HELIOS SR250HI Series 250W DC UPS User Manual
- June 9, 2024
- HELIOS
Table of Contents
- SR250HI Series 250W DC UPS
- SAFETY
- INTRODUCTION:
- SR250HI Series – SYSTEM BLOCK DIAGRAM
- OPERATION OF ELECTRONIC CIRCUIT BREAKER (ECB) FOR PROTECTION OF BATTERY
- BACK & FRONT PANEL LAYOUT
- CONNECTION AND INITIAL TESTING
- LED INDICATION
- SR250HI DC SETTINGS
- MOUNTING DETAILS
- SR250HI CONNECTIONS – Typical Examples
- MODEL CODING AND OPTIONS
- TECHNICAL SPECIFICATIONS
- CUSTOMISED MODELS
- TERMS OF WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
User’s Manual
SR250HI Series – 250W DC UPS
No-Break™
DC UPS
SR250HI Series 250W DC UPS
STANDARD FEATURES | OPTIONAL FEATURES |
---|---|
3 Relay Alarms-Form C |
• RS232
• RS485
• Modbus RTU
• SNMP V1 & Webpages
| Float Charger –Lead Acid Batteries| | Customizable Digital I/O
| Temperature Sensor on 1.7m lead with adhesive
pad: -4mV / °C /cell ±10%| | BCT: Battery Condition Test.
| ELVD : Electronic low voltage disconnect| | N+1 Redundancy
SAFETY
The user is responsible for ensuring that input and output wiring segregation
complies with local standards and that in the use of the equipment, access is
confined to operators and service personnel. A low resistance earth connection
is essential to ensure safety and additionally, satisfactory EMI suppression
(see below).
HAZARDOUS VOLTAGES EXIST WITHIN A POWER SUPPLY ENCLOSURE AND ANY REPAIRS MUST
BE CARRIED OUT BY A QUALIFIED SERVICEPERSON.
Electrical Strength Tests
Components within the power supply responsible for providing the safety
barrier between input and output are constructed to provide electrical
isolation as required by the relevant standard. However EMI filtering
components could be damaged as result of excessively long high voltage tests
between input, output and ground. Please contact our technicians for advice
regarding electric strength tests.
Earth Leakage
Where fitted, EMC suppression circuits cause earth leakage currents which may
be to a maximum of 3.5mA.
Ventilation
High operating temperature is a major cause of power supply failures, for
example, a 10°C rise in the operating temperature of a component will halve
its expected life. Therefore always ensure that there is adequate ventilation
for the equipment. Batteries in particular suffer shortened lifetimes if
subjected to high ambient temperatures.
Water / Dust
Every effort must be made in the installation to minimise the risk of ingress
of water or dust. Water will almost always cause instant failure. The effects
of dust are slower in causing failure of electronic equipment but all
electrical equipment should be cleaned free of any dust accumulation at
regular intervals.
Electromagnetic Interference (EMI)
Switching power supplies and converters inherently generate electrical noise.
All wiring should be as short as practicable and segregated from all equipment
wiring which is sensitive to EMI. Residual noise can be reduced by looping DC
wiring through ferrite cores (sleeves). These are most effective as close to
the power supply as possible and as many turns of the wire taken through the
core (+ and – in the same direction) as the core will accommodate.
External fuse protection
Fuses or circuit breakers must be used in all battery circuits to protect
against short circuits. External fuses should be used for power supplies/
chargers even though they are usually internally protected.
Connection polarity
It is critical to check the polarity carefully when connecting DC devices even
with models which have non-destructive reverse polarity protection.
Glossary of terms used in our user manuals
PSU = power supply unit
ELVD = electronic low voltage disconnect
SNMP = Simple Network Management Protocol| BCT = battery condition test
RPP = reverse polarity protection
EMC = Electromagnetic compatibility| ECB = electronic circuit breaker
EMI = electromagnetic interference
DOD = depth of discharge
---|---|---
INTRODUCTION:
The No-Break ™DC SR250Hi switch mode power supply is designed to provide DC power to lead acid batteries for critical back up applications.No-Break ™ DC UPS systems maximise the integrity of standby battery installations, whilst optimising the life and availability of back up batteries.
SR250HI Series – SYSTEM BLOCK DIAGRAM
OPERATION OF ELECTRONIC CIRCUIT BREAKER (ECB) FOR PROTECTION OF BATTERY
CIRCUIT & BATTERY
The ECB will operate on overcurrent as above & is also activated for the low voltage disconnect function on mains fail (no input power). It will reset when input power is restored, or can be manually reset by briefly shorting the BAT- and LOAD- terminals together when there is no input power.
BACK & FRONT PANEL LAYOUT
-
AC INPUT IEC60320 – C13 10A
-
Digital Inputs (pins 1,2)/ Input or Output (pin 3)/ Return (pin 4) I/O terminals are customizable and if used, the product will have a unique code.
-
ALARMS RELAY FORM C
AUX : Activated by BCT ( Battery Condition Test)
POWER (Mains Fail):
• Loss of mains input power. This alarm has 30 seconds delay before activation upon mains failure.
