Simplex 2099-9767 Intrinsically Safe Fire Alarm Stations Instruction Manual
- June 10, 2024
- Simplex
Table of Contents
2099-9767 Intrinsically Safe Fire Alarm Stations
Instruction Manual 2099-9767, -9799
Intrinsically-Safe Fire Alarm Stations
Installation and Operating Instructions
2099-9767 Intrinsically Safe Fire Alarm Stations
OPERATION OF SINGLE ACTION TYPE
2099-976
Pulling the handle down firmly to break the rod (visible below the handle)
causes the sounding of an alarm. The front of the station must be unlocked and
opened
to reset the handle before the fire alarm system can be returned to normal.
Replace the rod as shown in mounting drawing.
OPERATION OF GLASS DOUBLE ACTION TYPE
2099-9799
Breaking the glass with the hammer and pulling the handle down firmly to break the rod (visible below the handle) causes the sounding of an alarm. The front of the station must be unlocked and opened to reset the handle before the fire alarm system can be returned to normal. Replace the glass plate as shown in the replacement drawing and replace the rod as shown in the mounting drawing.
TESTING
Notify local authorities and operate station as in an actual alarm station. After testing, replace rod (and glass plate on glass double action units), reset the station, and restore the control panel.
APPLICATION
The National Fire Protection Association (NFPA), Bulletin number 72, gives
specilic minimum requirements on this subject. When manual station coverage
appears limited in any way, additional units should be installed. Stations
should be mounted with the bottom of the station not less than 3-112 ft.
(1.07M) or more than 5 feet (1.52M) from the floor. Usually stations are
mounted at the 4-112 ft. (1.4M) level.
Note: In order to make building and facilities accessible to, and usable
by, the physically handicapped, some specifications may require that the
station be installed not more than 3-l/2 ft. (1.07M) from the floor.
Stations should be located in the normal path of exit, and distributed in the
protected area so that they are unobstructed and readily accessible.
NOTE: (ON ALL 2099 STATIONS) Once installed, unlocking and opening the
front of station causes an alarm.
Stations should be provided on each floor to obtain a travel distance of not
more than 200 feet (60.96M) to the nearest station from any point in the
building. One station should be provided for each floor where the maximum
floor area is 10,000 square feet (929 sq. meters) or more. One station should
be provided on the first floor and on each succeeding alternate floor if the
areas to be protected are smaller than the limits as described above.
INSTALLATION
Important:
All equipment within the hazardous area must be installed in accordance with
NEC ANSVNFPA 70 and ANSI/ISA-RP 12.6-1987.
Refer to Control Drawing #841-848 for wiring information.
MOUNTING
For surface mounting, use a 2975-9178 red steel back box or a 29759022
aluminum back box. Do not substitute a box with a depth less than 2-3/16”
(5.55cm).
For semi-flush mounting, use a standard 4” (10.16cm) square outlet box with a
minimum depth of 2-118” (5.39cm) fitted with a 3/4” (1.9cm) deep single gang
switch cover set flush (DO NOT RECESS) or protruding l/l 6” (. 16cm) from the
wall surface.
REPLACEMENT OF GLASS PLATE ON GLASS DOUBLE ACTION TYPE 2099-9799
- Lift hammer.
- Fit glass under tab 2.
- Fit glass plate into notch of glass retainer 3.
- Push glass retainer into place.
- Gently lower hammer.
SEMI-FLUSH STATIONS
SURFACE STATIONS
ALTERNATE SEMI-FLUSH MTG. WIRING
Use no. 18 AWG minimum, No. 14 AWG maximum (TERMINAL SPEC.).
CAUTION
FOR SYSTEM SUPERVISION, DO NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE RUN
TO PROVIDE SUPERVISION OF CONNECTIONS.
STATION TYPE | TERMINAL CONNECTIONS |
---|
2099-9767
2099-9799|
© 1992 Simplex Time Recorder Co.
PER-21-506 (574-680) Ed 10 92
AlI specifications and other information shown wore current as of publication
and aro subject to change without notice.
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>