INOR APAQ R130TC Programmable 2 Wire Transmitter for Thermocouple User Manual

June 4, 2024
INOR

APAQ R130TC Programmable 2 Wire Transmitter for Thermocouple
User Manual

INOR APAQ R130TC Programmable 2 Wire Transmitter for
Thermocouple

The user instruction must be read prior to adjustment and/or installation.
All information is subject to change without notice.

GENERAL INFORMATION

APAQ R130TC is a low-cost, non-isolated, easy-to-use 2-wire transmitter, for thermocouple input, intended to be used in an industrial environment.
The transmitter is configured from a mobile device via NFC communication, by using the app INOR Connect. Inner Connect is available for free download on App Store,  Google Play Store, and Huawei AppGallery.

DATA (short form)

Input 2-wire connection
TC type B – Pt3ORh-Pt6Rh (IEC 60584) 0…+1820 °C / +32…+3308 °F
TC type E – NiCr-CuNi (IEC 60584) -270…+1000 °C / -454…+1832 °F
TC type 3 – Fe-CuNi (IEC 60584) -210…+1200 °C / -346…+2192 °F
TC type K – NiCr-NiAl (IEC 60584) -270…+1300 °C / -454…+2372 °F
TC type N – NiCrSi-NiSi (IEC 60584) -270…+1300 °C / -454…+2372 °F
TC type R – Pt13Rh-Pt (IEC 60584) -50…+1750 °C / -58…+3182 °F
TC type S – Pt1ORh-Pt (IEC 60584) -50…+1750 °C / -58…+3182 °F
TC type T – Cu-CuNi (IEC 60584) -270…+400 °C / -454…+752 °F
Input impedance 10 MQ
Maximum wire loop resistance Field transmitter (including TC sensor): 101(C
Cold Junction Compensation Internal or fixed
Output 4-20 mA, temperature linear
Sensor failure indication Upscale (?21.0 mA) or downscale W.6 rr
NAMUR Compliance Current limitations and failure currents acc to NAMUR NE 43
Adjustable filtering level 0.4 to 26 sec.
Warm-up time After a max. 20 minutes the accuracy specifications are reached

(due to the internal cold junction)
Ambient temperature|
Storage and operation| -40 to +85 °C / -40 to +185 °F
Galvanic isolation| None
Power supply| 6 to 32 VDC
Accuracy|
IC type B| See Data Sheet
IC type R, S, T| Max. of ±2.0 °C or ±0.2% of span
| Max. of ±3.6 °F or ±0.2% of span
TC type E, 3, K| Max. of ±1 °C or ±0.2% of span
| Max. of ±1.8 °F or ±0.2% of span
TC type N (-100…+1300 °C)| Max. of ±1 °C or ±0.2% of span
| Max. of ±1.8 °F or ±0.2% of span
TC type N (-270…-100 °C)| ±2.0 °C / ±3.6 °F
CJC accuracy| Typical ±1 °C / ±1.8 °F (max ±3 °C / ±5.4 °F) within an ambient temperature range
Mounting| DIN-rail according to DIN 50022 / EN 60715, 35 mm / 1.38 in
Configuration| App INOR Connect via NEC”‘
RoHS, China RoHS| Directive: 2011/65/EU and 2015/863/EU Harmonized standard: EN IEC 63000 China RoHS 2
Factory settings| Type K
Input| 0 to 1000 °C
Output| 4 to 20 mA
Sensor error indication| Upscale

CONFIGURATION

Before making a configuration of APAQ R130TC you need to do the following: Make sure that you have a mobile device with NFC communication activated. Download the app  INOR Connect to your mobile device.

Required versions:

iOS
iOS 13 or later and iPhone 7 or later for NFC

Android
Android 4.4 or later

Configuration procedure:

  1. Launch the app by clicking on the App icon or holding your mobile device against the transmitter on the part of the device where NFC™ is located (only possible with Android).

  2. Click on “Read Configuration” and hold your mobile device against the transmitter as explained in the first section.

  3. In the app you can edit the following:
    a. Sensor type
    b. Measuring range
    c. Upscale or downscale sensor error indication
    d. Filter level
    e. TAG-number
    f. Password

  4. Once you have set the desired values in the app, you transfer it to the transmitter by clicking the transfer button and holding the mobile device against the transmitter until a  green check box appears confirming that the transfer has been completed.

OUTPUT LOAD DIAGRAM

INOR APAQ R130TC Programmable 2 Wire Transmitter for Thermocouple -
DIAGRAM

Maximum load depending on power supply Formula for the max. permissible output load for APAQ R130TC:
Load R =(U-6)/0.022

DIMENSIONS

INOR APAQ R130TC Programmable 2 Wire Transmitter for Thermocouple -
DIMENSIONS

LIMITED WARRANTY

INOR Process AB, or any other affiliated company within the Inor Group (hereinafter jointly referred to as ”Inor”), hereby warrants that the Product will be free from defects in materials or workmanship for a period of five (5) years from the date of delivery (”Limited Warranty”). This Limited Warranty is limited to repair or replacement at Inor’s option and is effective only for the first end-user of the Product. Upon receipt of a warranty claim, Inor shall respond within a reasonable time period as to its decision concerning:

  1. Whether Inor acknowledges its responsibility for any asserted defect in materials or workmanship; and, if so,
  2. the appropriate cause of action to be taken (i.e. whether a defective product should be replaced or repaired by Inor).

This Limited Warranty applies only if the Product:

  1. is installed according to the instructions furnished by Inor;
  2. is connected to a proper power supply;
  3. is not misused or abused; and
  4. there is no evidence of tampering, mishandling, neglect, accidental damage, modification, or repair without the approval of Inor or damage done to the Product by anyone other than Inor.

This Limited Warranty is provided by Inor and contains the only express warranty provided.
INOR SPECIFICALLY DISCLAIMS ANY EXPRESS WARRANTY NOT PROVIDED HEREIN AND ANY IMPLIED WARRANTY, GUARANTEE, OR  REPRESENTATION AS TO SUITABILITY FOR ANY PARTICULAR PURPOSE, PERFORMANCE, QUALITY, AND ABSENCE OF ANY HIDDEN DEFECTS, AND ANY REMEDY FOR BREACH OF CONTRACT, WHICH BUT FOR THIS PROVISION, MIGHT ARISE BY IMPLICATION, OPERATION OF LAW, CUSTOM  OF TRADE OR COURSE OF DEALING, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. EXCEPT AS PROVIDED HEREIN,INOR FURTHER DISCLAIMS ANY RESPONSIBILITY FOR LOSSES, EXPENSES, INCONVENIENCES, SPECIAL,  DIRECT, SECONDARY, OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR  USE OF THE PRODUCT.

Products that are covered by the Limited Warranty will either be repaired or replaced at the option of Inor. The customer pays freight to Inor, and Inor will pay the return freight by post or other “normal” way of transport. If any other type of return freight is requested, customer pays the whole return cost.

INSTALLATION

APAQ R130TC is designed to be mounted on a 35 mm DIN Rail according to EN 60715 / DIN 50022.

Connect input, output, and power supply acc. to “CONNECTIONS”. The cable is connected using a spring cage connection. In order to minimize measuring errors ensure that the cable is securely fastened.

  1. Insert a screwdriver into the opening above the connection terminal block.
  2. Insert the wire into the corresponding connection terminal block.

MOUNTING

INOR APAQ R130TC Programmable 2 Wire Transmitter for Thermocouple -
MOUNTING

Mounting and removal of the transmitter

  1. Fix the upper part of the transmitter onto the rail.
  2. Press the lower part of the transmitter against the rail.
  3. To remove the transmitter, use a screwdriver and bend the locking under the transmitter downwards.

CONNECTIONS

INOR APAQ R130TC Programmable 2 Wire Transmitter for Thermocouple -
CONNECTIONS

ORDERING INFORMATION

APAQ R130TC 70R1300211

The transmitters are delivered with either a default factory setting or configured according to the customer’s specifications.

INOR Process AB, PO Box 9125, SE-200 39 Malmö, Sweden,
Phone: +46 40 312 560, Fax: +46 40 312 570, E-mail: [email protected]
INOR Transmitter OY, Unikkotie 13, FI-01300 Vantaa, Finland,
Phone:+358 10 421 7900, Fax: +358 10 421 7901, E-mail: [email protected]
INOR Transmitter GmbH, Am See 24, D-47279 Duisburg, Germany,
Phone: +49-203 7382 762 0, Fax: +49-203 7382 762 2, E-mail: info@inor- gmbh.de
KROHNE Temperature Division INOR, 55 Cherry Hill Drive,
Beverly, MA 01915, United States
Phone: +1 978 826 6900, Fax: +1 978 535 1720, E-mail: inor- [email protected]

www.inor.com, www.inor.se

This product should not be mixed with another kind of scrap, after usage.
It should be handled as an electronic/electric device.

References