Ditec 0DT866 52E Control Panel
Product Information
The product is a control panel for Ditec doors with K22INV and K10INV motors, equipped with limit switches group. It comes with an installation manual in French and English and optional accessories such as the Safety Confort and Safety Top.
The control panel has several features such as Smart Reset, Sector Reset, Smart Plus, Sector Plus, Traffic C, and alarms. It also has input connectors for N.F. STOP, N.O Ouverture, N.O Fermeture, N.F Position de fermeture, N.F Position d’ouverture, N.F Position de ralentissement, and Activation de la fermeture avec porte de fonctionner uniquement avec un homme mort. It also has output connectors for 24 V = / 0,5 A LAMP, 230 V~ Flash clignotant (FML), Signal non intermittent, -F, +F, 200 V = / 0,2 A o, 24 V = / 0,5 A, U, W, and V.
The control panel also has trimmers and switches for adjusting the speed of opening and closing the door.
Product Usage Instructions
- Refer to the installation manual for proper installation of the control panel.
- Connect the input connectors for N.F. STOP, N.O Ouverture, N.O Fermeture, N.F Position de fermeture, N.F Position d’ouverture, N.F Position de ralentissement, and Activation de la fermeture avec porte de fonctionner uniquement avec un homme mort.
- Connect the output connectors for 24 V = / 0,5 A LAMP, 230 V~ Flash clignotant (FML), Signal non intermittent, -F, +F, 200 V = / 0,2 A o, 24 V = / 0,5 A, U, W, and V.
- Adjust the speed of opening and closing the door using the trimmers P1 and P2.
- Adjust the maximum opening time using the trimmer P3.
- Adjust the maximum closing time using the trimmer P4.
- Adjust the delay time for the safety device using the trimmer P5.
- Use the switches DIP 1 and DIP 2 for future usage.
- Refer to the manual for programming options such as Smart Reset, Sector Reset, Smart Plus, Sector Plus, Traffic C, and alarms.
GENERAL SAFETY PRECAUTIONS
This installation manual is intended for professionally competent personnel
only.
Installation, electrical connections and adjustments must be performed in
accordance with Good Working Methods and in compliance with the current
standards.
Read the instructions carefully before installing the product. Incorrect
installation could be dangerous. The packaging materials (plastic,
polystyrene, etc.) should not be discarded in the environment or left within
reach of children, as they are a potential source of danger.
Before installing the product, make sure it is in perfect condition. Do not
install the product in explosive areas and atmospheres: the presence of
inflammable gas or fumes represents a serious safety hazard. Before installing
the door, make all the structural modifications necessary in order to create
safety clearance and to guard or isolate all the crushing, shearing, trapping
and general danger areas.
Make sure the existing structure is up to standard in terms of strength and
stability. The safety devices (photocells, safety edges, emergency stops,
etc.) must be installed taking into account current laws and directives, Good
Working Methods, the installation environment, the system operating logic and
the forces developed by the motorised door or gate.
The safety devices must protect any crushing, shearing, trapping and general
hazardous areas of the door. Display the signs required by law to identify
hazardous areas.
Each installation must clearly indicate the door identification data.
Before connecting the power supply, make sure the plate data correspond to
those of the mains power supply. An omnipolar disconnection switch with a
contact opening distance of at least 3mm must be fitted on the mains supply.
Check there is an adequate residual current circuit breaker and overcurrent
cutout upstream of the electrical system. Connect the door to an efficient
earthing system that complies with current safety standards. The door
manufacturer declines all responsibility if components not compatible with
safety and good functioning are installed, or modifications of any kind are
made that have not been specifically authorised by the manufacturer. Use only
original Ditec spare parts when repairing or replacing products. The installer
must supply all information concerning the automatic, manual and emergency
operation of the motorised door or gate, and must provide the user with the
operating instructions.
O Optional accessory
C Comfort Safety
T Top Safety
All rights reserved
The data given have been compiled and checked with the greatest care. We
cannot, however, assume any responsibility for any errors, omissions or
approximations due to technical or graphical requirements.
52E 1. 52E CONTROL PANEL (INVERTER) – Connections
CONTROL PANEL CONNECTORS
M2 | Safety device / Commands |
---|---|
M3 | Position signal |
M4 | Interlock |
M4A | Back |
M5 | Motor / brake motor |
J4 | Brake resistance |
--- | --- |
OPEN | Auxiliary panel card |
SAFETY | Auxiliary safety card |
52E 2. ADJUSTMENTS AND SETTINGS
Trimmer | Description |
---|---|
P1 | **** |
Opening speed
P2| ****
Closing speed
P3
| ****
Deceleration during opening
P4
| ****
Adjustment of deceleration during closure
P5
| ****
Adjustment of display contrast.
Dip-switches | Description | OFF | ON |
---|---|---|---|
DIP 1 | Future use | – | – |
DIP 2 | Access to advanced menu | Disabled | Enabled |
DIP 3 | Trimmer enabling | Disabled | Enabled |
DIP 4
| Counter
TOT: Number of operations
SVC: Number of operations left until service
| ****
Disabled
| ****
Enabled
DIP 5| Access to service menu| Disabled| Enabled
DIP 6| Door operating data display
(F working, I Bus, I peak, V Bus)
| Disabled| Enabled
DIP 7| Future use| –| –
DIP 8| Cyclic operation menu| Disabled| Enabled
LED| On
---|---
DL2| Closing position
DL3| Deceleration
DL6| Partial opening
DL7| Opening position
DL15| Autostart
Buttons| Description
---|---
S2| USED FOR PROGRAMMING
S3| NOT USED
S4| NOT USED
S5| USED FOR PROGRAMMING
| Operating mode Standard| Programming Operating
---|---|---
Button| LED| Button
Starts the opening operation.| – The green LED on indicates the presence of
the 24 V= power supply.| Menu scrolling
Starts the partial opening operation.| | Confirm
Starts and stops the STOP operation.
| – The red LED on indicates that the STOP has been activated.
– The flashing red LED indicates that the safety devices have
been activated.
– The quick flashing red LED indicates that the service threshold
has been reached
|
Starts the closing operation.| | Menu scrolling
SMART RESET
SECTOR RESET
SMART PLUS
SECTOR PLUS
TRAFFIC C
LIMIT SWITCH ADJUSTMENT
- Set the deceleration ramps at zero (P3 – P4)
- Set the limit switch (C) on the gearmotor so that the door stops about 200/300mm from its closure point.
- Set the opening limit switch (A) at the opening point.
- Set the deceleration limit switch (B) so it is triggered at about ¾ of the opening stroke.
- Set the opening and closure speeds using trimmers (P1) and (P2) respectively.
- Set the trimmers of the deceleration ramps – (P3) for opening and (P4) for closure – to ensure the door stops at its actual “open” and “closed” positions.
TROUBLESHOOTING
Display message | Problem | Check |
---|---|---|
Current limit exceeded | Requested motor torque exceeds available torque. | • |
Reduce opening speed.
• Check power supply.
• Check power supply wiring.
Insert brake resistance| Voltage on BUS exceeds
threshold
| • For Sector Reset doors, connect the brake resistance and set the item on the advanced menu to “YES”.
• Switch off the control panel, wait 3 minutes and reconnect the
power supply.
• If the error reoccurs, check that the voltage on the BUS is lower
than 360 V.
Max. BUS voltage| BUS voltage exceeds
threshold
| • Switch off the control panel, wait 3 minutes and reconnect the
power supply.
• Check the control panel power supply voltage.
Stand by Encoder| Installation of a new control/ replacement control already programmed previously
Absolute Encoder not connected.
| To reset the control panel follow the procedure:
• DIP2 in ON
• push STOP (the control panel goes in the “programmin menu” showing the data already set)
• scroll the menù till the step “COMMAND MODE” and set LIMIT SWITCHES
• DIP2 in OFF
PROGRAMMING
INSTALLATION MENU
When the control panel is switched on, after showing the messages DITEC and
microprocessor and card FW VERSION, the device automatically enters the
installation menu and displays the message SELECT LANGUAGE.
Confirm with
Remove cables from PIN 3, 4, 20 during programming
PROGRAMMING COMPLETED
The door is now programmed and operating with the set default speed values.
With the door MOVING, the voltage and current values will be displayed on the
BUS.
ADVANCED MENU
The advanced menu allows you to modify the position of the limit switches
which have previously been set and modify the set default parameters.
To access the Advanced Menu:
- STOP the door
- Set DIP 2 to ON
“LIM. SWITCH CAL.”, the first item in the advanced menu, will appear on the display.
- ONCE PROGRAMMING HAS ENDED, SET DIP2 TO OFF
- Remove cables from PIN 3, 4, 20 during programming
ONCE PROGRAMMING HAS ENDED, SET DIP2 TO OFF
Timed opening menu
With door in STOP position and DIP 8 ON you enter the menu CYCLIC MODE. By
activating this mode it is possible to set a timed opening at regular time
intervals. Once the mode is set put DIP 8 OFF.
When CYCLIC MODE is active, the display shows every 2 sec:
TOT cycle – count down to next open/OPENING TIME
Service menu (password required)
To access the Service menu:
- STOP the door
- Set DIP5 to ON
- Enter the PW: button sequence OPEN- OPEN- CLOSE- PARTIAL OPENING
Remove cables from PIN 3, 4, 20 during programming
1| MIN BRAKING VOLT. Default 340Vdc| Threshold for partial intervention of
braking resistance
---|---|---
2| MAX BRAKING VOLT. Default 380Vdc| Threshold for total intervention of
braking resistance
3| OVERCURRENT LIMIT
Default 10A
| If the current on the BUS exceeds the set threshold, the door opens at
half the speed to reduce absorption.
4| RAMP SLOPE DURING OPENING| Changes the slope of the deceleration ramp when
opening. Default 15. (If the value is increased, the ramp distance is
reduced).
5| BATTERY LEVEL| Visualizes the encoder battery charge level from 0% to 100%
6| ALARM LIST| The last 50 alarms are displayed: Overcurrent; bus voltage
exceeds limit, Intervention of brake resistance, inverter overtemperature,
faulty motor driver (encoder). To exit, press partial opening
ONCE PROGRAMMING HAS ENDED, SET DIP5 TO OFF
ALARMS
MESSAGE SITUATION NOTES
Ditec| door closed waiting for command|
---|---|---
Opening of VBUS IBUS| door opening|
Door open – automatic closing time| Door open|
Closing of VBUS IBUS| door closing|
Input 40 closed; input 8 open| intervention of photocell| When door is moving
input 40 open; input 8 closed| Primary safety device intervention
(SLEC / SAFETY EDGE)
| When door is moving
Limit switches open| Intervention of safety microswitch on manual opening
device / intervention of thermal protection on motor / opening (A) and closure
(C) limit switches simultaneously active.
|
Opening safety device activated| photocell engaged when door is closed and
door does not open| Message that only appears if the “safety in open” function
is set to YES on the advanced menu (step 7).
Door stopped| stop command activated|
Stand by encoder| New control panel power on / replacing control panel power
on
Absolute Encoder not connected.
| Control panel already programmed to work with motor having absolute encoder. To reset see troubleshooting chapter.
INTERLOCK