INOR Programmable Temperature Transmitter IPAQ R460 Instructions
- June 3, 2024
- INOR
Table of Contents
USER INSTRUCTIONS
Programmable Temperature Transmitter
IPAQ R460
Programmable Temperature Transmitter IPAQ R460
Read these instructions before using the product and retain for future information.
► Before Startup
When operating the signal converter, certain parts of the module can carry
dangerous voltage! Ignoring the warnings can lead to serious injury and/or
cause damage!
The signal converter should only be installed and put into operation by
qualified staff. The staff must have studied the warnings in these operating
instructions thoroughly.
The signal converter may not be put into operation if the housing is open.
In applications with high operating voltages sufficient distance and isolation
as well as shock protection must be ensured.
Safe and trouble-free operation of this device can only be guaranteed if
transport, storage and installation are carried out correctly and operation an
maintenance are carried out with care.
Appropriate safety measures against electrostatic discharge (ESD) should be
taken during range selection and assembly on the transmitter.
► Short description
The programmable transmitter is designed for operating various industrial
sensors. The measured values are converted into a current or voltage signal.
The configuration can be done either via DIP switch for preference measuring
ranges or extensive ranges via an USBinterface with the PC configuration
program INOR-Set.
The 3-way isolation guarantees reliable decoupling of the sensor circuit from
the processing circuit and prevents linked measurement circuits from
influencing each other. The auxiliary power can either be supplied via the
connection terminals or via the In-Rail-Bus connector (see Accessories).
Configuration and startup
Configuring with DIP switch
Use the DIP switches to configure the device, according to table.
Via the DIP switches you can select only a limited number of sensors. A wider
range of sensors you can select via software configuration.
Configuring with software INOR-Set
Use the software INOR-Set to configure the device. Changes to the
configuration and parameterization data can be performed both during operation
with a connected measuring circuit and in a disconnected state. The INOR-Set
software is free and can be downloaded from our website.
The device is equipped with a programming socket on the front. Use the INOR-
Set USB Converter (Order no.: 70USBIM010) for connecting the device to the PC.
To change the configuration and parameterization DIP switch S1- 1, 2, 3 have
to be set ON!
Commissioning Function
The Commissioning Function with a stepped keystone signal on output supports a
fast and simple testing of cabling and connection of downstream devices or
measuring adjustment. Press the function button located behind the front cover
for longer than 3 seconds. The Commissioning Function will be indicated with a
yellow LED (quick double off).
Output value:
Output| 0 %| | 50 %| | 100 %| | 50%|
---|---|---|---|---|---|---|---|---
Time| 5 s| 3 s| 3 s| 3 s| 5 s| 3 s| 3 s| 3 s
The stepped keystone signal is output continuously. Exit the Commissioning
Function by pressing the button again for 3 seconds or power off.
Teach-In Function for Potentiometer, Resistor and mV- Input
The Teach-In function can be used to teach in the start value and end value.
There are two ways of the Teach-In function:
- Automatic set up mode (Auto Teach-In)
- Manual Teach-In of the start and end value (Manual-Teach-In)
The taught-in values remain stored under the Teach-In setting. The start value is 0 % and the end value is 100 % by default.
Starting the Teach-In Function
Use the function button located behind the front cover of the device to teach in the device (use screw driver to push).
-
Configure the device using the DIP switches on the side of the device.
-
Press the function button for longer than 3 seconds.
The yellow LED will flash quickly -
Auto Teach-In: Set input signal to both min and max range limits as often as desired. Start value and end value will be automatically determined and recorded.
or
Manual Teach-In : Set input signal to first range limit and press the
function button for around 0.5 seconds. Set second limit and press the
function button for around 0.5 seconds. This can be repeated as often as
required. The value of the last two keystrokes will be stored for start value
and end value.
Ending the Teach-In, Saving the Start Value and End Value
Press the function button for longer than 3 seconds. Release the button
when the yellow LED lights up constant. The values are stored. The green LED
indicates the successfully storage.
