Dik Geurts Ivar 8 Low Wood Stove Instruction Manual

June 11, 2024
Dik Geurts

Table of Contents

Dik Geurts Ivar 8 Low Wood Stove Instruction Manual

Introduction

As a manufacturer of fires, DRU Verwarming develops and produces products according to the highest possible English quality, performance and safety requirements. These woodburning Dik Geurts fires are provided with a CE mark that is only awarded for fires complying with the essential requirements of the European Construction Products Regulation, including requirements made of safety, the environment and energy consumption.
An installation manual and user manual is supplied with the fire. An installer must be certified and a competent professional in the field of woodburning appliances.
The installation manual provides the information you need to install the fire in such a way that it works properly and safely.
This manual covers installation of the fire and the applicable instructions. You will also find the technical details of the fire.
The figures are annexed at the back of this booklet.
You must fully and carefully read the installation manual before using it to install the fire. If you have any questions or doubts always contact your supplier.
The user manual gives you the information you need to ensure that the appliance works properly and safely. Carefully read the user manual before starting to use the fire.
The manuals include the following indications to show important information:

  • Action to take

Tip!   Suggestions and advice
!Caution These instructions are required to prevent possible problems during installation and/or use.
!CAUTION These instructions are required to prevent fire, personal injury or other serious damage. After delivery you must give the user manual and this installation manual to the user. The user must safely keep the user manual and installation manual.

 2. DECLARATION OFCONFORMITY

The undersigned, representative of:
Manufacturer:
DRU Verwarming BV Postbus 1021
NL-6920 BA Duiven
Ratio 8, NL-6921 RW Duiven

hereby declares that the design and construction of the woodburning heating appliance supplied by DRU satisfies the essential requirements of the Construction Products Regulation and is produced and distributed according to the requirements of the Belgian Royal Decree of 12 October 2010 for the regulation of the minimum requirements of efficiency and emission levels of pollutants for solid fuel heating equipment.

The product properties/technical information is included in annex 1, Table 2 at the back of the manual. Internal company measures guarantee that the serial production fires satisfy the essential requirements of the applicable EC directives and their derivative standards.
This declaration is no longer valid if changes are made to the appliance without written permission from DRU. Duiven, 23-03-2022
R.P. Zantinge, Managing director

 3.SAFETY

3.1  General

!CAUTION •Carefully read this section about safety before you start installation or maintenance.

  • Comply with the generally applicable conditions and the precautionary measures/safety instructions in this
3.2  Regulations

Install the appliance according to the applicable European, national, local and construction (installation) regulations.
In the Netherlands this includes the Building Decree.

3.3  Precautions/safety instructions during installation

Carefully comply with the precautionary measures/safety regulations below:

  • Only install and maintain the fire if you are a trained installer of woodburning

  • Only install the fire in a space where the location, the technical construction and the activity in this space cannot involve any danger due to the burning of the

  • Depending on the type of suspension, install the fire on a floor, against a wall or on a ceiling with sufficient load bearing capacity.

  • Take account of any combustible chimney beams above the Remove them or apply sufficient non-combustible insulation material according to the construction regulations under European fire classification A1 EN 13501-1.

  • If you find other combustible materials, apply sufficient non-combustible insulation material according to the construction regulations under European fire classification A1 EN 13501-1.

  • When installing a free-standing fire take account of the minimum required distance from the fire to a non-combustible This distance amounts to 50 mm.

  • Use heater piping material that at least suffices with regard to EN 1856-2

  • When installing the fire and/or the flue pipes respect the minimum distance to combustible objects and materials (see Annex 1, Table 2 and the data plate at the front of this installation manual).

  • Lay a protective floor plate if the floor is combustible (see section 7).

  • Never cover a free-standing fire and/or pack it with an insulation blanket or any other

  • Connect the fire to a suitable flue

  • Remove any stop valve or slide in the flue duct of the existing open

  • Have the flue duct inspected and cleaned by a certified chimney sweeping company

  • Do not make any changes to the fire

  • Only use original parts for

  • Ensure sufficient ventilation in the installation Fit an extra air supply opening if necessary.

  • Make sure that there is never underpressure in the installation If applicable, connect the outside air connection to immediately extract the combustion air to outside the home.
    Extra information if you are installing an insert/built-in appliance:

  • Use non-combustible and heat-resistant material according to European fire classification A1 EN 13501-1 for the chimney breast (including the upper face), the material in the chimney breast and the back wall against which the appliance is Plate material or stony materials can be used for this.

  • Take adequate measures according to the construction regulations to prevent too high temperatures (>85 °C) of a wall behind the chimney breast, including the materials and/or objects behind the wall.

  • Take account of the minimum required internal dimensions of the chimney

  • Convection heat can be extracted from the chimney breast by using ventilation

  • If applicable connect the convection opening with a flexible aluminium pipe and ventilation

  • These accessories can be ordered from your

  • If applicable use heat-resistant electrical connections and fit them away from the

4.Unpacking

Follow the below points below when unpacking:

  • Check the appliance with accessories for (transport)
  • Never install a damaged fire!
  • If necessary contact your

!CAUTION Keep plastic bags away from children.

  • Annex 1, Table 1 mentions which parts you must have after

  • For technical transport reasons the flame baffle plate is at the bottom of the fire with some For fitting this flame baffle plate we refer to section 9 ‘Appliance-specific information’ as applicable.

  • Transport may have caused parts to move Check the position of the baffle plate and inner lining plates.

  • Before installing check the operation of the air slide valve, door locking and any turning
    For the assembly/disassembly of these parts we refer to section 9 ‘Appliance- specific information’ as applicable.

  • Remove any remaining blasting grit from the air slide

  • If necessary contact your

Dispose of packaging in accordance with local regulations.

 5.Installation

Read the manual carefully to ensure the correct and safe installation of the appliance.

5.1  Regulations
  • Install the fire according to the applicable European, national, local and construction (installation)
  • Follow the instructions as given in this
  • DRU Verwarming provides no guarantee to cover installation and maintenance of the fire and is not responsible for any resulting consequential
5.2  Flue duct

The following requirements apply for the flue duct:

  • The flue duct must be inspected by a specialist
  • The flue duct must be suitable for a woodburning
  • The fire must be connected to a single, one-piece flue
  • The flue duct must be clean and
  • For the flue duct use material that at least suffices with regard to EN 1856-1
  • For the fire pipe use material that at least suffices with regard to EN 1856-2
  • The offset in the flue duct may be a maximum of 5 metres with a maximum angle of 45 degrees from the horizontal plane, providing the chimney draught is not too weak.
  • With a rear fire connection the horizontal part of the flue duct may be a maximum of 500
  • With a rear fire connection to a vertical flue duct a T-piece with soot bag must be
  • The diameter of the flue duct must be at least equal to the diameter of the flue gas discharge pipe from the
  • The flue duct draught must be at least 12
  • Fit a flue ventilator if the draught is too weak or if mechanical ventilation in the home causes underpressure in the installation
  • A flue gas regulator must be used in a duct with a (too) strong draught (30 – 40 Pa). The draught can then be

controlled. Your appliance can be fitted with a “restrictor cap” to slow any strong draughts (if applicable see section 9 ‘Appliance-specific information’).

  • When fitting a flexible pipe always use a double-walled stainless steel-design with a “smooth”
  • A rain cap must be fitted on top of the flue duct to limit rusting and damage to the interior lining of the fire due to
  • The flue duct must be self-supporting and may not rest on the
5.3  Convection

When installing an appliance in a hollow chimney breast, it is necessary to create convection openings. If applicable, open the convection openings on the appliance, as described in chapter 9 ‘Appliance specific information’. If there are no convection openings on the appliance, you must create the required chimney breast aeration and de-aeration yourself. For this, you should assume a minimum chimney breast de-aeration of 200 cm2 (at the top side) and a minimum aeration of 200 cm2 (at the bottom side). Place the de- aeration at the top side at least 30 cm below the ceiling and at least 180 cm above the floor.

Appliances that are made with one or more fans will heat a room more quickly and increase comfort. As soon as the fan is switched on you will be able to sense a pleasant, warm air flow. The fan can be set in various positions. The air flow can leave the appliance both at the front and via the convection openings. For more information on appliances with fans, we would like to refer you to chapter 9 “Appliance specific information”.

5.5  Country-specific installation requirements
  • Install the appliance according to the applicable European, national, local and construction (installation)

In the Netherlands this includes the Building Decree.

5.5.1   HETAS amendments

For supplementary information for the verification of Ecodesign Compliance under the HETAS product approval scheme see appendix 3 if applicable.

Health and safety precautions

Special care must be taken when installing the stove such that the requirements of the Health and Safety at Work Act are met.

Handling

Adequate facilities must be available for loading, unloading and site handling.

Fire Cement

Some types of fire cement are caustic and should not be allowed to come into contact with the skin. In case of contact wash immediately with plenty of water.

Asbestos

This stove contains no asbestos. If there is a possibility of disturbing any asbestos in the course of installation then please seek specialist guidance and use appropriate protective equipment.

Metal Parts

When installing or servicing this stove care should be taken to avoid the possibility of personal injury.

Note of references to the current UK regulations

In all cases the installation must comply with current Building Regulations, Local Authority Byelaws and other specifications or regulations as they affect the installation of the stove. It should be noted that the Building Regulations requirements may be met by adopting the relevant recommendations given in British Standards BS 8303, BS EN 15287-1:2007 as an alternative means to achieve an equivalent level of performance to that obtained following the guidance given in Approved Document J.

Please note that it is a legal requirement under England and Wales Building Regulations that the installation of the stove is either carried out under Local Authority Building Control approval or is installed by a Competent Person registered with a Government approved Competent Persons Scheme. HETAS Ltd operate such a Scheme and a listing of their Registered Competent Persons can be found on their website at www.hetas.co.uk.

This stove must not be installed into a chimney that serves any other heating appliance. More detailed advice about existing chimney usage.
!Note A chimney height of not less than 4.5 metres measured vertically from the outlet of the stove to the top of the chimney should be satisfactory. Alternatively the calculation procedure given in EN 13384-1 may be used as the basis for deciding whether a particular chimney design will provide sufficient draught.
The outlet from the chimney should be above the roof of the building in accordance with the provisions of Building Regulations Approved Document J.
If installation is into an existing chimney then it must be sound and have no cracks or other faults which might allow fumes into the house. Older properties, especially, may have chimney faults or the cross section may be too large i.e. more than 230 mm x 230 mm. Remedial action should be taken, if required, seeking expert advice, if necessary. If it is found necessary to line the chimney then a flue liner suitable for solid fuel must be used in accordance with Building Regulations Approved Document J.

Any existing chimney must be clear of obstruction and have been swept clean immediately before installation of the stove. If the stove is fitted in place of an open fire then the chimney should be swept one month after installation to clear any soot falls which may have occurred due to the difference in combustion between the stove and the open fire. If there is no existing chimney then any new system must be to the designation described above and in accordance with Building Regulations Approved Document J.A single wall metal fluepipe is suitable for connecting the stove to the chimney but is not suitable for use as the complete chimney. The chimney and connecting fluepipe must have a minimum diameter and its dimension should be not less than the size of the outlet socket of the stove (see Annex 1, table 2).

Any bend in the chimney or connecting fluepipe should not exceed 45°. 90° bends should not be used. Combustible material should not be located where the heat dissipating through the walls of fireplaces or flues could ignite it. Therefore when installing the stove in the presence of combustible materials due account must be taken of the guidance on the separation of combustible material given in Building Regulations Approved Document J and also in these stove instructions.

If it is found that there is excessive draught in the chimney then a draught stabiliser should be fitted. Fitting of a draught stabiliser will affect the requirement for the permanent air supply into the room in which the stove is fitted in accordance with Approved Document J (see also combustion air supply).

Commissioning and handover

Ensure all parts are fitted in accordance with the instructions.

On completion of the installation allow a suitable period of time for any fire cement and mortar to dry out, before lighting the stove. Once the stove is under fire check all seals for soundness and check that the flue is functioning correctly and that all products of combustion are vented safely to atmosphere via the chimney terminal. On completion of the installation and commissioning ensure that the operating instructions for the stove are left with the customer. Ensure to advise the customer on the correct use of the appliance and warn them to use only the recommended fuel for the stove.

Advise the user what to do should smoke or fumes be emitted from the stove. The customer should be warned to use a fireguard to BS 8423:2002 (Replaces BS 6539) in the presence of children, aged and/or infirm persons.

Warning note on fume emission

Properly installed, operated and maintained this appliance will not emit fumes into the dwelling.

Occasional fumes from de-ashing and re-fuelling may occur. However, persistent fume emission is potentially dangerous and must not be tolerated. If fume emission does persist, the following immediate actions should be taken:

  1. Open doors and windows to ventilate
  2. Let the fire out or eject and safely dispose of fuel from the
  3. Check for flue or chimney blockage, and clean if

Do not attempt to relight the fire until the cause of the fume emission has been identified and corrected. If necessary seek expert advice.

Extractor fan

There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit smoke and fumes into the room.

Permanent air vent

The stove requires a permanent and adequate air supply in order for it to operate safely and efficiently.
In accordance with current Building Regulations the installer may have fitted a permanent air supply vent into the room in which the stove is installed to provide combustion air. This air vent should not under any circumstances be shut off or sealed.

Chimney cleaning

The chimney should be swept at least twice a year. It is important that the flue connection and chimney are swept prior to lighting up after a prolonged shutdown period. If the stove is fitted in place of an open fire then the chimney will require sweeping after a month of continuous operation. This is a precaution to ensure that any “softer” deposits left from the open fire usage have not been loosened by the higher flue temperatures generated by the closed stove.

Periods of Prolonged Non-Use

If the stove is to be left unused for a prolonged period of time then it should be given a thorough clean to remove ash and unburned fuel residues. To enable a good flow of air through the appliance to reduce condensation and subsequent damage, leave the air controls fully open.

Use of fireguard

When using the stove in situations where children, aged and/or infirm persons are present a fireguard must be used to prevent accidental contact with the stove. The fireguard should be manufactured in accordance with BS 8423:2002 (Replaces BS 6539).

CO Alarm

Building regulations require that whenever a new or replacement fixed solid fuel or wood/biomass appliance is installed in a dwelling a carbon monoxide alarm must be fitted in the same room as the appliance. Further guidance on the installation of the carbon monoxide alarm is available in BS EN 50292:2002 and from the alarm manufacturer’s instructions. Provision of an alarm must not be considered a substitute for either installing the appliance correctly or ensuring regular servicing and maintenance of the appliance and chimney system.

Use of operating tools

Always use the operating tools provided when handling parts likely to be hot when the stove is in use.

Aerosol sprays

Do not use an aerosol spray on or near the stove when it is alight.

5.5.2   The Clean Air Act 1993 and Smoke Control Areas
  • Smoke Control Areas

Under the Clean Air Act local authorities may declare the whole or part of the district of the authority to be a smoke control area. It is an offence to emit smoke from a chimney of a building, from a furnace or from any fixed boiler if located in a designated smoke control area. It is also an offence to acquire an “unauthorised fuel” for use within a smoke control area unless it is used in an “exempt” appliance (“exempted” from the controls which generally apply in the smoke control area).

In England appliances are exempted by publication on a list by the Secretary of State in accordance with changes made to sections 20 and 21 of the Clean Air Act 1993 by section 15 of the Deregulation Act 2015. In Scotland appliances are exempted by publication on a list by Scottish Ministers under section 50 of the Regulatory Reform (Scotland) Act 2014. Similarly, In Northern Ireland appliances are exempted by publication on a list by the Department of Agriculture, Environment and Rural Affairs under Section 16 of the Environmental Better regulation Act (Northern Ireland) 2016. In Wales appliances are exempted by regulations made by Welsh Ministers.

Further information on the requirements of the Clean Air Act can be found here: https://www.gov.uk/smoke-control-area-rules

Your local authority is responsible for implementing the Clean Air Act 1993 including designation and supervision of smoke control areas and you can contact them for details of Clean Air Act requirements.

5.5.2.1.1    Additional Operational Information:

Refuelling on to a low fire bed

If there is insufficient burning material in the firebed to light a new fuel charge, excessive smoke emission can occur. Refuelling must be carried out onto a sufficient quantity of glowing embers and ash that the new fuel charge will ignite in a reasonable period. If there are too few embers in the fire bed, add suitable kindling to prevent excessive smoke.

Fuel overloading

The maximum amount of fuel specified in this manual should not be exceeded, overloading can cause excess smoke.

Operation with door left open

Operation with the door open can cause excess smoke. The appliance must not be operated with the appliance door left open except as directed in the instructions.

Dampers left open

Operation with the air controls or appliance dampers open can cause excess smoke. The appliance must not be operated with air controls, appliance dampers or door left open except as directed in the instructions.

5.5.2.2   Exempt appliances

Exempt appliances are appliances (ovens, wood burners and stoves) which have been exempted under the Clean Air Act 1993 or Clean Air (Northern Ireland) Order 1981.

Appliances which are exempt for use in Smoke Control Areas: https://smokecontrol.defra.gov.uk/appliances.php

5.6  Outside air connection (if applicable)

Some fires can be provided with an outside air connection. For an optimum operation of the appliance, the following should be taken into account in case of an outside air connection:

  • The passage of the outside air connection and possibly the passage of a grate may not be smaller than the passage of the outside air connection on the
  • Make sure the maximum underpressure created in the combustion air supply pipe is 4 If a higher underpressure is created, the fire will not function properly and (hot) flue gases may flow back into the supply pipe.
  • Prevent placing the outside air supply in an underpressure area on the outside of the If possible, place a supply pipe with T piece to 2 sides of the house.
  • The combustion air supply pipe may not be placed higher than the bottom of the This will prevent flue gases from flowing back.
  • The combustion air pipe that is connected to the fire should be made of non combustible
  • The fire will function properly with a flexible pipe with a maximum length of 11 metres and 4 In case of a longer pipe or more bends, we recommend placing a pipe with a larger diameter (100-125mm).
  • If a crawl space is properly aerated with open grates, it is allowed to retrieve combustion air from there. If there is no proper aeration in the crawl space, it is possible that harmful radon gases are drawn This is not allowed according to national regulations.

Further information on the outside air connection, if applicable, can be found in section 9 ‘Appliance specific information’.
Please note that HETAS product approval remains valid for the appliance only when installed with its air supply taken from the room of installation and the room is ventilated permanently to outside air as necessary in accordance with the guidelines given in Approved Document J. HETAS product approval is not valid for appliances fitted with an external air supply ducted directly to the appliance.

5.7  Installing the fire, general

!Caution •      Do not make any changes to the fire yourself.

  • Use clean fabric gloves and avoid fingerprints on the fire and flue
  • Depending on the type of suspension, install the fire on a floor, against a wall or on a ceiling with sufficient load bearing
  • Lay a fire-resistant floor plate if the floor is combustible. The floor plate in non-combustible material must extend at least 300 mm away from the fire and be at least 300 mm wider than the Check these distances before installation on the basis of applicable national/local laws.

Tip!A floor plate offers protection against smouldering ash and prevents the soiling of a marble or flagstone floor, for example. We therefore also advise using a fire-resistant floor plate when installing appliances on a wall or ceiling.

  • Use the fire’s dimensional sketch to see which fire pipe diameter you need (see Annex 1, table 2).
  • Use a fire pipe that at least meets the requirements of standards as established in EN 1856-2
  • Install the flue pipes in such a way that a fire hazard can never
  • When installing a free-standing fire take account of the minimum required distance from the fire to a non-combustible This distance amounts to 50 mm.
  • When installing the fire and/or flue pipes respect the minimum distance to combustible objects and materials as shown in Annex 1, table 2.
  • Take adequate measures to avoid too high temperatures in any walls behind the chimney This also applies for materials and/or objects behind the wall.
  • Respect the flue duct requirements as described in 5.2.

For any appliance-specific instructions we refer to section 9 ‘Appliance- specific information’.
!CAUTION If you are installing a built-in appliance take account of:

  • The minimum building-in dimensions according to Annex 1, Table
  • Free-standing/design fires
    • Conversion from fire top connection to rear connection (if applicable).

The fire is supplied with a top connection for connecting the flue duct. The top connection can be converted to a rear connection.
To do this proceed as follows (see Annex 2, Fig. 2):

  • Take the flame baffle plate or baffle plates out of the fireplace (if applicable see section 9, ‘Appliance-specific information’).
  • Your appliance can be provided with an extra steel restrictor cap (if applicable see section 9, ‘Appliance-specific

information’). Remove this by sliding the restrictor cap forwards and taking it out of the rails. This restrictor cap is not replaced with a rear connection.

  • Remove the fire’s convection back plate by undoing the
  • Remove the push-through plate from the convection back
  • Remove the cover plate for the flue from the back wall of the fire by undoing the 2 or 3
  • Remove the flue ring from the top plate by undoing the nuts and/or
  • Fit the flue ring on the back wall using the bolts and/or
  • Fasten the convection back plate again with the
  • Assemble the cover plate for the flue in the opening in the top plate using the
  • Replace the flame baffle plate or baffle plates in the reverse

5.7.1.2    Installing a free-standing fire, general

A free-standing fire is installed as follows:

  • Determine the fire The dimensions of the appliance are given in Annex 1, Table 2.
  • For any appliance-specific instructions we refer to section 9 ‘Appliance-specific information’.
  • Make sure there are no combustible materials
  • Lay the floor plate if
  • Place the fire on a blanket or sheet of cardboard (to avoid damaging the floor) then put it in the desired
  • Connect the fire to the flue Follow the instructions of the supplier of the flue gas extraction system. Use heater piping material that at least suffices with regard to EN 1856-2 T600.
  • Lift the fire a little if necessary so the blanket or cardboard can be
  • For completing installation we refer to paragraph 8.

5.7.1.3    Design fire installation

To install a design fire we refer to Section 9 ‘Appliance-specific information’.

5.7.2   Insert fires (existing and new situation)

  • With an existing chimney or chimney breast

To install an insert fire with an existing chimney or chimney breast proceed as follows:

  • Determine the fire The dimensions of the appliance are given in Annex 1, Table 2.
  • Leave a space of at least 10 mm between the fire and construction
  • Check the size of the If necessary the walls of the open hearth can be broken out a little. Make sure that the chimney top is still sufficiently supported.
  • If applicable make room for the connection of the convection openings (if applicable see section 9

‘Appliance-specific information’) and section 5.3 ‘Convection’)) with a flexible aluminium pipe and ventilation elements (see section 5.4 ‘Appliances with fan(s)’. These accessories can be ordered from your supplier.

  • Be careful with the chimney breast Plaster beading makes the recess smaller.

  • Remove any existing valve from the open hearth or slide and clean the chimney top so all soot is

  • Remove the fire door and disassemble the frame when it is supplied separately (see section 9 ‘Appliance-specific information’).

  • Carefully remove the inner lining plates (mark them), the baffle plate and (if present) the restrictor cap from thefire (if applicable see, section 9 ‘Appliance-specific information’).

  • Lay any bottom plate supplied where the fire is to be

  • Turn the adjustable legs in with the hexagonal socket screwdriver supplied and check whether they are properly There may still be some blasting grit present.

  • Make sure there is sufficient room under fire for the supply of combustion air when there is no outside air connection.

  • An outside air connection can be made (if applicable see section 9 ‘Appliance-specific information’).

  • Carefully slide the fire into the Make sure that no damage is caused.

  • If applicable connect the convection opening ( see section 3 ‘Convection’) with the flexible aluminium pipe and ventilation elements (see section 5.4 ‘Appliances with fan(s))’.

  • The fire may never support the

  • Make a good, airtight seal between the fire and the flue, possibly with a register plate and preferably with a fixed fire pipe or stainless steel double-walled flexible pipe that at least suffices with regard to standard EN 1856-2

  • If applicable, and depending on national regulations, the connection between the existing flue duct and the fire may be plugged with heat-resistant ceramic wool Proceed as follows:

  • Check whether the open hearth valve has been

  • Remove the frame (if the frame is already fitted).

  • Remove the bottom plates and turn the fire as far as possible downwards with the adjustable legs to make space for the ceramic

  • Fill any space behind the fire with fire-resistant insulation material so no dirt can get

  • Remove the flame baffle

  • Apply the ceramic wool between the top side of the fire and the chimney for an airtight

  • Turn the fire up again with the adjustable legs and check whether the ceramic wool seals

  • Replace the flame baffle plate (see section 9 ‘Appliance-specific information’).

!Caution After the chimney has been swept always check that the connection is still airtight.

  • A handy kit is available through your supplier for the direct connection of a stainless steel flexible pipe to the The use of a kit is, however, not required for all appliances (if applicable see section 9 ‘Appliance-specific information’).
  • After the fire has been connected turn the adjustable legs with the Allen key supplied until the fire is in the

desired position. Make sure that the combustion air supply is not blocked.

  • Replace the restrictor cap for the outflow, fit the inner lining plates in reverse order and place the baffle plate against the back wall and on the profiles (if applicable see section 9 ‘Appliance-specific information’).
  • Use a torch or a thin screwdriver to check that the secondary ventilation holes in the back wall are directly facing

the recesses in the interior lining.

  • If applicable replace the frame around the fire (if applicable see section 9 ‘Appliance-specific information’).
5.7.2.2   In a new situation

To install an insert fire with a newly built chimney breast proceed as follows:

  • Determine the fire The dimensions are given in Annex 1, Table 2.

  • Place the fire on a floor with a sufficient load bearing

  • If applicable make a recess for an outside air connection (if applicable see section 9 ‘Appliance-specific information’).

  • Use non-combustible and heat-resistant material according to European fire classification A1 EN 13501-1 for the
    plate on the floor, chimney breast (including the upper face), the material in the chimney breast and the back wall against which the appliance is fitted. Plate material or stony materials can be used for this.

  • Leave a space of at least 10 mm between the fire and construction

  • Be careful with the chimney breast Plaster beading makes the recess smaller.

  • Take account of the expansion of the Keep the fire free of plasterwork.

  • If there is a combustible ceiling, place a fire-resistant plate with a 10 cm thick heat-insulating layer on top 30 cm below the ceiling in the chimney

  • If are there combustible materials (e.g. wooden floor parts/beams ) below or behind the fire, sufficient

non-combustible insulation material according to European fire classification A1 EN 13501-1 must be applied. Comply with national regulations here.

  • If there is a combustible wall build a 10 cm-thick fire-safe
  • Build the base or elevation with heat resistant
  • Place the steel plate supplied in the place for the If applicable make a recess in it for the outside air connection. Remove the fire door and disassemble the frame when it is supplied separately.
  • Remove the fire door and disassemble the frame when it is supplied separately (see section 9 ‘Appliance-specific

information’).

  • Install the
  • If applicable connect the outside air connection (see section 9 ‘Appliance-specific information’).
  • If applicable connect the convection opening (see section 3 ‘Convection’) with the flexible aluminium pipe and ventilation elements (see section 5.4 ‘Appliances with fan(s))’.

Keeps these elements at least 30 cm away from the ceiling.

  • Use single-walled stainless steel flue pipes or stainless steel double-walled flexible pipes that at least meet the requirements of standard EN 1856-2
  • The fire may never support the
  • After the fire has been connected turn the adjustable legs with the Allen key supplied until the fire is in the desired Make sure that the combustion air supply is not blocked when doing this.
  • Replace the restrictor cap for the outflow, fit the inner lining plates in reverse order and place the baffle plate

against the back wall and on the profiles (see section 9 ‘Appliance-specific information’).

  • Use a torch or a thin screwdriver to check that the secondary ventilation holes in the back wall are directly facing the recesses in the interior
  • Replace the door and if applicable the frame around the fire (if applicable see section 9 ‘Appliance-specific

information’).

  • Lay a fire-resistant floor plate for the fire if the floor is The floor plate of non-combustible material must extend at least 300 mm away from the fire and be at least 300 mm wider than the fire.
5.7.3   Built-in fires
  • Determine the place of the
  • Slide the build-in frame into the desired
  • Use non-combustible and heat-resistant material according to European fire classification A1 EN 13501-1 for the plate on the floor, chimney breast (including the upper face), the material in the chimney breast and the back wall against which the appliance is Plate material or stony materials can be used for this.
  • If there is a combustible ceiling, place a fire-resistant plate with a 10 cm thick heat-insulating layer on top 30 cm

below the ceiling in the chimney breast.

  • Place the fire level at the desired height and fix it with metal
  • Connect the flue duct to the fire
  • Always connect any convection openings (see section 3 ‘Convection’) with heat-resistant flexible pipe and ventilation elements (see section 5.4 ‘Appliances wit fan(s)) to protect the plasterwork against high temperatures. If the chimney breast is made of non-combustible materials (e.g. facing brickwork) this is not required.
  • Make sure there is sufficient space under the fire for the supply of combustion When the outside air

connection ring is not used, it must remain at least 20 mm free for sufficient combustion air.

  • If applicable connect the outside air connection (see section 9 ‘Appliance-specific information’).
  • The fire is not suitable to support a flue duct, it must be self-supporting.
  • Stony materials may absolutely not rest on the For this use e.g. a brick lintel with ceramic felt.
  • Make sure that the opening in the chimney breast is 6 mm wider than the built-in
  • The chimney breast may not be warmer than 90 degrees Celsius on the
  • Lay a fire-resistant floor plate for the fire if the floor is The floor plate in non-combustible material must extend at least 300 mm away from the fire and be at least 300 mm wider than the fire.
5.8  Completing installation
  • Check if grit, dust or other materials are left behind in the chimney breast (odours).
  • Use clean fabric gloves and avoid fingerprints on the fire and flue
  • Check whether the interior lining and the baffle plates are fitted properly in the fire (if applicable see section 9 ‘Appliance-specific information’). Correct the position of these plates if
  • Check whether the holes of the secondary ventilation in the back plate are immediately facing the recesses in the

interior lining.

  • Clean the fire with a soft cloth and check it for The fire can be sprayed with the spray can supplied. Before doing this read the instructions for use on the label. Always first check the colour on a piece of white paper or cardboard before you treat the fire.

First carefully read the user manual before starting to use the fire. We refer to the user manual for lighting and burning the fire.

 6. Delivery and maintenance

  • You must make the user familiar with the Among other things you must instruct her/him about bringing the fire into use and its burning and maintenance.
  • When bringing into use point out that
    • after rebuilding or new building all building materials must have thoroughly dried out to avoid dust (including smoke particles) adhering to damp surfaces;
    • the first time of burning volatile components will evaporate from paint, materials ;
    • the space must then be well
  • Point out the necessity to have the flue duct inspected and cleaned at least once a year by a
  • Give the user the user manual and installation manual (the installation manual must be kept with the appliance).

The user manual includes a number of tips/instructions for maintenance of the fire. It also mentions how a number of parts can be replaced.

 7. End of life / Recycling

At the end of the use cycle, the device must be disposed of and recycled in a responsible manner. To do this, follow the steps below. Local laws and regulations must always be followed when disposing/recycling the appliance. If in doubt, contact the local government about the available collection flows.
!Caution Only disassemble and remove the device when it has cooled down and is at room temperature.

  • Remove the inner lining, glass and the sealing material from/from the These parts can be returned to a designated collection point.

!Caution The pane is made of ceramic material and can therefore not be returned to a glass recycling center.

  • The steel parts can be offered to a designated recycling

 8.Malfunctions

The user manual contains a table with a summary of malfunctions that can occur, their possible cause and the solution.

9. Appliance-specific information

!CAUTION •      The appliance-specific instructions as described in this section prevail over the instructions in the other sections! If in doubt follow the instructions in section 9 or contact your supplier.

  • The appliance-specific information as described in paragraphs 1 to 9.5 applies to all models described in this manual. Supplementary installation instructions (per appliance) are described in paragraph 9.6.
9.1  Smoke control area United Kingdom

The Dik Geurts Ivar 8, Store / Ivar 8, Low wood burning stove have been recommended as suitable for use in smoke control areas when burning wood logs.
The Ivar 8, Store and Low wood burning stove must be fitted with a permanent stop to prevent closure of the primary air control beyond the 6.0cm open position.
Exemption details can be found at: https://smokecontrol.defra.gov.uk/appliances.php
A limiting screw is accordingly supplied with all appliances. This is supplied as a kit in the combustion chamber. This screw is therefore only used in the smoke control areas in the United Kingdom. In other countries this screw can be disposed of in the appropriate way.
With the installation of an appliance in the United Kingdom:

  • Install the screw as shown in Appendix 2, 3. After fitting, the air slide valve cannot be slid further shut than legally allowed.

If this screw is not fitted or is removed the appliance will no longer be legally allowed to burn the permitted fuels in Smoke Control Areas.

9.2  Air slide valve and heat shield
9.2.1   Air slide valve

When installing and maintaining the appliance, please check the operation of the air slide valve (see Appendix 2, fig. 4). It is possible that steel grit entered the air slide valve during transport. If the air slide valve does not move smoothly it must be cleaned. For this purpose, the air slide valve must be disassembled. The suspended air slide valve is spring-mounted using a bolt and a spring, which are located below the cover plate.
When mounting the air slide valve, please proceed as follows (see Appendix 2, fig. 4):
Caution! If an outside air connection has been mounted, it must first be removed, before the air slide valve can be mounted (for removing the outside air connection: see section 9.5).

  • Remove the vermiculite plates from the bottom (see section 3.1).
  • Then remove the little square plate located in a recess below the vermiculite bottom
  • Loosen the allen screw using the socket head

Caution! As soon as the bolt has been loosened, the air slide valve will fall down. Make sure you catch the air slide valve!

  • Check the air slide valve and clean it if

In order to replace the air slide valve, proceed as described for removal, only in reverse order.

9.2.2   Heat shield (optional)

Using a heat shield will allow you to place the appliance closer to the wall. This ‘heat shield kit’ consists of two guard plates and is optionally available through your supplier.
Caution! It is only possible to place a heat shield if the flue gas discharge is connected at the top of the appliance.
Proceed as follows:

Guard plate attached to the appliance:

  • Loosen the 4 pre-mounted bolts at the rear of the appliance by a few turns (see appendix 2, 5).
  • Place the plate against the back of the
  • Tighten the 4
Guard plate attached to the discharge pipe:

(only applicable in case of a single wall pipe)

  • Allow the guard plate to rest on the appliance at the rear of the flue
  • Then press the plate against the flue
  • Drill 4 holes (Ø 4 mm) and fix the plate using the supplied screws (see appendix 2, 6).
9.3  Interior lining
9.3.1   Vermiculite

The fire’s vermiculite plates are located on the bottom and against the rear and side walls of the appliance. In the following situations the vermiculite plates must be taken out:

  • When disassembling the air slide valve (see section 2.1).
  • When replacing the vermiculite

The bottom plates are removed first and the rear plates are removed last.
!Caution Make sure that the vermiculite plates are placed back in their original position! The back plate, for instance, must be placed with the small, not countersunk, holes towards the front.

9.3.2   Flame baffle plate

On delivery the flame baffle plate (see Appendix 2, fig. 7) is located in the top section of the appliance. In case of maintenance to the appliance, the flame baffle plate has to be removed.
To do this proceed as follows:

  • Take hold of the flame baffle plate and push the right side
  • Slide the flame baffle plate over the ridge to the
  • Lower the left side of the flame baffle plate and remove the flame baffle

Placing the flame baffle plate takes place in reverse order.
!Caution The stainless steel profile must be placed at the front with the screw heads on top (see Appendix 2, fig. 7).

9.4  Door

Check the closing of the door during installation or maintenance. To do this proceed as follows:

  • Check the sealing of the door by placing a sheet of paper between the door and the After closing the door, it should not be possible to pull out the sheet of paper easily. Check the outside of the fire. In case the door still doesn’t seal properly:
  • Replace the door seal (see section 4.1)

9.4.1   Replacing door seal

When replacing the door seal proceed as follows:

  • Open the
  • Remove the cord and the mastic from the
  • Apply a new layer of heat resistant mastic in the recess where the cord
  • Place a new cord in the Do this loosely and do not pull the cord tight.
  • Insert both ends of the cord in the special

The cord, the sleeve and the mastic are available through your supplier.
!Caution Make sure that the sleeve is placed on the underside of the glass pane.
!Caution Regularly check the sealing in the case of an RS appliance, replace if necessary to ensure RS.

9.5  Glass pane
9.5.1   (Dis)assembly of the glass pane

!Tip Use the supplied glass pane cleaner to remove fingerprints from the glass pane(s).
To remove the glass pane and then remount it in the door, please follow the instructions below (see Appendix 2, fig. 8).

Disassembly of glass pane in door:
  • Open the
  • Lift out the door by sliding it
  • Place the door on a flat
  • Unscrew the 4 bolts that hold the
  • Lift out the glass pane. The pane seal is also taken

Assembly of glass pane in door:

  • Mount the glass pane and place back the door by performing the steps for disassembling the glass pane in reverse

!Caution Do not fasten the bolts too tight to avoid breaking off and/or stripping: overtightening will cause breakage.

  • Place the glass pane (including new pane seal) with the logo to the bottom
9.6  Supplementary installation instructions per appliance
9.6.1   Ivar 8, Low
  • Flue gas exhaust

The flue gas exhaust has a 6″ diameter connection. The draining connection can be achieved by means of a fixed pipe of 6″. The flue gas exhaust can be connected at the top or rear of the appliance (see Appendix 2, fig. 2).In case of a connection at the rear, please proceed as follows:

  • Remove the 2 bolts from the exhaust ring mounted at the top of the
  • Remove the bolts from the plate at the rear of the
  • Mount this plate on the top of the appliance, on the location where the exhaust ring used to
  • Mount the exhaust ring at the rear of the appliance by tightening the 2
9.6.1.2   Outside air connection

An outside air connection is available for this appliance as accessory. Assembly always takes place at the bottom of the appliance. In case of this appliance, supply is possible via the rear and the back.
!Caution When installing an Ivar 8, Low appliance, the outdoor air connection is pre-mounted at delivery. If so, observe the steps described under the heading ‘ Outdoor air connection pre-mounted ‘.

Outdoor air connection not pre-mounted:

When mounting the outside air connection, please proceed as follows (see Appendix 2, fig. 9a + 9b):

  • Loosen the 5 bolts that are pre-mounted on the outside air
  • Bring the outside air connection against the plate on the bottom of the
  • Then re-tighten the 5
  • Fasten the tray for the benefit of the rear connection with 4
  • Connect the flexible hose to the round ‘pipe opening’ of the above-mentioned The flexible hose can only be fed from the rear.

Caution! The round pipe opening for the benefit of the lower connection is not needed during installation and should be disposed of responsibly.

Outdoor air connection pre-mounted:

  • Connect the flexible hose (Ø 80 mm) to the round ‘pipe mouth’ of the outdoor air

!Caution In the case of the Ivar 8, Low, you are dealing with a fully closed system. This means that you must always ensure an airtight connection of the flexible hose to the round ‘pipe mouth’ by using heat resistant sealant.
If you want to disassemble the outdoor air connection, you should perform the above-mentioned steps in reverse order.

9.6.2   Ivar 8, Store
  • Flue gas exhaust

The flue gas exhaust has a 6″ diameter connection. The draining connection can be achieved by means of a fixed pipe of 6″. The flue gas exhaust can be connected at the top or rear of the appliance (see Appendix 2, fig. 2).

In case of a connection at the rear, please proceed as follows:

  • Remove the 2 bolts from the exhaust ring mounted at the top of the
  • Remove the bolts from the plate at the rear of the
  • Mount this plate on the top of the appliance, on the location where the exhaust ring used to
  • Mount the exhaust ring at the rear of the appliance by tightening the 2
9.6.2.2 Outside air connection

An outside air connection is available for this appliance as an accessory. Assembly always takes place on the bottom of the appliance.
With this appliance the supply is possible at the back and bottom side.
!Caution When installing an Ivar 8, Store appliance, the outdoor air connection is pre-mounted at delivery. If so, observe the steps described under the heading ‘ Outdoor air connection pre-mounted ‘.

Outdoor air connection not pre-mounted:

When mounting the outside air connection, please proceed as follows (see Appendix 2, fig. 10a + 10b + 10c):

Supply through the back side:
  • Unscrew the 4 screws of the reflection plate and remove the The reflection plate is located under the air slide and protects the wood stacked below the stove against the high temperatures created in the appliance.
  • Break out the plate at the back of the appliance with a
  • Loosen the 5 bolts that are pre-mounted on the outside air
  • Bring the outside air connection against the plate on the bottom of the
  • Then re-tighten the 5
  • Fasten the tray for the benefit of the rear connection with 4
  • Connect the flexible hose to the round ‘pipe opening’ of the above-mentioned

Caution! The round pipe opening for the benefit of the lower connection is not needed during installation and should be disposed of responsibly.

CAUTION! Always place back the reflection plate!.

Supply through the bottom side:
  • Remove the 4 reflection plate screws and remove the The reflection plate is located under the air slide valve and protects the wood stacked below the stove against the high temperatures created in the appliance.
  • Break the plate out of the reflector plate and break the plate out of the bottom of the
  • Loosen the 5 bolts that are pre-mounted on the outside air
  • Bring the outside air connection against the plate on the bottom of the
  • Then re-tighten the 5
  • Fasten the pipe opening for the bottom connection with 4
  • Bring the flexible hose through the hole in the reflector
  • Connect the flexible hose to the pipe
  • Replace the restriction

Caution! The tray for the rear connection is not needed during installation and should be disposed of responsibly.

Outdoor air connection pre-mounted:

  • Connect the flexible hose (Ø 80 mm) to the round ‘pipe mouth’ of the outdoor air

!Caution In the case of the Ivar 8 StoreRS, you are dealing with a fully closed system. This means that you must always ensure an airtight connection of the flexible hose to the round ‘pipe mouth’ by using heat resistant sealant.
If you want to disassemble the outdoor air connection, you should perform the above-mentioned steps in reverse order.

Read More About This Manual & Download PDF:

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals