WaterFurnace 500 WSHP Geothermal Heat Pump Instruction Manual
- June 9, 2024
- WaterFurnace
Table of Contents
500 WSHP Geothermal Heat Pump
Versatec 500 0.75-6 Ton Installation Manual
Formerly Envision2 Compact Commercial 60 Hz Water Source/Geothermal Heat Pump
· R-410A Refrigerant · Commercial 0.75-6 Ton
Installation Information Water Piping Connections Hot Water Connections
Electrical Startup Procedures Troubleshooting Preventive Maintenance
IM1022ANA 01/22
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General
Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . 5 Dimensional Data . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 6 Installing Horizontal Units .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 10 Hanger Bracket Locations . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .11 Duct System . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 12 Water Piping . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 12 Condensate Drain . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 12 Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 13 System Cleaning and Flushing . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Open Loop
Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 14 Hot Water Generator Connections . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 15 Freeze Detection . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 17 Electrical Connections . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 17 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Blower Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Wiring
Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 Controls . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Unit Startup. .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .49 Operating Limits .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .50 Operating Parameters. . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .50 Pressure Drop . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 52 Reference Calculations and Legend. . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 53 Refrigerant Circuit Guideline . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .54 Heat of Extraction/Rejection
Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 55 Troubleshooting . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .56 Preventive Maintenance and Replacement Parts . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59 Revision Guide
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Model Nomenclature
1-2 3 4-6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21-22 23 NB V 048 T L 0 0 0 C A N A N 1 A 3 0 SS *
Model Type NB Envision2 Compact
Cabinet Configuration V Vertical H – Horizontal
Unit Capacity (MBTUH) Single Speed 009, 012, 015, 018, 024, 030 036, 042, 048,
060, 070 Dual-Capacity 026, 038, 049, 064, 072
Discharge Configuration T Top (Vertical) E End (Horizontal) S Side
(Horizontal)
Return Air Configuration L Left R Right
Voltage 0 208-230/60/1 2 265-277/60/1 (009-038) 3 208-230/60/3 (024-072)
4 460/60/3 (024-072) 5 575/60/3 (PSC Only 042-070)
Refrigeration Option 0 None 2 HWG Only w/o Pump (Vertical 018-072) G Hot
Gas Bypass (015-072) R Hot Gas Reheat (015-072) B Hot Gas Bypass w/Hot Gas
Reheat (015-072)
Blower Option 0 PSC Blower (Single Speed Only) 1 Variable Speed ECM Blower
(015-072) 2 High Static Variable Speed ECM Blower (036, 038, 042, 048, 049)
3 High Static PSC Blower (024-048) 4 5-Speed ECM Blower (015-072) 6
Variable Speed Constant Torque ECM Blower (009-012)
Water Coil Option C Copper D Insulated Copper N CuproNickel P
Insulated CuproNickel
Sound Kit Option A None B Sound Kit
Note:
1 – Phase G uard O nly Available on 208-230/60/3, 460/60/3, and 575/60/3. 2
Waterside economizer option must be ordered with stainless steel drain pan and
either 5-speed ECM or variable speed ECM (024-072). 3 Control Option not
available with PSC Motor.
Vintage * Factory Use Only
Non-Standard Option SS Standard
Drain Pan Option 0 Composite, No Secondary Connection 1 Composite,
Secondary Connection 2 Stainless Steel, No Secondary Connection 3
Stainless Steel, Secondary Connection
Air Coil Option 3 All-Aluminum, Uncoated 4 All-Aluminum, AlumiSealTM
Filter Option A MERV 4 B MERV 13
Cabinet Option 0 Unpainted Cabinet, Filter Rail 1 Painted Cabinet, Filter
Rail 2 Unpainted Cabinet, 4-Sided Filter Rack 3 Painted Cabinet, 4-Sided
Filter Rack
Electrical Option1 N None A IntelliStart® Only E IntelliStart and
Disconnect P Phase Guard, No Disconnect B Phase Guard, Disconnect D No
Phase Guard, Disconnect
Control Option A AuroraTM Base Control (ABC) C AuroraTM Advanced Control3
D AuroraTM Advanced Control & Refrigeration3 E AuroraTM UPC DDC Controler
F AuroraTM UPC DDC Controler with LON G AuroraTM UPC DDC Controler
Advanced Control3 H AuroraTM UPC DDC Controler Advanced Control &
Refrigeration3 J AuroraTM UPC DDC Controler w/ LON Advanced Control3 K
AuroraTM UPC DDC Controler w/ LON Advanced Control & Refrigeration3
Water Control Option2 N None R Water Flow Regulator V 2-Way Valve B
2-Way Valve w/ Water Flow Regulator W Waterside Economizer S Waterside
Economizer w/ Water Flow Regulator E Waterside Economizer w/ 2-Way Valve C
Waterside Economizer w/ 2-Way Valve & Water Flow Regulator
Note: See separate manual for economizer option
4
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
General Installation Information
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn
off main power switches to the indoor unit. If applicable, turn off the
accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be
hazardous due to system pressure and electrical components. Only trained and
qualified service personnel should install, repair or service heating and air
conditioning equipment. Untrained personnel can perform the basic maintenance
functions of cleaning coils and cleaning and replacing filters. All other
operations should be performed by trained service personnel. When working on
heating and air conditioning equipment, observe precautions in the literature,
tags and labels attached to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching
cloth for brazing operations and have a fire extinguisher available.
Unit Location Locate the unit in an indoor area that allows for easy removal
of the filter and access panels. Location should have enough space for service
personnel to perform maintenance or repair. Provide sufficient room to make
water, electrical and duct connection(s). If the unit is located in a confined
space, such as a closet, provisions must be made for return air to freely
enter the space by means of a louvered door, etc. Any access panel screws that
would be difficult to remove after the unit is installed should be removed
prior to setting the unit. On horizontal units, allow adequate room below the
unit for a condensate drain trap and do not locate the unit above supply
piping. Care should be taken when units are located in unconditioned spaces to
prevent damage from frozen water lines and excessive heat that could damage
electrical components.
Installing Vertical Units
Prior to setting the unit in place, remove and discard the compressor hold
down shipping bolt located at the front of the compressor mounting bracket.
Moving and Storage
Move units in the normal “up” orientation. Horizontal units may be moved and
stored per the information on the packaging. Do not stack more than three
units in total height. Vertical units may be stored one upon another to a
maximum height of two units. Do not attempt to move units while stacked. When
the equipment is received, all items should be carefully checked against the
bill of lading to be sure all crates and cartons have been received. Examine
units for shipping damage, removing the units from the packaging if necessary.
Units in question should also be internally inspected. If any damage is noted,
the carrier should make the proper notation on the delivery receipt,
acknowledging the damage.
Vertical units are available in left or right air return configurations. Top
flow vertical units should be mounted level on a vibration absorbing pad
slightly larger than the base to provide isolation between the unit and the
floor. It is not necessary to anchor the unit to the floor (see figure below).
