HELIOS Monitoring Inview S With Measure Box Battery User Manual
- June 9, 2024
- HELIOS
Table of Contents
Monitoring Inview S With Measure Box Battery
MONITORING INVIEW S
WITH MEASURE BOX BATTERY
User Manual V2.1
THE NEW GENERATION OF MONITORING
· WEB-BASED USER INTERFACE · EXTENDED LOG CAPABILITIES · IN BUILT DISPLAY
AU: sales@heliosps.com.au NZ: sales@heliosps.co.nz Asia & ME:
sales@heliosps.asia
Table of content
1. HELIOS at a glance ………………………………………………………………………………………………………………….. 5
2. Abbreviations ………………………………………………………………………………………………………………………. 6
3. Warranty and Safety Conditions ………………………………………………………………………………………………. 7 3.1
Disclaimer ………………………………………………………………………………………………………………….. 7 3.2 Technical care
…………………………………………………………………………………………………………….. 7 3.3 Installation
…………………………………………………………………………………………………………………. 8 3.3.1
Handling…………………………………………………………………………………………………………. 8 3.3.2 Surge and transients
………………………………………………………………………………………… 8 3.3.3
Other……………………………………………………………………………………………………………… 8 3.4 Pre-cautions before
maintenance ………………………………………………………………………………….. 9 3.5 Replacement and
Dismantling ……………………………………………………………………………………….. 9
4. Introduction …………………………………………………………………………………………………………………………. 10 4.1 Inview
S…………………………………………………………………………………………………………………….. 10 4.2 Inview S Slot
………………………………………………………………………………………………………………. 10 4.3 Inview S – Specifications
………………………………………………………………………………………………. 11 4.4
Accessories………………………………………………………………………………………………………………… 12 4.4.1 Measure Box
Battery (MBB)……………………………………………………………………………….. 12 4.4.2 Measure Box DC loads
(MBDC)…………………………………………………………………………… 13
5. Installation …………………………………………………………………………………………………………………………… 14 5.1 Site
preparation…………………………………………………………………………………………………………… 14 5.2 Mounting – Inview
S …………………………………………………………………………………………………….. 14 5.2.1 Panel Mounting
……………………………………………………………………………………………….. 14 5.3 Installing – Inview S Slot
……………………………………………………………………………………………….. 15 5.4 Hardware Connections
…………………………………………………………………………………………………. 15 5.4.1 Inview S –
Connections……………………………………………………………………………………… 15 5.4.2 Inview S Slot –
Connections ……………………………………………………………………………….. 16 5.4.3 Measure Box Battery –
Connections…………………………………………………………………….. 16 5.4.4 Measure Box DC (MBDC) –
Connections……………………………………………………………….. 17 5.4.5 Output relay connections
…………………………………………………………………………………… 18 5.4.6 Digital input connections
…………………………………………………………………………………… 18 5.4.7 Inview S with Bravo and Sierra –
System ……………………………………………………………… 19
6. Overview – Web Interface……………………………………………………………………………………………………….. 20 6.1
Login…………………………………………………………………………………………………………………………. 21 6.2 Interface Areas
……………………………………………………………………………………………………………. 21 6.2.1 Header
…………………………………………………………………………………………………………… 22 6.2.2 Home
Page……………………………………………………………………………………………………… 22 6.3 Web page and its
features…………………………………………………………………………………………….. 23 6.3.1
Monitoring………………………………………………………………………………………………………. 23 6.3.2 Events
……………………………………………………………………………………………………………. 28 6.3.3
Administration…………………………………………………………………………………………………. 29
2 Inview S with MBB User Manual v2.1
6.3.4 Account………………………………………………………………………………………………………….. 47 7. Overview – LCD
Interface ……………………………………………………………………………………………………….. 48
7.1 Inview S – LCD interface ……………………………………………………………………………………………….. 48 7.1.1
LED indications ……………………………………………………………………………………………….. 49 7.1.2 Menu
structure………………………………………………………………………………………………… 49
7.2 Inview S Slot – LCD Display …………………………………………………………………………………………… 50 7.2.1
LED indications ……………………………………………………………………………………………….. 50 7.2.2 Menu
structure………………………………………………………………………………………………… 51
7.3 LCD interface – Terminology …………………………………………………………………………………………. 52 8.
Defective unit……………………………………………………………………………………………………………………….. 53
8.1 Return defective Inview S …………………………………………………………………………………………….. 53 9.
Service ……………………………………………………………………………………………………………………………….. 54 10. Annexe 1:
Modules – Parameter List…………………………………………………………………………………………. 55
10.1 Module – Sierra 25 ………………………………………………………………………………………………………. 55 11. Annex
2: Inview S with MBB – Wiring diagram……………………………………………………………………………. 59 12.
Annex 3: Auxiliary power supply kit …………………………………………………………………………………………. 60
12.1 Auxiliary power supply kit with Din Rail …………………………………………………………………………… 60
12.2 Auxiliary power supply kit – Wiring diagram……………………………………………………………………… 60
13. Annex 4: Inview S panel sheets ………………………………………………………………………………………………. 61
14. Annex 5: Inview S – Software upgrading……………………………………………………………………………………. 62
3 Inview S with MBB User Manual v2.1
Release Note:
Version
1.0 1.1 2.0 2.1
Release date (DD/MM/YYYY)
14/12/2018
25/03/2019 25/11/2019 09/01/2020
Modified page number
–
60
Modifications
First release of the manual Updated the content and wiring diagrams Updated
the content and screen shots to software version 3.0 Updated the Aux power
supply information
4 Inview S with MBB User Manual v2.1
1. HELIOS at a glance
HELIOS Power designs, manufactures and markets a range of products for
industrial operators with mission critical applications, who are not satisfied
with existing AC backup systems performances, and related maintenance costs.
Our product is an innovative AC backup solution that unlike most used UPS’s
· Maximizes the operator’s applications uptime;
· Operates with lowest OPEX; · Provides best protection to disturbances; ·
Optimizes footprint. Our systems are: · Modular · Truly redundant · Highly
efficient · Maintenance free · Battery friendly
5 Inview S with MBB User Manual v2.1
2. Abbreviations
ECI EPC REG DSP AC DC PE N PCB TRS PWR ESD MET MBP MBB MBDC TCP/IP USB LAN ETH SNMP HTTP HTTPS NTP MIB DHCP NT/KO AL
Enhanced Conversion Innovation Enhanced Power Conversion Regular Digital Signal Processor Alternating current Direct current Protective Earth (also called Main Protective Conductor) Neutral Printed Circuit Board True Redundant Structure Power Electro Static Discharge Main Earth Terminal Manual By-pass Measure Box Battery Measure Box DC Loads Transmission Control Protocol/Internet Protocol Universal Serial Bus Local Access Network Ethernet Simple Network Management Protocol HyperText Transfer Protocol Secure HyperText Transfer Protocol Network Time Protocol Management Information Base Dynamic Host Configuration Protocol Not Okay Alarm
6 Inview S with MBB User Manual v2.1
Abbreviations
Warranty and Safety Conditions
3. Warranty and Safety Conditions*
WARNING:
The electronics in the power supply system are designed for an indoor, clean
environment. When installed in a dusty and/or corrosive environment, outdoor
or indoor, it is important to:
· Install an appropriate filter on the enclosure door, or on the room’s air
conditioning system. · Keep the enclosure door closed during operation. ·
Replace the filters on a regular basis.
Important safety instructions, save these instructions.
3.1 Disclaimer
· The manufacturer declines all responsibilities if equipment is not
installed, used or operated according to the instructions herein by skilled
technicians according to local regulations.
· Warranty does not apply if the product is not installed, used and handled
according to the instructions in the manuals.
3.2 Technical care
· This electric equipment can only be repaired or maintained by a “qualified
employee” with adequate training. Even personnel who are in charge of simple
repairs or maintenance are required to have knowledge or experience related to
product maintenance.
· Please follow the procedures contained in this Manual, and note all the
“DANGER”, “WARNING” AND “NOTICE” marks contained in this Manual. Warning
labels must not be removed.
· Qualified employees are trained to recognize and avoid any dangers that
might be present when working on or near exposed electrical parts.
· Qualified employees understand how to lock out and tag out machines so the
machines will not accidentally be turned on and injure employees working on
them.
· Qualified employees also understand safety related work practices, including
those by OSHA and NFPA, as well as knowing what personal protective equipment
should be worn.
· All operators are to be trained to perform the emergency shut-down
procedure. · Never wear metallic objects such as rings, watches, or bracelets
during installation, service and maintenance of
the product. · Insulated tools must be used at all times when working with
live systems. · When handling the system/units pay attention to sharp edges.
7 Inview S with MBB User Manual v2.1
Warranty and Safety Conditions
3.3 Installation
· This product is intended to be installed only in restricted access areas. ·
The Inverter System may contain output over current protection in the form of
circuit breakers. In addition to
these circuit breakers, the user must observe the recommended upstream and
downstream circuit breaker requirements as per the local regulations. · Please
use extreme caution when accessing circuits that may be at hazardous voltages
or energy levels. · The modular inverter rack is a dual input power supply.