Ending the Teach-In without Saving the Start Value and End Value
Press the function button for longer than 6 seconds. Release the button when
the yellow LED starts to flash again after lit up constant.
The values are ignored and not stored.
Or switch off the device. The values are not stored.
Teach-In Fault
If the span between the start value and the end value is too small, the red
LED will flash slowly after saving the values (configuration error). In case
of a fault, the Teach-In function must be performed again in its entirety.
Technical Data
Input
Sensor | Span min. | Error |
---|---|---|
Pt100, Pt200, Pt500, Pt1000 | 10 K | < 0.1 K + 0,05 % meas. val. |
Ni100, Ni200, Ni500, Ni1000 | 10 K | < 0.2 K + 0,05 % meas. val. |
KTY (29 types) | 25 K | < 0.3 K + 0.05 % meas. val. |
Resistor 0…5000Q | 100 Q | < 0.1 52 + 0.02 % meas. val. |
Sensor current/ connection | 0.2 mA / 4-wire, 3-wire, 2-wire | |
Cable resistance | < 100 S2 per wire, manual compensation for 2-wire connection |
programmable
TC Sensor E, J, K, L, N, R, S, T, U / B, C, D| 50 K / 100 K| < 0.3 K + 0.08 %
meas. val.
Cold junction compensation| intern, extern Pt100, uncompensated, manual
setting
(Error of cold junction compensation internal < 1.5 K)
±100 mV, ±1000 mV| 5 mV, 50 mV| < 50 pV + 0.02 % meas. val.
Poti 100 c2 to 50 kS2| 10%| < 0.05 %
Output| Current| Voltage
---|---|---
Output signal| 0…20 mA 0…10 mA
4…20 mA 2…10 mA| 0…10 V 0…5 V
2…10V 1…5 V
Load| 12 V (600 .0 at 20 mA)| 5 mA (2 kf.) at 10 V)
Residual ripple| < 10 mVrms
Transfer range| 0 to 102.5 % (3.8 to 20.5 mA at output 4 to 20 mA) Transfer
characteristic rising / falling
Error signal| Sensor- / wire break, error signal programmable
General data
Transmission error | < 0.1 % full scale |
---|---|
Temperature coefficient2) | < 100 ppm/K |
Measurement rate | 4 / s |
Response time T99 | 250 ms |
Test voltage | 3 kV, 50 Hz, 1 min. |
Input against output against power supply
Working voltage³) (basic insulation)| 600 V AC/DC for overvoltage category II
and contamination class 2 acc. to EN 61010-1
Protection against dangerous body currents³| Protective Separation by
reinforced insulation acc. to EN 61010-1 up to 300 V AC/DC for overvoltage
category II and contamination class 2 between input and output and power
supply.
Ambient temperature| Operation -25 °C to +70 °C (-13 to +158 °F)
Transport and storage -40 °C to +85 °C (-40 to +185 °F)
Power supply| 24 V DC 16.8 V … 31.2 V, approx. 0.8 W
EMV4)| EN 61326-1
Construction| 6.2 mm (0.244″) housing, protection type: IP 20 mounting on 35
mm DIN rail acc. to EN 60715
Connection (captive plus-minus clamp screws)| Solid: 0.5 mm2 – 4 mm2 / AWG
20-12
Fine-stranded: 0.5 mm2 – 2.5 mm2 / AWG 20-14
Stripped length: 8 mm / 0.3 in
Screw terminal: torque 0.6 Nm / 5 lbf in
Weight| Approx. 70 g
-
Factory setting:
Input: Pt100, 0…100°C, 4-wire-sensor connection
Output: 0…20 mA, Characteristic rising, error signal 22 mA -
Average TC in specified operating temperature range
-
As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipment’s. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
-
Minor deviations possible during interference
Dimensions
► Mounting, Electrical Connection
The transmitter is mounted on standard 35 mm DIN rail
► Order Information
Temperature Transmitter | Order No. |
---|---|
IPAQ R460 | 70R4600010 |
LIMITED WARRANTY
INOR Process AB hereby warrants that the Product will be free from defects in
materials or workmanship for a period of five (5) years from the date of
delivery (”Limited Warranty”). This Limited Warranty is limited to repair or
replacement at INOR’s option and is effective only for the first end-user of
the Product.