Vertical Unit Mounting
2 in. PEX Foam
5
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Vertical Dimensional Data
Standard filter rails for open return applications
Field installed duct flange
A
N
R
Q
Deluxe filter rack for ductable return applications
A
S
N
Air coil
Q
ACCESS PANEL
AIR COIL SIDE
AIR COIL SIDE
BP
4
G
3
FRONT
F
1.4 in (3.5 cm)
Top View – Right Return
M
M
Air coil
PB
4
FRONT 3
2′ (61 cm) Alternate Service Access G
F 1.4 in (3.5 cm)
Top View – Left Return
2′ (61 cm)
Service Access Left Return
(Right Return opposite side)
Air coil
Isometric View – Left Return
U
T
W
ACCESS PANEL
C
H E D
1.6 in (4.1 cm)
Condensate 3/4 in
PVC glue socket 1.6 in (4.1 cm)
5
6
2
8
1
Power supply 1 in (25.4 mm)
knockout
Low voltage
1/2″ (12.7 mm)
knockout
LJ
LK
Front View – Right Return
ACCESS PANEL
Condensate 3/4 in PVC glue socket
1.6 in (4.1 cm)
5
8
2
7
1
C
1.6 in (4.1 cm)
H E D
Front View – Left Return
V
6
ACCESS
8
PANEL
8
JL
7
Right View – Right Return Left View – Left Return
KL
6
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Vertical Dimensional Data cont.
Overall Cabinet
Vertical
1
Models
A
B
C
D
Width Depth Height*
In
in. 22.5
22.2
30.2
2.6
009-012
cm. 57.2
56.4
76.7
6.6
015-018 in.
22.5
26.2
40.2
2.6
cm. 57.2
66.5
102.1
6.6
in. 22.5
26.2
44.2
2.6
024-030
cm. 57.2
66.5
112.3
6.6
in. 25.5
31.2
44.2
2.6
036-038
cm. 64.8
79.2
112.3
6.6
in. 25.5
31.2
48.2
2.6
042-049
cm. 64.8
79.2
122.4
6.6
in. 25.5
31.2
52.2
2.6
060-072
cm. 64.8
79.2
132.6
6.6
Water Connections
Electrical Knockouts
6
7
8
2
3
4
5
J
K
L
E
F
G
H
Loop
Knockout
1/2 in. cond
1/2 in. cond
1 in. cond
Out
HWG In HWG Out
Condensate
Water HWG
Low
Low Power
FPT Provisions Voltage Voltage Supply
7.6
N/A
N/A
10.8
1/2 in.
N/A
9.4
5.4
7.4
19.3
N/A
N/A
27.4 12.7 mm N/A
23.9
13.7
18.8
7.6
1.4
4.4
10.8
3/4 in. 0.875
10.1
6.1
8.1
19.3
3.6
11.2
27.4 19.1 mm 22.2 mm 25.7
15.5
20.6
7.6
1.4
4.4
10.8
3/4 in. 0.875
10.1
6.1
8.1
19.3
3.6
11.2
27.4 19.1 mm 22.2 mm 25.7
15.5
20.6
7.6
1.4
4.4
10.8
1 in.
0.875
10.1
6.1
8.1
19.3
3.6
11.2
27.4 25.4 mm 22.2 mm 25.7
15.5
20.6
7.6
1.4
4.4
10.8
1 in.
0.875
10.1
6.1
8.1
19.3
3.6
11.2
27.4 25.4 mm 22.2 mm 25.7
15.5
20.6
7.6
1.4
4.4
10.8
1 in.
0.875
10.1
6.1
8.1
19.3
3.6
11.2
27.4 25.4 mm 22.2 mm 25.7
15.5
20.6
3/16/12
Discharge Connection
duct flange installed (±0.10 in)
Vertical Models
M
N
P
Q
R
S
Filter Rack Supply
Supply
Width
Width
Depth
**Return Connection using deluxe filter rack (±0.10 in)
T
U
V
Return Depth
Return Height
in.
2.2
10.0
10.0
6.1
5.3
9.8
2.0
18.1
14.0
009-012
cm.
5.6
25.4
25.4
15.5
13.5
24.9
5.1
46.0
35.6
in.
2.2
14.0
14.0
6.1
4.5
7.7
2.0
22.1
22.0
015-018
cm.
5.6
35.6
35.6
15.5
11.4
19.6
5.1
56.1
55.9
in.
2.2
14.0
14.0
6.1
4.5
7.7
2.0
22.1
26.1
024-030
cm.
5.6
35.6
35.6
15.5
11.4
19.6
5.1
56.1
66.3
in.
2.2
18.0
18.0
6.6
4.6
6.3
1.6
28.1
26.1
036-038
cm.
5.6
45.7
45.7
16.8
11.7
16.0
4.1
71.4
66.3
in.
2.2
18.0
18.0
6.6
4.6
6.3
1.6
28.1
30.0
042-049
cm.
5.6
45.7
45.7
16.8
11.7
16.0
4.1
71.4
76.2
060-072 in.
2.2
18.0
18.0
6.6
5.0
6.4
1.6
28.1
34.0
cm.
5.6
45.7
45.7
16.8
12.7
16.3
4.1
71.4
86.4
Condensate is 3/4 in. PVC female glue socket and is switchable from side to front. *Discharge flange is field installed and extends 1 in. (25.4 mm) from top of cabinet. **Vertical units shipped with standard 2 in. (field adjustable to 1 in.) open application filter rack extending 2.2 in. from unit and is not suitable for duct connection, for ductable return connection applications, order the deluxe 2 in. (field adjustable to 1 in.) duct collar/filter rack which extends 3.25 in. from the unit and is suitable for duct connections.
W
2.0 5.1 1.9 4.8 1.8 4.6 2.0 5.1 2.0 5.1 2.0 5.1 3/16/12
Vertical Disconnect
When using disconnect, do not use dimension L from the standard vertical
dimensional data. Use dimension LL from the vertical disconnect dimensional
data.