The complete system shall be wired in a way that both input and output leads
can be made power free. · In REG systems, to comply with local and
international safety standards the N (output) and PE shall be bonded. The
bonded connection between N (output) and PE must be removed once the AC input
is connected. · AC and DC circuits shall be terminated with no voltage / power
applied. · The safety standard IEC/EN62040-1-1 requires that, in the event of
an output short circuit, the inverter must disconnect in 5 seconds maximum.
The parameter can be adjusted on Inview controller; however, if the parameter
is set at a value > 5 seconds, an external protection must be provided so that
the short circuit protection operates within 5 seconds. Default setting is 60
seconds. · The system is designed for installation within an IP20 or IP21
environment. When installed in a dusty or humid environment, appropriate
measures (air filtering) must be taken. · All illustrations in the manual are
for general reference.
3.3.1 Handling
· The cabinet shall not be lifted using lifting eyes. · Remove weight from the
cabinet by unplugging the inverters. Mark inverters clearly with shelf and
position for
correct rebuild. This is especially important in dual or three phase
configurations. · Empty module positions must not be left open. Replace with
dummy cover.
3.3.2 Surge and transients
The mains (AC) supply of the modular inverter system shall be fitted with
Lightning surge suppression and Transient voltage surge suppression suitable
for the application at hand. Manufacturer’s recommendations of installation
shall be adhered to. Selecting a device with an alarm relay for function
failure is advised. Indoor sites are considered to have a working lightning
surge suppression device in service.
· Indoor sites Min Class II. · Outdoor sites Min Class I + Class II or
combined Class I+II. The modular inverter system/rack can reach
hazardous leakage currents. Earthing must be carried out prior to energizing
the system. Earthing shall be made according to local regulations.
3.3.3 Other
· Isolation test (Hi-Pot) must not be performed without instructions from the
manufacturer.
8 Inview S with MBB User Manual v2.1
Warranty and Safety Conditions
3.4 Pre-cautions before maintenance
· The modular inverter system/rack can reach hazardous leakage currents.
Earthing must be carried out prior to energizing the system. Earthing shall be
made according to local regulations.
· Prior to any work conducted on a system/unit make sure that AC input voltage
and DC input voltage are disconnected.
· Inverter modules and shelves contain capacitors for filtering and energy
storage. Prior to accessing the system/ modules after power down, wait at
least 5 minutes to allow capacitors to discharge.
· Some components and terminals carry high voltage during operation. Contact
may result in fatal injury.
3.5 Replacement and Dismantling
· ESD Strap must be worn when handling PCBs and open units. · CE+T cannot be
held responsible for disposal of the Inverter system and therefore the
customer must segregate
and dispose of the materials which are potentially harmful to the environment,
in accordance with the local regulations in force in the country of
installation. · If the equipment is dismantled, to dispose of its component
products, you must comply with the local regulations in force in the country
of destination and in any case avoid causing any kind of pollution.
9 Inview S with MBB User Manual v2.1
Introduction
4. Introduction
4.1 Inview S
Inview S is an advanced monitoring and controller unit for Bravo 20, Bravo 10,
Sierra 25, and Sierra 10 power systems. It allows the user to easily access
the system information through inbuilt powerful touch screen graphic display.
In addition to the touch screen display, the user can also access the system
information through the web interface and SNMP protocol. The Inview S
interface provides the user to access the configuration and setup files of the
modules in the system. Also, it is a controller for DC regulation. Inview S
can monitor up to 32 inverters/converters and featured with:
· 2.8″ LCD touch screen display · Three LED’s to indicate Major alarm, Minor
alarm and System
status · Two Digital Inputs · Two Output Relay contacts · Records 5000 logs as
FIFO
4.2 Inview S Slot
Inview S Slot is also an advanced monitoring and controller unit, but it for
Bravo 10 and Sierra 10 power systems. This product is specially designed in 1U
height to accommodate in the module shelf and reduces the additional space in
the cabinet. As like Inview S, it also allows the user to easily access the
system information through inbuilt powerful LCD touch screen graphic display.
In addition to the touch screen display, the user can also access the system
information through the web interface and SNMP protocol. The Inview S Slot
interface provides the user to access the configuration and setup files of the
modules in the system. As like Inview S, it is also a controller for DC
regulation. Inview S Slot can monitor up to 32 inverters/converters and
featured with:
· 1.8″ LCD touch screen display · Three LED’s to indicate Major alarm, Minor
alarm and System status · Two Digital Inputs · Two Output Relay contacts ·
Records 5000 logs as FIFO
10 Inview S with MBB User Manual v2.1
Introduction
4.3 Inview S – Specifications
Models
Modules compatibility Touch screen display Web interface Hardware / software
interfaces Output relays Digital input Voltage sensor Current sensor
Temperature sensor Mounting
Power supply
Dimension (W x H x D) mm Weight Part number * Available soon.
Inview S Bravo 10 and 20 2.8” capacitive
Inview S Slot Bravo 10
1.8” resistive
Inview S + MBB
Bravo 10 and 20 Sierra 10 and 25 2.8” capacitive
YES (monitoring and configuration)
Inview S Slot + MBB Bravo 10 and Sierra 10
1.8” resistive
ETH, Modbus TCP, SNMP v1, v2c and v3, NTP, HTTP/HTTPS
2
8
2
10
–
3
–
3
–
2
DIN or panel
Shelf
12 Vdc (10-14 Vdc)
+ PE Connection (auxiliary source)
48 Vdc (from the busbar)
180 x 83 x 31 87 x 42 x 331
240 g
650 g
T602004100
T602004110
DIN or Panel + DIN (MBB)
12 Vdc (10-14 Vdc) + PE Connection (auxiliary source)
180 x 83 x 31 + 160 x 97 x 38
240 + 240 g
T602004100 + T602006000
Shelf + DIN (MBB)
48 Vdc (from the busbar) 12 Vdc (auxiliary source for
MBB)
87 x 42 x 331 + 160 x 97 x 38
650 + 240 g
T602004110 + T602006000
11 Inview S with MBB User Manual v2.1
Introduction
4.4 Accessories
4.4.1 Measure Box Battery (MBB)
Measure Box Battery is a unit which monitors the battery parameters such as
battery voltage, current, and temperature and LVD. In addition it contains
extended Digital Inputs and Output Relay contacts. MBB can connect upto three
in parallel.
4.4.1.1 Specifications
Measure Box Battery
VDC
IDC Temperature sensor Output relays Digital inputs Communication Power supply
Synoptics Mounting Dimension (W x H x D) Weight Part number
3 VDC inputs (V COM, V midpoint string 1, V midpoint string 2), maximum 60 Vdc 3 IDC inputs, 0-60mV shunt (I COM, I string 1, I string 2) Yes 6 dry contacts (maximum 60 Vdc, 0.5 A) 8 (0 – 5V) CAN Bus 12 Vdc input (10 – 14 Vdc) + PE connection 1 LED DIN Rail 160 x 97 x 38 mm 240 g T602006000
12 Inview S with MBB User Manual v2.1
Introduction
4.4.2 Measure Box DC loads (MBDC)
Measure Box DC loads is a unit which monitors the current parameters of DC
loads. It measures the exact current value at each DC load terminal through
shunt. Each MBDC can monitor up to maximum 20 DC loads. In addition, it
contains extended 20 Digital Inputs. MBDC can connect upto three in parallel.
4.4.2.1 Specifications
Measure Box DC Loads
IDC Digital inputs Communication Power supply Synoptics Mounting Dimension (W x H x D) Weight Part number
20 IDC inputs, 0-60mV shunt (I COM, I string 1, I string 2) 20 (0 – 5V) CAN Bus 12 Vdc input (10 – 14 Vdc) + PE connection 1 LED DIN Rail 160 x 97 x 38 mm 240 g T602006001
13 Inview S with MBB User Manual v2.1
Installation
5. Installation
5.1 Site preparation
· All cables should be copper wire and must be rated for min 90°C (194°F). ·
All cables must be sized according to the rated current of the Inview S /
Measure Box Battery and to the
customer terminal connection. · All power and signal cables should be routed
properly.
5.2 Mounting – Inview S
5.2.1 Panel Mounting
Before mounting the Inview S in the system, route all the required connection
cables from the system and place near to the Inview S mounting location.
1. Place the Inview S in the panel sheet. 2. Lock all the four latches at the
rear side of the Inview S in the panel sheet. 3. Connect required connection
cables to the Inview S. 4. Mount the panel sheet in the system with screws.
Latch
Place the Inview S in the panel sheet
Lock it with four latches
Connect wires and place the panel sheet in the cabinet
Mount the panel sheet with screws
Note: To know about panel sheet dimension and cut-out details, refer “13. Annex 4: Inview S panel sheets”, page 61.
14 Inview S with MBB User Manual v2.1
5.3 Installing – Inview S Slot
1. Place the Inview S Slot and slide into the shelf. 2. Push the unit firmly
until the controller rear part is engaged correctly with shelf. 3. Make sure
the latch is locked in the shelf.
Installation
Place the module & slide into the shelf
Push firmly until module is engaged
Make sure the latch is locked in the shelf
5.4 Hardware Connections
5.4.1 Inview S – Connections
Inview S is composed of multiple network ports, digital inputs and Output Relay contacts which are present at the rear side of the product.