This Limited Warranty applies only if the Product:
- is installed according to the instructions furnished by INOR;
- is connected to a proper power supply;
- is not misused or abused; and
- there is no evidence of tampering, mishandling, neglect, accidental damage, modification or repair without the approval of INOR or damage done to the Product by anyone other than INOR.
Delivery conditions are based upon the „GENERAL CONDITIONS FOR THE SUPPLY OF
PRODUCTS AND SERVICES OF THE ELECTRICAL AND ELECTRONICS INDUSTRY“
Subject to change!
Set the input and output ranges with DIP switches (● = ON) as indicated in
the following table:
Input
DIP S1 ● = on
1| 2| 3| 4| 5|
---|---|---|---|---|---
| | | | | Pt100
●| | | | | Pt1000
| ●| | | | Ni100
●| | ●| | | Resistor
| | | | ●| 2-wire
| | | ●| | 3- wire
| | | | | 4- wire
●| | ●| ●| ●| Potentiometer
---|---|---|---|---|---
●| ●| | | | Type J
---|---|---|---|---|---
| | ●| | | Type K
| | | | | CJC internal
| | | ●| | CJC external (Pt100)
| | | | ●| CJC off
| ●| ●| | | ± 100mV
---|---|---|---|---|---
| ●| ●| | ●| mV x 10
●| ●| ●| | | PC (USB) Setting
---|---|---|---|---|---
Output
DIP S2
7| 8| 9| 10|
---|---|---|---|---
| | | | 0 … 20 mA
●| | | | 4 … 20 mA
| ●| | | 0 … 10 V
●| ●| | | 0 … 5 V
| | | | Characteristic
| | | | rising
| | ●| | falling
| | | | Error Message
| | | | signalize
| | | ●| not signalize
● = ON
Factory settings: all switches in position OFF
Start Value
DIP S1
6| 7| 8| 9| 10| °C| °F| Ω| Pot|
mV
---|---|---|---|---|---|---|---|---|---
●| | | | | -200| -328| 0| 0%| -100
| ●| | | | -175| -283| 50| 1%| -90
●| ●| | | | -150| -238| 100| 2%| -80
| | ●| | | -125| -193| 150| 3%| -70
●| | ●| | | -100| -148| 200| 4%| -60
| ●| ●| | | -75| -103| 250| 5%| -50
●| ●| ●| | | -50| -58| 300| 6%| -45
| | | ●| | -25| -13| 350| 7%| -40
| | | | | 0| 32| 400| 8%| -35
●| | | ●| | 25| 77| 450| 9%| -30
| ●| | ●| | 50| 122| 500| 10%| -25
●| ●| | ●| | 75| 167| 550| 11%| -20
| | ●| ●| | 100| 212| 600| 12%| -15
●| | ●| ●| | 125| 257| 650| 13%| -10
| ●| ●| ●| | 150| 302| 700| 14%| -5
●| ●| ●| ●| | 175| 347| 750| 15%| 0
| | | | ●| 200| 392| 800| 20%| 5
●| | | | ●| 225| 437| 850| 25%| 10
| ●| | | ●| 250| 482| 900| 30%| 15
●| ●| | | ●| 275| 527| 950| 35%| 20
| | ●| | ●| 300| 572| 1000| 40%| 25
●| | ●| | ●| 350| 662| 1500| 45%| 30
| ●| ●| | ●| 400| 752| 2000| 50%| 35
●| ●| ●| | ●| 450| 842| 2500| 55%| 40
| | | ●| ●| 500| 932| 3000| 60%| 45
●| | | ●| ●| 550| 1022| 3500| 65%| 50
| ●| | ●| ●| 600| 1112| 4000| 70%| 60
●| ●| | ●| ●| 650| 1202| 4500| 75%| 70
| | ●| ●| ●| 700| 1292| -/-| 80%| 80
●| | ●| ●| ●| 800| 1472| -/-| 85%| 90
| ●| ●| ●| ●| 900| 1652| -/-| 90%| -/-
●| ●| ●| ●| ●| 1000| 1832| Teach In
End Value
DIP S2
1| 2| 3| 4| 5| 6| °C| °F| Ω|
Poti| mV
---|---|---|---|---|---|---|---|---|---|---
●| | | | | | -150| -238| 100| 10%| -/-
| ●| | | | | -125| -193| 150| 15%| -/-
●| ●| | | | | -100| -148| 200| 20%| -/-
| | ●| | | | -75| -103| 250| 25%| -/-
●| | ●| | | | -50| -58| 300| 30%| -/-
| ●| ●| | | | -25| -13| 350| 35%| -/-
●| ●| ●| | | | 0| 32| 400| 40%| -/-
| | | ●| | | 25| 77| 450| 45%| -/-
●| | | ●| | | 50| 122| 500| 46%| -/-
| ●| | ●| | | 75| 167| 550| 47%| -/-
| | | | | | 100| 212| 600| 48%| 100
●| ●| | ●| | | 125| 257| 650| 49%| 95
| | ●| ●| | | 150| 302| 700| 50%| 90
●| | ●| ●| | | 175| 347| 750| 51%| 85
| ●| ●| ●| | | 200| 392| 800| 52%| 80
●| ●| ●| ●| | | 225| 437| 850| 53%| 75
| | | | ●| | 250| 482| 900| 54%| 70
●| | | | ●| | 275| 527| 950| 55%| 65
| ●| | | ●| | 300| 572| 1000| 56%| 60
●| ●| | | ●| | 325| 617| 1050| 57%| 55
| | ●| | ●| | 350| 662| 1100| 58%| 50
●| | ●| | ●| | 375| 707| 1150| 59%| 45
| ●| ●| | ●| | 400| 752| 1200| 60%| 40
●| ●| ●| | ●| | 425| 797| 1250| 61%| 35
| | | ●| ●| | 450| 842| 1300| 62%| 30
●| | | ●| ●| | 475| 887| 1400| 63%| 25
| ●| | ●| ●| | 500| 932| 1500| 64%| 20
●| ●| | ●| ●| | 525| 977| 1600| 65%| 15
| | ●| ●| ●| | 550| 1022| 1700| 66%| 10
●| | ●| ●| ●| | 575| 1067| 1800| 67%| 5
| ●| ●| ●| ●| | 600| 1112| 1900| 68%| 0
●| ●| ●| ●| ●| | 625| 1157| 2000| 69%| -5
DIP S2
1| 2| 3| 4| 5| 6| °C| °F| Ω|
Poti| mV
---|---|---|---|---|---|---|---|---|---|---
| | | | | ●| 650| 1202| 2100| 70%| -10
●| | | | | ●| 675| 1247| 2200| 71%| -15
| ●| | | | ●| 700| 1292| 2300| 72%| -20
●| ●| | | | ●| 725| 1337| 2400| 73%| -25
| | ●| | | ●| 750| 1382| 2500| 74%| -30
●| | ●| | | ●| 775| 1427| 2600| 75%| -35
| ●| ●| | | ●| 800| 1472| 2700| 76%| -40
●| ●| ●| | | ●| 825| 1517| 2800| 77%| -45
| | | ●| | ●| 850| 1562| 2900| 78%| -50
●| | | ●| | ●| 875| 1607| 3000| 79%| -55
| ●| | ●| | ●| 900| 1652| 3100| 80%| -60
●| ●| | ●| | ●| 925| 1697| 3200| 81%| -65
| | ●| ●| | ●| 950| 1742| 3300| 82%| -70
●| | ●| ●| | ●| 975| 1787| 3400| 83%| -75
| ●| ●| ●| | ●| 1000| 1832| 3500| 84%| -80
●| ●| ●| ●| | ●| 1025| 1877| 3600| 85%| -85
| | | | ●| ●| 1050| 1922| 3700| 86%| -90
●| | | | ●| ●| 1075| 1967| 3800| 87%| -/-
| ●| | | ●| ●| 1100| 2012| 3900| 88%| -/-
●| ●| | | ●| ●| 1125| 2057| 4000| 89%| -/-
| | ●| | ●| ●| 1150| 2102| 4100| 90%| -/-
●| | ●| | ●| ●| 1175| 2147| 4200| 91%| -/-
| ●| ●| | ●| ●| 1200| 2192| 4300| 92%| -/-
●| ●| ●| | ●| ●| 1225| 2237| 4400| 93%| -/-
| | | ●| ●| ●| 1250| 2282| 4500| 94%| -/-
●| | | ●| ●| ●| 1275| 2327| 4600| 95%| -/-
| ●| | ●| ●| ●| 1300| 2372| 4700| 96%| -/-
●| ●| | ●| ●| ●| 1325| 2417| 4800| 97%| -/-
| | ●| ●| ●| ●| 1350| 2462| 4900| 98%| -/-
●| | ●| ●| ●| ●| 1375| 2507| 5000| 99%| -/-
| ●| ●| ●| ●| ●| 1400| 2552| -/-| 100%| -/-
●| ●| ●| ●| ●| ●| 1425| 2597| Teach In
LED indication
The transmitter has a green and a red/yellow LED on front panel.
LED | Announcement |
---|---|
green | continuous |
green | flashing |
yellow | quick flashing |
yellow | slow double flashing |
red | flashing |
red | continuous |
Error diagnostic function on output
(other output ranges react analogous to the table)
Characteristic| Error| Output| Under range| Over
range| Sensor break / invalid setting
---|---|---|---|---|---
rising
S2-9 OFF
| signalize S2-10 = OFF| 0 … 20 mA
4 … 20 mA
0 … 5 V
0 … 10 V| 0 mA
3.8 mA 0 V 0 V| 20.5 mA
20.5 mA
5.125 V
10.25 V| 22 mA
22 mA
5.5 V 11 V
not signalize S2-10 = ON| 0 … 20 mA
4 … 20 mA
0 … 5 V
0 … 10 V| 0 mA
4 mA
0 V
0 V| 20 mA
20 mA
5 V
10 V| 0 mA
4 mA
0 V
0 V
falling S2-9 ON| signalize S2-10 = OFF| 20 … 0 mA
20 … 4 mA
5 … 0 V
10 … 0 V| 20.5 mA
20.5 mA
5.125 V
10.25 V| 0 mA
3.8 mA 0 V 0 V| 22 mA
22 mA
5.5 V 11 V
not signalize S2-10 = ON| 20 … 0 mA
20 … 4 mA
5 … 0 V
10 … 0 V| 20 mA
20 mA
5 V
10 V| 0 mA
4 mA
0 V
0 V| 0 mA
4 mA
0 V
0V
INOR Process AB , PO Box 9125, SE-200 39 Malmö, Sweden, Phone: +46 40 312
560, Fax: +46 40 312 570,
E-mail: support@inor.se
INOR Transmitter OY, Tuupakantie 3 01740 Vantaa, Finland, Phone:+358 10
421 7900, Fax: +358 10 421 7901,
E-mail: myynti@inor.fi
INOR Transmitter GmbH, Am See 24, D-47279 Duisburg, Germany, Phone: +49-203
7382 762 0, Fax: +49-203 7382 762 2,
E-mail: info@inor-gmbh.de
KROHNE Temperature Division INOR, 55 Cherry Hill Drive, Beverly, MA 01915,
United States, Phone: +1 978 826 6900,
Fax: +1 978 535 1720,
E-mail: inor-info@krohne.com
© INOR 11/2022 – 4009623201 – MA IPAQ R460 R01
All information subject to change without notice.