Vertical Models 009-012 015-018 024-030 036-038 042-049 060-064 070-072
Dimensions in inches [cm]
LL 17.8 [45.2] 14.3 [36.3] 15.3 [38.9] 14.3 [36.3] 14.3 [36.3] 14.3 [36.3] External
3/16/12
7
Power Supply
1.8 in. [4.6 cm]
Disconnect Location
Alternative Power Location
Disconnect Located on this Side for a Right Return
LL
Vertical Shown in Left Return Configuration
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Horizontal Dimensional Data
Right Return
Standard filter rails 1 in. [2.5 cm] knockout K
0.5 in. [1.3 cm] knockout Front
J AP CMP
2′ (61 cm) Service Access
1.7 in. [5.3 cm] CP AP
A RR Front View
1.7
1.7
1.7 in. [5.3 cm]
Standard filter rails Front
E
D
AP
CMP
2′ (61 cm)
J
Service Access
Left Return
Condensate “X” PVC size
End Discharge
Side Discharge
Deluxe filter rack option shown
2.3 in. [5.8 cm]
N
P
BLOWER OUTLET
MC
FILTER RACK AIR COIL SIDE
H
L
2.1 in. [5.3 cm] A
Right Return End Discharge
CP AP E
0.5 in. [1.3 cm] knockout
K 1 in. [2.5 cm] knockout
D
LR Front View
Legend AP = Alternate Service Panel BP = Blower Service Panel CP = Control Access Panel CMP = Compressor Service Panel
Side Discharge
Condensate “X” PVC size
End Discharge
Deluxe filter rack option shown
P
N
L
2.3 in. [5.8 cm]
FILTER RACK AIR COIL SIDE
CM
BLOWER
OUTLET
H
2.1 in. [5.3 cm] A
Left Return End Discharge
P
N
L
M BP
BLOWER OUTLET
1.5 in. [3.8 cm] AP CMP
Right Return Side Discharge
K 0.5 in. [1.3 cm] J knockout
Front
Front
1 in. [2.5 cm]
J
knockout
K
0.5 in. [1.3 cm]
knockout
1.5 in. [3.8 cm] AP CMP
N
P
BLOWER OUTLET
BP M
L
Left Return Side Discharge
Air Coil
C Front
Q FILTER RACK CONNECTION
S
T
TS
Deluxe filter rack option (shown)
R
CR
Q FILTER RACK CONNECTION
B Right Return Side View
B Left Return Side View
Air Coil Front
8
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Horizontal Dimensional Data cont.
Overall Cabinet
Horizontal
1
Models
A
B
C
D
Width
Depth
Height*
In
in.
22.5
35.0
17.2
1.8
009-012
cm.
57.2
88.9
43.7
4.6
in.
22.5
42.0
19.2
1.8
015-018
cm.
57.2
106.7
48.8
4.6
in.
22.5
45.0
19.2
1.8
024-030
cm.
57.2
114.3
48.8
4.6
036-038 in.
25.5
48.0
21.2
1.8
cm.
64.8
121.9
53.8
4.6
in.
25.5
53.0
21.2
1.8
042-049
cm.
64.8
134.6
53.8
4.6
in.
25.5
61.0
21.2
1.8
060-064
cm.
64.8
154.9
53.8
4.6
in.
25.5
68.0
21.2
1.8
070-072
cm.
64.8
172.7
53.8
4.6
Water Connections
2
3
E
H
Out
Condensate
6.8
0.8
17.3
2.0
6.8
0.8
17.3
2.0
6.8
0.8
17.3
2.0
6.8
0.8
17.3
2.0
6.8
0.8
17.3
2.0
6.8
0.8
17.3
2.0
6.8
0.8
17.3
2.0
Loop Water FPT
1/2 in. 12.7 mm 3/4 in. 19.05 mm 3/4 in. 19.05 mm
1 in. 25.4 mm
1 in. 25.4 mm
1 in. 25.4 mm
1 in. 25.4 mm
Electrical Knockouts
J
K
1/2 in. cond 1 in. cond
Low Voltage Power Supply
7.1
7.1
18.0
18.0
9.1
7.1
23.1
18.0
9.2
7.1
23.4
18.0
9.2
9.1
23.4
23.1
9.2
9.1
23.4
23.1
9.2
9.1
23.4
23.1
9.2
9.1
23.4
23.1
3/16/12
Horizontal Models
Discharge Connection
duct flange installed (±0.10 in.)
L
M
N
P
Return Connection
using deluxe filter rack option (±0.10 in.)
Q
R
S
T
Supply Width Supply Depth
Return Depth Return Height
in.
5.9
7.2
9.5
6.0
16.4
14.5
2.0
1.4
009-012
cm.
15.0
18.3
24.1
15.2
41.7
36.8
5.1
3.6
in.
6.7
10.5
9.4
4.9
27.4
16.6
2.0
1.4
015-018
cm.
17.0
26.7
23.9
12.4
69.6
42.2
5.1
3.6
in.
6.7
10.5
9.4
4.9
30.4
16.6
2.0
1.5
024-030
cm.
17.0
26.7
23.9
12.4
77.2
42.2
5.1
3.8
in.
4.9
13.6
13.2
4.6
35.4
18.6
2.3
1.4
036-038
cm.
12.4
34.5
33.5
11.7
89.9
47.2
5.8
3.6
in.
4.9
13.6
13.2
4.6
40.4
18.6
2.3
1.4
042-049
cm.
12.4
34.5
33.5
11.7
102.6
47.2
5.8
3.6
in.
4.9
13.6
13.2
4.6
45.4
18.6
2.3
1.4
060-064
cm.
12.4
34.5
33.5
11.7
115.3
47.2
5.8
3.6
in.
4.9
13.6
13.2
4.6
45.4
18.6
2.3
1.4
070-072
cm.
12.4
34.5
33.5
11.7
115.3
47.2
5.8
3.6
Horizontal units shipped with standard 2 in. (field adjustable to 1 in.) open application filter rack extending 2.2 in. from unit and is not suitable for duct connection, for ductable return connection applications, order the deluxe 2 in. (field adjustable to 1 in.) filter rail/filter rack which extends 3.25 in. from the unit and is suitable for duct connections.
PVC Size
X
3/4″ 1.9 3/4″ 1.9 3/4″ 1.9 3/4″ 1.9 3/4″ 1.9 3/4″ 1.9 3/4″ 1.9
3/16/12
Horizontal Disconnect
When using disconnect, do not use dimension K from the standard horizontal
dimensional data. Use dimension KK from the horizontal disconnect dimensional
data.
Horizontal Models 009-012 015-018 024-030 036-038 042-049 060-064 070-072
Dimensions in inches [cm]
KK 8.2 [20.8] 9.2 [23.4] 9.2 [23.4] 11.2 [28.4] 10.2 [25.9] 11.2 [28.4] 10.2 [25.9]
Disconnect Located on this Side for a Left Return
3/16/12
Disconnect Location
KK
2.1 in. [5.3 cm]
Power Supply
Horizontal Shown in Right Return Configuration
9
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Installing Horizontal Units
Installing Horizontal Units Remove and discard the compressor hold down
shipping bolt located at the front of the compressor mounting bracket prior to
setting the unit in place. Horizontal units are available with side or end
discharge.
NOTE: Horizontal units are normally suspended from a ceiling by four (009-060
models) or five (070-072 models) 3/8 in. diameter threaded rods. The rods are
usually attached to the unit by hanger bracket kits furnished with each unit.