CE+T COM
ETH
CAN iso RS485
USB – Digital Input 2 + – Digital Input 1 + C NC Output Relay 2 NO C NC Output
Relay 1 NO
PE Power 12 Vdc +
· Helios COM port is dedicated to establish connection between Inview S and
converters.
· ETH ( ) port is used for network connectivity and user can access the system
information in the Web Interface and SNMP.
· CAN / iso RS485 port is used to establish communication between Inview S and
accessories such as Measure Box Battery and Measure Box DC load. Note: In
future version, user can use this port for RS485-Modbus communication.
· USB port is used to update the Inview S firmware.
· Digital Inputs (D1 and D2): Two digital inputs are available for customer
connections.
· Output Relays (K1 and K2): Two output relays are available and it is used
for Major and Minor Alarms.
· Power: The regulated separate +12 Vdc is required for powering the
controller and the power consumption is 5W. ( Helios can provide auxiliary
power supply converter (48 to 12 Vdc). Part number is T602006004)
15 Inview S with MBB User Manual v2.1
Installation
5.4.2 Inview S Slot – Connections
ETH
Inview S Slot has an ETH port and USB at the front. Output relays, digital inputs, CAN and power connections are present at the rear side of the Inview S Slot connected shelf.
USB
5.4.2.1 Inview S Slot – Front connections
LAN port is used for network connectivity and user can access the system
information in the Web Interface.
USB port is used to update the Inview S firmware.
5.4.2.2 Inview S Slot – Shelf rear connections
· Digital Inputs (D1 and D2): Two digital inputs are available for customer
connections.
· Output Relays (K1 and K2): Two output relays are available and can be used
for Major and Minor Alarms.
· CAN / Modbus (RS485) port is used to establish communication between Inview
S Slot and accessories. It also provide the +12 Vdc power to one accessory
such as Measure Box Battery or Measure Box DC load. Note: In future version,
user can use this port for RS485-Modbus communication.
· Power: The redundant external auxiliary +12 Vdc and the power consumption is
5W. By default, Inview S Slot takes power from DC bus. If DC is not present,
it takes +12 V from external Auxiliary power supply converter (AC to DC).
Shelf Rear
NO NC
C NO NC
C
K1 K2
D1 D2
CAN Modbus (RS485)
PE Power
5.4.3 Measure Box Battery – Connections
Measure Box Battery is composed of multiple digital inputs and analog outputs.
· Voltage (V1 to V3) is used to monitor the voltage of DC. Ensure the polarity
while wiring. V1: common DC 48V voltage V2: string 1 monitoring V3: string 2
monitoring
16 Inview S with MBB User Manual v2.1
Installation
· Current (I1 to I3) terminal is used to monitor the current of Battery.
Ensure the polarity from the shunt while wiring. I1: battery shunt when a
common shunt is used for all strings I2: string 1 shunt when measuring each
battery I3: string 2 shunt when measuring each battery
Note: MBB is designed to monitor the current from 50mV or 60mV shunt only. ·
Temperature (T1 & T2): T1 terminal is used for temperature compensation and T2
terminal is not available. For temperature monitoring, the LM335 sensor must
be used and wired as per the following.
· CAN 1 port is used to establish the connection between Inview S and Measure
Box Battery. · CAN 2 port is used to connect and parallel up to three MBB. It
also helps to connect the MBDC. · Digital Inputs (D1 to D8): Eight Digital
Inputs are available for customer connections. · Output Relays (K1 to K6): Six
output relays are available for customer connections
K1 and K2 – Major and Minor alarms K5 and K6 – LVD Connections · Power: The
regulated separate +12 V power supply is required for powering MBB and the
power consumption is 2W. (CET can provide auxiliary power supply converter (48
to 12 Vdc). Part number is T602006004).
5.4.4 Measure Box DC (MBDC) – Connections
Measure Box DC load is composed of multiple digital inputs. · Current (I1 to
I20) terminal is used to monitor the current of DC loads. · Digital Inputs (D1
to D20): Twenty potential free extended Digital Inputs are available for
customer connections. · CAN 1 port is used to establish the connection between
Inview S or Measure Box Battery. · CAN 2 port is used to connect and parallel
up to three MBDC. · Power: The regulated separate +12 V power supply is
required for powering MBDC and the power consumption is 2W. (CET can provide
auxiliary power supply converter (48 to 12 Vdc). Part number is T602006004)
17 Inview S with MBB User Manual v2.1
Installation
5.4.5 Output relay connections
Each output relay terminal in Inview S and MBB should be connected as below
diagram. A possible way of connecting Ground and 12 Vdc in order to get a “0”
or a “1” based on the relay state.
NO Com NC
GND 0
12 Vdc 1
5.4.6 Digital input connections
In digital input terminal, the external voltage should not be applied and it
is mandatory to connect only like switches. Each digital input terminal in
Inview S, MBB and MBDC should be connected as below diagram.
Digital input terminal
18 Inview S with MBB User Manual v2.1
Installation
5.4.7 Inview S with Bravo and Sierra – System
In Bravo and Sierra systems, the Inview S, Measure Box Battery and Measure Box
DC should be connected as per the following:
1. Connect “RJ45” port in shelf and “Helios COM” port in Inview S using RJ45
straight cable. 2. Connect “CAN / iso RS485” port in Inview S and “CAN1” port
in Measure Box Battery using RJ45 straight cable. 3. Connect “CAN2” port in
Measure Box Battery and “CAN1” port in Measure Box DC using RJ45 straight
cable.
(Note: Measure Box DC is an optional) 4. Connect 12 V supply to Inview S and
MBB from auxiliary power supply kit.
RJ45 port
1
RJ45 Cable
CE+T COM
Shelf
Inview S
4
Auxiliary Power
CAN / iso RS485
Power
supply kit
(12 V DC)
2 RJ45 Cable
CAN 2
CAN 1
CAN 1
CAN 2
3
Measure Box DC
Measure Box Battery
Power
Power
For more information about wiring refer “11. Annex 2: Inview S with MBB – Wiring diagram”, page 59
19 Inview S with MBB User Manual v2.1
Overview – Web Interface
6. Overview – Web Interface
The web interface of both controller Inview S and Inview S Slot is same.
Inview web interface provides the user to interact with system, access,
configure and modify the system parameters. The below tree provides an
overview of the menu structure in the web interface. Note: Clicking on a
parameter in the tree goes to the corresponding section.
Home Monitoring
AC Input DC Power System AC Output
Battery summary DC Load
Converters Accessories
Events Administration
Accounts
Logs Users Parameters Maintenance
Administration About
Supervisor Communication Events Power
Phase DC Converters Topology
Site Information Time Buzzer Screen brightness Network Accessories Digital
inputs
Web server SNMP Debug system
DC events Converter events System events Customer events
Phase 1 to Phase 3 Loads Battery Parameter List
MBDC
Characteristics LVD Temperature compensation Boost charging Battery test
20 Inview S with MBB User Manual v2.1
Overview – Web Interface
6.1 Login
Open the web browser and type the default IP address 10.250.250.1 in the
address field and press enter. Note: Use any one of the following latest
version of web browser: Google Chrome, Mozilla Firefox, Safari or microsoft
edge. Inview S has three login Basic, Expert and Admin. All three login is
password protected. The default password for all three logins is “1234”. It
can be modified, refer section , page 30. Basic login can only browse the
pages and download the files, but Expert and Admin login can access and also
modify the system parameter values. An auto-logout feature is available to
avoid a user being connected all the time. When no action is performed for
more than 10 minutes, the session will expire and goes to login screen.
6.2 Interface Areas
1 Header 2 Main Page
1 2
21 Inview S with MBB User Manual v2.1
Overview – Web Interface
6.2.1 Header
1
2
3
456
7
The tabs in header provide quick access to the corresponding pages.
1 Home: Clicking on
goes to the home page from any page you are accessing in the interface.
2 Breadcrumbs: Provide navigation of the page. It trails all levels so that user can know where you are within the interface and can go to any previous menu.
3 Display the date, time and the site name of the system.
4 Events: Clicking on goes to Events and Logs page.
5 Administration: Clicking on provide access to Users, Parameters and
Maintenance pages.
6 Info: Clicking on in the home page, provides brief information about the
system, while in other pages provide the latest three ongoing events.
7 Account: Provides the information of which account is logged in (Basic,
Expert or Admin). Clicking on dropdown arrow user can access the following
pages:
Administration – Provide quick access to Users, Parameters and Maintenance
pages. About – Provides the information of Inview product details and network
connectivity details.
6.2.2 Home Page
1 AC Input: Clicking on the AC Input region displays the page contain all
measurements regarding AC Input. 2 DC: Clicking on the DC region displays the
page contains all measurements regarding DC input and output. 3 Power System:
Clicking on the Power System region display the page contains regarding system
information
such as overall system power and also in each phase, configured modules,
active modules, and list of detected modules and accessories.
22 Inview S with MBB User Manual v2.1
Overview – Web Interface
4 AC Output: Clicking on the AC Output region displays the page contains all
measurements regarding AC Output. Regardless of the system configuration (1P,
3P), display the power fed to the load on each phase.
