HELIOS SR750HL Power Supply/ Float Charger for Lead Acid Batteries 750W User Manual

June 9, 2024
HELIOS

HELIOS logo User’s Manual
SR750HL Power Supply/ Float Charger for Lead Acid Batteries 750WHELIOS
SR750HL Power Supply Float Charger for Lead Acid Batteries
750W

SR750HL Power Supply/ Float Charger for Lead Acid Batteries 750W

STANDARD FEATURES

| 3 Relay Alarms-Form C
---|---
| Float Charger –Lead Acid Batteries
| Comms:
• RS232
• RS485
• Modbus RTU
• SNMP V1 & Webpages
| Customizable Digital I/O
| Temperature Sensor on 1.7m lead with adhesive pad: -4mV / °C /cell ±10%
HELIOS SR750HL Power Supply Float Charger for Lead Acid Batteries 750W -
icon 6| N+1 Redundancy
| Rack Mounting
| Internal Meter

SAFETY

The user is responsible for ensuring that input and output wiring segregation complies with local standards and that in the use of the equipment, access is confined to operators and service personnel. A low resistance earth connection is essential to ensure safety and additionally, satisfactory EMI suppression (see below).
HAZARDOUS VOLTAGES EXIST WITHIN A POWER SUPPLY ENCLOSURE AND ANY REPAIRS MUST BE CARRIED OUT BY A QUALIFIED SERVICEPERSON.
Electrical Strength Tests
Components within the power supply responsible for providing the safety barrier between input and output are constructed to provide electrical isolation as required by the relevant standard. However EMI filtering components could be damaged as result of excessively long high voltage tests between input, output and ground. Please contact our technicians for advice regarding electric strength tests.
Earth Leakage
Where fitted, EMC suppression circuits cause earth leakage currents which may be to a maximum of 3.5mA.
Ventilation
High operating temperature is a major cause of power supply failures, for example, a 10°C rise in the operating temperature of a component will halve its expected life. Therefore always ensure that there is adequate ventilation for the equipment. Batteries in particular suffer shortened lifetimes if subjected to high ambient temperatures.
Water / Dust
Every effort must be made in the installation to minimise the risk of ingress of water or dust. Water will almost always cause instant failure. The effects of dust are slower in causing failure of electronic equipment but all electrical equipment should be cleaned free of any dust accumulation at regular intervals.
Electromagnetic Interference (EMI)
Switching power supplies and converters inherently generate electrical noise. All wiring should be as short as practicable and segregated from all equipment wiring which is sensitive to EMI. Residual noise can be reduced by looping DC wiring through ferrite cores (sleeves). These are most effective as close to the power supply as possible and as many turns of the wire taken through the core (+ and – in the same direction) as the core will accommodate.
External fuse protection
Fuses or circuit breakers must be used in all battery circuits to protect against short circuits. External fuses should be used for power supplies/ chargers even though they are usually internally protected.
Connection polarity
It is critical to check the polarity carefully when connecting DC devices even with models which have non-destructive reverse polarity protection.
Glossary of terms used in our user manuals
PSU = power supply unit
BCT = battery condition test
ECB = electronic circuit breaker
ELVD = electronic low voltage disconnect
RPP = reverse polarity protection
EMI = electromagnetic interference
SNMP = Simple Network Management Protocol
EMC = Electromagnetic compatibility
DOD = depth of discharge

INTRODUCTION:

The SR750HL range is designed for use as a reliable and stable AC to DC power supply, or float charger for lead acid batteries.
Note that for float charging the output voltage must be set to approximately 15% above the nominal battery voltage models. This is done as the default voltage for the 12V model but must be specified at time of order for all higher voltage models.

FRONT & BACK PANEL LAYOUT

HELIOS SR750HL Power Supply Float Charger for Lead Acid Batteries 750W -
FRONT & BACK PANEL LAYOUT

  1. AC INPUT IEC60320 – C13 10A

  2. Digital Inputs (pins 1,2)/ Input or Output (pin 3)/ Return (pin 4) I/O terminals are customizable and if used, the product will have a unique code.

  3. ALARMS RELAY FORM C: Relay contacts shown in de-energised state (ie. When there is a fault condition). Alarm relays are energised when power supply is operating normally, eg. “Power” alarm relay is energised when input voltage present.
    • DC HIGH: DC Output High.
    • POWER: Loss of mains input power. This alarm has 30 seconds delay before activation upon mains failure. PSU fails
    • DC LOW: DC Output Low or Battery voltage low if used as a charger.
    • Fan Fail/Stall: There are two fans inside the SR750HL unit and will give an alarm with one or both of the fan is stalled or failed. When fan is stall/fail alarm occurs is display through the DC high alarm relay ( DC high relay will toggle every 5 seconds) and slow flashing of the POWER OK LED. If a fan fail/stall occurs at the same time as DC High, the relay will activate like normal, but every 5 seconds it will toggle showing fan fail/stall alarm.

  4. DC CONNECTIONS: M8 brass stud (shown on the picture above ), plug-in style phoenix socket & mating screw terminal and plugin style Anderson connector options. Where screw/plug in terminals are fitted both terminals must be used if the power supply current exceeds 20A. This is to ensure that the current rating.

HELIOS SR750HL Power Supply Float Charger for Lead Acid Batteries 750W -
Plug-in style Phoenix DC Terminals

LED INDICATIONS CODE

DC OK: DC output is present, either from PSU or battery
POWER OK: Mains fail and/ Or internal PSU fail.
STANDBY: Power supply unit off

DC OK POWER OK STANDBY Condition
System Normal: Input power on, Battery output levels ok
DC Output Low: Input power on and battery has discharged to < Battery

Low
| | | DC Output High: Input power on, Battery output high
| | | Mains fail: No mains and battery output levels low
| | | Fan fail/stall: Input power on and DC OK. The Power OK LED will slow flash during this 5 second period
| | | Fan fail/stall and DC High alarm on: DC OK LED will fast flash to show DC high alarm. Power OK LED will slow flash to show fan fait/stall
| | | PSU is in standby: Turns the output of the power supply off. If there is a battery connected, the DC OK LED remains on even though the power supply in turned off ( except for -P versions with output diode)
| | | PSU is in standby and battery has discharged to < Battery Low

HELIOS SR750HL Power Supply Float Charger for Lead Acid Batteries 750W -
icon 13

ALARM TERMINAL LAYOUT

HELIOS SR750HL Power Supply Float Charger for Lead Acid Batteries 750W -
ALARM TERMINAL LAYOUTRelay contacts shown in de-energised state ( ie when there is a fault condition). Alarm relay are energised when power supply is operating normally.
DC OK alarm indicates either DC low or DC high.

COMMS PORT

Note: A battery is required on the output for the communications to continue working in the event of an input/internal converter failure.

FG – FRAME GROUND

Where provided this terminal provides a connection to the metal case for earthing.

MODEL CODING AND OPTIONS

HELIOS SR750HL Power Supply Float Charger for Lead Acid Batteries 750W -
MODEL CODING AND OPTIONS

N+1 REDUNDANCY

An external diode is required for N+1 redundancy or parallel applications. A diode and DC Power Supply can be installed in a 2U Rack as shown in the picture below. Please contact our sales technical engineers so we can configure a DC Power Solution according your specific requirements. HELIOS
SR750HL Power Supply Float Charger for Lead Acid Batteries 750W - N+1
REDUNDANCY

CONNECTION NOTES

  • The models with the screw/unpluggable connectors have two terminals per polarity, each one is rated at 20A and so when the load current exceeds 20A both terminals must be used.
  • If used as a battery charger ensure that the battery polarity matches the power supply /charging output.
  • Alarms can be tested by using an external variable voltage supply.

TECHNICAL SPECIFICATIONS

Output power 750W (0-50°C )
Input Voltage 180V – 264VAC 45-65Hz
Output Voltages 88V – 132VAC   45-65Hz ( Optional)
Voltage Adj. Range 13.8V, 24, 30V, 36V, 48 V Other voltages by request
Fusing/ protection 85% – 120% of Vnominal
Overcurrent protection Input fuse and Varistor
Isolation Constant current limit under overload and short circuit conditions

Input – earth – 2.5KVdc
Efficiency| Output – earth – 750Vdc
Inrush Current| > 85%
Operating temperature| Soft start circuit
Humidity| -20  to 50 °C ambient at full load
OVP| 0 – 95% relative humidity non – condensing
Cooling| Over-voltage protection on output at 130% of nominal output voltage
LED Indication| Dual Fan Cooled
Green: DC OK
Green: Power OK
Flash code for different operating states
Alarms Relay| Form C contacts changeover, rated 30VDC,2A/110VDC,0.3A/125VAC,0.5A
30VDC, 2A/110VDC, 0.3A, 125VAC, 0.5A
DC High ( Fan fail/stall (toggle every 5 sec))
POWER  (mains fail, PSU fail)
DC Low
Line Regulation| <0.2% over AC input range
Load Regulation| <0.4% open circuit to 100% load
Noise| <1%

OPTIONS

Optional Input Voltage 88 – 132 VAC
Optional DC Input Voltage 110VDC (88V – 135VDC)

Please note that an external fuse or MCB
must be fitted on the output for short circuit protection.
Communication Port| RS232 (ASCII)
RS485 (ASCII)
Modbus RTU
SNMP, Webpages
Digital Inputs/Outputs| Digital Input (pins 1,2) / Input or Output (pin 3) / Return (pin 4)
Temp. Compensation| Temperature sensor on 1.7m lead with adhesive pad: -4mV / °C / cell ±10%
Internal Meter| Internal V/I meter displaying PSU operating states and analogue
Mounting| Standalone
19”Rack Mount – Optional V/I meter for subrack : SR-Meter
N+1 Redundancy| Using 2 chargers each with its own battery & output diodes
Conformal Coating| For harsh environments

PHYSICAL

AC input connector IEC60320— C13 10A input socket (similar to PCs etc)
DC Connections • M8 brass stud

• Plug-in style phoenix socket & mating screw terminal
• Anderson plug-in style connectors
Alarm connections| Plug in screw terminal block
Enclosure| Zinc plated & powder coated steel
Dimensions| 225W x 304D x 70H (± 1mm)
Weight| 3.85 Kg

STANDARDS

EMC To CISPR 22 / EN55022 Class A
Safety To IEC950  / EN60950 / AS/NZS3260

H-SERIES INTERNAL METER OPTION

SR500H & SR750H L & I models both have the internal meter option and the parameters displayed vary depending on the model.
The H-Series internal meter shows the status of the PSU and Battery (just for HI models) which has certain meanings. Check below each one of them to understand the information displayed. HELIOS SR750HL Power Supply Float
Charger for Lead Acid Batteries 750W - displayH-Series internal meter example display
SR500/750HL model with Internal meter:
Code A:
CC – charge cycle (normal operation)
MF – mains fail (mains failure, system on battery power)
OL – system overloaded, output voltage is below Vpres setting
Code B:
M? – possible mains fail, ie. No mains detected but brown out timer not expired (30sec)
BP – System OK
BM – DC Low alarm
BL – DC High alarm
Displayed values following Code B:
Vout = output voltage of PSU
Ibat = for HL models (2 terminal DC Power Supply) it will be always 0.
Ipsu = Total PSU output current
+20°C = temperature measured by temp. sensor

CUSTOMISED MODELS

MODEL CODE BASE MODEL SPECIAL FEATURES
CSR228 SR750HL48FXL Internal V/I meter, output voltage set to  56.4V
CSR229 SR750HL24TFSL Internal V/I meter
CSR236 SR750HL24TFXL-485 Internal V/I meter

TERMS OF WARRANTY

Helios Power Solutions warrants this product for 24 months from date of shipment against material and workmanship defects. Liability under this warranty is limited to the replacement or repair of the defective product as long as the product has not been damaged through misapplication, negligence, or unauthorized modification or repair.