Lay out the threaded rods per the Hanger Bracket Dimensions table. Assemble
the hangers to the unit as shown. Securely tighten the brackets to the unit
using the weld nuts located on the underside of the bottom panel. When
attaching the hanger rods to the bracket, a double nut is required since
vibration could loosen a single nut. To allow filter access, install hanger
brackets as illustrated in the Hanger Bracket Locations section. The unit
should
be pitched approximately 1/4 in. towards the drain in both directions to
facilitate the removal of condensate. Use only the bolts provided in the kit
to attach hanger brackets. The use of longer bolts could damage internal
parts.
Some applications require the installation of horizontal units on an attic
floor. In this case, the unit should be set in a full size secondary drain pan
on top of a vibration absorbing pad. The secondary drain pan prevents possible
condensate overflow or water leakage damage to the ceiling. The secondary
drain pan is usually placed on a plywood base isolated from the ceiling joists
by additional layers of vibration absorbing material.
CAUTION: Do not use rods smaller than 3/8 in. diameter since they may not be
strong enough to support the unit. The rods must be securely anchored to the
ceiling.
10
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Hanger Bracket Locations
H
Right
D Compressor Section
B
E
F
C Air Handler
Section G
A
3/8″ Threaded Rod (not supplied)
E
Compressor
D
Section
H
Vibration Isolator W asher
Left G
Air Handler Section
F
Bolt and Lockwasher
Hex Nuts (not supplied)
NOTE: Model sizes 070-072 will be shipped with six (6) hanger brackets. Only five (5) hanger brackets will be used on the unit. See the above illustration for the fifth hanger bracket location. All other models will use four (4) hanger brackets.
Hanger Bracket Dimensions
Single Speed
Model
Hanger Kit Part Number
in.
009-012
99S500A04
cm.
in.
015-018
99S500A04
cm.
in.
024-030
99S500A04
cm.
036
in. 99S500A04
cm.
in.
042-048
99S500A04
cm.
060
in. 99S500A04
cm.
070
in. 99S500A03
cm.
026
in. 99S500A04
cm.
in.
038
99S500A03
cm.
049
in. 99S500A04
cm.
064
in. 99S500A04
cm.
in.
072
99S500A03
cm.
Unit Hanger Dimensions
A
B
C
H
35.7
25.1
21.4
n/a
90.7
63.8
54.4
n/a
42.8
25.1
21.4
n/a
108.7
63.8
54.4
n/a
45.8
25.1
21.4
n/a
116.3
63.8
54.4
n/a
48.8
28.1
24.4
n/a
124.0
71.4
62.0
n/a
53.8
28.1
24.4
n/a
136.7
71.4
62.0
n/a
61.8
28.1
24.4
n/a
157.0
71.4
62.0
n/a
68.8
28.1
24.4
34.0
174.8
71.4
62.0
74.4
45.8
25.1
21.4
n/a
116.3
63.8
54.4
n/a
48.8
28.1
24.4
n/a
124.0
71.4
62.0
n/a
53.8
28.1
24.4
n/a
136.7
71.4
62.0
n/a
61.8
28.1
24.4
n/a
157.0
71.4
62.0
n/a
68.8
28.1
24.4
34.0
174.8
71.4
62.0
74.4
3/16/12
Dual Capacity
Weight Distribution
Model
Vertical Horizontal Weight Weight
009
171 [78]
176 [80]
171 012
[78]
176 [80]
210 015
[95]
220 [100]
210 018
[95]
220 [100]
Single Speed
024
280 [127]
295 [134]
030
285 [129]
295 [134]
036
300 [136]
305 [138]
042
365 [166]
375 [170]
048
370 [168]
380 [172]
060
410 [186]
420 [191]
070
445 [202]
455 [206]
026
280 [127]
295 [134]
Dual Capacity
038
360 [163]
375 [170]
049
370 [168]
380 [172]
064
410 [186]
420 [191]
445 072
[202]
455 [206]
Weights are listed in lbs. [kg].
Horizontal Weight Distribution
Front
Back
D
E
F
G
32
67
32
45
[15] [30] [15] [20]
32
67
32
45
[15] [30] [15] [20]
65
40
70
35
[29] [18] [32] [16]
65
40
70
35
[29] [18] [32] [16]
75
70
75
20
[34] [31] [34] [13]
75
70
75
30
[34] [31] [34] [13]
85
80
85
40
[39] [36] [39] [18]
115
95
75
60
[52] [43] [34] [27]
120
100
80
65
[54] [45] [36] [29]
120
110
95
80
[54] [50] [43] [36]
135
120
100
85
[61] [54] [45] [39]
75
70
75
50
[34] [31] [34] [13]
115
95
75
60
[52] [43] [34] [27]
120
100
80
65
[54] [45] [36] [29]
120
110
95
80
[54] [50] [43] [36]
135
120
100
85
[61] [54] [45] [39]
3/16/12
11
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Duct System
An air outlet collar is provided on vertical top flow units and all horizontal
units to facilitate a duct connection. A flexible connector is recommended for
discharge and return air duct connections on metal duct systems. Uninsulated
duct should be insulated with a minimum of 1-inch duct insulation. Application
of the unit to uninsulated ductwork in an unconditioned space is not
recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure
that it has the capacity to accommodate the air required for the unit
application. If the duct is too small, as in the replacement of heating only
systems, larger ductwork should be installed. All existing ductwork should be
checked for leaks and repaired if necessary.
The duct system should be sized to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed.
Water Piping
The proper water flow must be provided to each unit whenever the unit
operates. To assure proper flow, use pressure/temperature ports to determine
the flow rate. These ports should be located at the supply and return water
connections on the unit. The proper flow rate cannot be accurately set without
measuring the water pressure drop through the refrigerant-to-water heat
exchanger.
All source water connections on commercial units are fittings that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fitting with a wrench to provide a leakproof joint. When connecting to an open loop (groundwater) system, thread any copper MPT fitting into the connector and tighten in the same manner as described above.
Condensate Drain
On vertical units, the internal condensate drain assembly consists of a drain
tube which is connected to the drain pan, a 3/4 in. PVC female adapter and a
flexible connecting hose. The female adapter may exit either the front or the
side of the cabinet. The adapter should be glued to the field-installed PVC
condensate piping. On vertical units, a condensate hose is inside all cabinets
as a trapping loop; therefore, an external trap is not necessary.
Horizontal Drain Connection (Composite Drain Pan)
On horizontal units, a PVC stub or stainless steel tube is provided for
condensate drain piping connection. An external trap is required (see below).
If a vent is necessary, an open stand pipe may be applied to a tee in the
fieldinstalled condensate piping.
Unit Pitch for Drain
PVC tube stub
PVC coupling
1.5 in.
1.5 in.
Vent (if needed)
PVC tube stub 1/8 in. per foot
12
1/2” Pitch Drain
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas
with extremely hard water, the owner should be informed that the heat
exchanger may require occasional flushing. Failure to adhere to the guidelines
in the water quality table could result in loss of warranty.