5 Notifications: Display the current generated alarms and events.
6.3 Web page and its features
6.3.1 Monitoring 6.3.1.1 AC Input
AC input page displays Voltage, Current, Frequency, and Input Power, which is
measured by the modules on the AC Input. In multi-phase system displays the
information on each phase. Select Home page > AC input
6.3.1.2 DC
DC page displays the summary of DC information, which includes both battery
and DC load. Next to it, displays separately the summary of Battery and DC
Load which is measured by the modules on the DC input and DC Load. Select Home
page > DC
· Battery: Clicking on Battery region in DC page displays the detailed
information of battery. In this page, the user can set boost charging and
perform the battery test by clicking the “LAUNCH BATTERY BOOST” and “LAUNCH
BATTERY TEST” button.
23 Inview S with MBB User Manual v2.1
Overview – Web Interface
From this page, the user can go to battery configuration page and maintenance
page to view battery reports by clicking on the Configuration and Battery
reports region.
· DC Load: Clicking on the DC load region displays the summary of all DC
loads. Note: Negative sign “-” indicates discharging and positive sign “+”
indicates charging.
From this page, user can go to the MBDC page where all the DC loads are listed
by clicking Global region.
24 Inview S with MBB User Manual v2.1
Overview – Web Interface 6.3.1.3 Power System
Power System page provides detailed system information such as overall system
power and also in each phase, configured modules, active modules, Redundancy
configuration, and list of detected converters (modules) and accessories.
Note: Inview automatically detects the installed module in the system and
display as “Converter” in the interface. It can be either inverter, converter,
or rectifier. Select Home page > Power system
Note: By clicking on icon provide a quick brief description of the
corresponding parameters. Power system page contains Modules and Accessories
section. Converters Select Converters tab in the power system page. Bottom of
the page displays the list of all installed modules and provides the general
information of the modules. Clicking on “BLINK LED” button, the corresponding
module LED’s blink for 6 seconds. It helps to identify the module in the
system and also the assigned phase of the module. Note: Clicking on “REMOVE
MISSING MODULES” button removes all the non-active modules from the list. To
know more about the module, select a particular module from the list.
25 Inview S with MBB User Manual v2.1
Overview – Web Interface
Modules page displays General information, AC Input, DC and AC Output details
of the corresponding module. This page has other features such as BLINK LED,
SWITCH OFF and SET NEW FAN INSTALLED.
· General Information Module ID: Set identification number for module. DC:
Displays to which DC group the module is assigned. Phase: Assign to which
phase the module to function. (Note: the module output should be turned OFF
while assigning the phases) Module power, Serial Number, Software Version,
Type of the module and due days of module fan replacement.
· AC Inputs Voltage, Current, Frequency and Active Power. · DC Voltage,
Current and Active Power. · AC Output Voltage, Current, Frequency, Active
Power and Apparent Power. · Other Features:
Blink LED: Clicking on “BLINK LED” button, the corresponding module LED’s
blink for 6 seconds. It helps to identify the module in the system and also
the assigned phase of the module.
Switch OFF: Clicking on “SWITCH OFF” button, the corresponding module will be
turned OFF and generates an alarm in events page as module off.
Set new fan installed: Clicking on “SET NEW FAN INSTALLED” button, the
corresponding module “Module fan replacement” due will be reset to 2556 days
(7 years). (Note: Do not click this button, until a new fan is replaced inside
the module.)
26 Inview S with MBB User Manual v2.1
Overview – Web Interface Accessories
Select Accessories tab in the power system page, it displays the list of
Accessories installed in the system. Accessories are Measure Box Battery and
Measure Box DC. Clicking on “BLINK LED” button, the corresponding accessory
LED blink for 6 seconds. It helps to identify the accessory in the system.
To know more about the accessory, select a particular accessory from the list,
and it displays detailed information of that accessory. The following is an
accessory of Measure box battery page.
From this page, the user can view and configure the corresponding accessory by
clicking “Configuration” at the right corner of the web page.
27 Inview S with MBB User Manual v2.1
Overview – Web Interface 6.3.1.4 AC Output
AC Output page displays Voltage, Current, Frequency, Active Power, Apparent
Power and Power Factor, which is measured by the modules on the AC Output. In
multi-phase system displays the information of each phase. Select Home page >
AC output
The status bar below the Active and Apparent power indicates the load
delivering by the system. · Green – Load is within the range. · Orange –
Saturation. · Red – Overload.
6.3.2 Events
Events page displays the list of current alarms and events, and it stops
displaying once the alarms is cleared. It also provides the information of
events Severity, Origin, Description and Date & time. Events triggered depends
upon the delay time of the relay. Select Home page >
28 Inview S with MBB User Manual v2.1
Overview – Web Interface 6.3.2.1 Logs
Logs page display the list of changes that occurred in the system, to help
during troubleshooting. It also provides the information of Logs ID, Severity,
Origin, Description, Date & time, and State. It displays latest 5000 logs as
FIFO (First In First Out). Select Home page > > Logs In this page user can
download the log file (.csv) and clear logs by clicking “EXPORT” and “CLEAR”
button.
6.3.3 Administration
Administration page provide access to Users, Parameters and Maintenance pages.
· Users page provides the option to create, modify and delete user accounts. ·
Parameters page provide access to supervisor, communication, events and power
pages. · Maintenance page provides access to update software, download support
package, download logs, time setting, download MIB and view battery reports.
Select Home page >
29 Inview S with MBB User Manual v2.1
Overview – Web Interface
6.3.3.1 Users
Users page provides the access to create and modify the user accounts for web
interface and PIN modification for LCD interface. Select Home page > > Users
Web interface – User account Users can create up to ten accounts for web
interface and assign role as Admin, Expert, or Basic. Admin User can access,
modify all the applicable parameters, and manage user accounts. (The
manufacturer created Admin account cannot be deleted) Expert – User can access
and modify all the applicable parameters, and can change their own password.
Basic User can only view the parameters.
Note: The feature of creating and editing user account is available only in
Admin privilege.
· Creating a new user account a) In Users page, Click on “+ADD” button. A pop
window appears with the title “Add a new user.” b) Enter an appropriate user
name and assign a role from the drop down list as Basic, Expert or Admin. c)
Enter a new password, type the same password for confirmation, and then click
ADD button. The password length should be at least seven characters.
· Editing the existing user account In the Users page, choose a user account
which you like modify. Modify the privilege from the “Role” drop-down list as
Admin, Expert, or Basic. Click on “PASSWORD” button to edit existing password.
Click on “DELETE” button to remove the user account.
30 Inview S with MBB User Manual v2.1
Overview – Web Interface
LCD interface – PIN number Inview S and Inview S Slot LCD interface do not
have any user account; the user can view the system details and cannot modify
the parameters. The LCD interface is protected with the PIN during any action
request.
· Editing the LCD PIN number a) Select Home page > > Users. b) In users page,
Click on “EDIT PIN” button below the “Touch screen pin number”. c) Enter a new
pin, type the same for confirmation, and then click OK. The pin should be four
integers.
6.3.3.2 Parameters
Parameters page provide access to Supervisor, Communication, Events and Power
pages. Modification of parameter values in these pages reflects the function
of Inview S. Select Home page > > Parameters
Other Features · User can upload and download the system parameters by
clicking “IMPORT” and “EXPORT” button at the top right side of the page. These
two buttons are available in all parameters page. · Modifications list: At the
right side of the parameters page, displays the list of parameter
modifications. This list helps the user to overview the changes and can apply
the required parameters. Apply: Clicking on “APPLY” button, the controller
accepts all the parameter changes in the modifications list. Dismiss All:
Clicking on “DISMISS ALL” button, the controller rejects all the parameter
changes in the modifications list. Clicking on button, the controller rejects
only the particular modification from the list.
31 Inview S with MBB User Manual v2.1
Overview – Web Interface
· Controls: Placing or clicking on it, perform the corresponding action
Controls
Description
Provide short description about the corresponding parameters
Required values should be filled.
Drop down list more options are present
Page expands
Increment and decrement the parameter values.
Delete the corresponding parameter.
Supervisor Supervisor page display and access to global parameters such as
Site information, Time settings, Buzzer, Network, Accessories and Digital
input settings.
Select Home page > > Parameters > Supervisor
· Site Information: Enter the site location details where Inview is installed.
· Time: Set the time settings and it reflects in the header, logs and events.
Mode: Choose Computer or NTP from the drop down list and update in Time
management at Maintenance page, refer, page 47. Computer Inview read the
computer time during the configuration and adapt the time. NTP Inview
Internal clock synchronizes with the server time.
Time zone: Choose the time zone from the drop-down list. NTP server: Enter the
NTP server address.
32 Inview S with MBB User Manual v2.1
Overview – Web Interface
· Buzzer: Select the check box to enable the buzzer sound when any alarm is
generated. User can set different sound sequence to differentiate Major and
Minor alarm from the drop-down list. Even though this feature is disabled, the
buzzer produces sound during LVD notifications.
· Screen brightness: Adjust the LCD touch screen brightness between 25% to
100%. If no action is performed for more than 3 minutes, the LCD screen goes
off and wakes up once the screen was tapped.
