a soft cloth and check it for damage. The fire can be sprayed with the spray can supplied.
Before doing this read the instructions for use on the label. Always first check the colour on a piece of white paper or cardboard before you treat the fire.
First carefully read the user manual before starting to use the fire. We refer to the user manual for lighting and burning the fire.
Delivery and maintenance
- You must make the user familiar with the fire. Among other things you must instruct her/him about bringing the fire into use and its burning and maintenance.
- When bringing into use point out that
- after rebuilding or new building all building materials must have thoroughly dried out to avoid dust (including smoke particles) adhering to damp surfaces;
- the first time of burning volatile components will evaporate from paint, materials etc.;
- the space must then be well ventilated.
- Point out the necessity to have the flue duct inspected and cleaned at least once a year by a specialist.
- Give the user the user manual and installation manual (the installation manual must be kept with the appliance).
The user manual includes a number of tips/instructions for maintenance of the fire. It also mentions how a number of parts can be replaced.
End of life / Recycling
At the end of the use cycle, the device must be disposed of and recycled in a responsible manner. To do this, follow the steps below. Local laws and regulations must always be followed when disposing/recycling the appliance. If in doubt, contact the local government about the available collection flows.
!Caution
Only disassemble and remove the device when it has cooled down and is at room
temperature.
Remove the inner lining, glass and the sealing material from/from the appliance. These parts can be returned to a designated collection point.
!Caution
The pane is made of ceramic material and can therefore not be returned to a
glass recycling center.
The steel parts can be offered to a designated recycling center.
Malfunctions
The user manual contains a table with a summary of malfunctions that can occur, their possible cause and the solution.
Appliance-specific information
!CAUTION
The appliance-specific instructions as described in this section prevail over
the instructions in the other sections! If in doubt follow the instructions in
section 9 or contact your supplier.
Appliance-specific information: Folke
Air slide valve and heat shield
Air slide valve
When installing and maintaining the appliance, please check the operation of the air slide valve (see Appendix 2, fig. 5). It is possible that steel grit entered the air slide valve during transport. If the air slide valve does not move smoothly it must be cleaned. For this purpose, the air slide valve must be disassembled. The suspended air slide valve is spring-mounted using a bolt and a spring, which are located below the cover plate.
When mounting the air slide valve, please proceed as follows (see Appendix 2,
fig. 5):
Caution!
If an outside air connection has been mounted, it must first be removed,
before the air slide valve can be mounted (for removing the outside air
connection: see section 9.1.5.2).
-
Loosen the 4 screws, remove them and remove unit A (see appendix 2, figure. 13-I).
-
Remove the vermiculite plates from the bottom (see section 9.1.2.1).
-
Then remove the little square plate located in a recess below the vermiculite bottom plates.
-
Loosen the allen screw using the socket head wrench.
Caution! As soon as the bolt has been loosened, the air slide valve will fall down. Make sure you catch the air slide valve! -
Check the air slide valve and clean it if necessary.
In order to replace the air slide valve, proceed as described for removal, only in reverse order.
Heat shield (optional)
Using a heat shield will allow you to place the appliance with the back closer to a combustible wall. This heat shield kit is optionally available through your supplier.
Caution
- It is only possible to place a heat shield if the flue gas discharge is connected at the top of the appliance.
- Use a double-walled insulated flue gas discharge pipe if the distance to the flammable wall is short (see Appendix 1, table 2).
The heat shield has to be fixed to the appliance. Proceed as follows:
-
Place the heat shield against the back of the appliance.
Caution!
Make sure that the heat shield is assembled exactly according to figure 6 in Appendix 2. -
Tighten the 4 bolts supplied.
Interior lining
Vermiculite
The fire’s vermiculite plates are located on the bottom and against the rear
and side walls of the appliance.
In the following situations the vermiculite plates must be taken out:
- When disassembling the air slide valve (see section 9.1.1.1).
- When replacing the vermiculite plates
The bottom plates are removed first and the rear plates are removed last (see
Appendix 2, fig. 7).
