Kosnic BEM203 Universal Emergency Module for LED Batten Luminaires Owner’s Manual
- June 9, 2024
- Kosnic
Table of Contents
- BEM203 Universal Emergency Module for LED Batten Luminaires
- Product Information
- Safety Information
- Specifications
- Product Usage Instructions
- Universal Emergency Module for LED Batten Luminaires
- General Installation Information
- Specifications
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BEM203 Universal Emergency Module for LED Batten Luminaires
Product Information
The Universal Emergency Module for LED Batten Luminaires is a device manufactured by Kosnic Lighting Ltd. It is designed to be used with Kosnic LED batten luminaires where specified on the batten datasheet. The device is equipped with a rechargeable LiFePO4 battery that can provide emergency power in case of a power outage. The maximum output wattage of the device is 3W and it has a battery capacity of 2000mAh.
Safety Information
Please read the instructions thoroughly before use and retain them for future reference. The device is for built-in installation and has double insulation. The maximum case temperature of the device should not exceed the values specified in the specifications section. The device should not be disposed of with household waste as it may contain harmful substances to the environment.
Specifications
Order Code| Input Voltage| Input Current| Battery Output Wattage (max)| Output
Voltage| Output Current| Open Circuit Voltage| Maximum Working Voltage
Protection| Input to Output Protection| Battery| Battery Voltage| Battery
Capacity| Battery Charge Voltage| Battery Charge Current
---|---|---|---|---|---|---|---|---|---|---|---|---|---
BEM203| 220-240 Vac 50/60 Hz| 40 mA| 3W| 30-300 Vdc| 8-65 mA| 310 Vdc| IP20|
Double Insulation| LiFePO4 BAT20LFP2| 6.4 V| 2000 mAh| 8.0 Vdc| 30-250 mA
Product Usage Instructions
- Before use, read the instructions thoroughly and retain them for future reference.
- The emergency module is only suitable for use in Kosnic LED batten luminaires where specified on the batten datasheet.
- The device is for built-in installation and has double insulation.
- Connect the device to the input voltage of 220-240 Vac 50/60 Hz and input current of 40 mA.
- The device has a battery capacity of 2000mAh and a maximum output wattage of 3W.
- The battery charge voltage is 8.0 Vdc and the battery charge current is between 30-250 mA.
- The device has a test function that can be used to check if it is functioning properly.
- Do not dispose of the device with household waste as it may contain harmful substances to the environment.
Note:
The emergency module is not a replacement for a backup generator or other
emergency power sources. It is designed to provide temporary power during an
outage and should not be relied upon as a long-term solution.
Universal Emergency Module for LED Batten Luminaires
Please read these instructions thoroughly before use and retain for future
reference.
The emergency module is only suitable for use in Kosnic LED batten luminaires
where specified on the batten datasheet.
Safety Information
- Installation must be carried out in accordance with national building and wiring regulations.
- If you are in any doubt about installing this product, please consult a qualified electrician.
- Before commencing installation or maintenance, turn off and isolate the circuit to be worked on by removing the fuse or switching the circuit breaker off at the distribution board.
- This product is suitable for connection to a 220-240Vac 50/60Hz supply.
- This product is an IP20 built-in driver relying on the enclosure for protection.
- Do not use the emergency module if the cable is damaged.
- The emergency module is not suitable for use on a battery supply with a trickle or intermittent recharging circuit.
- The emergency module is not protected against supply voltage polarity reversal.
- Insulation between the emergency module supply and battery circuit is double insulation.
- The recharging device will recharge the battery normally after the removal of a battery short-circuit
- When cutting holes, drilling or screwing take care not to damage existing wiring or pipework.
Wiring Schematic
General Installation Information
- Follow the batten instructions to access the correct installation area inside the batten.
- The diagram below shows a typical installation. Specific details may vary from one compatible batten model to another.
- The optional emergency module provides power in the event of a cut in the supply and must be wired to the un-switched permanent supply through the un-switched Live terminal (L 1).
- Write the commissioning date on the battery label.
- Stick the Maintained or Non-Maintained emergency luminaire label on the luminaire where it can be seen.
- Ensure that all electrical connections are tight with no loose strands.
- Reconnect the supply.
- The battery leaves the factory in a charged state but may take up to 24 hours to fully charge for a 3-hour test. Charge for 5 minutes before performing a functional test to ensure there is some charge in the battery.
- To fully test the emergency function, the un-switched supply will need to be switched off. A quick functional test can be performed by pressing the test button.
- Replace the battery when the luminaire fails to meet the 3-hour duration requirement in testing.
Specifications
Order Code | BEM203 |
---|---|
Input Voltage | 220-240 Vac 50/60 Hz |
Input Current | 40 mA |
Battery Output Wattage (max) | 3W |
Output Voltage | 30-300 Vdc |
Output Current | 8-65 mA |
Open Circuit Voltage | 310 Vdc |
Maximum Working Voltage | 310 Vdc |
Protection | IP20, For built-in installation |
Input to Output Protection | Double Insulation |
Battery | LiFePO4 BAT20LFP2 |
Battery Voltage | 6.4 V |
Battery Capacity | 2000 mAh |
Battery Charge Voltage | 8.0 Vdc |
Battery Charge Current | 30-250 mA |
Battery Discharge Voltage | 5.8-8.0 Vdc |
--- | --- |
Battery Discharge Current | 400-500 mA |
Charging Time | 24 h |
Battery Life | 4 Years |
Emergency Conversion Time | 1 s |
Emergency Operation Time | >3 h |
Test Function | Manual |
Length x Width x Depth | 220 x 42 x 28mm |
Weight | 230 g |
Maximum Case Temperature | 75 °C |
Ambient Temperature Range | 0 to 45 °C |
Typical Installation Diagram Battery Replacement The Waste Electrical & Electronic Equipment
Regulations (WEEE) require that products bearing this symbol must not be
disposed of with household waste as they may contain substances harmful to the
environment. The Local Authority can provide advice on recycling.
Kosnic Lighting Ltd, Unit 2, Kennetside, Bone Lane, Newbury, RG14 5PX, UK
www.kosnic.com
References
- Kosnic: New age of lighting - Designers and manufacturers in LED Lighting
- Kosnic: New age of lighting - Designers and manufacturers in LED Lighting
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>