· Network: Inview supports IPv4 network. Choose the Address mode as dhcp or
static from the drop-down list. Depending upon the type, enter the network
address.
Note:
The 192.168.20.31/24 represents the IPv4 address 192.168.20.31 and its
associated routing prefix 192.168.20.0, or equivalently, its subnet mask
255.255.255.0, which has 24 leading 1-bits.
The higher bit count values such as /30, /31 limit the number of allowed IP addresses in the subnet. Ultimately, value /32 would make the device unreachable and must be avoided. The most common value is “/24” and corresponds to a 255.255.255.0 subnet mask.
· Accessories: Enter the number of accessories that are installed in the system. Accessories are Measure Box Battery and Measure Box DC.
· Digital inputs: Inview has two digital inputs, and it named as “IVS-DI1” and “IVS-DI2” in the interface. If a Measure Box Battery (MBB) is installed in the system, the user has additional 8 digital inputs, and they are “MBB-1-DI1 to DI8”.
Number of Digital Inputs = 2 from Inview S + (8 x number of Measure Box battery configured)
Configure Inview and Measure Box Battery Digital inputs:
Inview S: Select Home page > input to configure.
Parameters > Supervisor > Digital inputs > IVS and click the digital
Measure Box Battery: Select Home page > and click the digital input to configure.
Parameters > Supervisor > Digital inputs > MBB-1
Digital input mode: Select the option from the drop-down list.
Active when: Configure at which state the digital input should be triggered. By default, the digital input is in open condition. If it is closed, the action will be triggered.
Label: Enter an appropriate and distinct label. This label displays on the web pages, logs, events and touch screen display and it helps to identify the particular digital input easily from the list.
Note: In measure box battery the label display as its ID. If measure box DC load is connected, more digital inputs will be available along with Measure box battery.
33 Inview S with MBB User Manual v2.1
Overview – Web Interface Communication
Communication page provide access to Web server, SNMP and Debug system. Select
Home page > > Parameters > Communication
· Web server: Set the HTTP/HTTPS protocol and port parameters. After changing
the HTTP/HTTPS parameters, the user interface will log out and it reflect in
the URL page.
Note: If HTTPS protocol is used, the self- signed SSL certificate is required.
· SNMP: Set the mode and port parameter of SNMP. In this page you can view
list of Trap receiver and can define the destination port of Trap receiver for
SNMP. SNMP supports v1 and v2c. Port number and community strings are user
configurable. User can configure of maximum three TRAP receiver.
34 Inview S with MBB User Manual v2.1
Overview – Web Interface
· Debug system: Select the check box to enable debug feature. During normal
operation, the check box should be disabled.
Note: the debugging process must be performed by a qualified technical person
who has adequate knowledge on Helios monitoring products. Events Events page
provide access to configure DC, Converter, System and Customer events. Select
Home page > > Parameters > Events
Users can configure each event level and delay, and some events have threshold
fields. · Events level: Choose the level of the corresponding events as
Disabled, Notification, Minor alarm or Major Alarm from the drop-down list. ·
Events delay: Enter the delay time and can set from 0 to 3600 seconds. The
events will appear depend upon the relay time. · Events threshold: If the
parameter value goes below the mentioned value, the event will appear. ·
Events cancel threshold: If the parameter value reaches the mentioned value,
the event will be cleared.
The followings are the example of configuring the “LVD” and “DC voltage too
high” events . Similarly, other events can be configured. Select Home page > >
Parameters > Events > DC > LVD about to open
35 Inview S with MBB User Manual v2.1
Overview – Web Interface
Select Home page > > Parameters > Events > DC > DC voltage too high
· List of supported events
S.No
DC events
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Events
LVD about to open LVD open Battery midpoint unbalance Battery string
disconnected Battery strings current imbalance Battery temperature too high
Battery temperature too low Temperature sensor failure Battery test cancelled
Battery test failure Battery test ongoing DC load disconnected DC load
saturated Converter DC output power too high DC source lost DC voltage too
high DC voltage too low
36 Inview S with MBB User Manual v2.1
Overview – Web Interface
Converter events 1 2 3 4 5 6 7 8 9
Overload System parallelization bus issue Fan end of life Fan failure Missing converter Converter off Recoverable fault Unrecoverable fault Wrong configuration
System events 1 2 3 4 5 6 7 8 9 10 11
Less converters than configured Measure box missing Measure box wrong version AC In source failure System AC Out failure AC Out saturated Auxiliary power failure Manual Bypass On battery Redundancy lost Redundancy plus one lost
Customer events (based on digital inputs)
1 IVS (Inview S)
2
3
MBB-1
4
MBB-2
5
MBB-3
IVS-DI1 IVS-DI2 MBB-1-DI1 to DI8 MBB-2-DI1 to DI8 MBB-3-DI1 to DI8
37 Inview S with MBB User Manual v2.1
Overview – Web Interface
Power
Power page provide access to view and configure the AC Phases, DC groups, Module parameters and selecting Topology.
· Phase page displays the list of phases configured in the system. User can
configure the number of modules and redundancy based upon the system capacity
for each phase.
Select Home page > > Parameters > Power > Phases.
In a system, AC phases can be configured as one, two or three. Click on delete
the configured phase. Note: while configuring the AC phases, the AC output
should be in off.
Select a phase from the list to configure.
icon to add phases and icon to
Configured converters: Enter the number of modules for each phase based upon
the system capacity. It includes the redundancy modules.
Redundancy: Enter the number of redundancy modules required from the
configured modules in the corresponding phase. Available power and Installed
power will be displayed, depending on the module redundancy configuration.
38 Inview S with MBB User Manual v2.1
Overview – Web Interface
· DC page provide access and configure the DC loads and Battery parameters.
Select Home page > > Parameters > Power > DC
Loads page display the list of connected DC loads and these loads are
monitored through Measure Box DC.
Select Home page > > Parameters > Power > DC > Loads
Battery page provide access and configure the battery parameters such as
battery characteristics, LVD, temperature compensation, boost charging and
test.
Note: While modifying the parameters, it is advised to enter the values as per
in the battery datasheet. Select Home page > > Parameters > Power > DC >
Battery
1. Characteristics: Displays the battery parameters and configured with
default values. User can modify it as per the battery connected in the system.
39 Inview S with MBB User Manual v2.1
Overview – Web Interface
Select Home page > > Parameters > Power > DC > Battery > Characteristics
Current limitation: Enabling/Disabling the Battery current limitation. It is
only used when charging to limit the maximum charging current.
Max charging current: Enter the maximum charge current value as per in the
battery datasheet. The current limitation is applicable for the whole battery,
including all the strings.
Number of cells: Enter the total number of cells in each string. Floating
voltage per cell: Enter the floating voltage of the cell as per in the battery
datasheet. The value
should be entered in volts with two decimals. Current measure configuration:
select an option from the drop-down list.
Select “None” option, if shunt is not installed. Select “Single shunt” option,
if only one shunt is used for the entire string. Select “One shunt per string”
option, if a shunt is used for each string Temperature offset: Enter the value
for temperature offset and this value will be added to temperature
measurements. String capacity: Enter the total capacity of each string in AH.
Fuse rating: Enter the rating value of the fuse in amps which is installed
between the DC terminal and the battery string. Shunt: Enter the current
rating and voltage drop at a maximum current of the shunt, which is connected
between the DC terminal and battery string in the system. The value of “shunt
caliber” should be in amps and “shunt max. voltage drop” in mili volts. Min
current for imbalance monitoring: Below this threshold, string current
imbalance is not monitored. This feature is only available when system is
configured in “One shunt per string” and at least two strings. Strings:
Clicking on this displays the list of all strings in the system. Enabling a
string check box from the list, the Inview monitors the current, voltage and
temperature of the corresponding string through MBB and displays in MBB page
(Home > Power system > Accessories and click the corresponding MBB). List of
strings = 2 x number of MBB installed.
40 Inview S with MBB User Manual v2.1
Overview – Web Interface
2. LVD works as bistable only and it prevents batteries from discharging
beyond the critical low voltage. It is installed in-line between the load and
the battery. LVD continuously monitors the battery voltage, and if it falls
below the preset voltage threshold, then it automatically disconnects the
battery. It will automatically reconnect the load when the voltage is in
range. In this page, the parameters are configured with default values. User
can modify it as per the LVD installed in the system. Select Home page > >
Parameters > Power > DC > Battery > LVD
LVD: Select the checkbox to enable the feature. It is recommended to enable
this feature to protect batteries.
Inhibit LVD: Select the checkbox to enable the inhibit feature. It allows the
user to inhibit LVD operation and therefore, to maintain LVD closed.
Voltage: Enter the voltage in volts, and this is the reference voltage where
LVD disconnect or connect the battery and load, and it has the precision of
0.1V.
Delay: Enter the delay time in seconds of LVD closing. Some times there might
be a sudden spike in battery voltage, at that time LVD should not close. The
re-connection of LVD will only take place when the battery voltage is constant
for the set seconds.
Shutdown: Enter the shutdown sequence time in seconds.
