LEVITON Next Gen Load Center User Guide

June 9, 2024
Leviton

Leviton Load Center
First Time User Guide

LEVITON Next Gen Load Center

Next Gen Load Center

Thank you for choosing the Leviton Load Center!
This First Time User Guide offers tips and support.

  • Order the covers separately; clear doors are a popular option for indoor applications.

  • Each Load Center ships with a standard Panel Schedule. Window Doors/Covers include an alternate Panel Schedule that is compatible with the door design. Additionally, Panel Schedules for all Indoor panel sizes and door types can be purchased in bulk packs, and are available as a .PDF download on Leviton.com.

  • A temporary circuit directory is supplied on the Paint Shield (Figure 1).

  • Neutral wires must terminate at the circuit breaker for all smart  and safety breakers (AF, GF, EP, Dual). However, it is the preferred method for all circuits.

  • For 2-pole breakers that are 60A or lower, the Neutral wire must be installed in-between the two phase wires where the “N” is denoted on the breaker (Figure 2). For 2-Pole breakers greater than 60A, the Neutral wire must go to the Neutral bar (Figure 3).

  • All non-electronic 2-Pole breakers, as well as -G breakers operate at both 120/240V and 120/208V.

  • A Leviton Surge Protective Breaker can be installed in any breaker location to provide whole-panel surge protection, as well as visual indication of protection status. It also provides overcurrent protection for the spaces/circuits it inhabits.

  • All panels 20-Space and larger come with 23 ground terminals, factory installed. Each terminal is rated for landing multiple wires per the panel label.

  • There are 6 pre-drilled areas for additional ground bars on the back of the enclosure.

  • Utilize the bonding strap (Figure 4) for all service entrance panels. DO NOT use the bonding strap in a main lug only panel.

  • There is no need to remove the screw that bonds the structure back to the enclosure.

  • NEC® 2020 code 3-Wire vs 4-Wire 240V appliance Circuit Grounding: Many 240V appliances have the Ground and Neutral wires connected together in the appliance from the factory. This only works for a 3-wire hook up with no ground connection. When installing the appliance on a new install with 3 wires and a ground, the grounds and neutrals must be separated by removing the ground strap in the appliance. If the ground strap is left installed, then GFCI breakers will not reset.

LEVITON Next Gen Load Center - Figure 2

If you have any questions, we’re here to help:
1-800-824-3005, Option 4.

Leviton Manufacturing Co., Inc.
Tech Line: 1-800-824-3005
Mon-Fri 8am-10pm EST, Saturday 9am-7pm EST, Sunday 9am-5pm EST
For 24/7 product support visit www.leviton.com/support
Visit our Website at: www.leviton.com
© 2023 Leviton Manufacturing Co., Inc. All rights reserved.
All trademarks are the property of their respective owners.

GR-110922A-tp