Altronix Maximal3D Single Power Supply Access Power Controllers Installation Guide

June 4, 2024
Altronix

Altronix Maximal3D Single Power Supply Access Power Controllers

Installation Guide

Maximal D Series
Single Power Supply
Access Power Controllers (fused)

Maximal3D
– 12VDC @ 5A or 24VDC @ 5.4A.
– Sixteen (16) PTC protected Class 2 Rated power-limited outputs.

Maximal5D
– 12VDC @ 9A.
– Sixteen (16) PTC protected Class 2 Rated power-limited outputs.

Maximal7D
– 24VDC @ 9.42A.
– Sixteen (16) PTC protected Class 2 Rated power-limited outputs.

FIG 1.JPG

Maximal D Series Overview:

Maximal Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into sixteen (16) independently controlled 12VDC or 24VDC Class 2 Rated PTC protected power- limited outputs. The outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the sixteen (16) outputs. All interconnecting equipment must be UL Listed.

Maximal D Series Configuration Chart:

FIG 2 Maximal D Series Configuration Chart.JPG

*ANSI/UL 294 7th Ed. Access Control Performance Levels:
Destructive Attack – I; Endurance – I; Line Security – I; Stand-by Power – I, IV.

MaximalD Series Features:

  • Sixteen (16) independently trigger controlled outputs. Output options:
    a) Sixteen (16) Fail-Safe filtered and electronically regulated power outputs.
    b) Sixteen (16) Fail-Secure filtered and electronically regulated power outputs.
    c) Any combination of the above.

  • Sixteen (16) Access Control System trigger inputs. Input trigger options:
    a) Sixteen (16) normally open (NO) dry trigger inputs.
    b) Sixteen (16) open collector inputs.
    c) Any combination of the above.

  • Sixteen (16) unswitched filtered and electronically regulated aux. power outputs (outputs are rated @ 2.5A).

  • Red LEDs on ACM8CB board indicate individual outputs are triggered (relays energized).

  • Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the sixteen (16) outputs.
    Fire Alarm disconnect input trigger options:
    a) Normally open (NO) or normally closed (NC) dry trigger input.
    b) Polarity reversal input from FACP signaling circuit.

  • Green LED on ACM8CB board indicates FACP disconnect is triggered.

  • FACP output relay indicates that FACP input is triggered (form “C” contact rated @ 1A/28VDC, not evaluated by UL).

  • Power supply input is factory installed. It provides common power for both ACM8CB boards and all connected access control devices.

  • ACM8CB board main fuses are rated @ 10A. Output PTCs are rated @ 2.5A.

  • Built-in charger for sealed lead acid or gel type batteries.
    – Maximum charge current is 0.7A for AL600ULXB and AL1012ULXB power supply boards.
    – Maximum charge current is 3.6A for AL1024ULXB2 power supply board.

  • Automatic switch over to stand-by battery when AC fails.

  • Zero voltage drop when unit switches over to battery backup (AC failure condition).

  • Short circuit and thermal overload protection with auto reset.

  • Green AC input and red DC output LED indicators on power supply board(s).

  • AC fail supervision (form “C” contact rated @ 1A/28VDC).

  • Battery fail and battery presence supervision (form “C” contact rated @ 1A/28VDC).

  • Enclosure accommodates up to four (4) 12VDC/12AH batteries.

  • Enclosure dimensions (H x W x D): 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.8mm).

MaximalD Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.

Power Supply Board LED Diagnostics
Access Power Controller LED Diagnostics
Power Supply Board Terminal Identification
Access Power Controller Terminal Identification
Power Supply Board Stand-by Battery Specifications
Power Supply Board Output Voltage Settings
Access Power Controller Typical Application Diagram
FACP Hook-up Diagrams

  1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top three key holes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws; level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 16).

  2. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green grounding conductor lead. Connect unswitched AC power (115VAC 60Hz) to the terminals marked [L, N] on power supply board. Green “AC” LED on power supply board will turn on. This light can be seen through the LED lens on the door of the enclosure. Use 14 AWG or larger for all power connections.
    Keep power-limited wiring separate from non power-limited wiring.
    Minimum 0.25” spacing must be provided (Figs. 5-7, pgs. 10-12).
    CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside.
    Refer installation and servicing to qualified service personnel.

  3. Select desired DC output voltage by setting SW1 to the appropriate position on the Maximal3D power supply, (Figs. 1 and 1a, pg. 8). Maximal5D power supply is factory set at 12VDC and Maximal7D power
    supply is factory set at 24VDC.

  4. Measure the output voltage of the unit before connecting any devices to ensure proper operation. Improper or high voltage will damage these devices.

  5. Output options (Fig. 2, pg. 8):
    The unit will provide either sixteen (16) switched power outputs.
    (a) Fail-Safe Switched Power outputs:
    For Fail-Safe operation connect the positive (+) input of the access control devices to terminal marked [NC]. Connect the negative (–) input of the access control devices to terminal marked [COM].
    (b) Fail-Secure Switched Power outputs:
    For Fail-Secure operation connect the positive (+) input of the access control devices to terminal marked [NO]. Connect the negative (–) input of the access control devices to terminal marked [COM].

  6. Auxiliary Power outputs (unswitched):
    Connect access control devices that require constant power to the terminals marked [C] positive (+) and [COM] negative (–).

  7. Input trigger options (Fig. 2, pg. 8):
    (a) Normally Open [NO] input trigger:
    Inputs 1-8 are activated by normally open or open collector sink inputs.
    Connect access control panel outputs, keypads, push buttons, REX PIRs, etc. to terminals marked [IN] and [GND]. (b) Open Collector Sink inputs:
    Connect the access control panel open collector sink positive (+) to terminals marked [IN] and the negative (–) to terminals marked [GND].

  8. Fire Alarm Interface options (Figs. 8-12, pg. 14):
    A normally closed [NC] or normally open [NO] input trigger from a fire alarm control panel or a polarity reversal input from an FACP signaling circuit will affect selected outputs.
    To enable FACP Disconnect for an output turn the corresponding switch(es) [SW1-SW8] OFF on each ACM8CB board. To disable FACP disconnect for an output turn the corresponding switch(es) [SW1-SW8] ON on each ACM8CB board.
    (a) Normally Open [NO] input:
    For non-latching hook-up refer to Fig. 9, pg. 14. For latching hook-up refer to Fig. 10, pg. 14.
    (b) Normally Closed [NC] input:
    For non-latching hook-up refer to Fig. 11, pg. 14. For latching hook-up refer to Fig. 12, pg. 14.
    (c) FACP Signaling Circuit input trigger:
    Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals marked [+ INP –]. Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced in an alarm condition). Jumper located next to TRG LED must be cut (Fig. 2a, pg. 7 and Fig. 8, pg. 14).

  9. FACP Dry form “C” output (Fig. 2b, pg. 7):
    FACP form “C” contacts can be use to trigger reporting or signaling devices.
    These contact switch upon a fire alarm input trigger to the ACM8CB boards.

  10. Stand-by Battery Connections (Figs. 3-7, pgs. 9-13):
    For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the
    terminals marked [+ BAT –] for 12VDC operation (Fig. 3a, pg. 9). Use two (2) 12VDC batteries wired in series for 24VDC operation.

  11. Battery and AC Supervision outputs (Figs. 3-4, pgs. 9-10):
    It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] supervisory relay outputs marked [NC, C, NO] to appropriate visual notification devices.
    Use 22 AWG to 18 AWG for AC Fail & Low/No Battery reporting.

  12. Installation of tamper switch (Not Included) (Figs. 3b-4a, pgs. 9-10):
    Mount UL Listed tamper switch (Altronix Model TS112 or equivalent) at the top of the enclosure. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Figs. 3b and 4a, pgs. 9-10). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

FIG 3 Maintenance.JPG

Power Supply Board LED Diagnostics:

FIG 4 Power Supply Board LED Diagnostics.JPG

Access Power Controller LED Diagnostics:

FIG 5 Access Power Controller LED Diagnostics.JPG

Power Supply Board Terminal Identification:

FIG 6 Power Supply Board Terminal Identification.JPG

Access Power Controller Terminal Identification:

FIG 7 Access Power Controller Terminal
Identification.JPG

Power Supply Board Stand-by Battery Specifications:

FIG 8 Power Supply Board Stand by Battery
Specifications.JPG

Power Supply Board Output Voltage Settings:

FIG 9 Power Supply Board Output Voltage Settings.JPG

Access Power Controller Typical Application Diagram
(for each ACM8CB):

FIG 10 Access Power Controller Typical Application
Diagram.JPG

FIG 11 Access Power Controller Typical Application
Diagram.JPG

Maximal3D and Maximal5D

Fig. 3

FIG 12 Maximal3D and Maximal5D.JPG

FIG 13 Maximal3D and Maximal5D.JPG

FIG 14 Maximal3D and Maximal5D.JPG

Maximal7D

Fig. 4

FIG 15 Maximal7D.JPG

FIG 16 Maximal7D.JPG

NEC Power-Limited Wiring Requirements for Maximal3D:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 5a).

FIG 17 NEC Power-Limited Wiring Requirements for
Maximal3D.JPG

NEC Power-Limited Wiring Requirements for Maximal5D:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 6a).

FIG 19 NEC Power-Limited Wiring Requirements for
Maximal5D.JPG

NEC Power-Limited Wiring Requirements for Maximal7D:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 7a).

FIG 20 NEC Power-Limited Wiring Requirements for
Maximal7D.JPG

FACP Hook-Up Diagrams:

FIG 21 FACP Hook-Up Diagrams.JPG

FIG 22 FACP Hook-Up Diagrams.JPG

Enclosure Dimensions

(H x W x D approximate):
26” x 19” x 6.25” (660.4mm x 482.6mm x 158.8mm)

FIG 23 Enclosure Dimensions.JPG

FIG 24 Enclosure Dimensions.JPG

FIG 25 Enclosure Dimensions.JPG

Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty
IIMaximal3D/5D/7D Series

Read More About This Manual & Download PDF:

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Altronix User Manuals

Related Manuals