3. Temperature compensation feature will optimize the battery performance and
increase the operational life of the battery. Inview precisely monitors the
battery temperature through temperature sensor and ensure the battery is
appropriately charged according to the temperature. In this page, the
parameters are configured with default values, and the user can modify it.
Select Home page > > Parameters > Power > DC > Battery > Temperature
compensation
41 Inview S with MBB User Manual v2.1
Overview – Web Interface
Temperature compensation: Select the check-box to enable the feature.
Reference temperature: Enter the battery reference temperature. It is the
temperature, where battery to
be maintained at constant voltage for the best performance. Refer the battery
manufacturer datasheet for the temperature. Coefficient: Enter the coefficient
value for temperature compensation of each cell. Temperature: Enter the
minimum and maximum temperature of the battery. If the temperature is out of
the range, the set charging voltage becomes constant.
4. Boost charging involves a high current for short period of time to charge
the battery. It is generally if the battery has been discharged heavily. Boost
charge enables the quick charging of depleted batteries. In this page, the
parameters are configured with default values, and the user can modify it.
Select Home page > > Parameters > Power > DC > Battery > Boost charging
Enabled: Select the check-box to enable the boost charging feature. Voltage
per cell: Enter the boost voltage of per cell as per in the battery datasheet.
According to this
voltage, the battery charges. Boost charging stops automatically and starts
charging the battery in float voltage. If any one of the
following conditions are met. If it reaches the seconds mentioned in “Timeout
duration.” If current drops below the amps mentioned in “Current stop
threshold.” If the temperature goes beyond the Celsius mentioned in
“Temperature stop threshold.”
Boost charging mode starts, if any one of the following conditions are met. If
the battery cell voltage drops to mentioned voltage level in “Low cell voltage
start.” If the battery is discharging more than the seconds mentioned in
“Discharge duration.”
42 Inview S with MBB User Manual v2.1
Overview – Web Interface
5. Battery test is a preventive maintenance test to determine the battery
condition during system running. The test is based on a constant power set
point and the min voltage at the end of the test. In this page, the parameters
are configured with default values, and the user can modify it. Select Home
page > > Parameters > Power > DC > Battery > Test
Enabled: Select the checkbox to enable the battery test feature. Type: choose
the type of battery test from the drop-down list.
DC + AC (constant power): The system will discharge the battery at the
configured constant power using AC and DC.
DC Only (voltage using only loads): In this mode, module stops charging and
battery feed the DC load till configured set output DC voltage.
Power set point: It is the exact value in Watts that will be taken from the
battery during the test. If the system has DC loads consuming more than this
power value, then the module will supply the delta needed to secure these
loads. If DC loads are lower than that value, power will be taken from the
battery to feed the AC output. If the AC output consumption is lower than
that, then the remaining power will be fed back to the grid, only if grid
reinjection is configured and allowed. If the system cannot consume the whole
power taken from the battery as configured, the test is interrupted, and an
event is generated. The whole logic also applies for a system where no DC load
is installed, i.e., DC load = 0 Watts.
Timeout and Low voltage stop: The battery test is successful if the configured
timeout in seconds is reached before the low voltage threshold. In the other
case, if the low voltage threshold is reached before the timeout, then the
test is considered as failed. Note: if a battery test fails, it is recommended
to check the battery condition before trying the battery test again.
43 Inview S with MBB User Manual v2.1
Overview – Web Interface
The following event list will interrupt an ongoing battery test. If an event
is configured as “disabled,” then it’s not taken into account during the
battery test neither.
BatteryLvdIncoming BatteryStringDisconnected BatteryTemperatureHigh
BatteryTemperatureSensorFailure BatteryVoltageHigh BatteryVoltageLow
SystemParallelizationBusIssue Overload SupervisorMeasureBoxMissing
SystemAcInSourceLost / SystemAcInVoltageHigh / SystemAcInVoltageLow
SystemDcOutExceeded / SystemDcSourceLost / SystemDcVoltageHigh /
SystemDcVoltageLow / SystemMBP
Scheduling: The battery test can be scheduled based on: Date of the first test
DD/MM/YYYY Hour of the test: the time of the day when the test will be
launched (and every occurrence) Recurrence in Weeks: the number of weeks
between two scheduled tests
The following event list will prevent a battery test to start. If an event is
configured as “disabled”, then it’s not taken in account.
BatteryFloatVoltageLow BatteryLvdIncoming BatteryLvdOpen
BatteryStringDisconnected BatteryTemperatureHigh
BatteryTemperatureSensorFailure BatteryTestFailure: previous failed test has
not beeck ack BatteryTestOngoing: a test is already running BatteryVoltageHigh
BatteryVoltageLow System parallelization bus issue Overload
SupervisorMeasureBoxMissing / SupervisorMeasureBoxWrongVersion
SystemAcInSourceLost / SystemAcInVoltageHigh / SystemAcInVoltageLow /
SystemDcOutExceeded SystemDcSourceLost / SystemDcVoltageHigh /
SystemDcVoltageLow SystemMBP SystemOnBattery If an occurrence of scheduled
test should start and one of the events of this list is ongoing in the system,
then the test is discarded, and a log entry is written.
44 Inview S with MBB User Manual v2.1
Overview – Web Interface
Remarks
If an occurrence of scheduled test should start during a time shift (daylight
saving time or user changing the system time), then it is discarded.
If an occurrence of scheduled test should start and the system is already in
discharge or boost, it’s discarded, and a log entry is written.
Reporting: A report is generated for every battery test. There are 4 columns: Timestamp: date and time Voltage of the battery Current of the battery Temperature of the battery
Timestamp temperature
Battery voltage Battery current Battery
07/03/2019 09:47
53.6
-4.1
24.7
07/03/2019 09:47
53.2
-7.9
24.8
Guard time: In order to prevent successive battery tests close to each other,
a guard time is implemented and can be configured (in hours). Meanwhile, this
can be disabled in order to run smoothly Factory Acceptance Test or
Commissioning that would require to do so.
If an occurrence of scheduled test should start and the system is within guard
time, it’s discarded, and a log entry is written.
· Converters page provide access to view and configure the module parameters.
In this page, the parameters are configured with default values, and the user
can modify it.
Select Home page > > Parameters > Power > Modules / Converters
To know more about the description of each module parameters, Refer “10.
Annexe 1: Modules – Parameter List”, page 55
45 Inview S with MBB User Manual v2.1
Overview – Web Interface
· Topology: Select the topology from the drop-down list based upon the system
design. Select Home page > > Parameters > Power
Topology Inverter Inverter connected to grid UPS for AC loads UPS for AC and DC loads
Supported Modules Bravo 20 and 10 Bravo 20 and 10 Flexa 25 and 200 Sierra 25 and 10
Input DC AC and DC AC and DC AC and DC
Output AC load AC load AC load and battery charging AC & DC load and battery charging
Note: Depending upon the topology selection, the home and DC pages vary in the web interface.
6.3.3.3 Maintenance
Maintenance page provides the access to update the device software, download
support package and log files, setting the time with local or NTP, downloading
SNMP MIP file and can view the battery reports.
Select Home page > > Maintenance
46 Inview S with MBB User Manual v2.1
Overview – Web Interface
· Software update: User can view the currently installed software version and
can update it to the latest software. Perform the following steps to updates
the latest software. Download the latest software (.upg) from my.cet-power.com
and save it on your laptop, Click “UPLOAD UPDATE FILE” button and link to the
downloaded software file.
Note: For more details, refer section “14. Annex 5: Inview S – Software
upgrading”, page 62 · Support package: User can download the debug package by
clicking the “DOWNLOAD DEBUG PACKAGE” button and provide to the CE+T support
team for system analysis. · Logs History: User can download (.csv) and clear
the logs list which is recorded in the system by clicking “EXPORT” and “CLEAR”
button. This feature is also available on Events > Logs page. · Time
Management: User can choose either Local or NTP server time. To change time
parameters click “change time parameters” below the time management or go to
Administration > Parameters > Supervisor >Time. Set the time zone and NTP
server address · SNMP MIB: User can download the SNMP MIB file by clicking the
“EXPORT” button. · Battery Reports: Displays the list of battery test and
discharge reports. User can download and delete the particular reports by
clicking the three dotted vertical bar at the end of the corresponding row.
Note: Inview S supports a maximum of 12 Battery event reports (6 tests + 6
discharges).
6.3.4 Account
User management display the login account such as Admin, Expert or Basic and
by clicking on dropdown arrow provide access to the following pages.
· Administration page provides access to Users, Parameters and Maintenance
pages. To know more about “Administration,” refer section 6.3.3, page 29.
· About page provides product brief information such as software version, part
and serial numbers, and network connectivity details.
47 Inview S with MBB User Manual v2.1
Overview – LCD Interface
7. Overview – LCD Interface
7.1 Inview S – LCD interface
Inview S LCD interface is a 2.8-inch touch screen. It does not have any have
any user account, the user can only view the system details. The LCD interface
is protected with the PIN during any action request. To modify the PIN, refer
section 6.3.3.1, page 30. Once system is powered upon, the Inview S is up and
ready for operation.
