ZURN FSC Ductile Iron Y Type Strainer Owner’s Manual

June 13, 2024
ZURN

ZURN FSC Ductile Iron Y Type Strainer

Product Information

Model: FSC
Product Name: Ductile Iron Y Type Strainer
Application: The Zurn Wilkins Model FSC is designed for installation on water lines to protect downstream equipment from malfunction or premature failure due to build-up of sediment or debris.

Standards Compliance

  • MIL-S 16293F Type 2
  • Meets the requirements of NSF/ANSI 372

Materials

Main valve body Ductile Iron ASTM A536
Access cover Ductile Iron ASTM A536

Coatings
Fusion Epoxy Finish (Meets requirements of NSF/ANSI/CAN 61)

Screens **

**

Perforated Stainless Steel, 300 Series

Size Openings (inch dia.) Material Thickness Holes per sq(in) Open Area
2 1/2 0.045 0.020 (26 Ga.) 225 36%
3 0.045 0.020 (26 Ga.) 225 36%
4 1/16 0.020 (26 Ga.) 98 30%
6 1/16 0.020 (26 Ga.) 98 30%
8 1/8 0.020 (26 Ga.) 29 36%
10 1/8 0.032 (22 Ga.) 29 36%
12 1/8 0.025 (24 Ga.) 35 43%

Features

  • Sizes: 2 1/2, 3, 4, 6, 8, 10, 12
  • Pressure/temperature: ASME B16.42 Class 150
  • End connections: 1 1/4 NPT (2 1/2 and 3), 2 NPT (4, 6, 8, 10, 12)

Dimensions

Size (in) A (in) B (in) C (in) D* (in)
2 1/2 10 8 1/4 1 1/4 NPT 6
3 10 1/2 9 1/4 1 1/4 NPT 6
4 15 12 1/2 2 NPT 9
6 18 14 2 NPT 10
8 24 1/4 17 3/4 2 NPT 11
10 29 1/2 21 1/4 2 NPT 14
12 29 7/8 21 5/16 2 NPT 17
SIZE DIMENSIONS (approximate) WEIGHT
--- --- ---
A B C D*
in mm in mm in
2 1/2 65 10 254 8 1/4
3 80 10 1/2 267 9 1/4
4 100 15 381 12 1/2
6 150 18 457 14
8 200 24 1/4 616 17 3/4
10 250 29 1/2 749 21 1/4
12 300 29 7/8 759 21 5/16

*Vertical clearance for screen removal

Weight

Size (in) Weight (lbs.) Weight (kg)
2 1/2 35 16
3 45 20.5
4 61 27.5
6 165 75
8 239 108.5
10 394 178.5
12 489 222

Product Usage Instructions

Installation
This product is designed for installation on water lines. Follow the steps below for proper installation:

  1. Select the appropriate size of the Model FSC based on your requirements.
  2. Ensure that the pressure/temperature rating of the strainer matches your application.
  3. Connect the strainer to the water line using the specified endconnections (1 1/4 NPT for 2 1/2 and 3, 2 NPT for 4, 6, 8, 10, and 12).
  4. Make sure to provide the recommended vertical clearance (D*) for screen removal.
  5. If installing outdoors, follow the outdoor installation guidelines. If installing indoors, follow the indoor installation guidelines.

Maintenance
To ensure proper functioning of the strainer, regular maintenance is required:

  • Periodically inspect the strainer screen for sediment or debris build-up.
  • If necessary, remove the screen for cleaning without removing the device from the line.
  • Follow the recommended cleaning procedure provided in the user manual.

For any further assistance or inquiries, please contact Zurn Industries or visit their website.

MODEL FSC 2 1/2″, 3″ & 4″ (STANDARD & METRIC)

ZURN -FSC -Ductile -Iron -Y -Type -Strainer -FIG \(3\)

ZURN -FSC -Ductile -Iron -Y -Type -Strainer -FIG \(4\)

Typical Installation
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted with sufficient clearance for maintenance in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. The installation shall be made so that no part of the unit can be submerged. Horizontal installation with the strainer cap facing downward is the preferred installation orientation; however the strainer will provide protection in any orientation

Capacity thru Schedule 40 Pipe (GPM)

Pipe Size| 5 ft/sec| 7.5 ft/sec| 10 ft/sec| 15 ft/sec
2 1/2″| 75| 112| 149| 224
3″| 115| 173| 230| 346
4″| 198| 298| 397| 595
6″| 450| 675| 900| 1351
8″| 780| 1169| 1559| 2339
10″| 1229| 1843| 2458| 3687
12″| 1744| 2617| 3489| 5233

ZURN -FSC -Ductile -Iron -Y -Type -Strainer -FIG \(1\)

Specifications
The Ductile Iron “Y” type strainer shall meet the requirements of NSF/ANSI 372, and MIL-S-16293F Type 2. The main body and access cover shall be ductile iron ASTM A536 with an NSF/ANSI/CAN 61 certified Fusion Epoxy Finish coating inside and out. The integral strainer screen shall be accessible for cleaning without removing the device from the line. The Ductile Iron “Y” type strainer shall be a ZURN WILKINS Model FSC.

Zurn Industries, LLC | Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446
Ph. 855-663-9876,
Fax 805-238-5766
In Canada | Zurn Industries Limited
7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6, 877-892-5216
www.zurn.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ZURN User Manuals

Related Manuals