User’s Manual
SR750HL Power Supply/ Float Charger for Lead Acid Batteries 750W
SR750HL Power Supply/ Float Charger for Lead Acid Batteries 750W
STANDARD FEATURES
| 3 Relay Alarms-Form C
---|---
| Float Charger –Lead Acid Batteries
| Comms:
• RS232
• RS485
• Modbus RTU
• SNMP V1 & Webpages
| Customizable Digital I/O
| Temperature Sensor on 1.7m lead with adhesive pad: -4mV / °C /cell ±10%
| N+1 Redundancy
| Rack Mounting
| Internal Meter
SAFETY
The user is responsible for ensuring that input and output wiring segregation
complies with local standards and that in the use of the equipment, access is
confined to operators and service personnel. A low resistance earth connection
is essential to ensure safety and additionally, satisfactory EMI suppression
(see below).
HAZARDOUS VOLTAGES EXIST WITHIN A POWER SUPPLY ENCLOSURE AND ANY REPAIRS MUST
BE CARRIED OUT BY A QUALIFIED SERVICEPERSON.
Electrical Strength Tests
Components within the power supply responsible for providing the safety
barrier between input and output are constructed to provide electrical
isolation as required by the relevant standard. However EMI filtering
components could be damaged as result of excessively long high voltage tests
between input, output and ground. Please contact our technicians for advice
regarding electric strength tests.
Earth Leakage
Where fitted, EMC suppression circuits cause earth leakage currents which may
be to a maximum of 3.5mA.
Ventilation
High operating temperature is a major cause of power supply failures, for
example, a 10°C rise in the operating temperature of a component will halve
its expected life. Therefore always ensure that there is adequate ventilation
for the equipment. Batteries in particular suffer shortened lifetimes if
subjected to high ambient temperatures.
Water / Dust
Every effort must be made in the installation to minimise the risk of ingress
of water or dust. Water will almost always cause instant failure. The effects
of dust are slower in causing failure of electronic equipment but all
electrical equipment should be cleaned free of any dust accumulation at
regular intervals.
Electromagnetic Interference (EMI)
Switching power supplies and converters inherently generate electrical noise.
All wiring should be as short as practicable and segregated from all equipment
wiring which is sensitive to EMI. Residual noise can be reduced by looping DC
wiring through ferrite cores (sleeves). These are most effective as close to
the power supply as possible and as many turns of the wire taken through the
core (+ and – in the same direction) as the core will accommodate.
External fuse protection
Fuses or circuit breakers must be used in all battery circuits to protect
against short circuits. External fuses should be used for power supplies/
chargers even though they are usually internally protected.
Connection polarity
It is critical to check the polarity carefully when connecting DC devices even
with models which have non-destructive reverse polarity protection.
Glossary of terms used in our user manuals
PSU = power supply unit
BCT = battery condition test
ECB = electronic circuit breaker
ELVD = electronic low voltage disconnect
RPP = reverse polarity protection
EMI = electromagnetic interference
SNMP = Simple Network Management Protocol
EMC = Electromagnetic compatibility
DOD = depth of discharge
INTRODUCTION:
The SR750HL range is designed for use as a reliable and stable AC to DC power
supply, or float charger for lead acid batteries.
Note that for float charging the output voltage must be set to
approximately 15% above the nominal battery voltage models. This is done as
the default voltage for the 12V model but must be specified at time of order
for all higher voltage models.
FRONT & BACK PANEL LAYOUT
-
AC INPUT IEC60320 – C13 10A
-
Digital Inputs (pins 1,2)/ Input or Output (pin 3)/ Return (pin 4) I/O terminals are customizable and if used, the product will have a unique code.
-
ALARMS RELAY FORM C: Relay contacts shown in de-energised state (ie. When there is a fault condition). Alarm relays are energised when power supply is operating normally, eg. “Power” alarm relay is energised when input voltage present.
• DC HIGH: DC Output High.
• POWER: Loss of mains input power. This alarm has 30 seconds delay before activation upon mains failure. PSU fails
• DC LOW: DC Output Low or Battery voltage low if used as a charger.