Units with cupronickel heat exchangers are recommended for open loop
applications due to the increased resistance to build-up and corrosion, along
with reduced wear caused by acid cleaning.
Material pH
Scaling
Acidity/Alkalinity Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Corrosion
Iron Fouling (Biological Growth)
Sulfates Chlorine Chlorides Carbon Dioxide Ammonia Ammonia Chloride Ammonia
Nitrate Ammonia Hydroxide Ammonia Sulfate Total Dissolved Solids (TDS) LSI
Index Iron, FE2+ (Ferrous) Bacterial Iron Potential
Iron Oxide
Suspended Solids
Erosion
Threshold Velocity
(Fresh Water)
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Copper 7 – 9
(Total Hardness) less than 350 ppm Less than 0.5 ppm (rotten egg smell appears
at 0.5 ppm) Less than 125 ppm Less than 0.5 ppm Less than 20 ppm Less than 50
ppm Less than 2 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Less
than 0.5 ppm Less than 1000 ppm
+0.5 to -0.5
90/10 Cupronickel 7 – 9
(Total Hardness) less than 350 ppm
10 – 50 ppm
Less than 125 ppm Less than 0.5 ppm Less than 125 ppm
10 – 50 ppm Less than 2 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5
ppm Less than 0.5 ppm 1000 – 1500 ppm
+0.5 to -0.5
< 0.2 ppm
< 0.2 ppm
Less than 1 ppm, above this level deposition will occur
Less than 10 ppm and filtered for max. of 600 micron size
Less than 1 ppm, above this level deposition will occur
Less than 10 ppm and filtered for max. of 600 micron size
< 6 ft/sec
< 6 ft/sec
316 Stainless Steel 7 – 9
(Total Hardness) less than 350 ppm
Less than 1 ppm
Less than 200 ppm Less than 0.5 ppm Less than 300 ppm
10 – 50 ppm Less than 20 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5
ppm Less than 0.5 ppm 1000 – 1500 ppm
+0.5 to -0.5
< 0.2 ppm
Less than 1 ppm, above this level deposition will occur Less than 10 ppm and
filtered for max. of 600 micron size
< 6 ft/sec
2/22/12
System Cleaning and Flushing
Cleaning and Flushing
Prior to start up of any heat pump, the water circulating system must be
cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the supply and return
runouts must be connected together at each unit location (This will prevent
the introduction of dirt into the unit, see Flushing with Water Shutoff Valve
Equipped Systems illustration). The system should be filled at the water make-
up connection with all air vents open. After filling, vents should be closed.
The contractor should start the main circulator with the pressure reducing
valve makeup open. Vents should be checked in sequence to bleed off any
trapped air and to verify circulation through all components of the system.
As water circulates through the system, the contractor should check and repair
any leaks found in the piping system. Drain(s) at the lowest point(s) in the
system should
Flushing with Water Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Rubber Hose
Mains
Runouts Initially Connected Together
13
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
System Cleaning and Flushing cont.
be opened for initial flush and blowdown, making sure water fill valves are
set at the same rate. Check the pressure gauge at the pump suction and
manually adjust the makeup water valve to hold the same positive pressure both
before and after opening the drain valves. Flushing should continue for at
least two hours, or longer if required, until drain water is clean and clear.
The supplemental heater and/or circulator pump, if used, should be shut off.
All drains and vents should be opened to completely drain the system. Short-
circuited supply and return runouts should now be connected to the unit supply
and return connections.
Refill the system with clean water. Test the system water for acidity and
treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The
specified percentage of antifreeze may also be added at this time. Use
commercial grade antifreeze designed for HVAC systems only. EnvironolTM brand
antifreeze is recommended.
Once the system has been filled with clean water and antifreeze (if used),
precautions should be taken to protect the system from dirty water conditions.
Dirty water will result in system-wide degradation of performance, and solids
may clog valves, strainers, flow regulators, etc. Additionally, the heat
exchanger may become clogged which reduces compressor service life and can
cause premature unit failure.
In boiler/tower application, set the loop control panel set points to desired
temperatures. Supply power to all motors and start the circulating pumps.
After full flow has
been established through all components including the heat rejector
(regardless of season), air vented and loop temperatures stabilized, each of
the units will be ready for check, test and start up and for air and water
balancing.
Ground Source Loop System Checkout
Once piping is completed between the unit pumping system and ground loop,
final purging and charging of the loop is needed. A high pressure pump is
needed to achieve adequate flow velocity in the loop to purge air and dirt
particles from the loop itself. Antifreeze solution is used in most areas to
prevent freezing. Flush the system adequately to remove as much air as
possible; then pressurize the loop to a static pressure of 40-50 PSI (summer)
or 50-75 PSI (winter). This is normally adequate for good system operation.
Loop static pressure may decrease soon after initial installation, due to pipe
expansion and loop temperature change. Running the unit for at least 30
minutes after the system has been completely purged of air will allow for the
“break-in” period. It may be necessary to adjust static loop pressure (by
adding water) after the unit has run for the first time. Loop static pressure
will also fluctuate with the seasons. Pressures will be higher in the winter
months than during the cooling season. This fluctuation is normal and should
be considered when charging the system initially.
Ensure the pump provides adequate flow through the unit by checking pressure
drop across the heat exchanger. Usually 2.25-3.0 gpm of flow per ton of
cooling capacity is recommended in earth loop applications.
Open Loop Ground Water Systems
Typical open loop piping is shown below. Always maintain water pressure in the
heat exchanger by placing water control valves at the outlet of the unit to
prevent mineral precipitation. Use a closed, bladder-type expansion tank to
minimize mineral formation due to air exposure. Insure proper water flow
through the unit by checking pressure drop across the heat exchanger and
comparing it to the figures in unit capacity data tables in the specification
catalog. 1.5-2 gpm of flow per ton of cooling capacity is recommended in open
loop applications. Due to only minor differences in flow rate from low to
high, only one solenoid valve should be used. The valve should be sized for
full flow.
Discharge water from the unit is not contaminated in any manner and can be
disposed of in various ways, depending on local codes, i.e. recharge well,
storm sewer, drain field, adjacent stream or pond, etc. Most local codes
forbid the use of sanitary sewer for disposal. Consult your local building and
zoning departments to assure compliance in your area.
Open System – Groundwater Application
Unit Supply Aux. Heat Supply
Flexible Duct Collar
Rubber Bladder Expansion Tank
Hot Water Generator Connections
Drain
Solenoid Valve
Flow Control Valve
(on outlet of Solenoid Valve)
Water Out Water In
Disconnects (If Applicable)
Shut Off Valves
Shut Off Valves (to isolate solenoid valve while acid flushing)
Compressor Line Voltage
Low Voltage to Thermostat
and Valve
P/T Plugs
Vibration Absorbing Pad
Strainer
Boiler Drains For HX Flushing
14
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Hot Water Generator Connections
The heat reclaiming hot water generator coil is of vented double-wall copper
construction and is suitable for potable water.
To maximize the benefits of the hot water generator a minimum 50-gallon water
heater is recommended. For higher demand applications, use an 80-gallon water
heater or two 50-gallon water heaters connected in a series as shown below.
Electric water heaters are recommended. Make sure all local electrical and
plumbing codes are met for installing a hot water generator. A water softener
is recommended with hard water (greater than 10 grains or 170 total hardness).
Typical Hot Water Generator Installation
3/4 in. x 3/4 in. x 1/2 in. Tee Ball Valve
Cold Water In
Hot Water Out
Vent
HWG Water Out
P/T Relief Valve
In
Field Installed
HWG HWG Pump
Water In
Drain Valve
Water Tank Preparation
To install a unit with a hot water generator, follow these installation
guidelines.
1. Turn off the power to the water heater. 2. Attach a water hose to the
water tank drain connection and
run the other end of the hose to an open drain or outdoors. 3. Close the cold
water inlet valve to the water heater tank. 4. Drain the tank by opening the
valve on the bottom of the
tank, then open the pressure relief valve or hot water faucet. 5. Flush the
tank by opening the cold water inlet valve to
the water heater to free the tank of sediments. Close when draining water is
clear. 6. Disconnect the garden hose and remove the drain valve from the water
heater. 7. Refer to Plumbing Installation and Hot Water Generator Startup.
Hot Water Generator Installation In Preheat Tank
3/4 in. x 3/4 in. x 1/2 in. Tee Ball Valve Vent
Cold Water In
Hot Water Out
HWG Water Out
P/T Relief Valve
P/T Relief Valve
In
Field Installed HWG HWG Pump Water In
Drain Valve
NOTE: This configuration maximizes hot water generator capability.
CAUTION: Elements will burn out if energized dry.
Plumbing Installation
1. Inspect the dip tube in the water heater cold inlet for a check valve. If
a check valve is present it must be removed or damage to the hot water
generator circulator will occur.
2. Remove drain valve and fitting. 3. Thread the 3/4-inch NPT x 3-1/2-inch
brass nipple into
the water heater drain port. 4. Attach the center port of the 3/4-inch FPT tee
to the
opposite end of the brass nipple. 5. Attach the 1/2-inch copper to 3/4-inch
NPT adaptor to
the side of the tee closest to the unit. 6. Install the drain valve on the tee
opposite the adaptor. 7. Run interconnecting tubing from the tee to HWG
water out.
8. Cut the cold water “IN” line going to the water heater. 9. Insert the
reducing solder tee in line with cold water
“IN” line as shown. 10. Run interconnecting copper tubing between the unit
DHW water “IN” and the tee (1/2-inch nominal). The recommended maximum
distance is 50 feet. 11. To prevent air entrapment in the system, install a
vent coupling at the highest point of the interconnecting lines. 12. Insulate
all exposed surfaces of both connecting water lines with 3/8-inch wall closed
cell insulation.
NOTE: All plumbing and piping connections must comply with local plumbing
codes.
15
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Hot Water Generator Connections cont.
Hot Water Generator Startup
1. Make sure the power is off to the heat pump. Connect the wire from the hot
water generator pump to T1 on the contactor.
2. Close the drain valve to the water heater. 3. Open the cold water supply
to the tank. 4. Open a hot water faucet in the building to bleed air
from the system. Close when full. 5. Open the pressure relief valve to bleed
any remaining
air from the tank, then close. 6. If so equipped, turn the venting (burping)
screw in the
center of the pump two (2) turns open (water will drip out), wait until all
air is purged from the pump, then tighten the plug. Use vent couplings to
bleed air from the lines. 7. Carefully inspect all plumbing for water leaks
and correct as required. 8. Before restoring electrical supply to the water
heater, adjust the temperature setting on the tank.
· On tanks with both upper and lower elements, the lower element should be
turned down to the lowest setting, approximately 100°F. The upper element
should be adjusted to 120°F to 130°F. Depending upon the specific needs of the
customer, you may want to adjust the upper element differently.
· On tanks with a single element, lower the thermostat setting to 120°F.
9. After the thermostat(s) is adjusted, replace the access cover and restore
electrical supply to the water heater.
10. Make sure that any valves in the hot water generator circuit are open.
11. Turn on the unit to heating. 12. The HWG pump should be running. When the
pump
is first started, turn the venting (burping) screw (if equipped) in the center
of the pump two (2) turns open until water dribbles out, then replace. Allow
the pump to run for at least five minutes to ensure that water has filled the
circulator properly. 13. The temperature difference between the water entering
and leaving the hot water generator should be 5°F to 15°F. The water flow
should be approximately 0.4 gpm per ton of nominal cooling. 14. Allow the unit
to heat water for 15 to 20 minutes to be sure operation is normal.
CAUTION: Never operate the HWG circulating pump while dry. If the unit is
placed in operation before the hot water generator piping is connected, be
sure that the pump wires are disconnected from the contactor.
16
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Freeze Detection
For Aurora Base Control, set SW2-1, FP1, on the printed circuit board for
applications using a closed loop antifreeze solution to 15°F [-9.4°C]. On
applications using an open loop/ground water system (or closed loop no
antifreeze), set this dip switch to 30°F [-1.1°C], the factory default
setting. (Refer to the Dip Switch Field Selection table).
Electrical Connections
General
Be sure the available power is the same voltage and phase as that shown on the
unit serial plate. Line and low voltage wiring must be done in accordance with
local codes or the National Electric Code, whichever is applicable.
Power Connection
Connect the incoming line voltage wires to L1 and L2 of the contactor for
single-phase unit. Consult the Electrical Data tables for correct fuse sizes.
Aurora Base Control Box
208 Volt Operation
All 208/230 units are factory wired for 230 volt operation. For 208 volt
operation, the red and blue transformer wires must be switched on terminal
strip PS.
CAUTION: When installing a unit with a variable speed ECM blower motor in
460/60/3 voltage, a neutral wire is required to allow proper unit operation.
