Multi V INDOOR UNITS VRF LG Air Conditioning User Guide

June 7, 2024
LG

Multi V INDOOR UNITS VRF LG Air Conditioning

INDOOR UNITS VRF SYSTEMS
LG Air Conditioning Technologies

ABOUT LG
About LG Electronics USA
LG Electronics USA, Inc., based in Englewood Cliffs, New Jersey, is the North American subsidiary of LG Electronics, Inc., a $54 billion global force and technology leader. LG Electronics, named an ENERGY STAR® Partner of the Year for many years, sells a range of stylish and innovative home entertainment products, home appliances, commercial displays, air conditioning systems and solar energy solutions in the United States, all under LG’s “Life’s Good” marketing theme. For more news and information on LG Electronics, please visit www.LG.com.
LG Electronics USA Air Conditioning Technologies
The LG Electronics USA Air Conditioning Technologies business is based in Alpharetta, Georgia. LG is a leading player in the global air conditioning market, manufacturing both commercial and residential air conditioners and providing total sustainability and building management solutions. From consumer and individual units to industrial and specialized air conditioning systems, LG provides a wide range of products for heating, ventilating and air conditioning. For more information, please visit www.lghvac.com.
1 LG Air Conditioning Technologies

ABOUT LG VRF

A Variable Refrigerant Flow (VRF) system is a single refrigerant circuit that connects many indoor units to one
outdoor unit. VRF is a superior way to heat and cool any space, providing improved humidity control, individual set points per indoor unit, and a very quiet comfort experience. In the heat recovery configuration, VRF also allows for heating and cooling simultaneously in different zones, further enhancing energy savings and increasing occupant comfort. Energy efficient and easy to design, install, and maintain; a VRF system has low life cycle cost compared to other systems
on the market today.

Why LG VRF?

The benefits are numerous: less piping for installers, energy efficiency for owners, and modern indoor units that

complement every setting. Sound levels of LG VRF products are among the lowest in the industry, so units can

be installed where noise is an issue. Inverter scroll compressors manufactured by LG optimize system energy

efficiency.

LGRED

With the addition of LGRED° heating capability, the Multi VTM 5 provides continuous operational performance with heating down to -22°F and cooling up to 122°F for
all units with no additional accessories or modifications to the equipment,

Powerful Heat Technology
RELIABLE TO EXTREME DEGREES

making it a robust solution for all climates.

1. High Elevation Piping Distances

3,280 ft.
Total piping length
738 ft.
Longest piping length

NOTE: All piping lengths are equivalent.

360 ft.
Height between ODU-IDU

2. Optimized Heat Recovery Piping
· Flexible piping layout reduces materials and labor costs during installation
· LG Heat Recovery Unit (HRU) is quiet, compact, lightweight, and does not need condensate drains
· Configured for fully independent heating and cooling, ensuring occupant comfort

131 ft.
Height between IDU-IDU

4. Quiet Operation · Quiet indoor unit operation down to 23 dB(A), comparable to the sound of rustling leaves

50 dB(A)
Conversation at Home

3. Operation Range

· Industry-leading operation ranges without
LGRED additional accessories or performance deficits:
· Heating: -22°F to 61°F WB

· Cooling: 5°F to 122°F DB

Powerful Heat Technology

· Simultaneous Operation: 14°F to 81°F DB RELIABLE TO EXTREME DEGREES

40 dB(A)
Bird Calls
23 dB(A)
LG Low-Static Ducted Indoor Unit
Noise Level Comparison dB(A)

60 dB(A)
Conversation in Restaurant
70 dB(A)
Vacuum Cleaner

2

LG VRF ADVANTAGES

Efficiency

Advanced features for superior efficiency:
· Advanced Smart Load Control Automatically adjusts system target pressures based on outdoor temperature and humidity for increased cooling performance.
· Active Refrigerant Control Depending on the operating mode and conditions, the system refrigerant level is automatically adjusted for increased part load and heating efficiency.
· Variable Path Heat Exchanger Depending on the operating mode and conditions, both the refrigerant flow path and velocity are adjusted for improved efficiency.
· Advanced PCB Cooling Improved cooling performance of the inverter PCB by using liquid refrigerant instead of heat sink cooling methods.

· LG Inverter Scroll Innovative high side-shell design creates a more compact unit providing the same capacity output, with greater reliability in cold climates.
· HiPORTM (High-Pressure Oil Return) Oil is returned to the compressor through a separate inlet pipe, ensuring that compressor energy is used to compress refrigerant only.
· Smart Oil Control Eliminates timed oil-return cycles and takes hours off of the time required to return oil compared to systems that use a timed oil- recovery cycle.
· Intelligent Heating By monitoring the outdoor humidity, system target pressures can be reduced to extend heating operation, delay defrost operation and reduce power consumption.
Performance

Expansive operating range in cooling and heating without adding accessories:
· LG Multi V 5 uses vapor injection technology
for improved heating performance in ambient conditions as low as -22°F.
· Using a variable path heat exchanger, LG Multi VTM 5
performs in low ambient conditions to provide cooling down to 5°F.

Comfort

Design Flexibility
· Higher-Elevation Piping Technology More floors with fewer systems. LG Multi VTM 5 eliminates the need to invest in extra systems and saves on installation. Enjoy no heating capacity losses due to long pipe length.
· Compact and Lightweight More indoor zones, less outdoor space. When space or access is at a premium, Multi V 5 offers significant cost advantages on large projects.

· Quiet Operation Multi V indoor units are among the quietest in the industry, with rated sound levels as low as 23dB(A). In addition to temperature, airflow and dehumidification, extremely low sound levels contribute to a relaxing environment.
· Individualized Zone Control Multi V systems allow the user to control the space to the exact temperature desired. This further enhances comfort while promoting reduced power consumption.
· Indoor Air Quality All Multi V indoor units incorporate a reusable, washable filter. Since distribution and return ducts are not required for this system, dust and duct mold accumulation are reduced, contributing to improved indoor air quality.

3 LG Air Conditioning Technologies

TRAINING
Training
The LG US Air Conditioning division is headquartered near Atlanta in Alpharetta, Georgia, along with a full training academy. Additional training academies are located in California, Texas and New Jersey. Since 2008, our academies have trained thousands on the advantages of LG air conditioning systems, and even more have been trained through LG’s online training modules. World class trainers with years of experience teach classes in duct-free technology, with topics covering everything from installation to service for the full range of LG air conditioning products. LG also has a number of strategically placed training academies throughout the United States that offer a number of LG training classes as well. For HVAC professionals, LG offers online instruction via our Learning Management System and classroom training at our training academies, strategically placed throughout the country. Training is open to all contractors; ask your LG Electronics authorized distributor for details. For more information and to find out how you can be part of the next training class near you, visit https://lghvac.com/training.
Design and Service Tools
As part of our commitment to innovation, LG has developed innovative ways to enhance the service technician’s experience during routine maintenance or service with these tools: · LG Monitoring View (LGMV) Software and Mobile App both connect to LG Multi V Systems to allow
technicians to troubleshoot accurately and evaluate equipment performance by interfacing directly with the unit. The software provides an accurate picture of an operating system without the need to check system temperatures manually, access the refrigerant circuit for system pressures, or perform time-consuming resistance and voltage tests. This service tool provides the most effective troubleshooting method for LG Multi V equipment. · LATS HVAC is a system design tool for LG Air Conditioning Technologies systems, including Multi V, Multi F, Single Zone, and ERV. Also available to assist with the system design process are an AutoCAD plug-in (LATS CAD) and an Autodesk Revit plug-in (LATS Revit). Using drag and drop functionality, design your LG system quickly and let the system calculate critical details like output capacity and additional refrigerant and confirm pipe lengths are within allowable tolerances. Reach out to your local LG representative for help designing your next system with LATS to save time.
4