[1] [2] [3] · [1] Header Displays the title of the current page and navigation
buttons for next and previous page. In some pages, Up and Down navigation
buttons appear at the right side, indicating more contents are present.
· [2] Information Area Provides information about the corresponding page.
· [3] Toolbar The toolbar is present at the bottom throughout the interface,
to provide quick access to following pages: Measures Settings Alarms and Logs
48 Inview S with MBB User Manual v2.1
Overview – LCD Interface
7.1.1 LED indications
Three LED’s are present at front side of the controller to indicate major
alarm, minor alarm, and system status.
Major Alarm Minor Alarm System Status
7.1.2 Menu structure
The below tree provides an overview of the menu structure in the Inview S LCD
interface.
Inview S LCD Interface
Monitoring
Settings
Events
Refresh Module list
Cutoff Alarms
Information
Enable Wifi*
Logs
- Wifi available in future version.
Home
AC Out
DC
AC In
System
System summary · AC In · DC · AC out · Configured modules · Redundancy status · Installed power
AC Out details · Voltage · Current · Active power · Apparent power · Power factor
DC details · Voltage · Battery current · Battery power · Load current · Load power · Battery temperature
AC In details · Voltage · Current · Power · Frequency
49 Inview S with MBB User Manual v2.1
System details · Redundancy · Installed power · Available power · Configured modules · Module status
Overview – LCD Interface
7.2 Inview S Slot – LCD Display
Once the system is powered upon, the Inview S Slot is up and ready for
operation. The LCD is a 1.8-inch touch screen and user can only view the
system details through the interface.
[1]
Navigation arrow
[2] · [1] Interface area Interface area provides information about the
corresponding page. At the bottom of the screen, left and right arrows are
present for moving next and the previous screen. In some screens, up and down
arrows appear at the top of the page, indicating more contents are present.
· [2] Status bar The status bar appears throughout the interface and
illuminate the current page icon.
7.2.1 LED indications
Three LED’s are present behind the front black plastic of the controller to
indicate major alarm, minor alarm, and system status. These LED’s are not
visible until they illuminate during the corresponding action occurs.
(Red) Major alarm (Orange) Minor alarm (Green) System status
Front black plastic
50 Inview S with MBB User Manual v2.1
Overview – LCD Interface
7.2.2 Menu structure
The home page is the default page in the LCD interface, and other pages are
arranged in the below sequence.
Inview S Slot LCD Interface
Info
Action
Logs
Events
Home
AC In
Ac Out
DC
System
· IP address
· MAC address
· Software version
· Refresh module list
· Cut off alarms
System summary · AC In · AC Out · Battery · DC
AC In details · Current · Voltage · Hertz · Active
power (kW) · Apparent
Power (kVA)
AC In details · Current · Voltage · Active
power (kW) · Apparent
Power (kVA)
DC details · Current · Voltage · Power
AC details
· Redundancy
· Installed power
· Available power
· Module configured
· System status – OK, OFF, AL and NT/KO
51 Inview S with MBB User Manual v2.1
Overview – LCD Interface
7.3 LCD interface – Terminology
The below table provides the description of abbreviation and terminology which
appears in both Inview S and Inview S Slot LCD interface.
S.NO
Terminology
Description
1
MOD
Number of modules configured in the system
2
RED
Redundancy satisfied or not
3
INST
Installed Power
4
Redundancy
Number of redundancy from the configured modules
5
OK
Number of active modules
6
OFF
OFF: Number of non-active or switched off modules.
7
AL
Displays the alarms
8
NT/OK (Not Okay) Number of faulty modules or missing modules when compare to configured modules
9
Installed power
It is the total power of the configured modules, including redundancy. Moreover, it is a user configuration based upon the system capacity.
10
Available power
It is the total power of active modules present in the system.
11
Modules configured Total number of modules configured in the system
The controller performs a complete scan and remove the non-active modules from the
module list.
12
Refresh module list
Note: If any parameter is changed, an authentication page appears. Enter the display
PIN password to apply changes. To modify the password, refer section , page 31.
13
Cutoff alarms
Buzzer sound will be muted
14
Logs
Display the latest 100 events occurred.
15
Information
Displays product and network details
52 Inview S with MBB User Manual v2.1
Defective unit
8. Defective unit
8.1 Return defective Inview S
· A repair request should follow the regular logistics chain: End-user =>
Distributor => HELIOS
· Before returning a defective product, a RMA number must be requested through
the sales@heliosps.co.nz Repair registering guidelines may be requested by
email.
· Freight costs: The cost to ship the unit(s) from the Customer’s premises
back to Helios is at the Customer’s charge. Helios will pay for the shipping
of the unit(s) back to the Customer’s premises.
· Warranty: The warranty will be void if the transport conditions or packing
were inadequate. The warranty will be canceled if the unit sent for repair has
been opened by parties other than a Helios approved Repair Centre.
· Repair costs: If the faulty unit is under warranty, Helios will bear the
repair costs. If the warranty is void, the repair costs will be invoiced to
the Customer. If a unit sent back to Helios (Repair or Swap) presents no
defect or failure, a lump sum amount will be charged to the Customer.
· Swap conditions: You must provide Helios with a Purchase Order for the new
unit that you are requesting, at the current price. No Swap request will be
accepted without it! Within 3 months of the reception of our Swap approval
email, you will have to provide Helios with a tracking reference proving that
you have shipped the faulty unit(s) back to Helios. If Helios does not receive
the tracking reference or the unit in time, Helios will automatically invoice
the unit(s) sent in exchange, at the current price list value.
· RMA: Your Return Material Authorization number (RMA) and the address of the
appropriate Repair Centre will be confirmed to you after careful review of
your request. The RMA number must be present on the packing and all the
paperwork of the returned material. So PLEASE, wait until you receive these
two informations before you ship us the faulty unit.
53 Inview S with MBB User Manual v2.1
Service
9. Service
For Service · Check Service Level Agreement (SLA) of your vendor. Most of the
time they provide assistance on call with integrated service. If such SLA is
in place, you must call their assistance first. · If your vendor doesn’t
provide such assistance (*) you may contact Helios through email.
54 Inview S with MBB User Manual v2.1
Annexe 1: Modules – Parameter List
10. Annexe 1: Modules – Parameter List
10.1 Module – Sierra 25
Parameter V DC in low start – dV (000) V DC in low transfer – dV (001) V DC in
low stop – dV (002) V DC in high start – dV (003) V DC in high transfer – dV
(004) V DC in high stop – dV (005) V AC in low start – dV (006) V AC in low
transfer – dV (007)
V AC in low stop – dV (008)
V AC in high start – dV (009) V AC in high transfer – dV (010) V AC in high
stop – dV (011) F AC in low start – cHz (012) F AC in low stop – cHz (013) F
AC in high start – cHz (014)
Description
Low DC Voltage where a higher value leads the DC/AC converter to re-start
Low DC Voltage where a lower value leads to transfer the load from DC IN to AC
IN. Under this voltage peak-shaving is relaxed and battery discharge test is
stopped.
Low DC voltage where a lower value stops the DC/AC converter
High DC voltage where a higher value re-starts the DC/AC converter
High DC Voltage where a higher value leads to transfer the load from DC IN to
AC IN
High DC voltage where a higher value stops the DC IN converter. Value
increased from sw 173 to 62 VDC
AC IN Voltage where a higher value leads the AC IN to start
AC IN Voltage where a lower value leads to the transfer of the load from the
AC IN to DC IN
AC IN Voltage where a lower value leads the AC IN converter to stops.
It is possible to step down to 150 Vac. In this case, the AC/DC converter will
run at a lower power.
The converter DC/DC supply the rest (ONLY if DC is available, if not, there is
a de-rating)
AC IN Voltage where a lower value leads the AC IN converter re-start
AC IN Voltage where a higher value leads to the transfer the load of the
charge from the AC IN converter to the DC IN converter
AC IN Voltage where a higher value leads to stop the AC IN converter
Frequency where a higher value leads the outlet of the inverters trying to
synchronize with AC IN
Frequency where a lower value leads the outlet of inverters stop to
synchronize with AC IN
Frequency where a lower value leads the inverters outlet to synchronize with
AC IN
Min Default Max Unit
390
440 610 dV
390
390 610 dV
390
390 610 dV
390
580 610 dV
390
610 610 dV
390
610 610 dV
1950 1950 1950 dV 1850 1850 1850 dV
1820 1820 1820 dV
2550 2550 2550 dV 2600 2600 2600 dV 2650 2650 2650 dV 4700 4730 6300 cHz 4700 4700 6300 cHz 4700 5270 6300 cHz
55 Inview S with MBB User Manual v2.1
Annexe 1: Modules – Parameter List
F AC in high stop – cHz (015)
Frequency where a higher value leads the inverters outlet to stop to synchronize with AC IN
4700
Free running frequency – cHz (016)
Set the Inverters system frequency. This frequency is used when the system is not synchronized on AC input.
–
Out 1 phase shift – deg (018)
0
Out 2 phase shift – deg (019)
0
Out 3 phase shift – deg (020)
0
Out 4 phase shift – deg (021)
0
Phase displacement.