17
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Electrical Data
PSC Motor
Model
Rated Voltage
Voltage Min/Max
Single Speed
009 012 015 018 024 024 030 030 036 036 042 042 048 048* 060 070
208-230/60/1 265/60/1
208-230/60/1 265/60/1
208-230/60/1 265/60/1
208-230/60/1 265/60/1
208-230/60/1 265/60/1
208-230/60/3 460/60/3
208-230/60/1 265/60/1
208-230/60/3 460/60/3
208-230/60/1 265/60/1
208-230/60/3 460/60/3
208-230/60/1 265/60/1
208-230/60/3 460/60/3
208-230/60/1 265/60/1
208-230/60/3 460/60/3
208-230/60/1 265/60/1
208-230/60/3 460/60/3
208-230/60/1 208-230/60/3
460/60/3 575/60/3 208-230/60/1 208-230/60/3 460/60/3 575/60/3 208-230/60/1
208-230/60/3 460/60/3 575/60/3 208-230/60/1 208-230/60/3 460/60/3 575/60/3
208-230/60/1 208-230/60/3 460/60/3 575/60/3 208-230/60/1 208-230/60/3 460/60/3
575/60/3
187/253 238/292 187/253 238/292 187/253 238/292 187/253 238/292 187/253 238/292 187/253 414/506 187/253 238/292 187/253 414/506 187/253 238/292 187/253 414/506 187/253 238/292 187/253 414/506 187/253 238/292 187/253 414/506 187/253 238/292 187/253 414/506 187/253 187/253 414/506 517/633 187/253 187/253 414/506 517/633 187/253 187/253 414/506 517/633 187/253 187/253 414/506 517/633 187/253 187/253 414/506 517/633 187/253 187/253 414/506 517/633
HACR circuit breaker in USA only *With optional High-static PSC motor **With optional IntelliStart
MCC
6.4 6.7 7.7 7.0 9.7 7.8 13.1 8.7 21.0 14.0 11.0 5.5 21.0 14.0 11.0 5.5 20.0
15.0 12.0 5.6 20.0 15.0 12.0 5.6 22.0 17.5 13.9 6.5 22.0 17.5 13.9 6.5 26.0
16.3 9.0 5.9 26.0 16.3 9.0 5.9 31.0 21.2 9.5 6.5 31.0 21.2 9.5 6.5 41.2 24.9
12.1 8.9 44.2 30.0 13.6 10.7
Compressor
RLA
LRA
4.1 4.3 4.9 4.5 6.2 5.0 8.4 5.6 13.5 9.0 7.1 3.5 13.5 9.0 7.1 3.5 12.8 9.6 7.7 3.6 12.8 9.6 7.7 3.6 14.1 11.2 8.9 4.2 14.1 11.2 8.9 4.2 16.7 10.4 5.8 3.8 16.7 10.4 5.8 3.8 19.9 13.6 6.1 4.2 19.9 13.6 6.1 4.2 26.4 16.0 7.8 5.7 28.3 19.2 8.7 6.9
21.0 22.0 25.0 22.0 29.0 28.0 33.5 28.0 58.3 54.0 55.4 28.0 58.3 54.0 55.4 28.0 58.0 54.0 55.4 28.0 58.0 54.0 55.4 28.0 73.0 60.0 58.0 28.0 73.0 60.0 58.0 28.0 79.0 73.0 38.0 36.5 79.0 73.0 38.0 36.5 109.0 83.1 41.0 33.0 109.0 83.1 41.0 33.0 134.0 110.0 52.0 38.9 178.0 136.0 66.1 55.3
LRA**
n/a n/a n/a n/a n/a n/a 13.4 n/a 23.3 n/a 33.2 16.8 23.3 n/a 33.2 16.8 23.2
n/a 33.2 16.8 23.2 n/a 33.2 16.8 29.2 n/a 34.8 16.8 29.2 n/a 34.8 16.8 31.6
43.8 22.8 n/a 31.6 43.8 22.8 n/a 43.6 49.9 24.6 n/a 43.6 49.9 24.6 n/a 53.6
66.0 31.2 n/a 71.2 81.6 39.7 n/a
Blower Motor FLA
0.6 0.6 0.6 0.6 1.1 1.0 1.1 1.0 1.2 1.1 1.2 0.6 1.5 1.5 1.5 1.0 1.5 1.5 1.5
1.0 2.8 2.0 2.2 1.1 2.8 2.0 2.8 1.4 3.5 3.5 1.8 1.8 3.5 3.5 1.8 1.4 4.6 4.6
2.3 1.9 3.5 3.5 1.8 1.4 4.6 4.6 2.3 1.9 5.9 5.9 3.0 1.9 5.9 5.9 3.0 1.9
Total Unit FLA
4.7 4.9 5.5 5.1 7.3 6.0 9.5 6.6 14.7 10.1 8.3 4.1 15.0 10.5 8.6 4.5 14.3 11.1
9.2 4.6 15.6 11.6 9.9 4.7 16.9 13.2 11.7 5.6 17.6 14.7 10.7 5.6 20.2 13.9 7.6
5.2 21.3 15.0 8.1 5.7 23.4 17.1 7.9 5.6 24.5 18.2 8.4 6.1 32.3 21.9 10.8 7.6
34.2 25.1 11.7 8.8
18
Min Circ Amp
5.7 6.0 6.7 6.2 8.9 7.3 11.6 8.0 18.1 12.4 10.1 5.0 18.4 12.8 10.4 5.4 17.5
13.5 11.1 5.5 18.8 14.0 11.8 5.6 20.4 16.0 13.9 6.7 21.1 17.5 12.9 6.7 24.4
16.5 9.0 6.1 25.5 17.6 9.5 6.6 28.4 20.5 9.4 6.7 29.5 21.6 9.9 7.2 38.9 25.9
12.8 9.0 41.3 29.9 13.9 10.5
Max Fuse/ HACR Breaker
10/15 10/15 10/15 10/15
15 10/15
20 10/15
25 20 15 10/15 30 20 15 10/15 30 20 15 10/15 30 20 15 10/15 30 25 20 10/15 35
25 20 10/15 40 25 10/15 10/15 40 25 15 10/15 45 30 15 10/15 45 35 15 10/15 60
40 20 10/15 70 45 20 15 8/06/13
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Electrical Data cont.