VRF INDOOR UNITS
For use with:
5 LG Air Conditioning Technologies

TABLE OF CONTENTS

INDOOR UNITS

Wall Mounted Unit

11

Ceiling Mounted Cassette 14

Ceiling Suspended

17

Vertical AHU

18

Ceiling Concealed Ducted 19

Floor Standing Unit

22

INDOOR OPTIONS AND ACCESSORIES

Hydro Kit

23

Split Rooftop Unit (RTU) 25

Accessories

26

6

OUTDOOR UNIT

LINEUP

OUTDOOR UNIT Lineup

System Type

Multi VTM 5
LGRED
Powerful Heat Technology
RELIABLE TO EXTREME DEGREES

· Heat Pump and Heat Recovery in the same chassis
· Available in 208230V and 460V

Air Source

Multi VTM S

· Heat Pump and Heat Recovery in the same chassis
· Single-Phase Power

Multi VTM S
LGRED
Powerful Heat Technology
RELIABLE TO EXTREME DEGREES

· Heat Pump and Heat Recovery in the same chassis
· Single-Phase Power

Multi VTM Water IV 208-230V

· Heat Pump or Heat Recovery Systems

Frames

2

3

4

5

6

8 10

12

·· ·· ·· ··

· ·· ·· ·· ·· ·· ·· ·· ·· ··

Water Source

Multi VTM Water IV
460V

· Heat Pump or Heat Recovery Systems

·· ·· ·· ··

· · = Heat Pump = Heat Recovery Unit : Tons

14

16 18 20 22 24 26 28 30 32 34 36 38 40 42 48

·· ·· ·· ··

·· ·· ·· ·· ·· ·· ··

·· ·· ·· ··

·· ·· ·· ··
·· ·· ·· ··

·· ·· ·· ··

7 LG Air Conditioning Technologies

8

INDOOR UNIT Lineup

Chassis

Art CoolTM

Gallery Mirror

Standard

Wall Mounted

1-Way

2-Way Ceiling Cassette
4-Way (2’x2′)

4-Way (3’x3′)

CeilingSuspended Ceiling Mounted

Low Static

Ceiling Concealed Duct

Mid Static

High Static

Vertical AHU Vertical / Horizontal

With Case Floor Standing
Without Case

9 LG Air Conditioning Technologies

5

7

9

12

15

18

··

····· ·

····· ·

···

·

·

····· ·

···· ·

·

···· ·

···· ·

···· ·

·

·

···· ·

···· ·

LG indoor units offer a wide range of styles and features to fit all of your cooling and heating needs. With cassettes that mount flush to the ceiling, ducted units that are completely concealed in the ceiling, and LG’s award- winning Art Cool Gallery and mirror-finished, wall-mounted units that fit into any décor, the Multi V system offers unparalleled aesthetic design and indoor units to fit into multiple applications.

Unit : kBtu/h

24

28

30

36

42

48

54

76

96

·

·

··

·

·

··

···

·

·

·

·

··

····

··

···

··

·

·····

·

·

10

LINEUP

ININDDOOOORRUUNNITIT

ART COOLTM GALLERY

Specifications

Chassis

Capacity

Cooling Heating

Power Input

Cooling Heating

Power Supply

Dimensions (W × H × D)

Body

Weight

Body

Sound Pressure (H / M / L)

Air Flow Rate, Standard Mode (H / M / L)

Unit
Btu/h Btu/h Watts Watts V , Hz , Ø inches
lbs dBA CFM

093SF SF
9,600 10,900
35 35 208/230, 60, 1 23-5/8 x 23-5/8 x 5-3/4 33 38 / 32 / 27 286 / 22 / 148

Digital Airflow Control

The airflow can be controlled to ensure maximum comfort and convenience.

Normal

Jet Cool

ARNU***SFA4
123SF SF
12,300 13,600
35 35 208/230, 60, 1 23-5/8 x 23-5/8 x 5-3/4 33 44 / 38 / 32 328 / 272 / 212
Sleep Mode

Customizable Picture Frame
With LG’s revolutionary Art Cool Gallery, you can change the look of your air conditioner to whatever you want, whenever you want.
Accessories
Description Wi-Fi Module
Note : 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org 2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.
11 LG Air Conditioning Technologies

Model PWFMDD200

ART COOLTM MIRROR

ARNU*****R4

Specifications Chassis Capacity
Power Input Power Supply

Unit
Cooling Btu/h Heating Btu/h Cooling Watts Heating Watts
V , Hz , Ø

053SJ SJ
5,500 6,100
11 11 208/230, 60, 1

073SJ SJ
7,500 8,500
21 12 208/230, 60, 1

093SJ SJ
9,600 10,900
21 13 208/230, 60, 1

123SJ SJ
12,300 13,600
21 15 208/230, 60, 1

153SJ SJ
15,400 17,100
21 23 208/230, 60, 1

183SK SK
19,100 21,500
39.5 32 208/230, 60, 1

243SK SK
24,200 25,600
39.5 39 208/230, 60, 1

Dimensions (W × H × D)

Body

inches

32-5/16 x 12-1/8 x 32-5/16 x 12-1/8 x 32-5/16 x 12-1/8 x 32-5/16 x 12-1/8 x 32-5/16 x 12-1/8 x 39-5/16 x 13-9/16

7-9/16

7-9/16

7-9/16

7-9/16

7-9/16

x 3-3/8

39-5/16 x 13-9/16 x 3-3/8

Weight

Net

lbs

Shipping lbs

Sound Pressure (H / M / L)

dBA

Air Flow Rate, Standard Mode (H / M / L)

CFM

20.2 27.7 30 / 29 / 28 240 / 230 / 208

20.2 27.7 32 / 30 / 28 254 / 240 / 208

20.2 27.7 34 / 32 / 28 275 / 254 / 208

20.2 27.7 37 / 34 / 30 300 / 254 / 240

20.2 27.7 42 / 39 / 32 371 / 336 / 240

29.5 38.8 43 / 39 / 34 494 / 424 / 371

29.5 38.8 46 / 41 / 34 537 / 449 / 371

Accessories
Description Auxiliary Heat Kit Wi-Fi Module

Model PRARS1 PWFMDD200

Note: 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org 2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.
12

INDOOR UNITS

STANDARD WALL MOUNTED

ARNU*****A4

Specifications

Unit

053SJ

073SJ

093SJ

123SJ

153SJ

183SK

Chassis

SJ

SJ

SJ

SJ

SJ

SK

Capacity

Cooling Heating

Btu/h Btu/h

5,500 6,100

7,500 8,500

9,600 10,900

12,300 13,600

15,400 17,100

19,100 21,500

Power Input

Cooling Watts

11

21

21

21

21

39.5

Heating Watts

11

12

13

15

23

32

Power Supply

V , Hz , Ø 208/230, 60, 1 208/230, 60, 1 208/230, 60, 1 208/230, 60, 1 208/230, 60, 1 208/230, 60, 1