Placing the vermiculate plates takes place in reverse order.
!Caution
Make sure that the vermiculite plates are placed back in their original
position! The back plate, for instance, must be placed with the small, not
countersunk, holes towards the front.
Flame baffle plate
On delivery the flame baffle plate (see Appendix 2, fig. 3) is located in the
top section of the appliance.
In case of maintenance to the appliance, the flame baffle plate has to be
removed.
To do this proceed as follows:
- Take the flame baffle plate.
- Tilt the flame baffle plate forwards so the rear comes upwards.
- Slide the flame baffle plate forwards so the rear of the flame baffle plate is released from the ridge.
- Lower the flame baffle plate and remove it.
Placing the flame baffle plate takes place in reverse order.
Door
Check the closing of the door during installation or maintenance.
To do this proceed as follows:
Check the sealing of the door by placing a sheet of paper between the door and
the fire. After closing the door, it should not be possible to pull out the
sheet of paper easily. Check the outside of the fire.
In case the door still doesn’t seal properly:
- Adjust the door (see section 9.1.3.1) and/or
- replace the door seal (see section 9.1.3.2).
Adjusting the door
You can adjust the door by slightly moving 2 door catches (see Appendix 2,
fig. 8). The door catches are found on the top side and bottom side of the
appliance.
Proceed as follows:
-
Loosen the 2 bolts on the top side of the appliance a little.
-
Adjust the catch.
-
Then re-tighten the bolts properly.
-
Repeat these steps at the bottom of the appliance.
Tip!
It may be the case that the door already closes properly after adjusting the top or bottom door catch.So it is not always necessary to adjust both door catches. -
Check whether the sealing tape makes a good connection by clamping a sheet of paper between the stove and the sealing tape when closing the door.
-
It should not be easy to pull out the sheet of paper. If necessary, adjust the door and/or replace the door seal (= sealing tape, see section 9.3.2). If the door seal is in order or replaced, the process of adjusting the door must be repeated until the door closes properly.
-
After adjusting the door check that cast-iron door handle still matches and closes properly. Adjust the door handle if this is not the case (see Appendix 2, figure 9).
-
Slightly loosen the bolts in the slotted holes and slide the door handle.
-
Then re-tighten the bolts properly.
Replacing door seal
When replacing the door seal proceed as follows (see Appendix 2, fig. 10):
- Open the door.
- Remove the cord and the mastic from the recess.
- Apply a new layer of heat resistant mastic in the recess where the cord was.
- Place a new cord in the recess. Do this loosely and do not pull the cord tight.
- Insert both ends of the cord in the special sleeve.
The cord, the sleeve and the mastic are available through your supplier.
!Caution
Make sure that the sleeve is placed on the underside of the glass pane.
Glass pane
(Dis)assembly of the glass pane
!Tip
Use the supplied glass pane cleaner to remove fingerprints from the glass
pane(s).
To remove the glass pane and then remount it in the door, please follow the
instructions below (see Appendix 2, fig. 10 and 11).
Disassembly of glass pane in door:
- Disassembly of glass pane in door:
- Open the door.
- Lift the top plate a little.
- Hold the door tight and remove the pin.
- Lift the door up a little and remove the door.
- Place the door on a flat surface.
- Unscrew the 4 bolts that hold the clamps.
- Lift the glass pane out. The pane seal is also taken out.
Assembly of glass pane in door:
Mount the glass pane and place back the door by performing the steps for disassembling the glass pane in reverse order.
Caution
- Do not fasten the bolts too tight to avoid breaking off and/or stripping: overtightening will cause breakage.
- Place the glass pane (including new pane seal) with the logo to the bottom right.
Disassembling side panes
!Caution
The side panes are made of IR glass. This glass has a coating that largely
reflects the infrared radiation (heat emission). This glass has a rough and a
smooth side (coating). It is very important that the side panes are assembled
with the coated side facing outwards.
