EATON 3S Power Inverter
Copyright © 2019 EATON All rights reserved.
614-09405-01_EN 3S EMEA
Special symbols
The following are examples of symbols used on the UPS or accessories to alert you to important information:
- DANGEROUS VOLTAGE – Observe the warning associated with the risk of electric shock symbol.
- Important instructions that must always be followed.
- Information, advice, help.
- Read the documentation provided.
- Disconnect input plug.
- This equipment should only be used in a dry indoor environment.
- 0 °C Operating range of temperature.
- Operating range of humidity.
- The UPS and their batteries must be kept in a ventilated place.
Introduction
- Thank you for selecting an Eaton product to protect your equipment.
- The Eaton 3S range has been designed with the utmost care. We recommend that you take the time to read this advanced user guide and documentations provided to take full advantage of the many features of your UPS (Uninterruptible Power System).
- Before installing your Eaton 3S, please read the information and safety instructions provided. Follow the instructions in the quick start guide and if necessary, refer to this advance user guide.
- To discover the entire range of Eaton products, we invite you to visit our web site at eaton.com or contact your Eaton representative.
- The Eaton 3S Uninterruptible Power System (UPS) is designed for computers and their peripherals, NAS, televisions, internet gateways, etc… It must not be used to supply other electrical equipment (lighting, heating, household appliances, etc.). It prevents your critical equipment from power problems such as power failures and power surges.
Presentation
- Protected outlets
- Backup & Protected outlets
- UPS status LED
- Protection circuit breaker
- Power supply cord / socket
- Surge protection LED
- Tel / xDSL surge protection (optional) 8 USB COM port (optional)
- ON/OFF button
- USB charging port (optional)
Installation
Package contents
- Eaton 3S UPS
- Quick start
- Information and safety instruction
- USB cable (for Eaton 3S with communication feature: 3S550, 3S700 and 3S850)
- 2 x Output cables (IEC models only)
Recommended positions
Eaton 3S can be wall-mounted, horizontal or vertical position, the distance between screws are 230 mm for 3S450 / 3S550 models and 240mm for 3S700 / 3S850 models.
For 3S450 and 3S550 only do not dispose the product on the side as shown below .
Connection
Power supply cord / socket
Connect the UPS to the AC-power source through a wall outlet equipped with an earth connector, using the attached cord for a UPS with FR / DIN sockets or the supply cord of your computer for a UPS with IEC sockets.
Protected outlets / Backup & Protected outlets
Plug critical equipment (computer, monitor, modem, etc.) to the backup & protected outlets 2 providing battery backup power and surge protection, taking care not to exceed the rated current indicated in amperes. Other devices (printer, scanner, fax, etc.) can be connected to the protected outlets 1 that provide surge protection only. The protected outlets are not backed up by battery power in the event of a power outage. Equipment connected to these outlets is supplied as soon as the AC cord is plugged in. These are not affected by ON/OFF button 9 .
Tel / xDSL surge protection (optional)
Protect your Tel / xDSL line using a RJ11 cable (not provided) from the wall phone plug to the Eaton 3S “In”port 7 then connect your device to the Eaton 3S “Out” port 7.
USB COM port (optional)
Connect the UPS to the computer using the USB cable 14 supplied. Enhance your purchase by downloading the configuration tool software using URL: <http://powerquality.eaton.com/EMEA/support/software-drivers/default.asp
USB charging port (optional)
Connect your device to the USB charging port 10 (2A maximum).
ON/OFF button
Switch on the UPS by pressing ON/OFF button 9 during 1.5 second.
Register warranty
Register warranty at www.powerquality.eaton.com/EMEA/Product- Registration.
Operation
Battery charge
The UPS charges the battery as soon as it is connected to the AC outlet, whether ON/OFF button 9 is pressed or not. When used for the first time, the battery will only provide its maximum autonomy after it has been charged for 8 hours. It is recommended that the UPS be permanently connected to the AC power supply to ensure the best possible autonomy.
AC-power disturbance
If AC power is disturbed or fails, the UPS continues to operate on battery
power. UPS status LED 3 flashes green. In normal mode, the audio alarm beeps
every five seconds, then every two seconds when the end of battery backup time
is near.
If the power outage lasts longer than the battery backup time, the UPS shuts
down and automatically restarts when power is restored. Following a complete
discharge, 10 hours are required to recharge the battery backto full backup
time.
To save battery power, it is possible to press ON/OFF button 9 to cut the
supply of power to the devices connected to the battery backup outlets.
Protected outlets
All protected outlets 1 provide surge protection, whatever the position of ON/OFF button 9 . The Surge protection LED 6 provide the status of the protection. When the Surge protection LED 6 is OFF your protection is defective, please contact after sales services or local representative.
Equipment Care
For full battery life, keep the equipment at an ambient temperature of 25 °C (77 °F). Battery service life is reduced by 50 % for every ten degrees above 25 °C. If the UPS requires any type of transportation, verify that the UPS is turned off.
Battery replacement
For battery replacement follow Eaton instructions provided on www.eaton.eu/BatteryServices.
The following precautions should be observed when working on batteries:
- shut down the UPS (ON/OFF button 9 ),
- disconnect the source prior to connecting or disconnecting battery terminals,
- do not wear any metal objects including watches and rings,
- do not lay tools or metal parts on top of batteries,
- it is imperative to use the same battery type and number.
CAUTION : Batteries present a risk of electrical shock or burn from high short circuit current. Observe proper precaution. Batteries may contain HIGH VOLTAGE and CORROSIVE, TOXIC and EXPLOSIVE substances. Because of the battery the output receptacles may carry high voltages even when the AC supply is notconnected to the UPS. Do not dispose of batteries in a fire. When exposed to flame, batteries may explode. Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes and may be extremely toxic.
Battery change
Warning : take care not to reverse the polarity + (red) and – (black) when connecting the batteries as this will destroy the device.
Troubleshooting
The Eaton 3S is designed for durable, automatic operation and alerts you whenever potential operating problem may occur.
Problem | Possible cause | Action |
---|
The battery backup outlets 2
are not supplied with power.
| ON/OFF Button 9 is not pressed.| Press ON/OFF button 9 for 1.5 seconds
and check that LED 3 turns to green.
The connected devices are not supplied when AC power fails.| The devices are
not connected to the battery backup outlets 2.| Connect the devices to the
battery backup outlets 2.
AC power is available, but the UPS operates on battery power.| Circuit
breaker 4 has been tripped by an overload on the UPS output.| Disconnect
excess equipment and reset the circuit breaker 4 by pressing the
corresponding button.
The filtered outlets 1 and 2
are not supplied.
| The wall outlet is not supplied.
Circuit breaker 4 has been tripped by an overload on the UPS output.
| Supply power from the wall outlet. Disconnect excess equipment and reset the
circuit breaker 4 by pressing the corresponding button.
Green LED 3 flashes every 1 second and audio alarm beeps every 5 seconds.|
The UPS frequently operates on battery power because the AC power source is of
poor quality.| Have the electrical installation checked by a professional or
use another wall outlet.
Green LED 3 flashes every 1 second and audio alarm beeps every 1 second.|
The UPS battery backup outlets 2 are overloaded.| Disconnect excess
equipment connected to the battery backup outlets.
Red LED 3 is on and the audio alarm beeps continuous.| A fault has
occurred on the UPS. The battery backup outlets 2 are no longer supplied.|
Contact Eaton service and support.
The telephone line is disturbed or modem access is not possible.
Surge protection LED 6 is OFF.
| Surge protection on the telephone line is no longer provided.| Disconnect the telephone line from the wall outlet.
Contact Eaton service and support.
USB communication fails.| Cable connection may be defective.| Re-connect the
USB cable 14 , if still not available Contact Eaton service and
support.
USB charger ports 10 are not supplied.| The battery voltage is too low.|
Recharge the battery, if still not available contact Eaton service and
support.
The following table describes typical conditions:
Service and support
If you have any question or problem with the UPS, call Eaton or your local
service representative in your country / region.
Please have the following information ready when you call for service:
- model number,
- serial number,
- date of failure or problem,
- symptoms of failure or problem,
- customer return address and contact information,
- description of the installation.
Specification and technical characteristics
Eaton 3S | 450 | 550 | 700 | 850 |
---|---|---|---|---|
UPS power | 450 VA / 270 W | 550 VA / 330 W | 700 VA / 420 W | 850 VA / 510 W |
Input mains voltage | 220 – 240 V~ ; Ph + N + PE | |||
Input voltage range | 184 – 264 V, adjustable to 160 – 284 V | |||
Input frequency | 50 / 60 Hz (46 – 65 Hz working range) | |||
Input protection | 10 A (thermal breaker) | |||
Output Voltage for backup outlets | 220 V / 230 V / 240 V ~ | |||
Output Current for backup outlets | 2 A | 2.4 A | 3 A | 3.7 A |
Total output current for all outlets | 9 A maximum | |||
Performance Classification | VFD SY 333 | |||
Battery | 12 V; 4.5 Ah | 12 V; 5 Ah | 12 V; 7 Ah | 12 V; 9 Ah |
Communication interface | NA | USB port (cable included) | ||
USB Charge | NA | NA | 2 USB ports 2 A maximum | |
Telephone surge protection | NA | NA | T3 Uoc = 6 kV; Up < 1.5 kV; In = 3 kA | |
Power surge protection | T3 Uoc = 6 kV; Up < 1.5 kV; In = 3 kA | |||
Operating temperature | 0 to 40 °C | |||
Storage temperature | -25 °C to +55 °C | |||
Operating relative humidity | Operating relative humidity 0 to 85 % | |||
Operating elevation | 0 to 3000 m | |||
Compliances | IEC 62040-1; IEC 62040-2 C2*; IEC 62040-3; IEC 62040-4; IEC |
61643-11 T3
Conformity| CE / EAC / Ukr (DIN models) CE / Cm (FR models)
CE / EAC / Cm / Ukr (IEC models)
Warranty| 2 years
Weight| 2.9 kg| 3.2 kg| 4 kg| 4.3 kg
Dimensions| 325 x 140 x 86 mm| 335 x 170 x 86 mm
Note:
The Eaton 3S is a IEC 62040-2 cat C2 UPS product. In a residential
environment, this product may cause radio interference, in which case the user
may be required to take additional measures. Output cables should not exceed
10 m length.
Glossary
- Backup time Time during which the load can be supplied by the UPS operating on battery power.
- UPS Uninterruptible Power Supply.
References