Dimensions (W × H × D)

Body

inches

32-3/16 x 12-7/16 x 32-3/16 x 12-7/16 x 32-3/16 x 12-7/16 x 32-3/16 x 12-7/16 x 32-3/16 x 12-7/16 x 38-1/8 x 13-15/16

7-7/16

7-7/16

7-7/16

7-7/16

7-7/16

x 8-1/4

Weight

Net

lbs

18.5

18.5

18.5

18.5

18.5

26.9

Shipping lbs

24.9

24.9

24.9

24.9

24.9

35.3

Sound Pressure (H / M / L)

dBA

30 / 29 / 28

32 / 30 / 28

34 / 32 / 28

37 / 34 / 30

42 / 39 / 32

43 / 39 / 34

Air Flow Rate, Standard Mode (H / M / L)

CFM 240 / 230 / 208 254 / 240 / 208 275 / 254 / 208 300 / 254 / 240 371 / 336 / 240 494 / 424 / 371

243SK SK
24,200 25,600
39.5 39 208/230, 60, 1 38-1/8 x 13-15/16 x 8-1/4 26.9 35.3 46 / 41 / 34 537 / 449 / 371

Specifications Chassis Capacity
Power Input Power Supply Dimensions (W × H × D) Weight Sound Pressure (H / M / L) Air Flow Rate, Standard Mode (H / M / L)
Accessories
Description Auxiliary Heat Kit Wi-Fi Module

Cooling Heating Cooling Heating
Body Net Shipping

Unit
Btu/h Btu/h Watts Watts V , Hz , Ø inches
lbs lbs dBA CFM

Note : 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org
2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.

13 LG Air Conditioning Technologies

303SV SV
30,000 32,000
67 67 208/230, 60, 1 46-27/32 x 10-7/16 x 13-5/8 37 48 49 / 44 / 42 812 / 706 / 600
Model PRARS1 PWFMDD200

ARNU*****A4
363SV SV
35,500 37,000
104 104 208/230, 60, 1 46-27/32 x 10-7/16 x 13-5/8 37 48 52 / 47 / 43 918 / 812 / 671

1-WAY CASSETTE AND 2-WAY CASSETTE

ARNU TUD4 ARNU TTD4

ARNU***TSA4

Specifications

Unit

073TU

Chassis

TU

Capacity

Cooling Heating

Btu/h Btu/h

7,500 8,500

Power Input

Cooling Watts

40

Heating Watts

40

Power Supply Dimensions (W × H × D) Unit Weight

Body Grille Net

V , Hz , Ø inches inches
lbs

208/230, 60, 1 33-7/8 x 17-3/4
x 6-11/16 43-5/16 x 19-3/4
x 1-3/8
33

Shipping lbs

40

Grille Weight

Net

lbs

10

Shipping lbs

10

Sound Pressure (H / M / L)

dBA

32 / 29 / 25

Air Flow Rate, Standard Mode (H / M / L)

CFM 290 / 258 / 226

Grille

PT-UUC1

093TU TU
9,600 10,900
40
40 208/230, 60, 1 33-7/8 x 17-3/4
x 6-11/16 43-5/16 x 19-3/4
x 1-3/8 33
40 10 10 35 / 34 / 32 325 / 304 / 290 PT-UUC1

123TU

183TT

243TT

183TS

243TS

TU

TT

TT

TS

TS

12,300

19,100

24,200

19,100

24,200

13,600

21,500

24,200

21,500

27,300

40

70

70

19

31

40

70

70

19

31

208/230, 60, 1
33-7/8 x 17-3/4 x 6-11/16
43-5/16 x 19-3/4 x 1-3/8

208/230, 60, 1
46-1/2 x 17-3/4 x 6-7/8
55-15/16 x 19-3/4 x 1-3/8

208/230, 60, 1
46-1/2 x 17-3/4 x 6-7/8
55-15/16 x 19-3/4 x 1-3/8

208/230, 60, 1
32-11/16 x 23-5/8 x 8-7/8
43-5/16 x 27-3/16 x 1-1/8

208/230, 60, 1
32-11/16 x 23-5/8 x 8-7/8
43-5/16 x 27-3/16 x 1-1/8

33

42

42

39.9

39.9

40

13

13

10.3

10.3

10

13

13

10.3

10.3

10

20

20

14.3

14.3

38 / 35 / 32

40 / 37 / 35

43 / 40 / 36

35 / 33 / 31

48 / 45 / 40

353 / 325 / 290 470 / 427 / 385 515 / 470 / 406 417 / 381 / 348 512 / 438 / 364

PT-UUC1

PT-UTC

PT-UTC

PT-USC

PT-USC

Accessories
Description Grille for 1-Way Cassette, TU Chassis Grille for 1-Way Cassette, TT Chassis Grille for 2-Way Cassette, TS Chassis Auxiliary Heat Kit Wi-Fi Module

Model PT-UUC1 PT-UTC PT-USC PRARH1 PWFMDD200

Note: 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org 2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.
14

INDOOR UNITS

INDOOR UNITS

4-WAY CASSETTE (2×2)

4-WAY CASSETTE (3×3)

ARNU*****D4

Specifications Chassis Capacity
Power Input Power Supply

Unit

Cooling Heating Cooling Heating

Btu/h Btu/h Watts Watts V , Hz , Ø

053TR TR
5,500 6,100
30 30 208/230, 60, 1

073TR TR
7,500 8,500
30 30 208/230, 60, 1

093TR TR
9,600 10,900
30 30 208/230, 60, 1

123TR TR
12,300 13,600
30 30 208/230, 60, 1

153TQ TQ
15,400 17,100
30 30 208/230, 60, 1

183TQ TQ
19,100 21,500
30 30 208/230, 60, 1

Dimensions (W × H × D)

Body Grille

inches inches

22-7/16 x 22-7/16 22-7/16 x 22-7/16 22-7/16 x 22-7/16 22-7/16 x 22-7/16 x 22-7/16 x 22-7/16 22-7/16 x 22-7/16

x 8-7/16

x 8-7/16

x 8-7/16

8-7/16

x 10-3/32

x 10-3/32

24-7/16 x 24-7/16 x 24-7/16 x 24-7/16 x 24-7/16 x 24-7/16 x 24-7/16 x 24-7/16 x 24-7/16 x 24-7/16 x 24-7/16 x 24-7/16 x

1-5/16

1-5/16

1-5/16

1-5/16

1-5/16

1-5/16

Unit Weight

Net

lbs

Shipping lbs

Grille Weight

Net

lbs

Shipping lbs

Sound Pressure (H / M / L)

dBA

Air Flow Rate, Standard Mode (H / M / L)

CFM

Grille

29 34 7 11 29 / 27 / 26 265 / 247 / 212 PT-QCHW0

29 34 7 11 29 / 27 / 26 265 / 247 / 212 PT-QCHW0

32 38 7 11 30 / 29 / 27 283 / 265 / 251 PT-QCHW0

32 38 7 11 32 / 30 / 27 307 / 283 / 247 PT-QCHW0

35 40 7 11 36 / 34 / 32 388 / 353 / 328 PT-QCHW0

35 40 7 11 37 / 35 / 34 396 / 388 / 353 PT-QCHW0

Accessories
Description Ventilation Kit Grille (True 2 x2) Auxiliary Heat Kit Wi-Fi Module

Model PTVK430 PT-QCHW0 PRARH1 PWFMDD200

Note : 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org 2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.
15 LG Air Conditioning Technologies

Specifications Chassis Capacity
Power Input Power Supply

Cooling Heating Cooling Heating

Dimensions (W × H × D)

Body Grille

Unit Weight

Net Shipping

Grille Weight

Net Shipping

Sound Pressure (H / M / L)

Air Flow Rate, Standard Mode (H / M / L)

Grille

Specifications Chassis Capacity
Power Input Power Supply

Cooling Heating Cooling Heating

Dimensions (W × H × D)

Body Grille

Unit Weight

Net Shipping

Grille Weight

Net Shipping

Sound Pressure (H / M / L)

Air Flow Rate, Standard Mode (H / M / L)

Grille

Accessories

Model Description Grille Auto Elevation Grille Ventilation Kit Cassette Cover Auxiliary Heat Kit Wi-Fi Module

Unit
Btu/h Btu/h Watts Watts V , Hz , Ø
inches
inches
lbs lbs lbs lbs dBA CFM
Unit
Btu/h Btu/h Watts Watts V , Hz , Ø
inches
inches
lbs lbs lbs lbs dBA CFM

073TNA TN
7,500 8,500 144 144 208/230, 60, 1 33-1/16 x 33-1/16 x 9-11/16 37-3/8 x 37-3/8 x 1-7/16
53.6 66.1 13 20 29 / 26 / 24 459 / 424 / 388 PT-UMC1
243TNA TN
24,200 27,300
144 144 208/230, 60, 1 33-1/16 x 33-1/16 x 9-11/16 37-3/8 x 37-3/8 x 1-7/16
53.6 66.1 13 20 40 / 38 / 35 742 / 671 / 600 PT-UMC1

093TNA TN
9,600 10,900
144 144 208/230, 60, 1 33-1/16 x 33-1/16 x 9-11/16 37-3/8 x 37-3/8 x 1-7/16
53.6 66.1 13 20 29 / 26 / 24 477 / 424 / 388 PT-UMC1
283TMA TM
28,000 31,500
144 144 208/230, 60, 1 33-1/16 x 33-1/16 x 11-5/16 37-3/8 x 37-3/8 x 1-7/16
58.4 70.5 13 20 41 / 39 / 35 812 / 741 / 635 PT-UMC1

123TNA TN
12,300 13,600
144 144 208/230, 60, 1 33-1/16 x 33-1/16 x 9-11/16 37-3/8 x 37-3/8 x 1-7/16
53.6 66.1 13 20 31 / 29 / 26 494 / 459 / 424 PT-UMC1
363TMA TM
36,200 40,600
144 144 208/230, 60, 1 33-1/16 x 33-1/16 x 11-5/16 37-3/8 x 37-3/8 x 1-7/16
58.4 70.5 13 20 44 / 41 / 37 918 / 812 / 706 PT-UMC1

ARNU**4

153TNA TN
15,400 17,100
144 144 208/230, 60, 1 33-1/16 x 33-1/16 x 9-11/16
37-3/8 x 37-3/8 x 1-7/16
53.6 66.1 13 20 32 / 29 / 26 530 / 459 / 424 PT-UMC1

183TNA TN
19,100 21,500
144 144 208/230, 60, 1 33-1/16 x 33-1/16 x 9-11/16
37-3/8 x 37-3/8 x 1-7/16
53.6 66.1 13 20 34 / 30 / 26 565 / 530 / 424 PT-UMC1

423TMC TM
42,000 43,800
144 144 208/230, 60, 1 33-1/16 x 33-1/16 x 11-5/16
37-3/8 x 37-3/8 x 1-7/16
59 69 13 20 45 / 41 / 38 1,059 / 918 / 812 PT-UMC1

483TMC TM
48,100 51,200
144 144 208/230, 60, 1 33-1/16 x 33-1/16 x 11-5/16
37-3/8 x 37-3/8 x 1-7/16
59 69 13 20 46 / 42 / 40 1,130 / 953 / 883 P-UMC1

Model ARNU423TMC4 PT-UMC1 PTEGM0 PTVK410 and PTVK420 or PTVK430 PTDCM PRARH1 PWFMDD200

Note: 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org 2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.
16

CEILING SUSPENDED

ARNU*****A4

Specifications Chassis Capacity
Power Input Power Supply Dimensions (W × H × D) Unit Weight Sound Pressure (H / M / L) Air Flow Rate (H / M / L)

Unit

Cooling Heating Cooling Heating
Body Net Shipping

Btu/h Btu/h Watts Watts V , Hz , Ø inches
lbs lbs dBA CFM

ARNU183V1A4 V1
19,100 21,500
130 130 208/230, 60, 1 47-1/4 × 9-1/4 × 27-3/16 64
79 36 / 34 / 33 477 / 441 / 424

ARNU243V1A4 V1
24,200 27,300
130 130 208/230, 60, 1 47-1/4 × 9-1/4 × 27-3/16 64 79 37 / 35 / 33 495 / 459 / 424

ARNU363V2A4 V2
36,200 40,600
184 184 208/230, 60, 1 63 × 9-1/4 × 27-5/32 82 100 45 / 44 / 41 954 / 848 / 706

ARNU483V2A4 V2
48,100 51,200
184 184 208/230, 60, 1 63 × 9-1/4 × 27-5/32 82 100 47 / 44 / 41 1,024 / 848 / 706

Accessories
Description Ventilation Kit Auxiliary Heat Kit Wi-Fi Module

Model PTVK430 PRARH1 PWFMDD200

Note : 1. Power Input is rated at high speed. 2. Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations
(40 CFR Part 82, Subpart F) under section 608 of CAA. 3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply with applicable and national code. 5. If the temperature rise above 86 °F or the humidity rise above RH 80%, “the dew-protective kit should be equipped or use additional insulation to the indoor unit body.”
17 LG Air Conditioning Technologies

VERTICAL AHU

ARNU*****A4

Specifications

Unit

123NJ

183NJ

243NJ

303NJ

363NJ

423NK

483NK

543NK

Chassis Capacity

Cooling Heating

Btu/h Btu/h

NJ 12,000 13,500

NJ 18,000 20,000

NJ 24,000 27,000

NJ 30,000 34,000

NJ 36,000 40,000

NK 42,000 46,000

NK 48,000 54,000

NK 54,000 60,000

Power Input Power Supply

Watts

228

228

228

228

228

366

366

366

V , Hz , Ø 208/230, 60, 1 208/230, 60, 1 208/230, 60, 1 208/230, 60, 1 208/230, 60, 1 208/230, 60, 1 208/230, 60, 1 208/230, 60, 1

Dimensions (W × H × D) Body

inches

18 x 21-1/4 x 48-11/16

18 x 21-1/4 x 48-11/16

18 x 21-1/4 x 48-11/16

18 x 21-1/4 x 48-11/16

18 x 21-1/4 x 48-11/16

25 x 21-1/4 x 55-3/16

25 x 21-1/4 x 55-3/16

25 x 21-1/4 x 55-3/16

Weight

Net

lbs

117

117

117

117

121

165

165

165

Shipping lbs

140

140

140

140

144

181

181

181

Sound Pressure (H / M / L)

dBA

42 / 41 / 39

42 / 42 / 41

43 / 42 / 41

44 / 43 / 42

45 / 44 / 43

46 / 44 / 41

49/47/41

50/49/47

Air Flow Rate, Standard Mode (H / M / L) CFM 530 / 480 / 380 580 / 530 / 480 710 / 640 / 480 880 / 800 / 630 990 / 880 / 800 1,250/1,100/1,000 1,400/1,260/1,000 1,475/1,400/1,260

External Static Pressure, Standard Mode Air Flow Rate, High Mode (H / M / L)

in wg

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

CFM 530 / 480 / 380 580 / 530 / 480 710 / 640 / 480 880 / 800 / 630 990 / 880 / 800 1,250/1,100/1,000 1,400/1,260/1,000 1,475/1,400/1,260

External Static Pressure, High Mode ESP Range (Min/Max)

in wg in wg

0.5 0 .1 – 1.0

0.5 0.1 – 1.0

0.5 0.1 – 1.0

0.5 0.1 – 1.0

0.5 0.1 – 1.0

0.5 0.1 – 1.0

0.5 0.1 – 1.0

0.5 0.1 – 1.0

Accessories
Description 3 kW Heat Kit 5 kW Heat Kit 8 kW Heat Kit 10 kW Heat Kit 15 kW Heat Kit 20 kW Heat Kit Auxiliary Heat Kit

Model ANEH033B1 ANEH053B1 ANEH083B2 ANEH103B2 ANEH153B2 ANEH203B2
PRARH1

Note : 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org 2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.
18

INDOOR UNITS

LOW STATIC DUCTED

ARNU*****G4

Specifications

Unit

073L1

093L1

123L2

153L2

183L2

243L3

Chassis

L1

L1

L2

L2

L2

L3

Capacity

Cooling Heating

Btu/h Btu/h

7,500 8,500

9,600 10,900

12,300 13,600

15,400 17,100

19,100 21,500

24,000 27,300

Power Input

Watts

40

40

85

85

85

115

Power Supply

V , Hz , Ø 208/230, 60, 1

208/230, 60, 1

208/230, 60, 1

208/230, 60, 1

208/230, 60, 1

208/230, 60, 1

Dimensions (W × H × D)

Body

inches 30-1/2×27-9/16×7-1/2 30-1/2×27-9/16×7-1/2 38-3/8×27-9/16×7-1/2 38-3/8×27-9/16×7-1/2 38-3/8×27-9/16×7-1/2 46-1/4×27-9/16×7-1/2

Weight

Net

lbs

38.6

38.6

50.7

50.7

50.7

59.5

Shipping lbs

47.4

47.4

60.6

60.6

60.6

68.3

Sound Pressure (H / M / L)

dBA

27 / 26 / 23

30 / 26 / 23

31 / 29 / 26

34 / 31 / 29

36 / 34 / 31

39 / 35 / 32

Air Flow Rate, Standard Mode (H / M / L)

CFM

270 / 230 / 200

320 / 250 / 200

360 / 310 / 250

450 / 360 / 310

530 / 450 / 360

710 / 570 / 430

External Static Pressure, Standard Mode

in wg

0

0

0

0

0

0

Air Flow Rate, High Mode (H / M / L)

CFM

270 / 230 / 200

320 / 250 / 200

360 / 310 / 250

450 / 360 / 310

530 / 450 / 360

710 / 570 / 430

External Static Pressure, High Mode

in wg

0.1

0.1

0.1

0.1

0.1

0.1

ESP Range (Min/Max)

in wg

0 – 0.19

0 – 0.19

0 – 0.19

0 – 0.19

0 – 0.19

0 – 0.19

Accessories
Description Auxiliary Heat Kit Wi-Fi Module

Model PRARH1 PWFMDD200

Note : 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org 2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.
19 LG Air Conditioning Technologies

MID STATIC DUCTED

ARNU*****A4 (M1, M2 & M3 Models)

Specifications

Chassis

Capacity

Cooling Heating

Power Input

Power Supply

Dimensions (W × H × D)

Body

Weight

Net Shipping

Sound Pressure @ 0.24″ ESP (H / M / L)

Air Flow Rate, Standard Mode (H / M / L)

External Static Pressure, Standard Mode Air Flow Rate, High Mode (H / M / L)

External Static Pressure, High Mode ESP Range (Min/Max)

Unit
Btu/h Btu/h Watts V , Hz , Ø inches
lbs lbs dBA CFM in wg CFM in wg in wg

073M1 M1 7,500
8,500 190 208/230, 60, 1 35-1/2 x 10-19/32 x 28-11/32 56.0
67.0 27 / 24 / 23 372 / 315 / 257
0.10 361 / 279 / 211
0.24 0.10 – 0.59

93M1 M1 9,600
10,900 190
208/230, 60, 1 35-1/2 x 10-19/32 x
28-11/32 56.0
67.0 27 / 25 / 23 385 / 329 / 272
0.10 376 / 296 / 229
0.24 0.10 – 0.59

123M1 M1
12,300 13,600
190 208/230, 60, 1 35-1/2 x 10-19/32 x
28-11/32 56.0
67.0 28 / 25 / 23 399 / 344 / 286
0.10 392 / 328 / 262
0.24 0.10 – 0.59

153M1 M1
15,400 17,100
190 208/230, 60, 1 35-1/2 x 10-19/32 x
28-11/32 56.0
67.0 30 / 27 / 24 593 / 413 / 344
0.10 570 / 392 / 328
0.24 0.10 – 0.59

183M1 M1
19,100 21,500
190 208/230, 60, 1 35-1/2 x 10-19/32 x
28-11/32 56.0
67.0 32 / 29 / 27 606 / 493 / 413
0.10 638 / 556 / 392
0.24 0.10 – 0.59

243M1 M1
24,200
27,300 190
208/230, 60, 1 35-1/2 x 10-19/32 x
28-11/32 59.0
70.0 33 / 30 / 28 641 / 592 / 493
0.10 703 / 638 / 556
0.24 0.10 – 0.59

Specifications Chassis Capacity Power Input

Cooling Heating

Power Supply

Dimensions (W × H × D)

Body

Weight

Net Shipping

Sound Pressure @ 0.24″ ESP (H / M / L)

Air Flow Rate, Standard Mode (H / M / L)

External Static Pressure, Standard Mode Air Flow Rate High Mode (H / M / L)

External Static Pressure, High Mode ESP Range (Min/Max)

Unit

283M2

363M2

423M2

483M3

543M3

Btu/h Btu/h

M2 28,000 31,500

M2 36,200 40,600

M2 42,000 47,000

M3 48,100 54,200

M3 54,000 61,400

Watts

430

430

430

650

650

V , Hz , Ø

208/230, 60, 1

208/230, 60, 1

208/230, 60, 1

208/230, 60, 1

208/230, 60, 1

inches 49-9/32×10-11/16×27-1/4 49-9/32×10-11/16×27-1/4 49-9/32×10-11/16×27-1/4 49-1/4 x14-3/16×27-3/16 49-1/4 x14-3/16×27-3/16

lbs lbs dBA CFM in wg CFM

86.2 99.2 40 / 39 / 37 892 / 770 / 645 0.20 845 / 676 / 528

86.2 99.2 42 / 40 / 38 1,021 / 844 / 695 0.20 1,031 / 845 / 676

86.2 99.2 44 / 43 / 40 1,262 / 1,087 / 917 0.20 1,260 / 1,076 / 888

96.1 110 42 / 39 / 37 1,457 / 1,189 / 952 0.19 1,482 / 1,191 / 918

96.1 110 44 / 43 / 42 1,720/1,558/1,424 0.19 1,744/1,614/1,482

in wg in wg

0.24 0.16 – 0.71

0.24 0.16 – 0.71

0.24 0.16 – 0.71

0.23 0.16 – 0.79

0.23 0.16 – 0.79

Accessories

Description
Auxiliary Heat Kit High-Capacity Filter Box for M1 MSD Chassis High-Capacity Filter Box for M2 HSD / MSD Chassis High-Capacity Filter Box for M3 HSD / MSD Chassis
Wi-Fi Module
Note: 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org 2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.

Model PRARH1 ZFBXM101A ZFBXM201A ZFBXM301A
PWFMDD200

20

INDOOR UNITS

HIGH STATIC DUCTED

ARNU*****A4 (M2 & M3 Models)

ARNU*****A4 (B8 Models)

Specifications Chassis
Capacity
Power Input Power Supply

Cooling Heating

Dimensions (W × H × D)

Body

Weight

Net Shipping

Sound Pressure @ 0.24″ ESP (H / M / L)

Air Flow Rate, Standard Mode (H / M / L)

External Static Pressure, Standard Mode Air Flow Rate, High Mode (H / M / L)

External Static Pressure, High Mode

ESP Range (Min/Max)

Unit
Btu/h Btu/h Watts V , Hz , Ø

073M2 M2 7,500 8,500 430
208/230, 60, 1

093M2 M2 9,600
10,900 430
208/230, 60, 1

123M2 M2
12,300 13,600
430 208/230, 60, 1

153M2 M2
15,400 17,100
430 208/230, 60, 1

183M2 M2
19,100 21,500
430 208/230, 60, 1

243M2 M2
24,200 27,300
430 208/230, 60, 1

inches

49-9/32 x 10-11/16 x 49-9/32 x 10-11/16 x 49-9/32 x 10-11/16 x 49-9/32 x 10-11/16 x 49-9/32 x 10-11/16 x 49-9/32 x 10-11/16 x

27-1/4

27-1/4

27-1/4

27-1/4

27-1/4

27-1/4

lbs lbs dBA CFM in wg CFM in wg in wg

82.9 95.5 38 / 37 / 36 477 / 399 / 327 0.20 468 / 381 / 294 0.24 0.16 – 0.71

82.9 95.5 38 / 38 / 36 477 / 399 / 327 0.20 468 / 381 / 294 0.24 0.16 – 0.71

82.9 95.5 38 / 38 / 36 520 / 435 / 363 0.20 512 / 425 / 337 0.24 0.16 – 0.71

82.9 95.5 38 / 38 / 36 520 / 435 / 363 0.20 512 / 425 / 337 0.24 0.16 – 0.71

82.9 95.5 39 / 38 / 37 640 / 520 / 435 0.20 673 / 512 / 425 0.24 0.16 – 0.71

82.9 95.5 39 / 38 / 37 640 / 520 / 435 0.20 673 / 512 / 425 0.24 0.16 – 0.71

Specifications Chassis
Capacity
Power Input Power Supply

Cooling Heating

Dimensions (W × H × D)

Body

Weight

Net Shipping

Sound Pressure @ 0.24″ ESP (H / M / L)

Air Flow Rate, Standard Mode (H / M / L)

External Static Pressure, Standard Mode Air Flow Rate, High Mode (H / M / L)

External Static Pressure, High Mode

ESP Range (Min/Max)

MAodcelcessories

Unit
Btu/h Btu/h Watts V , Hz , Ø
inches
lbs lbs dBA CFM in wg CFM in wg in wg

283M3

363B8

423B8

483B8

763B8

M3 28,000 31,500

B8 36,200 40,600

B8 42,000 43,800

B8 48,100 51,200

B8 76,400 86,000

650 208/230, 60, 1

800 208/230, 60, 1

800 208/230, 60, 1

800 208/230, 60, 1

800 208/230, 60, 1

49-1/4 x 14-3/16 x 27-3/16

61-1/2 x 27-1/8 x 18-1/8

61-1/2 x 27-1/8 x 18-1/8

61-1/2 x 27-1/8 x 18-1/8

61-1/2 x 27-1/8 x 18-1/8

96.1 110 40 / 39 / 37 1,235 / 1,060 / 915 0.19 1,250 / 1,017 / 837

192 222 46 / 45 / 42 1,896/1,748/1,550 0.35 1,730/1,317/1,066

192 222 47 / 46 / 43 1,963/1,786/1,589 0.35 1,914/1,458/1,123

192 222 47 / 46 / 44 2,048/1,846/1,670 0.35 2,019/1,518/1,200

192 222 50 / 48 / 48 2,050/1,766/1,766 0.59 2,260/1,766/1,766

0.23 0.16 – 0.79

0.70 0.35 – 0.98

0.70 0.35 – 0.98

0.7 0.35 – 0.98

0.87 0.47 – 0.98

963B8 B8
95,900 107,500
800 208/230, 60, 1 61-1/2 x 27-1/8
x 18-1/8 192 222
52 / 50 / 50 2,684/2,260/2,260
0.59 2,542/2,260/2,260
0.87 0.47 – 0.98

Description
Auxiliary Heat Kit
High-Capacity Filter Box for B8 HSD Chassis
High-Capacity Filter Box for M1 MSD Chassis High-Capacity Filter Box for M2 HSD / MSD Chassis High-Capacity Filter Box for M3 HSD / MSD Chassis
Wi-Fi Module
Note: 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org 2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.

Model PRARH1 ZFBXB801A ZFBXM101A ZFBXM201A ZFBXM301A
PWFMDD200

21 LG Air Conditioning Technologies

FLOOR STANDING UNIT

-A : Floor-Standing with case -U : Floor-Standing without case ARNU**4

Specifications

Unit

Chassis

Capacity

Cooling Heating

Btu/h Btu/h

Power Input

Watts

Power Supply

V , Hz , Ø

Dimensions (W × H × D)

Body

inches

Weight

Net

lbs

Shipping lbs

Sound Pressure (H / M / L)

dBA

Air Flow Rate, High Mode (H / M / L)

CFM

External Static Pressure, High Mode

in wg

073CEA CE
7,500 8,500
85 208/230, 60, 1
42 x 25 x 8 59.5 68.3
35 / 33 / 31 300 / 265 / 229
0

093CEA CE
9,600 10,900
85 2208/230, 60, 1
42 x 25 x 8 59.5 68.3
36 / 34 / 32 335 / 300 / 265
0

123CEA CE
12,300 13,600
85 208/230, 60, 1
42 x 25 x 8 59.5 68.3
37 / 35 / 33 371 / 335 / 300
0

153CEA CE
15,400 17,100
85 208/230, 60, 1
42 x 25 x 8 59.5 68.3
38 / 37 / 35 406 / 353 / 335
0

183CFA CF
19,100 21,500
115 208/230, 60, 1
53 x 25 x 8 75 86
40 / 37 / 34 565 / 494 / 424
0

243CFA CF
24,200 27,300
115 208/230, 60, 1
53 x 25 x 8 75 86
43 / 40 / 37 635 / 565 / 494
0

Specifications

Unit

Chassis

Capacity

Cooling Heating

Btu/h Btu/h

Power Input

Watts

Power Supply

V , Hz , Ø

Dimensions (W × H × D)

Body

inches

Weight

Net

lbs

Shipping lbs

Sound Pressure (H / M / L)

dBA

Air Flow Rate, High Mode (H / M / L)

CFM

ESP Range (Min/Max)

in wg

073CEU CE
7,500 8,500
85 208/230, 60, 1 38-1/2 x 25-3/16 x 8
46.3 56.2 35 / 33 / 31 300 / 265 / 229 0 – 0.2

093CEU CE
9,600 10,900
85 208/230, 60, 1 38-1/2 x 25-3/16 x 8
46.3 56.2 36 / 34 / 32 335 / 300 / 265 0 – 0.2

123CEU CE
12,300 13,600
85 208/230, 60, 1 38-1/2 x 25-3/16 x 8
46.3 56.2 37 / 35 / 33 371 / 335 / 300 0 – 0.2

153CEU

183CFU

243CFU

CE

CF

CF

15,400

19,100

24,200

17,100

21,500

27,300

85

115

115

208/230, 60, 1

208/230, 60, 1

208/230, 60, 1

38-1/2 x 25-3/16 x 8 49-7/16×25-3/16×7-1/2 49-7/16×25-3/16×7-1/2

46.3

58.4

58.4

56.2

68.3

68.3

38 / 37 / 35

40 / 37 / 34

43 / 40 / 37

406 / 353 / 335

565 / 494 / 424

635 / 565 / 494

0 – 0.2

0 – 0.24

0 – 0.24

Accessories
Description Auxiliary Heat Kit Wi-Fi Module

Model PRARH1 PWFMDD200

Note: 1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org 2. Max. power input is rated at maximum setting value. 3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. Due to our commitment to continued innovation, some specifications may be changed without notification.
22

INDOOR UNITS

HYDRO KIT

Cooling Mode Performance Heating Mode Performance
Unit Data
Heat Exchanger
Piping Electrical Data

Specifications Rated Capacity1 Entering Water Temp Range Leaving Water Temp Range Indoor Air Temp Setpoint Range Rated Capacity1 Entering Water Temp Range Leaving Water Temp Range Indoor Air Temp Setpoint Range Hot Water Tank Setpoint Range Refrigerant Type Refrigerant Control Sound Pressure2 Net Unit Weight Shipping Weight Dimensions (W × H × D) Heat Rejected to Equipment Room Oil Type Material/Type Rated Water Flow Rated Pressure Drop3 Range of Flow Waterside Volume Waterside Design Pressure Liquid Line (OD) Vapor Line (OD) Condensate Line (ID) Water Inlet/Outlet (ID) MCA MOP Rated Amps Power Supply Power Input (Cooling/Heating)

Unit Btu/h
°F °F °F Btu/h °F °F °F °F
dB(A) lbs lbs
Btu/h
GPM ft-wg GPM US Gallons psig inches inches inches inches
A A A V / Hz / Ø Watts

ARNH423K2A4 42,100 50~96 41~77 64~86 47,200 59~113 68~122 64~86 86~122 R410A EEV 26 67 79
20-1/2 x 24-13/16 x 15-7/8 Negligible –
316 Stainless/Brazed Plate 10.4 13.7
5.3-10.4 0.31 640
3/8 Braze 5/8 Braze
1-MPT 1-MPT
0.1 15 0.08 208-230/60/1 0.01/0.01

ARNH423K2A4 ARNH963K2A4
ARNH963K2A4 95,900 50~96 41~77 64~86 170,500 59~113 68~122 64~86 86~122 R410A EEV 26 77 89
20-1/2 x 24-13/16 x 15-7/8 Negligible –
316 Stainless/Brazed Plate 24.3 23.1 8-24.3 0.58 640
3/8 Braze 7/8 Braze
1-MPT 1-MPT
0.1 15 0.08 208-230/60/1 0.01/0.01

1. All capacities are net, with a combination ratio between 95 and100%. 2. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 3. Water only (no antifreeze). The combination ratio range for dedicated use (all Hydro Kit units) is 50% – 100%. The combination ratio range for mixed use (Hydro Kit mixed with indoor units) is 50% – 130%.
23 LG Air Conditioning Technologies

HYDRO KIT
How Hydro Kit Works
The Hydro Kit system uses a refrigerant-to-water heat exchanger to produce chilled or heated water. The Hydro Kit can be used to preheat domestic water stored in an indirect storage tank, snow melt, in-floor or other radiant heating systems. Alternatively, the K4 Hydro Kit can supply chilled or heated water for use with two-pipe fan coils. The LG Hydro Kit may be used with LG Multi V 5, Multi V Water IV, and Multi V S systems.
Features & Benefits
n Provides hot water and floor heating with less energy consumption than a boiler
n No exhaust or exhaust piping required n Compact and easy to install n LG Central controller and BMS interface compatible n Flexible design options

Applications

n Universities n Offices n Schools n Hospitals

n Hotels n Retail stores n Restaurants n Multi-use facilities

24

SPLIT ROOFTOP UNIT (RTU)

ARNU363DDA4 ARNU483DDA4 ARNU603DDA4 ARNU723DDA4

Cooling Mode Performance Heating Mode Performance Entering Mixed Air
Unit Data
Fan
Piping Filtration Electrical Data

Specifications Rated Capacity Max Power Input1 L/M/H Power Input at Factory Default Rated Capacity Max Power Input1 L/M/H Power Input at Factory Default Cooling Max. Heating Min. Refrigerant Type3 Refrigerant Control Sound Pressure4 (H / M / L) Net Unit Weight Shipping Weight Dimensions (W × H × D) Communication Cable5 Type Motor Motor/Drive Airflow Rate (H / M / L) Standaard Mode External Static Pressure Standaard Mode External Static Pressure Liquid Line (OD) High Pressure Vapor Line (OD) Low Pressure Vapor Line (OD) Condensate Line (ID) Outdoor MCA MOP Rated Amps Power Supply Power Input (Cooling/Heating)

Unit Btu/h
W W Btu/h W W °F WB °F DB2
dB(A) lbs lbs
No. x AWG
CFM in. wg in. wg inches inches inches inches inches
A A A V / Hz / Ø Watts

ARNU363DDA4 36,000 640
110 / 130 / 150 38,000 640
110 / 130 / 150 76 59
R410A EEV
66 / 63 / 60 430 470
76.7″ x 38.9″ x 46.7″ 2×18
3D Plug 1
1200 / 1000 / 800 1.7
0.2 – 1.7 3/8 Braze 1/2 Braze 5/8 Braze
1, Plain 2 Merv8
7.4 15 5.9 208-230/60/1 640/640

ARNU483DDA4

ARNU603DDA4

48,000

60,000

700 120 / 150 / 260
52,000 700
120 / 150 / 260

760 130 / 250 / 330
71,000 760
130 / 250 / 330

76

76

59 R410A

59 R410A

EEV 67 / 64 / 61

EEV 68 / 65 / 62

430

430

470 76.7″ x 38.9″ x 46.7″
2×18

470 76.7″ x 38.9″ x 46.7″
2×18

3D Plug

3D Plug

1

1

1ECM (Electronically Commutated Motor) / Direct

1400 / 1200 / 950

1700 / 1300 / 1000

1.6

1.5

0.2- 1.6

0.2 – 1.5

3/8 Braze

3/8 Braze

1/2 Braze 5/8 Braze
1, Plain

5/8 Braze 3/4 Braze
1, Plain

2 Merv8 7.8 15

2 Merv8 8.1 15

6.1 208-230/60/1
700/700

6.4 208-230/60/1
760/760

ARNU723DDA4 72,000 770
140 / 260 / 350 80,000 770
140 / 260 / 350 76 59
R410A EEV
69 / 66 / 63 430 470
76.7″ x 38.9″ x 46.7″ 2×18
3D Plug 1
1800 / 1400 / 1100 1.4
0.2 – 1.4 3/8 Braze 5/8 Braze 3/4 Braze
1, Plain 2 Merv8
8.3 15 6.7 208-230/60/1 770/770

EEV: Electronic Expansion Valve Power wiring is field supplied and must comply with the applicable local and national codes. This unit comes with a dry nitrogen charge. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
1. Max power input is rated at maximum setting value. 2. Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019. 3. Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA. 4. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745. 5. All communication cable to be minimum 18 AWG, 2-conductor, twisted, stranded, shielded and must comply with applicable local and national codes. Ensure the communication cable is properly
grounded at the main outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.

25 LG Air Conditioning Technologies

ACCESSORIES
Indoor Accessories

PTEGM0

PTDCM

PT-UMC1

PT-QCHW0

PT-USC

PT-UUC1 PT-UTC

PTVK410

PTVK420

PTVK430

PTPK*0

PRARH1 PRARS1

HSD Filter Box

ANEHB1 ANEHB2

PWFMDD200

Unit Type

Category Cassette Auto Elevation Kit Cassette Cover

Cassette Grille
Ceiling Cassettes Cassette Ventilation

Plasma Kit

HSD Filter Box

Mid and High Static Ducted

Air Cleaner Air Cleaner Media

Return Air Plenum

Ceiling & Wall-Mounted

Auxiliary Heat Kit Vertical AHU

Wi-Fi Module

Model PTEGM0 PTDCM PT-UTC PT-UUC1 PT-USC PT-QCHW0 PT-UMC1 PTVK410 PTVK420 PTVK430 PTPKU0 PTPKT0 PTPKM0 PTPKQ0 ZFBXM101A ZFBXM201A ZFBXM301A ZFBXB801A ZFBXD201A ZFBXD402A ZFLT1301A ZFLT1302A ZPLMV201A ZPLMV402A
PRARH1
PRARS1 ANEH033B1 ANEH053B1 ANEH083B2 ANEH103B2 ANEH153B2 ANEH203B2 PWFMDD200
PWYREW000

Description

Used with

Auto Elevation Grille Kit

TN, TM

Decorative Cover for 4-Way Ceiling Cassette 1-Way Ceiling Cassette Grille

TN, TM TT

1-Way Ceiling Cassette Grille

TU

2-Way Ceiling Cassette Grille

TS

4-Way Ceiling Cassette Grille, True 2×2

TQ, TR

4-Way Ceiling Cassette Grille

TN, TM

Ventilation Air Intake Spacer for 4-Way Ceiling Cassette (Requires PTVK420)

TN, TM

6″ Ø Ventilation Air Connection Flange for 4-Way Ceiling Cassette

TN, TM

3″ Ø Ventilation Air Connection Flange for 4-Way Ceiling Cassette

TQ, TR, TN, TM

1-Way Ceiling Cassette Plasma Kit

TU

1-Way Ceiling Cassette Plasma Kit

TT

4-Way Ceiling Cassette Plasma Kit (3×3)

TN, TM

4-Way Ceiling Cassette Plasma Kit (2×2) High-Capacity Filter Box

TQ, TR M1

High-Capacity Filter Box

M2

High-Capacity Filter Box

M3

High-Capacity Filter Box

B8

DYNAMIC V8-2VL Low-Profile Air Cleaner

M1/M2/M3/B8

DYNAMIC V8-4VL Standard-Profile Air Cleaner

M1/M2/M3/B8

Air Cleaner Media 4-Pack Air Cleaner Media 24-Pack
2VL Return Air Plenum

M1/M2/M3/B8 M1/M2/M3/B8 M1/M2/M3/B8

4VL Return Air Plenum

M1/M2/M3/B8

Auxiliary Heat Kit for Gen 4 Cassettes, Low Static, Mid Static, and High Static Units

B8, L1, L2, L3, M1, M2, M3, NJ, NK, TM, TN, TQ, TR, TS, TT, TU

Auxiliary Heat Kit for Wall-Mounted Units

SJ, SK

3 kW Electric Heat Kit

NJ, NK

5 kW Electric Heat Kit

NJ, NK

8 kW Electric Heat Kit 10 kW Electric Heat Kit 15 kW Electric Heat Kit

NJ, NK NJ (183, 243, 303, 363), NK
NJ (363), NK

20 kW Electric Heat Kit Connector to provide Wi-Fi signal for Control operation Optional 10 meter extension cable for PWFMDD200

NJ (363), NK
B8, CE, CF, L1, L2, L3, M1, M2, M3, NJ, NK, SF, SJ, SK, SV, TT, TU, TS, TM, TN, TQ, TR, V1, V2

26

NOTES:
27 LG Air Conditioning Technologies

UNIT NOMENCLATURE

ARN
Family

U 07 3 TN C 4

Type

IndoorUnit Electrical

Model

Nominal Ratings

Capacity

Feature Generation

Family

ARN Multi V Indoor Unit (Refrigerant R410A)

Type

U

DC Inverter Heat Pump

Indoor Unit

05

Nominal Capacity 07

09

12

15

18

24

28

5,000 Btu/h 7,000 Btu/h 9,000 Btu/h 12,000 Btu/h 15,000 Btu/h 18,000 Btu/h 24,000 Btu/h 28,000 Btu/h

30

30,000 Btu/h

36

36,000 Btu/h

42

42,000 Btu/h

48

48,000 Btu/h

54

54,000 Btu/h

76

76,000 Btu/h

96

96,000 Btu/h

Electrical Ratings 3

208­230V/60Hz/1Ph

Model

B8 Ducted (High Static)

CE Floor Standing (Small Frame)

CF Floor Standing (Large Frame)

L1 Ducted (Low Static)

L2 Ducted (Low Static)

L3 Ducted (Low Static)

M1 Ducted (Mid Static)

M2 Ducted (Mid/High Static)

M3 Ducted (Mid/High Static)

NJ

Vertical/Horizontal Air Handling Unit

NK Vertical/HorizontalAirHandlingUnit

SF

Wall Mounted / Art CoolTM Gallery

SJ

Wall Mounted / Art CoolTM Mirror

SK

Wall Mounted / Art CoolTM Mirror

SV Wall Mounted

TT

1-Way Ceiling Cassette

TU 1-Way Ceiling Cassette

TS 2-Way Ceiling Cassette

TM 4-Way Ceiling Cassette

TN 4-Way Ceiling Cassette

TQ 4-Way Ceiling Cassette

TR 4-Way Ceiling Cassette

V1 Ceiling Suspended

V2 Ceiling Suspended

Feature

A, C, L, R, D U G

Standard Uncased Low Static

Generation

2

Second

4

Fourth

A

Second, Revision A

28

UNIT NOMENCLATURE

LG Electronics USA, Inc.
Air Conditioning Technologies 4300 North Point Parkway, Alpharetta, GA 30022
www.lghvac.com
©2021 LG Electronics. All rights reserved.

Distributed by: Document Number: PC_MultiV_Indoor_Units_05_21

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals