fantech 463913 ATMO Series Fresh Air Appliance Instruction Manual
- June 4, 2024
- fantech
Table of Contents
- PARTS IN THE BOX
- PLEASE READ AND SAVE THESE INSTRUCTIONS
- DETERMINING YOUR AIRFLOW REQUIREMENT
- ASHRAE method
- INSTALLATION EXAMPLES
- EXTERIOR DUCTING INSTALLATION
- INTERIOR DUCTING INSTALLATION
- FAA INSTALLATION
- WALL CONTROLS
- WIRING DIAGRAM – ATMO PRODUCT LINE
- FAA MAINTENANCE CHART
- SERVICE MANUAL
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
463913 ATMO Series Fresh Air Appliance
Instruction Manual
PARTS IN THE BOX
Fresh Air Appliance, 1 pc
Hanging Chain Kit, 1 pc
Hardware Kit, 1 pc
Drain Hose Kit, 1 pc
Operation and Installation Manual, 1 pc
Your ventilation system should be installed in conformance with the appropriate provincial requirements or, in the absence of such requirements, with the current edition of the National Building Code, and/or ASHRAE’s “Good Engineering Practices”.
United States
10048 Industrial Blvd., Lenexa, KS, 66215
Tel.: 800.747.1762 • Fax: 800.487.9915
Canada
50 Kanalflakt Way, Bouctouche, NB, E4S 3M5
Tel.: 800.565.3548 • Fax: 877.747.8116
Fantech reserves the right to modify, at any time and without notice, any or all of its product features, designs, components, and specifications to maintain its technological leadership position. Please visit our website www.fantech.net for more detailed technical information.
PLEASE READ AND SAVE THESE INSTRUCTIONS
Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler operating at higher static pressure. After installation, the compatibility of the two pieces of equipment must be confirmed by measuring the airflow of the Fresh Air Appliance using the balancing procedure found in this manual. It is always important to assess how the operation of any FAA may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.)
Products are designed and manufactured to provide reliable performance, but
they are not guaranteed to be 100% free of defects. Even reliable products
will experience occasional failures, and this possibility should be recognized
by the user. If these products are used in a life support ventilation system
where failure could result in loss or injury,
the user should provide adequate backup ventilation, supplementary natural
ventilation or failure alarm system, or acknowledge willingness to accept the
risk of such loss or injury.
Your ventilation system should be installed in accordance with the local building code that is in effect, in absence of such requirements, it is recommended to check with local authorities having jurisdiction in your area prior to installing this product.
DETERMINING YOUR AIRFLOW REQUIREMENT
1 CFM = 0.47 L/s
1 L/s = 2.13 CFM
Room Count Method
Room classification | Number of rooms | CFM (Us) | CFM Required |
---|---|---|---|
Master bedroom | x 10 Us (20 CFM) | = | |
Basement | yes or no | if yes add 10 Us (20 CFM) if no = 0 | = |
Bedrooms | x 5 Us (10 CFM) | = | |
Living room | x 5 Us (10 CFM) | = | |
Others | x 5 Us (10 CFM) | = | |
Kitchen | x 5 Us (10 CFM) | = | |
Bathroom | x 5 Us (10 CFM) | = | |
Laundry room | x 5 Us (10 CFM) | = | |
Utility room | x 5 Us (10 CFM) | = | |
Total Ventilation Requirements (add the last column ) | = |
ASHRAE method
Ventilation Air requirements
Floor area| –| Bedrooms.
Ft2| m2| CFM| 1
Us| 2
CFM| 1
Us| 31
CFM| Us| • 4′
CFM| Us| . 5.
CFM| Us
<500| <47| 30| 128| 38| 18| 45| 21| 53| 25| 60| 28
501-1000| 47-93| 45| 21| 53| 24| 60| 28| 68| 31| 75| 35
1001-1500| 94-139| 60| 28| 68| 31| 75| 35| 83| 38| 90| 42
1501-2000| 140-186| 75| 35| 83| 38| 90| 42| 98| 45| 105| 49
2001-2500| 187-232| 90| 42| 98| 45| 105| 49| 113| 52| 120| 56
2501-3000| 233-279| 105| 49| 113| 52| 120| 56| 128| 59| 135| 63
3001-3500| 280-325| 120| 56| 128| 59| 135| 63| 143| 66| 150| 70
3501-4000| 326-372| 135| 63| 143| 66| 150| 70| 158| 73| 165| 77
4001-4500| 373-418| 150| 70| 158| 73| 165| 77| 173| 80| 180| 84
4501-5000| 419-465| 165| 77| 173| 80| 180| 84| 188| 87| 195| 91
- ASHRAE 62.2-2016 Table 4.1, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings.
Bathroom: If the FAA is going to provide the required local exhaust ventilation for each bathroom with each a continuous 20 CFM (10 L/s), this ventilation rate can be considered as part of the whole-building ventilation rate.
INSTALLATION EXAMPLES
The way your heat/energy-recovery ventilator is installed can make a significant difference to the electrical energy you use. To minimize the electricity use of the heat/energy-recovery ventilator, a stand-alone fully ducted installation is recommended. If you choose a simplified installation that operates your furnace air handler for room-to-room ventilation, an electrically efficient furnace that has an electronically commutated (EC) variable speed blower motor will minimize your electrical energy consumption and operating cost.
Example only – duct configuration may differ depending on the model.
FULLY DEDICATED SYSTEM BEST FOR NEW CONSTRUCTION
- Stale air is drawn from key areas of the home requiring local exhaust (bathroom, kitchen, laundry room).
- Fresh air is distributed directly to habitable rooms in the house (bedrooms, living room)
- The FAA’s airflow must be balanced after installation using the procedure found in the section “AIRFLOW
FAA ducting for fully Dedicated System
- Ductwork layout may differ depending on model
- Unit air flow should be balanced while FAA is on “Normal” speed and the furnace blower is running.
Suggested installation for:
- Hydronic baseboard
- In-floor heating
- Electric baseboard
- Mini split heat pump
Benefits: Provides the best fresh air distribution in the house; lowest operation cost since the furnace/air handler unit is not needed.
DIRECT CONNECTION of the FRESH air to the living area to the RETURN PLENUM of the AIR HANDLER (Stale air drawn from key areas of the home)
PARTIALLY DEDICATED SYSTEM (BETTER)
- In order to provide proper distribution of fresh air, it is recommended that the furnace blower be set to run continuously or be interconnected with FAA. See furnace electrical connection on page 16.
- Stale air is drawn from key areas of the home (bathroom, kitchen, laundry room).
- Fresh air is supplied to the return air plenum of the furnace.
- Due to the difference in pressure between the FAA and the equipment, it is being connected to the FAA’s airflow must be balanced on-site, using the procedure found in the section “AIRFLOW BALANCING”
- In the case of a multi-zone system, please contact Fantech customer service prior to installing any installation type requiring the use of the furnace interlock”
FAA/Furnace ducting for Partially Dedicated System
- Ductwork layout may differ depending on model
Fantech fresh air applicance (FAA or HRV/ERV) that use a supply fan
shutdown for frost prevention do not include an outdoor air motorized damper.
If you are using a simplified installation, i.e. connecting the FAA supply air
duct to a furnace’s return air duct, the FAA must operate continuously. When
the FAA is turned off, no warm exhaust air will flow through the FAA but the
furnace’s fan will continue to draw in outdoor air directly into the furnace.
If it’s cold outside, cold air will be introduced, without re-heating,
directly into the furnace.
If the FAA is installed such that the homeowner may turn off the FAA during
the winter, we recommend installing a motorized damper between the FAA’s
supply air and the furnace’s return air duct that closes when the FAA is not
operating. See the wiring diagram (figure 1). You may also choose to use a
Fantech FAA that uses a recirculation defrost that incorporates an outdoor air
damper.
Suggested installation for:
- Central furnace (air handling unit or central air conditioners)
- When ducting fresh air to the living area is not possible or practical, i.e. expensive or when the central AHU will operate year-round.
Benefits: Conditions the fresh air prior to distributing it throughout the house
DIRECT CONNECTION of both the FAA SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN
SIMPLIFIED INSTALLATION (GOOD)
(RETURN/RETURN METHOD)
- The furnace blower must operate when ventilation from FAA is required. The furnace should be set to run continuously or interlocked with FAA. See furnace electrical connection on page 16.
- A minimum separation of 1m (39’’) is recommended between the two direct connections.
- In order to prevent exhausting any fresh air, the FAA’s exhaust air connection should be upstream of the FAA’s supply air connection when ducting to the furnace’s cold air return.
- Due to the difference in pressure between the FAA and the equipment, it is being connected to the FAA’s airflow must be balanced on-site, using the procedure found in the
section “AIRFLOW BALANCING”
- In the case of a multi-zone system, please contact Fantech customer service prior to installing any installation type requiring the use of the furnace interlock”
FAA/Furnace ducting for Simplified Installation – Option 1
Fantech fresh air appliances (FAA) that use a supply fan shutdown for frost
prevention do not include an outdoor air motorized damper. If you are
using a simplified installation, i.e. connecting the FAA supply air duct
to a furnace’s return air duct, the FAA must operate continuously. When
the FAA is turned off, no warm exhaust air will flow through the FAA but
the furnace’s fan will continue to draw in outdoor air directly into the
furnace.
If it’s **cold outside, cold air will be introduced, without re-heating,
directly into the furnace. If the FAA is installed such that the homeowner
may turn off the FAA during the winter, we recommend installing a motorized
damper between the FAA’s supply air and the furnace’s return air duct that
closes when the FAA is not operating. See the wiring diagram (figure 1).
You may also choose to use a Fantech FAA that uses a recirculation defrost
that incorporates an outdoor air damper.**
Suggested installation for:
- When the bathroom and kitchen already have a local exhaust system
- It May be suitable for retrofitting
Benefits: Least expensive installation type
EXTERIOR DUCTING INSTALLATION
REQUIRES A WEATHER HOOD WITH A BACKDRAFT DAMPER ON THE EXHAUST SIDE.
WEATHER HOOD LOCATION
- Decide where your intake and exhaust hoods will be located.
Locating the Intake Weather hood
- Should be located upstream (if there are prevailing winds) from the exhaust outlet.
- At a minimum distance of 900 mm (3′) away from dryer vents and furnace exhaust (medium or high-efficiency furnaces), driveways, oil fill pipes, gas meters, or garbage containers.
- At a minimum height of 460mm (18’’) above the ground, or above the level of expected snow accumulation.
- Ideally, keep weather hoods 1m (3′) from corners.
- Do not locate in the garage, attic, crawl space, or underneath the deck.
Locating the Exhaust Weather hood
- At least 460mm (18″) above ground or above the depth of expected snow accumulation
- Ideally, keep weatherhoods 1m (3′) from corners.
- Not near a gas meter, electric meter, or a walkway where fog or ice could create a hazard
- Do not locate in a garage, workshop, or other unheated space
INSTALLING THE DUCTING TO THE WEATHERHOODS
A well-designed and installed ducting system will allow the FAA to operate at
its maximum efficiency. The inner liner of the flexible insulated duct must be
secured to the sleeve of the weather hood (as close to the outside as
possible) and to the appropriate duct connection on the FAA. The insulation
should remain full and not be crushed. The outer liner, which acts as a vapor
barrier, must be completely sealed to the outer wall and the FAA using tape
and/or caulking. A good bead of high-quality caulking (preferably acoustical
sealant) will seal the inner flexible duct to both the FAA duct connection and
the weather hood prior to securing them.
To minimize airflow restriction, the flexible insulated duct that connects the
two outside weatherhoods to the FAA should be stretched tightly and be as
short as possible.
Twisting or folding the duct will severely restrict airflow.
See “Installation Diagram Examples” for installation examples.
STEPS FOR HOOD INSTALLATION:
-
Using the duct connection of the outside hood, outline the intake & exhaust holes to be cut. The holes should be slightly larger than the duct connection to allow for the thickness of the insulated flexible duct. Cut a hole for both the intake and exhaust hoods.
-
Pull the insulated flexible duct through the opening until it is well extended and straight. Slide the duct’s inner vinyl sleeve over the hood duct connection and secure it. Pull the insulation over the duct and pull the vapor barrier over the sleeve. Secure with appropriate tape or sealant.
-
Push the hood into the opening and then attach the hood to the outside wall with mounting screws. Repeat the installation procedure for both the supply and exhaust hoods.
-
Using a caulking gun, seal around both hoods to prevent any leaks.
INTERIOR DUCTING INSTALLATION
- To maximize airflow through the ductwork system, all ducts should be kept short and have as few bends or elbows as possible.
- 45º elbows are preferable to 90º.
- Use “Y“ ducts instead of “T” ducts whenever possible.
- All duct joints must be fastened with screws or duct sealant and wrapped with aluminum foil duct tape to prevent leakage.
- Galvanized ducting from the FAA to the living areas in the house is recommended whenever possible, although flexible ducting can be used in moderation when necessary.
- To avoid possible noise transfer through the ductwork system, a short length (approximately 300 mm, 12’’) of the nonmetallic flexible insulated duct should be connected between the FAA and the supply/exhaust ductwork system.
- The main supply and return line to/from the FAA must have the same diameter as the duct connection or larger.
- Branch lines to the individual rooms may be as small as 100 mm (4’’).
Installing ducting to FAA
Warning: Always fix and secure the 6″ collars with the screws supplied.
Avoiding this critical step the unit will accumulate condensation.
Tip to Installer: To ensure a better installation and to avoid an undesired
bend in the duct, align the duct with the collar before securing over the four
hooks.
The fresh air from outside and the Exhaust air to outside from the termination ducts to the FAA must be fully insulated of thermal insulation ducts to minimize heat loss and gain. All tapes, mastics, and nonmetallic clamps used for field installation of flexible ducts shall be listed and labeled to Standard UL 181B – Closure Systems for Use With Flexible Air Ducts and Air Connectors.
Air Connector A category of flexible duct not meeting the requirements of an Air Duct per UL 181 Standard (not tested for flame penetration, puncture, and impact) and having limitations on use, length and location as defined by NFPA 90A and 90B. Air Connectors are identified by a “round shape” listing label of the listing agent.
Air Duct A category of flexible duct tested and classified as to the Surface Burning Characteristics in accordance with the UL 181 Standard. Air Ducts are identified by a “rectangular shape” listing label of the listing agent.
To ensure quiet operation of ENERGY STAR qualified FAA, each product should be installed using sound attenuation techniques appropriate for the installation. Once insulated flex is attached to the collar, slide the collar in the keeper section, fixed the collar to the unit with four screws supplied in the installation kit to insure a proper seal.
Warning: To reduce air leakage in the final installation always seal the joint between all collars and keepers with aluminum tape or mastic.
Supply air grilles location
In homes without a forced air furnace, fresh air should be supplied to all
habitable rooms, including bedrooms and living areas. It should be supplied
from the high wall or ceiling locations. Grilles that diffuse the air
comfortably are recommended. In homes with a forced air furnace, you may want
to connect the FAA to the furnace ductwork (see information below).
Exhaust air grilles location
The stale air exhaust system is used to draw air from the points in the house
where the worst air quality problems occur. It is recommended that return air
ducts be installed in the bathroom, kitchen, and laundry room. Additional
return air ducts from strategic locations may be installed. The furnace return
duct may also be used to exhaust. In this method, the exhaust air is not
ducted back from bathrooms, kitchens, etc to the HRV with “dedicated lines”.
As per building codes and installation requirements for combustion
appliances:
Air return ducts, or openings for air return, should not be placed in enclosed
spaces containing combustion appliances that are subject to spillage.
FAA INSTALLATION
- Have a nearby power supply (120 volts, 60Hz)
- Choose a location that allows the possibility of mounting the unit to supporting beams.
- The unit should be level in order to allow proper condensate drainage
- To minimize noise, do not install the unit in the living area
- Ensure proper drainage
LOCATION
The FAA must be located in a conditioned space where it will be possible to
conveniently service the unit. Typically the FAA would be located in the
mechanical room or an area close to the outside wall where the weatherhoods
will be mounted. If a basement area is not convenient or does not exist, a
utility room may be used.
Attic installation must meet the following conditions:
- Attic temperature must be above freezing conditions at all times and for best performance should be 12°C (54 °F).
- The condensate drain (if included) must be installed so that the condensate drains and is protected from freezing.
- The attic is easily accessible for equipment maintenance and inspection.
Connecting appliances to the FAA is not recommended. These include:
- Clothes dryer
- Range top
- Stovetop fan
- Central vacuum system
- Bathroom exhaust fans unless they are specifically designed for this purpose
These appliances may cause lint, dust or grease to collect in the FAA, damaging the unit.
Connecting any of these types of appliances to the FAA will void your warranty.
Mounting- Chain mount
|
---|---
1 Place fastening hooks on the strapping board or the floor joists.| 2 Take a
flat screwdriver and slightly pull on the punched-out tab. Put chain link
under hook.
|
3 Hang the unit by slipping a link onto the hanging hooks, making sure the
unit is level.| 4 Install a spring on each chain. Hook the spring in the links
so a loop is created in the chain. The spring will then support the unit’s
weight and absorb vibrations.
The drain nipple is placed upside down in the unit to prevent it from being damaged during shipping or the installation of the unit.
If the outdoor air temperature is above 32°F (0°C) at the extract air (30%
RH/72°F, 30% RH /22°C), no drain line installation is required.
If this is the case keep the drain spout as shipped from the factory with
the cap.
The Switch on the electrical box is used to toggle between STANDBY, REDUCED
speed, and NORMAL speed modes.
Place the unit at NORMAL speed to perform the balancing.
Airflow balancing
Balancing must be completed using the Fantech ECO-Touch® Programmable Touch
Screen Wall Control
ENTERING BALANCING MODE
In the options menu during the initial 5-second countdown sequence, long press
on the “ECO” area for 5 seconds to enter basic balancing mode. The supply and
exhaust fans are adjusted on high speed only and the offsets are
proportionally applied to the medium and low speed automatically.
| STAGE 1
(ADJUST THE LEVEL OF THE EXHAUST FAN AT HIGH SPEED):
• In this step, balance the exhaust fan and measure airflow on the exhaust air
side
• Pressing on “up” or “down” will adjust the fan speed in increments of 1%.
• Once the desired exhaust airflow is reached, press on “next” and move on to
the next stage.|
---|---|---
| STAGE 2
(BALANCE SUPPLY FAN ONLY IN HIGH SPEED):
• In this step, balance the supply fan and measure airflow on the supply air
side
• Pressing on “up” or “down” will adjust the fan speed in increments of 1%.
• Once happy with the outcome, press on
“Next” to complete balancing
• The supply and exhaust offset values will be proportionally applied to low
and medium speeds as well.|
WALL CONTROLS
-
Please see instruction manuals for individual controls for proper wiring and set up of control systems.
- Ensure that unit is not plugged in when connecting the control
- Recirculation mode is only available with the Flex100H ES, HERO series, and the models with the “R” suffix at the end of the model number.
The wiring connectors can be removed for easier connection.
CENTRAL CONTROLS
These cannot be used with another central control
*Maintain polarity between control and FAA (+ → + ; – → -)
**ECO SERIES***
|
FEATURES
|
CONNECT TO
---|---|---
| • Our most complete, yet easy-to-use control system
• Sleek design with backlight touchscreen LCD
• ECO mode selects the best operating mode and speed for the season,
minimizing energy use associated with ventilation
• Set preferred indoor relative humidity range and ventilation mode for the
day and night conditions
• No battery to replace, all programmed settings are retained during power
outages
• Maintenance reminder indicator
• Error code messages reduce troubleshooting time|
| • Integrated VOC Sensor
• Our most complete, yet easy-to-use control system
• Sleek design with backlight touchscreen LCD
• ECO mode selects the best operating mode and speed for the season,
minimizing energy use associated with ventilation
• Set preferred indoor relative humidity range and ventilation mode for the
day and night conditions
• No battery to replace, all programmed settings are retained during power
outages
• Maintenance reminder indicator
• Error code messages reduce troubleshooting time
| • ECO mode selects the best operating mode and speed for the season,
minimizing energy use associated with ventilation
• Integrated VOC Sensor
• No battery to replace, all programmed settings are retained during power
outages
| • MODE button provides 3 modes of operations: Ventilation, Recirculation and
Standby
• User selected fan speed: Reduced, Medium, Normal and 20 minutes per hour
• AUTO setting allows the homeowner to activate the dehumidistat
• When the humidity exceeds the desired setpoint, the ventilation system
operates at normal speed
• Once the desired humidity level is achieved, your ventilation system resumes
to its previous mode of operation.|
| • Press the button once for continuous Reduced speed
• Press the button twice and the unit will cycle 20 minutes ON/ 40 minutes OFF
and repeat
• EDF1 – Press the button a third time and the system will run continuously on
HIGH speed
AUXILIARY CONTROL –These controls can be paired with central controls or
combined together.
*Maintain polarity between control and FAA (+ → + ; – → -)
RTS SERIES
| FEATURES|
CONNECTS TO
---|---|---
| • Wireless timer
• Can only be paired with the ECO-TouchIAQ
• 20/40/60 minute timer with LED light
• Boosts system to high speed with the touch of a button
• Up to 5 can be used in one system
• Use in bathroom, kitchen, laundry room| Connects wirelessly to the
| • 20- minute timer with LED light
• Boosts system to high speed with the touch of a button
• Up to 5 can be used in one system
• Use in bathroom, kitchen, laundry room|
| • 20/40/60 minute timer with LED light
• Boosts system to high speed with the touch of a button
• Up to 5 can be used in one system
• Use in bathroom, kitchen, laundry room
MDEH SERIES
| FEATURES|
CONNECT TO
---|---|---
| • Rotary dial Dehumidistat
• Multiple units can be used
• We recommend setting the relative humidity above 80% during the summer|
WIRING DIAGRAM – ATMO PRODUCT LINE
WIRING DIAGRAM TO FURNACE
FOR A FURNACE CONNECTION TO A COOLING SYSTEM:
On some newer furnaces and older thermostats, energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on the cooling system. If you identify the type of thermostat, you must use the“Alternate Furnace Interlock Wiring”
As per building codes and installation requirements for combustion
appliances:
Air return ducts, or openings for air return, should not be placed in enclosed
spaces containing combustion appliances that are subject to spillage.
Problem | Causes | Solutions |
---|---|---|
Air is too dry | Dehumidistat control is set too low | Increase the desired |
level of humidity. Change ventilation mode from continuous mode to standby.
FAA out of balance| Have contractor balance FAA airflows
Air is too humid| Dehumidistat control is set too high| Reduce the desired
level of humidity. Combine this with the use of continuous exchange mode.
Sudden change in temperature| Wait until the outside temperature stabilizes
(winter). Heating will also improve situation.
Storing too much wood for heating| Store a majority of your wood outside. Even
dried, a cord of wood contains more than 20 gallons of water.
The dryer vent exhaust is inside the home| Make sure the dryer vent is
exhausting outside.
Poor air circulation near windows| Open curtains or blinds.
FAA out of balance| Have contractor balance FAA airflows
Well sealed basement door is closed| Open the door or install a grill on the
door.
Failed damper system may be stuck in recirculation mode| Check defrost damper.
If the damper is always blocking incoming fresh air, have contractor verifies
the damper system.
Persistent condensation
on window
| Improper adjustment of dehumidistat control| Reduce the desired level of
humidity. Combine this step with the use of continuous exchange mode.
FAA out of balance| Have contractor balance FAA
Poor air circulation near windows| Open curtains or blinds.
Poor Air Flows| 1/4″ (6mm) mesh on the outside hoods is plugged| Clean
exterior hoods or vents
Filters plugged| Remove and clean the filter
Core obstructed| Remove and clean core
Indoor grilles closed or blocked| Check and open grilles
Inadequate power supply at the site| Have the electrician check the supply
voltage
Ductwork is restricting airflow| Check duct installation
Improper speed control setting| Increase the speed of the FAA (i.e. change
unit control from REDUCED to NORMAL
speed)
FAA airflow improperly balanced| Have contractor balance FAA airflows
Ducting has fallen down or been disconnected from FAA| Have the contractor
reconnect ducting
Supply air feels cold| Poor location of supply grilles, the airflow may
irritate the occupant| Locate the grilles high on the walls or under the
baseboards, and install ceiling-mounted diffusers or grilles so as not to
directly spill the supply air on the occupant (eg. Over a sofa)
Turn down the FAA supply speed. A small duct heater (1kw) could be used to temper the supply of air The placement of furniture or closed doors is restricting the movement of air in the home
The outdoor temperature is extremely cold| If supply air is ducted into the
furnace return, the furnace fan may need to run continuously to distribute
ventilation air comfortably
FAA and/or Ducts frosting up| FAA air flows are improperly balanced| Have the
HVAC contractor balance the FAA airflows
Malfunction of the FAA defrost system| Note: minimal frost build-up is
expected on the core before the unit initiates defrost cycle functions
Condensation or Ice Build Up in Insulated Duct to the utside| Incomplete
vapor barrier around the insulated duct| Tape and seal all joints
A hole or tear in the outer duct covering| Tape any holes or tears made in the
outer duct covering
Ensure that the vapor barrier is completely sealed.
LED is flashing| Everything is in good operations|
LED is not flashing| No Power is being transmitted to the Control Board| Make
sure the unit is plugged. The transformer may need replacing.
FAA MAINTENANCE CHART
Maintenance Required| Recommended Frequency| Date Maintenance
Performed
---|---|---
Check and Clean Filters| Every 3 months or if dirty| | | | | |
Check Heat Recovery Core| Every 6 months| | | | | |
Check Drain Pan and Lines| Every 3 months| | | | | |
Vacuum the Inside of the Unit| Annually| | | | | |
Clean and Un-block Outside
Hoods| Annually| | | | | |
Clean and Inspect Duct Work| Annually| | | | | |
General Servicing by a Qualified Contractor| Annually| | | | | |
| | | | | | |
| | | | | | |
* Schedule may be altered to meet your own needs. More frequent servicing may be required depending on the severity of your home’s indoor and outdoor environments.
Contractor | Telephone Number | Date Serviced |
---|---|---|
Limited Warranty
- The Heat recovery aluminum core has a Limited Lifetime Warranty.
- The warranty is limited to 5 years on parts and 7 years on fans from the date of purchase, including parts replaced during this time period. If there is no proof of purchase available, the date associated with the serial number will be used for the beginning of the warranty period.
- The fans found in all Fantech FAAs require no lubrication and are factory balanced to prevent vibration and promote silent operation.
- The limited warranty covers normal use. It does not apply to any defects, malfunctions, or failures as a result of improper installation, abuse, mishandling, misapplication, fortuitous occurrence, or any other circumstances outside Fantech’s control.
- Inappropriate installation or maintenance may result in the cancellation of the warranty.
- Any unauthorized work will result in the cancellation of the warranty.
- Fantech is not responsible for any incidental or consequential damages incurred in the use of the ventilation system.
- Fantech is not responsible for providing an authorized service center near the purchaser or in the general area.
- Fantech reserves the right to supply refurbished parts as replacements.
- Transportation, removal, and installation fees are the responsibility of the purchaser.
- The purchaser is responsible to adhere to all codes in effect in his area.
- This warranty is the exclusive and only warranty in effect relative to the ventilation system and all other warranties either expressed or implied are invalid.
SERVICE MANUAL
BOM #| Description| ATMO 150H
(463888)| ATMO 200H
(463889)| ATMO 150E
(463890)| ATMO 200H
(463891)
---|---|---|---|---|---
1| Motor| 428515| 428515| 428515| 428515
2| MERV3, Electrostatic Filter Kit| 463939| 463940| 463939| 463940
3| Heat or Energy Exchanger Cell| 463098| 463097| 463937| 463938
4| Capacitor 6uF| 411222| 411222| 411222| 411222
5| PC Board| 428252| 428252| 428252| 428252
6| Speed Switch| 410213| 410213| 410213| 410213
7| Transformer| 411963| 411963| 411963| 411963
8| Drain Fitting Kit| 463088| 463088| 463088| 463088
9| 6″ Dia. Plastic Collar| 463102| 463102| 463102| 463102
10| 6″ Dia. Plastic Keeper| 463103| 463103| 463103| 463103
11| Door Kit, ATMO Series| 463941| 463948| 463948| 463948
| Fuse, 8A, 250 VAC 3A8 3AG| 414736| 414736| 414736| 414736
| Temp Probe| 461102| 461102| 461102| 461102
| Kit, Chain| 404261| 404261| 404261| 404261
| Kit, Wall Bracket| 463942| 463942| 463942| 463942
| Wiring Diagram| 463927| 463927| 463927| 463927
| Installation Manual| 463913| 463913| 463913| 463913
| Filter MERV 8 (Pack of 2)| 463943| 463945| 463943| 463945
| Filter MERV 13 (Pack of 2)| 463944| 463946| 463944| 463946
| Kit, AUX. 24V Damper| 463947| 463947| 463947| 463947
NOTE
Fantech reserves the right to make technical changes.
For updated documentation please refer to
www.fantech.net.