Out 5 phase shift – deg (022)
0
Out 6 phase shift – deg (023)
0
Out 7 phase shift – deg (024)
0
Out 8 phase shift – deg (025)
0
Out 1 nominal voltage – dV (026)
2000
Out 2 nominal voltage – dV (027)
2000
Out 3 nominal voltage – dV (028)
2000
Out 4 nominal voltage – dV (029)
2000
Set output voltage for each phase.
Out 5 nominal voltage – dV (030)
2000
Out 6 nominal voltage – dV (031)
2000
Out 7 nominal voltage – dV (032)
2000
Out 8 nominal voltage – dV (033)
2000
Short circuit voltage threshold – V Minimum Voltage Threshold where module
(034)
considers that outlet is in short circuit.
80
Time Duration when a module tries to eliminate
Short circuit hold time – ds (035)
the short-circuit existing on outlet. If the system is still in short-circuit after this time, the output
1
will be stopped.
Defines the priority source
Input source – % (036)
0 – Feeding from AC IN has priority
(converter AC/AC – EPC mode) default value.
0
100 – Feeding from DC has priority (converter DC/AC – On Line mode)
Synchronisation tracking speed (037)
The speed at which the module tries to synchronize the AC Out with AC IN. The lowest value will have the fastest synchronization.
-2
Max power – % (038)
Maximum Power that module can supply
30
Max current – % (039)
Maximum Current that module can supply.
30
Max overload duration – s (040)
Maximum Time Duration when module can run with overload
0
5300 6300 cHz
5000
– cHz
0
360 Deg
120 360 Deg
240 360 Deg
0
0 Deg
0
0 Deg
0
0 Deg
0
0 Deg
0
0 Deg
2300 2450 dV
2300 2450 dV
2300 2450 dV
2300 2450 dV
2300 2450 dV
2300 2450 dV
2300 2450 dV
2300 2450 dV
80
200 V
600 6000 ds
0
100 %
0
2
150 150 % 150 150 %
15
15
s
56 Inview S with MBB User Manual v2.1
Annexe 1: Modules – Parameter List
Allows to open the AC IN inlet relay
AC in mode (041)
0 – normal running in EPC mode
1 – AC IN inlet relay is open and so the system is insulated from the Mains.
0
This parameter can be set to 1 only if repartition is on DC (parameter 036 should be 100)
Booster 10x I in (042)
Allow to inhibit the Booster option which
generates a current of 10 In for 20ms in case of
0
short-circuit (9 In for Nova inverter).
This parameter change the attribution of the
remote ON/OFF input.
Remote off disable AC in power (043)
If parameter is 1, then, when system is in remote
0
OFF position, output is not stopped and AC input
is stopped instead.
Reinjection allowed (044)
If this parameter is 1, the module is allowed to inject power in the grid with its AC input.
0
Records the “External Clock” mode configuration
External clock (045) Walk in mode – das (046) Triangle mode (047)
0 – no protection in: phase drift is allowed.
1 – protection in: no phase drift allowed, stops
0
the system after 1 minute.
2 – System stops immediately.
The Walk-in mode allows the inverter to come
back progressively on the AC priority source after
0
an outage. Friendly use on Genset
Defines the protection type for working on Delta load.
0 – Default setting, and no delta load protection
0
1 – The mode is active. If one output phase stops, the other phases will also stop.
Airco mode (048)
When this mode is activated, the overload
capabilities are moved from default value to 330% overload in current and power for
0
maximum 900 ms.
Start without supervision (049)
When this mode is activated, the module is able to start without Inview S.
0
P DC max – W (050)
This feature allow to limit or reduce the INRUSH
DC current when the system work on battery. To
limit the current this configuration line should
limit the inrush DC current.
0
To allow for the high capability this inverter is build with extra capacitor running on 400VDC to provide the requested energy.
0
1
1
1
0
1
0
1
0
2
0
12
0
1
0
1
1
1
0
1
57 Inview S with MBB User Manual v2.1
Annexe 1: Modules – Parameter List
AC 1 stop power (051) AC 2 stop power (052) AC 3 stop power (053) AC 4 stop power (054)
Stops the power of the corresponding AC group.
0
The AC input of the modules of this AC group will
0
then be used for synchronisation only, no power
0
will be taken.
0
St module number (055)
NA
0
St module redundancy (056)
NA
0
Tus (057)
Mode TUS activation
0
Tus modules number (058)
Number of TUS modules in the system (typically 2) -> number of tus seen by local supervision
0
Tus sub sub system address (059)
address of the system on TUS bus -> address of
local supervision which need to be different from
0
other local supervisions
Tus sub sub system output phase (060)
Output phase in TUS mode
0
Tus sub system index (061)
System index in TUS mode (for example, if we have a A+B redundancy, this parameter is 1 for A systems, 2 for B systems)
Number of tus sub sub system (062)
Number of systems connected on TUS bus
0
Tus supply x supervision mode (063)
X TUS supply source
–
Tus supply y supervision mode (064)
Y TUS supply source
–
Tus sub sub system dc group (065)
DC group of the system in TUS mode
0
V DC charger safe mode – cV (066)
DC voltage set point in SIERRA mode
5300
P DC charger safe mode – W (067)
DC power setpoint in sierra mode (> 0 if battery discharge, <0 if battery charging)
0
P AC peak shaving safe mode – W (068)
global peak-shaving (-1 if no peak-shaving)
P AC max per phase safe mode – Peak-shaving for each individual phase (-1 if no
W (069)
peak-shaving)
Phase compensation (070)
Phase balancing
0
Sierra mode (071)
Is module allowed to run in charger mode
0
V DC low stop charger – cV (072) Dc voltage under which charger is stopped
0
Lvd mode (073)
If this mode is ON, module goes in low
consumption mode 1 minute after it stops by Vdc
0
LowStop
Max V DC increment safe mode – cV (074)
Vdc set point rising speed when there is no supervision
0
1
0
1
0
1
0
1
0
3
0
4
0
1
0
24
0
4
0
11
0
8
–
–
–
–
0
3
5400 5400 cV
–
2400 W
1
1
1
1
0
1
0
1
58 Inview S with MBB User Manual v2.1
Annex 2: Inview S with MBB – Wiring diagram
11. Annex 2: Inview S with MBB – Wiring diagram
59 Inview S with MBB User Manual v2.1
Annex 3: Auxiliary power supply kit
12. Annex 3: Auxiliary power supply kit
12.1 Auxiliary power supply kit with Din Rail
Part number: T602004120
Q10 A10 X10
L N PE
Q11
X11
+-
A11
K10 K11
X13
X14 X12
12
+-
Front View
X10 – AC input terminal (1P) X11 – DC input terminal (Battery voltage)
X12 – DC Output terminal (12 V DC)
X13 – Alarm contact for Aux power supply unit fail
12.2 Auxiliary power supply kit – Wiring diagram
(0.5 Blk) (0.5 Blk)
12
X14
12Vdc 15W
- X12/1
–
X12/2
L
X10/1
N
X10/2
PE
X10/3 -
X11/1
–
X11/2
(0.5 Blk) (0.5 Blk)
–
A10
OUT
A1
K10
A2
IN
L
N
(1,5 Blk)
Q10 10A
85-264Vac
–
OUT
A11
PE
IN
–
(1,5 Blk)
Q11 10A
18-60Vdc
A1
K11
A2
K10
C
NO
K11
C
NO
(0,5 Blk)
1
X13/1
APSU FAILURE
2
X13/2
60 Inview S with MBB User Manual v2.1
Annex 4: Inview S panel sheets
13. Annex 4: Inview S panel sheets
3U Panel sheet – cut out details
Dimensions are in mm
2U Panel sheet (center)- cut out details
Dimensions are in mm
2U Panel sheet (left)- cut out details
Dimensions are in mm
61 Inview S with MBB User Manual v2.1
Annex 5: Inview S – Software upgrading
14. Annex 5: Inview S – Software upgrading
Perform the following steps to upgrade Inview S software. 1. Check the
existing software version. LCD display: tap on “Information” icon at Settings
page in Inview S LCD display and note the existing software version and IP
address for web interface.
Note: Software upgrade can be done only through web interface.
Web interface: Login as admin privileged account, click on user account and
select About from the dropdown list.
2. Extract the “inview_X.Y.Zupgrade.upg.RAR” file downloaded on my.cet-
power.com. Its name should look like “inview.X.Y.Z_upgrade.upg”
62 Inview S with MBB User Manual v2.1
Annex 5: Inview S – Software upgrading
3. In Inview S web interface, select Home page > > Maintenance and click
“UPLOAD UPDATE FILE” under Software update. A pop will appears and click
UPDATE.
4. Select the downloaded .upg file
5. Wait, the upgrading process will take approximately 15 minutes to return
normal operating condition
6. After successful up-gradation, the web interface resume to login screen.
Check the new software version and network details in Info page. (refer step
- Note: · It is forbidden to “downgrade” systems. · It’s mandatory to have at
least Inview software version 2.0.2 or higher to proceed to this upgrade. If
the unit is below 2.0.2, get in touch with your Area Sales Manager or
supplier. · Note down the MBB serial and version number which is present at
rear side of the product. It may be also required to upgrade to the latest
version.
63 Inview S with MBB User Manual v2.1