HYTRONIK HIM31 IP65 High Bay Dual Sense Sensor Instruction Manual

June 9, 2024
HYTRONIK

HYTRONIK HIM31 IP65 High Bay Dual Sense Sensor

HYTRONIK-HIM31-IP65-High-Bay-Dual-Sense-Sensor-PRODUCT-
IMAGE

Technical Specifications

Product type Tri-level control dual sense sensor
Operating voltage 220-240VAC 50/60Hz
Rated load 800VA(Capacitive)

1000W(Resistive)
Power consumption| < 1W
Detection angle| 360o
Detection area (Max.)*| Installation Height : 15m Detection Range (Ø) :18m
Detection range| 10% / 50% / 75% / 100%
Hold time| 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time| 0s / 10s / 1min / 5min / 10min / 30min / 1h / + ∞
Stand-by dimming level| 10% / 20% / 30% / 50%
Daylight threshold| 2 ~ 500Lux, Disable
Warmming up time| 30s
Operating temperature| -30oC ~ +50oC
IP rating| IP65
Sensor mode| HF, PIR, HF+PIR, HF / PIR

Rotary Switch Settings

A rotary switch is built inside the sensor for scene selection / fast programming. Total of 16 channels available:

Channel| Detection range| Hold time| Stand-by time| Stand-by dimming level| Daylight threshold
---|---|---|---|---|---
0| 100%| 5s| 10s| 10%| Disable
1| 100%| 1min| 5min| 10%| 2Lux
2| 100%| 5min| 10min| 10%| 10Lux
3| 100%| 5min| 30min| 10%| 30Lux
4| 100%| 5min| 0s| Disable| 10Lux
5| 100%| 5min| +∞| 10%| 30Lux
6| 100%| 5min| +∞| 30%| Disable
7| 100%| 10min| 10min| 10%| 2Lux
8| 100%| 10min| 30min| 10%| 10Lux
9| 100%| 10min| +∞| 10%| 30Lux
A| 100%| 10min| +∞| 30%| Disable
B| 75%| 10min| +∞| 10%| 30Lux
C| 50%| 10min| +∞| 10%| 10Lux
D| 100%| 30min| +∞| 10%| 50Lux
E| 100%| 30min| +∞| 30%| Disable
F| 100%| 5s| 10s| 10%| 2Lux

Note: settings can also be changed by remote control HRC-11. The last action controls.

Functions

Tri-level Control (Corridor Function)
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas it requires a light change notice before switch-off.
It offers 3 levels of light: 100%–>dimmed light–>off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.

Lux Off Function
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically whenever artificial light is unnecessary (natural light lux level exceeds daylight threshold).
Note: if the stand-by time is preset at “+∞”, the fixture never switches off even when natural light is sufficient.

Load Indication
The light will flash ONCE rapidly after receiving the command from the remote controller.
Note: There is no load indication (the light will not flash) when button ON/OFF, POWER 100% or POWER 80% is pressed.

Installation

Warnings:

  1. Installation of the sensor involves connecting it to the mains supply. This work must be carried out by a specialist in accordance with electrotechnical regulations.
  2. Disconnect power supply before installing.
  • Ceiling mount
    HYTRONIK-HIM31-IP65-High-Bay-Dual-Sense-Sensor-2

  • Screw to the Luminaire by conduitHYTRONIK-HIM31-IP65-High-Bay-Dual-Sense-Sensor-3

  • Attach to the shade by clamp
    HYTRONIK-HIM31-IP65-High-Bay-Dual-Sense-Sensor-4

Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.

Wiring Diagram

Three Options for PIR Lens and Detection Patterns (End user can choose the suitable lens in real application for various requirements)

  • For single person walking across, the detection range is reduced by 1/3.

    • PIR detection: H x D:15 x 18m (max.) HF detection: H x D:15 x 14m (max.)

    • PIR detection: L x W x H:18 x 5 x 15m (max.) HF detection: H x D:15 x 14m (max. )

    • PIR detection: L x W x H:5 x 18 x 15m (max.) HF detection: H x D:15 x 14m (max. )

Descriptions of the Button Functions (remote control HRC-11)

Permanent ON/OFF [ button 1]
Press button1 , to select permanent ON or permanent OFF mode.

  • Press button2 /4 to resume automatic operation.
    The mode will change to AUTO Mode after power failure.

RESET[ button 2]
Press button2 , all settings go back to default values as below:
Hold-time 5min, daylight threshold Disabled.

Shift [ button3 ]
Press button3 , the LED on the top left corner is on for indication.
All values / settings in RED are in valid for 20 seconds.

Auto Mode [ button 4 ]
Press button 4 to initiate automatic mode. The sensor starts working
and all settings remain as before the light was switched ON/OFF.
Note: the function of Semi-auto is disabled

Sensor off [ button 5 ] (Daylight harvest without occupancy)
Note: the function of button 5 are all disabled.

Power output [ button 6 ]
Note: the function of button 6 are all disabled.

Brightness +/- [ button 7 ]
Note: the function of button 7 are all disabled.

Scene prog. [ zone ] (One-key-commissioning)

  1. Press button “Start” to program.
  2. Select the buttons10 in “Detection range”, 6/ 11“Daylight threshold”, 13“Hold time”, 14“Stand-by time” to set all parameters.
  3. Press button “Memory” to save all the settings programmed in the remote control.
  4. Press button “Apply” to set the settings to each sensor unit(s).
    For example, to pre-set detection range 100%, daylight threshold
    Disable, hold time 5min, stand-by time +, the steps should be as follows:
    Press button8 Start, button 100%, 12 Disable,3 Shift, 5min, Shift, +13, Memory. By pointing to the sensor unit(s) and pressing Apply, all settings are passed on the sensor(s).

Sensor function [button 9 ]
Note: the function of button 9 are all disabled.

Detection range [ button 10 ]
Press buttons 10 to set detection range at 100% / 75% / 50% / 10%.

Daylight threshold [ zone11 ] Press buttons 11 in zone to set the daylight sensor at 2Lux / 10Lux /
50Lux / 100Lux / 300Lux / 500Lux or Disable as threshold / target Lux level.
Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button3 Shift at first.

Ambient daylight threshold [ button  12]

  1. Press button 3 Shift, the red LED is on for indication.
  2. Press button 12 , the ambient lux level is sampled and set as daylight threshold / target Lux level.

Hold time [ zone 1 3 ]
Press buttons in zone to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.
Note:

  1. To set hold-time at 30s / 5min / 15min / 30min, press button Shift at first.
  2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode.
    *To exit from Test mode, press button or any button in zone .

Stand-by time [ zone 14 ]
Press buttons in zone 14 to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +14.
Note: To set 0s, 1min, 10min, +3, press button “Shift”at first.

All buttons in zone “Stand-by dimming level & Auto-config” and “Dual-tech & RF mode” are disabled.

Trouble Shooting

MALFUNCTION CAUSE REMEDY CAUSE REMEDY
The fixture does not light up Incorrect daylight threshold setting Adjust

daylight threshold setting
Faulty fixture| Replace fixture
No power supply| Check power to sensor
Detection zone not targeted| Check detection area setting
The fixture is always on| Continous movement in the detection zone| Check detection area setting
The fixture is on when it should not| Sudden change in temperature due to weather (wind, rain, snow) or air expelled from fans, open windows| Adjust zone, change installation site