• PSU fails
BATTERY:
• Battery Low: 1.8V/cell (for 2V cells) – operates only when no mains power present.
• Battery Missing or fault in battery circuit wiring (alarm does not activate for up to battery detection interval time.
• BCT fail -
LOAD & BATTERY CONNECTION
-
Front Panel LEDS ( For full list of LED flash codes please refer to the next page)
Battery OK: LED on: Battery present and above V batl
Power OK: LED on: Charger output present. LED off: no mains input or charger in standby mode
Standby: LED on: Charger in standby mode ( no output from charger) -
Comms Port (if installed) , for models with communications please refer to
• RS232 (ASCII) https://www.heliosps.com/sr-series-downloads/#rs232-rs485 -commands-sr-series
• RS485 (ASCII) https://www.heliosps.com/sr-series-downloads/#rs232-rs485 -commands-sr-series
• Modbus RTU https://www.heliosps.com/sr-series-downloads/#serial-modbus-rtu- sr-series
• SNMP, Webpages https://www.heliosps.com/sr-series-downloads/#snmp-sr- series
NOTES
Reverse polarity protection
If the battery is connected in reverse, the internal battery protection fuse
may be ruptured and the unit should be returned to the manufacturer for
repair. If the fuse is
good, the voltage measured as at step 3 above should be exactly the same on
boththe oad and battery outputs.
CONNECTION AND INITIAL TESTING
- Check input and output voltages of system, ensure that they match the equipment. All loads should be isolated.
- Check polarity of all wiring. Place temperature sensor probe near or on batteries.
- Plug in ac input and turn power on. Both LEDs will light up after approx. 4 sec, “BATT OK” LED will go out after another 10 secs (since there is no battery connected). DC output voltage should appear at both load and battery outputs (ensure screws are tightened down on the connector block).
- Turn off input power.
- Connect battery.
- Check that ELCB (internal electronic circuit breaker) closes by shorting together the BATTERY –ve and LOAD –ve terminals for about 2-3 sec. You will hear a relay operate and both LEDs will light up. If this does not happen, there is a fault in the wiring or the internal battery protection fuse is ruptured (see Note 2 below). The battery voltage will then appear at the load terminals and the “BATTERY OK” relay energises. The “POWER OK” LED stays on for about 30 seconds.
- Connect load wiring to LOAD+ and LOAD- terminals. Check that the load does not exceed 110% of the unit. Any peak loads which are > 110% must be connected to the B+ and B-terminals.
- Turn on ac power.
- After the batteries are fully charged, check that the battery continues to power up the load when the input power is turned off.
LED INDICATION
Power
OK LED| Battery OK LED| Power
Alarm| Battery
Low Alarm| Condition
---|---|---|---|---
| | Normal| Normal| System Normal: AC power is on, PSU output is OK, battery
circuit is OK and battery voltage is > V Battery Low.
| | Normal| Normal| Battery detection test imminent (LED begins flashing prior
to test ).
| | Normal| Alarm| System AC power is on, PSU output is OK but either:
1. Internal battery fuse has opened (only if battery has been reverse
polarity connected), or
2. Battery circuit open – battery missing, or fuse / circuit breaker / wiring
fault.
| | Alarm| Normal| Either AC power has failed, or PSU has failed. Battery
system is OK
| | Alarm| Alarm| AC Power is off / DC has failed and battery has discharged
to < V Battery Low, unit will continue delivering battery current until low
level initiates ELVD.
| | Alarm| Alarm| AC Power is off / DC has failed and ELVD has activated and
disconnected battery from load. Residual current drain on battery following
ELVD <1 mA.
| | Normal| Normal| Battery Condition Test is in progress: LEDs flash
alternately
| | Normal| Alarm| Battery Condition Unserviceable: failed to maintain
terminal voltage during battery condition test
SR250HI DC SETTINGS
Parameter| Nominal Voltage| Default
Value
---|---|---
12V| 24V| 30V| 36V| 48V
V out = Output voltage| 14.| 28.| 35.| 41.| 55.| 2.3V/cell
V pres = Voltage threshold for battery detection & battery condition test
(BCT). If voltage drops to this level during BCT then the test is aborted and
a BATLOW alarm generated| 12.| 24.| 31.| 37.| 49.| 2.03V/cell
V shutd = Output voltage of PSU during battery detection & BCT| 12.| 23| 29.|
35.| 46| 1.92V/cell
V bad = Battery voltage when BATLOW alarm generated during mains fail| 11| 22|
28.| 33| 44| 1.84V/cell
V disco = Battery disconnect voltage during mains fail| 10| 20| 25| 30| 40|
1.66V/cell
Bccl = Maximum charge current as % of rated PSU rated current| 100% •4
Comms = communications mode of PSU: F = continuous data stream of status M =
responds only to request made by a control-ler| F
BatDetect = Battery detection Interval time, active only when no battery
charge current is detected (the unit may not detect a missing battery for up
to this time)| 60 min
BCT Jumper: if fitted automatic BCT is enabled| Not fitted
BCT = length of battery condition test| 20 min
Ret = retest option: N = after a failed BCT further scheduled Bas are
inhibited Y = after a failed BCT further scheduled Bas will be allowed| Y
3 CC = Length of charge cycle in minutes/hours/days. ie. time between battery condition tests| 40m/23h/
027d
3 MfiBCT = time before mains fail check during BCT. A mains fall during a BCT will stop the BCT. if set longer than BCT time no
mains fail check will occur.| 030 min
MOUNTING DETAILS
SR250HI CONNECTIONS – Typical Examples
- Standard No-Break™DC charger and battery bank
This is the basic connection which is most commonly used, and provides adequate protection for the majority of systems requiring DC back up in the event of a mains power failure.
Alarms Available|
---|---
Input Fail| YES
Battery Missing| YES
Battery Low| YES
Battery Condition Test Fail| YES
Note: On stud connected output models the L+/B+ is one stud labelled “+ COMMON”
- Peak load connection using No-Break™DC charger
Peak loads which may exceed 1.5 x max. charger output can be connected to bypass the internal overcurrent trip circuit.
Alarms Available|
---|---
Input Fail| YES
Battery Missing| YES
Battery Low| YES
Battery Condition Test Fail| YES
- N+1 connection using two complete No-Break™DC systems with each one capable of supplying the loads- positive common
Alarms available|
---|---
Power OK| YES
Battery missing| YES
Battery low| YES
Battery condition test fail *1| YES
*1 interlock circuit required for automated BCT
MODEL CODING AND OPTIONS
TECHNICAL SPECIFICATIONS
Output power | 250W |
---|---|
Input Voltage | 180V – 264VAC & 88V-132VAC 45-65Hz |
Output Voltages | 12V, 24V, 30V, 36V, 48 VDC |
Voltage Atli. Range | 85%- 120% of Vnominal |
Overcurrent protection | Constant current limit under overload and short |
circuit conditions
Isolation| Input – earth – 2.5KVdc Output- earth – SO0Vdc
Efficiency| > 85%
Operating temperature| -20 to 50 *C ambient at full load
Humidity| 0 – 95% relative humidity non – condensing
Cooling| Natural convection except for 12 V model (fan)
LVD| Low Voltage Disconnect
LED Indication| Green: Batt OK Green: Power OK Red: Standby
Alarms Relay| Form C contacts 30VDC,2A/110VDC,0.3A,125VAC, 0.5A AUX (Activated
by BC7)
POWER (main falls, PSI) fails)
BATTERY (bait missing, bait low, BCT fail)
Temp. Compensation| Temperature sensor On 1.7m lead with adhesive pad: -4mV/
t/ cell ± 10%
Battery Charge Current Limit| Customizable on request.
Reverse Polarity| Battery reverse connection will open internal fuse (and
produce alarm)
Mon
BatteryMonitoring| Detects for presence of battery on start up, then every 60
minutes when charge current < 200mA
Battery Circuit Protection| Electronic circuit breaker (ECB) operates under
the following conditions:
| – Low Battery Volts: Battery Voltage drops to 1.67V/cell
| Overload: Max load must not exceed 110% of rated current. Peak loads must be
connected to B. & B- terminals. (Not suitable for N♦1 connection)
| Short Circuit: <2ms, backed up by fuse
Standby Mode| Turns off DC output of PSU & allows load to run off battery
Line Regulation| < 0.2% over AC Input range
Load Regulation| < 0.4% open circuit to 100% load
Noise| < 1% output voltage
Thermal Protection| Yes, self-resetting
Hold-up Time| 15 – 20 ms (nom – max. Vin) without battery
AC Input connector| IEC60320— C13 10A input sod<et (similar to PCs etc)
DCConnections| Plug-in style socket & mating screw terminal block: (max. wire
2.5mm’ / way) or M6 brass stud
Alarm connections| Plug in screw terminal block
Enclosure| Zinc plated & powder coated steel
Dimensions| 242W x 150Dx 61H (± 1mm)
Weight| 1.8 Kg
STANDARDS
EMC | To CISPR 22 / EN55022 class A |
---|---|
Safety | To IEC950 / EN60950 / AS/NZS3260 |
CUSTOMISED MODELS
Model code | BASE MODEL | SPECIAL FEATURES |
---|---|---|
CSR171 | SR250HI24TFXL | BCT enabled 1hr/ 7days |
CSR159 | SR250HI12TFSL | BCT enabled 20mins/ 28days, V pres = 12V |
CSR200 | SR250HI12TFSL | No fan, rated output at 50degC = 210W |
TERMS OF WARRANTY
Helios Power Solutions warrants this product for 24 months from date of shipment against material and workmanship defects. Liability under this warranty is limited to the replacement or repair of the defective product as long as the product has not been amaged through misapplication, negligence, or unauthorized modification or repair.
w Zealand: sales@heliosps.co.nz –
Australia: sales@heliosps.com.au –
Middle East & Asia: sales@heliosps.asia
12121212
References
- applications.no
- SR Series - Downloads | Helios Power Solutions International
- SR Series - Downloads | Helios Power Solutions International
- SR Series - Downloads | Helios Power Solutions International