!Tip
Mark the coated side of the side panes before you disassemble the side pane.
This will help you to correctly replace the side panes.
Proceed as follows to remove the side pane(s) (see Appendix 2, fig. 12):
-
Open the door.
-
Remove the side panel (left and right) by removing the 5 bolts.
-
Remove the glass clips.
Caution- Hold the glass pane before you remove the last glass clip.
- When replacing the side pane(s), the glass pane seal must also be replaced.
-
Remove the glass pane. Here, the pane seal is also removed.
Assembling side panes
Assemble the side pane(s) by observing the steps in section 9.1.4.2 in reverse order.
!Caution
Fit the panes with the coated side facing outwards (see 9.1.4.2).
Supplementary installation instructions
Flue gas exhaust
In case of the Folke the flue can be connected in two ways: drained or non-
drained. For this you will have to use the specially developed conical ring.
The required connecting pieces are available through your supplier.
In case of a connection at the rear, please proceed as follows (see Appendix
2, fig. 2):
- Remove the 3 bolts from the exhaust ring mounted at the top of the appliance.
- Remove the bolts from the plate at the rear of the appliance.
- Mount this plate on the top of the appliance, on the location where the exhaust ring used to be.
- Mount the exhaust ring at the rear of the appliance by tightening the 3 bolts.
!Caution
If a RS appliance is installed, the flue gas discharge must be connected
airtight. Do this with heat-resistant sealant.
Outside air connection
It is possible to provide the Folke with an outside air connection. This outside air connection is optionally available (as an external kit). This kit can be used for a connection on the bottom of the appliance and is available through your supplier (see Appendix 2, fig. 4).
Caution
If you install a Folke RS appliance, the outside air connection is already
pre-mounted on delivery. Observe the steps as described under the heading
‘Outside air connection pre-mounted’.
When assembling the outside air connection, proceed as follows:
Outside air connection not pre-mounted (see appendix 2, fig. 13):
- Remove unit ‘A’ (fig. 13-I) by loosening the 4 screws and removing them.
- Remove the plate (B, fig. 13-I) fixed on the air slide by loosening the 2 screws and removing them.
- Take the 4 pre-assembled screws (fig. 13-I) out of the bottom side of the appliance.
- Place the tray with mounted pipe opening against the bottom of the appliance (fig. 13-II).
- Re-use the 4 screws to mount the tray (fig. 13-II).
- Replace plate (B, fig. 13-III) and tighten it again with the 2 screws.
- Replace unit ‘A’ (fig. 13-III) and tighten the 4 screws again.
- Connect the flexible hose (Ø 80 mm) to the round pipe opening of the outside air connection. The flexible hose can be fed both from the back and the bottom. For this purpose, the round plate at the back or bottom of the appliance must be pressed out (see appendix 2, fig. 4).
For disassembling the outside air connection, please observe the above- mentioned steps in reverse order.
Outside air connection pre-mounted (see appendix 2, fig. 4):
Connect the flexible hose (Ø 80 mm) to the round pipe opening of the outside air connection.
Caution!
The Folke is a fully enclosed system. Always ensure an air-tight connection of
the flexible hose to the round pipe opening by using a heat resistant sealant.
For disassembling the outside air connection, please observe the above-
mentioned steps in reverse order.
Coverplate
When with the installation of the Folke you use an outside air connection, a coverplate (see annex 2, figure 14 and 15) is available from your supplier. This coverplate keeps the flexible hose out of sight.
Appliance-specific information: Kalle
Outside air connection, air slide and flue gas exhaust
Outside air connection
The fire is made with an outside air connection. This outside air connection is provided separately (see appendix 2, fig. 16-2). Assembly always takes place at the bottom of the appliance.
When mounting the outside air connection, please proceed as follows (see appendix 2, fig. 4 and 16):
- Remove the guard plate (see appendix 2, fig. 16-1).
- Unscrew the 4 pre-assembled bolts (see appendix 2, fig. 16-2).
- Place the outside air connection against the plate on the bottom of the appliance.
- Then re-tighten the 4 bolts.
- Connect the flexible hose (Ø 80 mm) to the round ‘pipe opening’ of the outside air connection. The flexible hose can be fed both from the back and the bottom. For this purpose, the round plate at the back or bottom of the appliance must be pressed out (see appendix 2, fig. 4).
- Place back the guard plate.
Air slide
When installing and maintaining the appliance, check the operation of the air
slide (see appendix 2, fig. 17).
It is possible that steel grit ended up in the air slide during
transportation. If the air slide does not run smoothly, it
has to be cleaned. For this, the air slide should be disassembled. The air
slide valve is suspended by means of a nut and a spring.
When disassembling the air slide, proceed as follows (see appendix 2, fig. 17):
-
Remove the guard plate (see appendix 2, fig. 16-1).
!Caution
If an outside air connection is mounted, it should be removed first. For this, observe the instructions in section 9.2.1.1 (see appendix 2, fig. 16-2). -
Unscrew the nut at the bottom of the air slide.
!Caution
As soon as the nut has been loosened, the air slide and accessory will drop down. Make sure you catch the accessory! -
Check the air slide valve and clean it if necessary.
For placing back the air slide, the actions described for disassembling should be performed in reverse order.
Flue exhaust
The flue exhaust has a 150 mm diameter connection and can be connected to the
conical exhaust ring in two ways: dewatering and non-dewatering.
Here, you should use the correct connection pieces
!Caution
In case of a dewatering connection, different connection pieces are used
than in case of a non-dewatering connection.
The required connection pieces are available via your supplier.
The flue exhaust can also be connected at the top or rear of the appliance.
In case of a connection at the rear, please proceed as follows:
-
Remove the cover plate on top of the appliance.
-
Remove the flame baffle plate (see section 9.2.2.2).
-
Unscrew the 3 nuts from the exhaust ring mounted at the top of the appliance.
-
Unscrew the nuts from the plate at the rear of the appliance.
!Caution
A disc has to be hammered out of the rear of the appliance, after this plate has been removed (see appendix 2, fig. 2). -
Mount the plate that you unscrewed from the rear of the appliance at the top of the appliance on the place where the exhaust ring used to be.
!Tip
For a clean finish, you will be able to obtain a special, closed top plate via your supplier. -
Mount the exhaust ring at the rear of the appliance by tightening the 3 bolts.
-
Place back the flame baffle plate (see section 9.2.2.2).
Inner lining
Wall and bottom lining
The plates are located on the bottom and against the rear and side walls of
the appliance (see appendix 2, fig. 18).
In the following situations the plates must be taken out:
- When disassembling the flame baffle plate (see section 9.2.2.2).
- When replacing the plates
The bottom plates are removed first and the rear plates are removed last. Placing the plates takes place in reverse order.
!Caution
Ensure that the plates are placed back in their original position! The back
plates, for instance, must be placed with the small, not countersunk, holes
towards the front.
Flame baffle plate
At delivery, the flame baffle plate (see appendix 2, fig. 3) is located in the top section of the appliance. In the following situations the flame baffle plate must be taken out:
- in case of general maintenance;
- when connecting the flue exhaust at the rear;
- when replacing the wall and bottom lining.
Proceed as follows:
- First remove the bottom plates, then the side plates (see appendix 2, fig. 18).
- Take the flame baffle plate and tilt it forward. Allow the rear of the flame baffle plate to drop.
- Slide the flame baffle plate over the ridge.
- Tilt the flame baffle plate towards you and remove it.
Placing the flame baffle plate takes place in reverse order.
!Caution
The stainless steel profile must be placed at the front with the screw heads
facing the top (see appendix 2, fig. 3).
Adjusting the door/Replacing the door seal
During delivery and maintenance you must check the door’s seal. If the door does not close properly, you can take the following measures:
- adjust the door;
- replace the door seal.
Adjusting the door
You can adjust the door by slightly moving the door catches (see appendix 2,
fig. 22).
Proceed as follows:
- Slightly loosen the 2 bolts.
- Adjust the catch.
- Then re-tighten the bolts properly.
- Check whether the sealing tape makes a good connection by clamping a sheet of paper between the stove and the sealing tape when closing the door.
- It should not be easy to pull out the sheet of paper. If necessary adjust the door and/or replace the door seal (= the sealing tape, see section 9.2.3.2). If the door seal is in order, or replaced, the process of adjusting the door must be repeated until the door closes properly
Replacing the door seal
For replacing the door seal, you must observe the following steps:
- Open the door.
- Lift out the door by sliding it upwards.
- Place the door on a flat surface.
- Unscrew the nuts on the inside of the door.
- Remove the 4 glass strips and the tape of the door seal.
- Place a new door seal.
- Attach both ends of the tape to each other at the bottom of the door with heat-resistant tape.
Glass pane
Caution
- Prevent damage when removing/placing the glass pane.
- Avoid/remove fingerprints on the glass pane(s) as they will burn into the glass.
!Tip
Use the supplied glass pane cleaner to remove fingerprints from the glass
pane(s).
Disassembly of glass pane in door
To remove the glass pane in the door, please follow the instructions below
(see appendix 2, fig. 19):
- Open the door.
- Lift out the door by sliding it upwards.
- Place the door on a flat surface.
- Unscrew the nuts on the inside of the door.
- Remove the 4 glass strips and the tape of the door seal.
- Lift the glass pane out. The pane seal is also taken out
Assembly of glass pane in door
Mount the glass pane in the door in accordance with the steps described in section 9.2.4.1. ‘Disassembly of glass pane in door’, only in reverse order.
Caution
- Do not fasten the nuts too tightly to avoid breaking off and/or stripping: overtightening will cause breakage.
- Place the glass pane (including new pane seal) with the logo to the bottom right.
- Place a new door seal (see section 9.2.3.2).
- Attach both ends of the tape to each other at the bottom of the door with heat-resistant tape.
!Caution
Make sure this connection of heat resistant tape is placed at the bottom of
the glass pane.
Disassembly of side pane(s)
Proceed as follows in order to remove the side pane(s) (see appendix 2, fig. 21):
-
Slightly lift the cover plate on top of the appliance or remove the cover plate.
-
Remove the side panel (left and/or right) by loosening and removing the 4 bolts.
-
Remove the glass clips.
!Caution
- Stop the glass pane, before you remove the last glass clip.
- When replacing the side pane(s), the glass pane seal must also be replaced.
-
Remove the glass pane. Here, the pane seal is also removed.
Assembly of side pane(s)
Mount the side pane(s) by observing the steps in section 9.4.3 in reverse order.
Table 1
Tabel 1: Meegeleverde onderdelen
Part| Quantity
Installation manual| 1x
User manual| 1x
Glove| 1x
Ash scoop| 1x
Glass cleaner spray bottle| 1x
Spray can of heat-resistant lacquer| 1x
|
Table 2
Feature | Unit | Result |
---|---|---|
Folke | ||
Operation: intermittent | V |
Type (1=wand 2=vrijst. 3=inzet)/ Kind of fireplace (1=wall 2=free st.