• Fan Fail/Stall: There are two fans inside the SR750HL unit and will give an alarm with one or both of the fan is stalled or failed. When fan is stall/fail alarm occurs is display through the DC high alarm relay ( DC high relay will toggle every 5 seconds) and slow flashing of the POWER OK LED. If a fan fail/stall occurs at the same time as DC High, the relay will activate like normal, but every 5 seconds it will toggle showing fan fail/stall alarm. -
DC CONNECTIONS: M8 brass stud (shown on the picture above ), plug-in style phoenix socket & mating screw terminal and plugin style Anderson connector options. Where screw/plug in terminals are fitted both terminals must be used if the power supply current exceeds 20A. This is to ensure that the current rating.
LED INDICATIONS CODE
DC OK: DC output is present, either from PSU or battery
POWER OK: Mains fail and/ Or internal PSU fail.
STANDBY: Power supply unit off
DC OK | POWER OK | STANDBY | Condition |
---|---|---|---|
System Normal: Input power on, Battery output levels ok | |||
DC Output Low: Input power on and battery has discharged to < Battery |
Low
| | | DC Output High: Input power on, Battery output high
| | | Mains fail: No mains and battery output levels low
| | | Fan fail/stall: Input power on and DC OK. The Power OK LED will slow
flash during this 5 second period
| | | Fan fail/stall and DC High alarm on: DC OK LED will fast flash to show
DC high alarm. Power OK LED will slow flash to show fan fait/stall
| | | PSU is in standby: Turns the output of the power supply off. If there is
a battery connected, the DC OK LED remains on even though the power supply in
turned off ( except for -P versions with output diode)
| | | PSU is in standby and battery has discharged to < Battery Low
ALARM TERMINAL LAYOUT
Relay contacts shown in de-energised state ( ie when there
is a fault condition). Alarm relay are energised when power supply is
operating normally.
DC OK alarm indicates either DC low or DC high.
COMMS PORT
- RS232 (ASCII) https://www.heliosps.com/sr-series-downloads/#rs232-rs485-commands-sr-series
- RS485 (ASCII) https://www.heliosps.com/sr-series-downloads/#rs232-rs485-commands-sr-series
- Modbus RTU https://www.heliosps.com/sr-series-downloads/#serial-modbus-rtu-sr-series
- SNMP, Webpages https://www.heliosps.com/sr-series-downloads/#snmp-sr-series
Note: A battery is required on the output for the communications to continue working in the event of an input/internal converter failure.
FG – FRAME GROUND
Where provided this terminal provides a connection to the metal case for earthing.
MODEL CODING AND OPTIONS
N+1 REDUNDANCY
An external diode is required for N+1 redundancy or parallel applications. A diode and DC Power Supply can be installed in a 2U Rack as shown in the picture below. Please contact our sales technical engineers so we can configure a DC Power Solution according your specific requirements.
CONNECTION NOTES
- The models with the screw/unpluggable connectors have two terminals per polarity, each one is rated at 20A and so when the load current exceeds 20A both terminals must be used.
- If used as a battery charger ensure that the battery polarity matches the power supply /charging output.
- Alarms can be tested by using an external variable voltage supply.
TECHNICAL SPECIFICATIONS
Output power | 750W (0-50°C ) |
---|---|
Input Voltage | 180V – 264VAC 45-65Hz |
Output Voltages | 88V – 132VAC 45-65Hz ( Optional) |
Voltage Adj. Range | 13.8V, 24, 30V, 36V, 48 V Other voltages by request |
Fusing/ protection | 85% – 120% of Vnominal |
Overcurrent protection | Input fuse and Varistor |
Isolation | Constant current limit under overload and short circuit conditions |
Input – earth – 2.5KVdc
Efficiency| Output – earth – 750Vdc
Inrush Current| > 85%
Operating temperature| Soft start circuit
Humidity| -20 to 50 °C ambient at full load
OVP| 0 – 95% relative humidity non – condensing
Cooling| Over-voltage protection on output at 130% of nominal output voltage
LED Indication| Dual Fan Cooled
Green: DC OK
Green: Power OK
Flash code for different operating states
Alarms Relay| Form C contacts changeover, rated
30VDC,2A/110VDC,0.3A/125VAC,0.5A
30VDC, 2A/110VDC, 0.3A, 125VAC, 0.5A
DC High ( Fan fail/stall (toggle every 5 sec))
POWER (mains fail, PSU fail)
DC Low
Line Regulation| <0.2% over AC input range
Load Regulation| <0.4% open circuit to 100% load
Noise| <1%
OPTIONS
Optional Input Voltage | 88 – 132 VAC |
---|---|
Optional DC Input Voltage | 110VDC (88V – 135VDC) |
Please note that an external fuse or MCB
must be fitted on the output for short circuit protection.
Communication Port| RS232 (ASCII)
RS485 (ASCII)
Modbus RTU
SNMP, Webpages
Digital Inputs/Outputs| Digital Input (pins 1,2) / Input or Output (pin 3) /
Return (pin 4)
Temp. Compensation| Temperature sensor on 1.7m lead with adhesive pad: -4mV /
°C / cell ±10%
Internal Meter| Internal V/I meter displaying PSU operating states and
analogue
Mounting| Standalone
19”Rack Mount – Optional V/I meter for subrack : SR-Meter
N+1 Redundancy| Using 2 chargers each with its own battery & output diodes
Conformal Coating| For harsh environments
PHYSICAL
AC input connector | IEC60320— C13 10A input socket (similar to PCs etc) |
---|---|
DC Connections | • M8 brass stud |
• Plug-in style phoenix socket & mating screw terminal
• Anderson plug-in style connectors
Alarm connections| Plug in screw terminal block
Enclosure| Zinc plated & powder coated steel
Dimensions| 225W x 304D x 70H (± 1mm)
Weight| 3.85 Kg
STANDARDS
EMC | To CISPR 22 / EN55022 Class A |
---|---|
Safety | To IEC950 / EN60950 / AS/NZS3260 |
H-SERIES INTERNAL METER OPTION
SR500H & SR750H L & I models both have the internal meter option and the
parameters displayed vary depending on the model.
The H-Series internal meter shows the status of the PSU and Battery (just for
HI models) which has certain meanings. Check below each one of them to
understand the information displayed. H-Series internal meter example display
SR500/750HL model with Internal meter:
Code A:
CC – charge cycle (normal operation)
MF – mains fail (mains failure, system on battery power)
OL – system overloaded, output voltage is below Vpres setting
Code B:
M? – possible mains fail, ie. No mains detected but brown out timer not
expired (30sec)
BP – System OK
BM – DC Low alarm
BL – DC High alarm
Displayed values following Code B:
Vout = output voltage of PSU
Ibat = for HL models (2 terminal DC Power Supply) it will be always 0.
Ipsu = Total PSU output current
+20°C = temperature measured by temp. sensor
CUSTOMISED MODELS
MODEL CODE | BASE MODEL | SPECIAL FEATURES |
---|---|---|
CSR228 | SR750HL48FXL | Internal V/I meter, output voltage set to 56.4V |
CSR229 | SR750HL24TFSL | Internal V/I meter |
CSR236 | SR750HL24TFXL-485 | Internal V/I meter |
TERMS OF WARRANTY
Helios Power Solutions warrants this product for 24 months from date of shipment against material and workmanship defects. Liability under this warranty is limited to the replacement or repair of the defective product as long as the product has not been damaged through misapplication, negligence, or unauthorized modification or repair.
New Zealand: sales@heliosps.co.nz
Australia: sales@heliosps.com.au
Middle East & Asia: sales@heliosps.asia
References
- Helios Power Solutions International - DC Solutions Partner
- SR Series - Downloads | Helios Power Solutions International
- SR Series - Downloads | Helios Power Solutions International
- SR Series - Downloads | Helios Power Solutions International