3=insert)/| | 2| 2| |
Centrally controlled air flow| | V| V| |
Brandstof (1= hout 2= briketten) / Fuel (1= wood 2= briquettes) /| | 1 + 2| 1
- 2| |
Output| cm| 4 – 8| 4 – 8| |
Size of fireplace (wxhxd)| kg| 476 x 1000 x 410| 546 x 1000 x 415| |
Connection exit (1=on top 2=from behind)| kW| 1 + 2| 1 + 2| |
Cross section exit| mm| 150| 150| |
Cross section exit| | 80| 80| |
Weight| mm| 120-125| 105| |
Colour fireplace (DA=Dark anthracite)| ****
mm
| DA
AF
| DA
AF
| |
Colour interior (N=Naturel)| | N| N| |
| | | | |
Feature| Unit| Result
---|---|---
| | Folke| Kalle| |
Report| | ****
EZKA/2016-07/16-1
| ****
09078/1
| |
CO Emission| 13% O2 (%)| 0.06| 0.07| |
Dust| 13% O2 (mg/Nm3)| 15| 18| |
NOx| 13% O2 (mg/Nm3)| 135| 52| |
CxHy| 13% O2 (mg/Nm3)| 54| 35| |
Flue gas flow| g/s| 6.2| 5.9| |
Flue gas temp.| °C| 330| 181| |
Minimum draught| Pa| 12| 12| |
Distance to flammable materials (front)| mm| 1200| –| |
Distance to flammable materials (back / back with heat shield)| mm| 400/100|
400| |
Distance to flammable materials (side)| mm| 700| 800| |
BlmSchV| Stufe| 2| 2| |
DIN+regulations| | V| V| |
Fire safety (C=compliant)| | V| V| |
Release harmful substances| | none| none| |
Surface temp. (C=compliant)| | V / C
EA / S
| V / C
EA / S
| |
Mechanical strength (C=compliant)| | V / C
EA / S
| V / C
EA / S
| |
| | | | |
Appendix
Name and address manufacturer| DRU, Ratio 8, NL-6921 RW,
Duiven, The Netherlands
---|---
Model identifier(s)| Dik Geurts Kalle
Equivalent models|
Test reports| KVBG 09078/1
Harmonized Standards| EN 13240:2001/A2:2004/AC:2007
Other applied standards/technical specs| CEN/TS 15883:2010
Indirect heating function| No
Direct heat output| 7.0 kW
Indirect heat output| –
Characteristics when operating with the preferred fuel
Seasonal space heating energy efficiency ηs| 75
Energy efficiency index (EEI)| 113
Energy Class| A+
Fuel| Preferred fuel| Preferred fuel| ηs[x%]:| Emissions at nominal
heat output
PM| OGC| CO| NOx
[x] mg/Nm3 (13 % O2)
Wood logs with ≤25% moisture| Yes| No| 75| 18| 35| 875| 52
Compressed wood with <12% moisture| No| Yes| 75| 18| 35| 875| 52
Other woody biomass| No| No| | | | |
Non-woody biomass| No| No| | | | |
Anthracite| No| No| | | | |
Hard coke| No| No| | | | |
Low temperature coke| No| No| | | | |
* cokes| No| No| | | | |
Lignite briquettes| No| No| | | | |
Peat briquettes| No| No| | | | |
Blended fossil fuel briquettes| No| No| | | | |
Other fossil fuel| No| No| | | | |
Blended biomass and fossil fuel briquettes| No| No| | | | |
Other blend of biomass and solid fuel| No| No| | | | |
Emissions at minimum heat output are not applicable
Characteristics for exclusive operation with the
preferred fuel**
Item
| Symbol| Value| Unit| | Item| Symbol| Value| Unit
Heat output| Fuel efficiency (Based on the net calorific value
(NCV)
Nominal heat output| Pnom| 7.0| kW| Fuel efficiency at nominal heat
output| ηth,nom| 85| %
Minimum heat output|
Pmin
| –| kW| Fuel efficiency at min- imum heat output| ηth,min| –| %
Auxiliary power consumption| Type of heat output/room temperature con-
trol
t nominal heat output| elmax| ****
–
| kW| stage heat output, no room temperature control| ****
Yes
t minimum heat output| elmin| ****
–
| kW| Two or more manually adjustable stages, no room temperature control|
No
In standby mode In standby mode| elSB| ****
–
| ****
kW
| Room temperature control with mechanical thermostat| ****
No
Power requirement of the pilot flame| With electronic room tempera- ture
control| No
Pilot flame power requirement (if applicable)| Ppilot| ****
–
| kW| With electronic room temperature control plus day timer| ****
No
| With electronic room temperature control plus week timer| ****
No
Other control options (multiple selection possible)
Room temperature control, with presence detection| No
Room temperature control, with open windows detection| ****
No
With distance control option| No
Specific precautions for assembly, installation or maintenance| See
instructions for more information. You must fully and carefully read the
installation & user manual before using or installing the fire.
Name and signature of authorised signatory|
R.P. Zantinge, Managing director
Name and address manufacturer Name| DRU, Ratio 8, NL-6921 RW,
Duiven, The Netherlands
---|---
Model identifier(s)| Dik Geurts Folke
Equivalent models|
Test reports| EZKA/2016-07/00016-1
Harmonized Standards| EN 13240:2001/A2:2004/AC:2007
Other applied standards/technical specs| CEN/TS 15883:2010
Indirect heating function| No
Direct heat output| 7.3 kW
Indirect heat output| –
Characteristics when operating with the preferred fuel
Seasonal space heating energy efficiency ηs| 67
Energy efficiency index (EEI)| 102
Energy Class| A
Fuel| Preferred fuel| Preferred fuel| ****
ηs[x%]:
| Emissions at nominal heat output
PM| OGC| CO| NOx
[x] mg/Nm3 (13 % O2)
Wood logs with ≤25% moisture| Yes| No| 67| 15| 54| 762| 135
Compressed wood with <12% moisture| No| Yes| 67| 15| 54| 762| 135
Other woody biomass| No| No| | | | |
Non-woody biomass| No| No| | | | |
Anthracite| No| No| | | | |
Hard coke| No| No| | | | |
Low temperature coke| No| No| | | | |
Bituminous coke| No| No| | | | |
Lignite briquettes| No| No| | | | |
Peat briquettes| No| No| | | | |
Blended fossil fuel briquettes| No| No| | | | |
Other fossil fuel| No| No| | | | |
Blended biomass and fossil fuel briquettes| No| No| | | | |
Other blend of biomass and solid fuel| No| No| | | | |
*Emissions at minimum heat output are not applicable
Characteristics for exclusive operation with the
preferred fuel
Item| Symbol| Value| Unit| | Item| Symbol| Value| Unit
Heat output| Fuel efficiency (Based on the net calorific value
(NCV)
Nominal heat output| ****
Pnom
| 7.3| ****
kW
| Fuel efficiency at nominal heat output| ηth,nom| 77| %
Minimum heat output| Pmin| –| kW| Fuel efficiency at min- imum heat output|
ηth,min| –| %
Auxiliary power consumption| Type of heat output/room temperature con-
trol
At nominal heat output| elmax| ****
–
| kW| Single-stage heat output, no room temperature control| Yes
At minimum heat output| ****
elmin
| ****
–
| kW| Two or more manually adjustable stages, no room temperature control|
No
In standby mode / In standby mode
| elSB| ****
–
| kW| Room temperature control with mechanical thermostat| No
Power requirement of the pilot flame| With electronic room tempera- ture
control| No
Pilot flame power requirement (if applicable)| Ppilot| ****
–
| kW| With electronic room temperature control plus day timer| No
| With electronic room temperature control plus week timer| No
Other control options (multiple selection possible)
Room temperature control, with presence detection| No
Room temperature control, with open windows detection| No
With distance control option| No
Specific precautions for assembly, installation or maintenance| See
instructions for more information. You must fully and carefully read the
installation & user manual before using or installing the fire.
Naam en handtekening van de tekenbevoegde Name and signature of authorised
signatory|
R.P. Zantinge, Managing director
DRU Verwarming B.V.
Ratio 8, 6921 RW Duiven
Postbus 1021, 6920 BA Duiven
Nederland
DRU Belgium
Kontichsesteenweg 69/1 Unit A-6
2630 Aartselaar
Belgium
Drugasar Ltd.
Deans Road, Swinton
Manchester M27 0JH
United Kingdom
References
- The domain name Catch.so is for sale | Dan.com
- Appliances - Defra, UK
- Smoke control areas: the rules - GOV.UK
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>