5-Speed ECM Motor
Model
Rated Voltage
Voltage Min/Max
Single Speed
015 018 024
030
036 042 048 060 070 026
038 049 064 072
208-230/60/1 265/60/1
208-230/60/1 265/60/1
208-230/60/1 265/60/1
208-230/60/3 460/60/3
208-230/60/1 265/60/1
208-230/60/3 460/60/3
208-230/60/1 265/60/1
208-230/60/3 460/60/3
208-230/60/1 208-230/60/3
460/60/3 208-230/60/1 208-230/60/3
460/60/3 208-230/60/1 208-230/60/3
460/60/3 208-230/60/1 208-230/60/3
460/60/3 208-230/60/1
265/60/1 208-230/60/3
460/60/3 208-230/60/1
265/60/1 208-230/60/3
460/60/3 208-230/60/1 208-230/60/3
460/60/3 208-230/60/1 208-230/60/3
460/60/3 208-230/60/1 208-230/60/3
460/60/3
187/253 238/292 187/253 238/292 187/253 238/292 187/253 414/506 187/253 238/292 187/253 414/506 187/253 238/292 187/253 414/506 187/253 187/253 414/506 187/253 187/253 414/506 187/253 187/253 414/506 187/253 187/253 414/506 187/253 238/292 187/253 414/506 187/253 238/292 187/253 414/506 187/253 187/253 414/506 187/253 187/253 414/506 187/253 187/253 414/506
Dual Capacity
HACR circuit breaker in USA only **With optional IntelliStart
MCC
9.7 7.8 13.1 8.7 21.0 14.0 11.0 5.5 20.0 15.0 12.0 5.6 22.0 17.5 13.9 6.5 26.0
16.3 9.0 31.0 21.2 9.5 41.2 24.9 12.1 44.2 30.0 13.6 18.2 14.2 10.1 5.4 23.8
20.3 18.1 8.9 33.0 21.9 10.0 42.3 25.8 11.3 46.3 27.4 13.2
Compressor
RLA
LRA
6.2 5.0 8.4 5.6 13.5 9.0 7.1 3.5 12.8 9.6 7.7 3.6 14.1 11.2 8.9 4.2 16.7 10.4 5.8 19.9 13.6 6.1 26.4 16.0 7.8 28.3 19.2 8.7 11.7 9.1 6.5 3.5 15.3 13.0 11.6 5.7 21.1 14.0 6.4 27.1 16.5 7.2 29.7 17.6 8.5
29.0 28.0 33.5 28.0 58.3 54.0 55.4 28.0 58.0 54.0 55.4 28.0 73.0 60.0 58.0 28.0 79.0 73.0 38.0 109.0 83.1 41.0 134.0 110.0 52.0 178.0 136.0 66.1 58.3 54.0 55.4 28.0 83.0 72.0 73.0 38.0 104.0 83.1 41.0 152.9 110.0 52.0 179.2 136.0 66.1
LRA**
n/a n/a 13.4 n/a 23.3 n/a 33.2 16.8 23.2 n/a 33.2 16.8 29.2 n/a 34.8 16.8 31.6
43.8 22.8 43.6 49.9 24.6 53.6 66.0 31.2 71.2 81.6 39.7 23.3 n/a 33.2 16.8 33.2
n/a 43.8 22.8 41.6 49.9 24.6 61.2 66.0 31.2 71.7 81.6 39.7
Blower Motor FLA
4.1 3.6 4.1 3.6 4.1 3.6 4.1 2.1 4.1 3.6 4.1 2.1 4.1 3.6 4.1 2.1 7.6 7.6 4.0
7.6 7.6 4.0 7.6 7.6 4.0 7.6 7.6 4.0 4.1 3.6 4.1 2.1 4.1 3.6 4.1 2.1 7.6 7.6
4.0 7.6 7.6 4.0 7.6 7.6 4.0
Total Unit FLA
10.3 8.6 12.5 9.2 17.6 12.6 11.2 5.6 16.9 13.2 11.8 5.7 18.2 14.8 13.0 6.3
24.3 18.0 9.8 27.5 21.2 10.1 34.0 23.6 11.8 35.9 26.8 12.7 15.8 12.7 10.6 5.6
19.4 16.6 15.7 7.8 28.7 21.6 10.4 34.7 24.1 11.2 37.3 25.2 12.5
Min Circ Amp
11.9 9.9 14.6 10.6 21.0 14.9 13.0 6.5 20.1 15.6 13.7 6.6 21.7 17.6 15.2 7.4
28.5 20.6 11.2 32.5 24.6 11.6 40.6 27.6 13.8 43.0 31.6 14.9 18.7 15.0 12.2 6.4
23.2 19.9 18.6 9.2 34.0 25.1 12.0 41.5 28.2 13.0 44.7 29.6 14.6
Max Fuse/ HACR Breaker
15 10/15
20 15 30 20 20 10/15 30 25 20 10/15 35 25 20 10/15 45 30 15 50 35 15 60 40 20
70 50 20 30 20 15 10/15 35 30 30 10/15 50 35 15 60 40 20 70 45 20
5/21/13
19
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Electrical Data cont.
Variable Speed ECM Motor
Model
Rated Voltage
009
208-230/60/1 265/60/1
012
208-230/60/1 265/60/1
015
208-230/60/1 265/60/1
018
208-230/60/1 265/60/1
208-230/60/1
024
265/60/1 208-230/60/3
460/60/3
208-230/60/1
030
265/60/1 208-230/60/3
460/60/3
208-230/60/1
036
265/60/1 208-230/60/3
Single Speed
460/60/3
208-230/60/1
036*
265/60/1 208-230/60/3
460/60/3
208-230/60/1
042
208-230/60/3
460/60/3
208-230/60/1
042*
208-230/60/3
460/60/3
208-230/60/1
048
208-230/60/3
460/60/3
208-230/60/1
048*
208-230/60/3
460/60/3
208-230/60/1
060
208-230/60/3
460/60/3
208-230/60/1
070
208-230/60/3
460/60/3
208-230/60/1
026
265/60/1 208-230/60/3
460/60/3
208-230/60/1
038
265/60/1 208-230/60/3
460/60/3
208-230/60/1
Dual Capacity
038*
265/60/1 208-230/60/3
460/60/3
208-230/60/1
049
208-230/60/3
460/60/3
208-230/60/1
049*
208-230/60/3
460/60/3
208-230/60/1
064
208-230/60/3
460/60/3
208-230/60/1
072
208-230/60/3
460/60/3
HACR circuit breaker in USA only *With optional 1 HP ECM motor **With optional IntelliStart
Voltage Min/Max
187/253 238/292 187/253 238/292 187/253 238/292 187/253 238/292 187/253
238/292 187/253 414/506 187/253 238/292 187/253 414/506 187/253 238/292
187/253 414/506 187/253 238/292 187/253 414/506 187/253 187/253 414/506
187/253 187/253 414/506 187/253 187/253 414/506 187/253 187/253 414/506
187/253 187/253 414/506 187/253 187/253 414/506 187/253 238/292 187/253
414/506 187/253 238/292 187/253 414/506 187/253 238/292 187/253 414/506
187/253 187/253 414/506 187/253 187/253 414/506 187/253 187/253 414/506
187/253 187/253 414/506
MCC
6.4 6.7 7.7 7.0 9.7 7.8 13.1 8.7 21.0 14.0 11.0 5.5 20.0 15.0 12.0 5.6 22.0
17.5 13.9 6.5 22.0 17.5 13.9 6.5 26.0 16.3 9.0 26.0 16.3 9.0 31.0 21.2 9.5
31.0 21.2 9.5 41.2 24.9 12.1 44.2 30.0 13.6 18.2 14.2 10.1 5.4 23.8 20.3 18.1
8.9 23.8 20.3 18.1 8.9 33.0 21.9 10.0 33.0 21.9 10.0 42.3 25.8 11.3 46.3 27.4
13.2
Compressor
RLA
LRA
4.1 4.3 4.9 4.5 6.2 5.0 8.4 5.6 13.5 9.0 7.1 3.5 12.8 9.6 7.7 3.6 14.1 11.2 8.9 4.2 14.1 11.2 8.9 4.2 16.7 10.4 5.8 16.6 10.4 5.8 19.9 13.6 6.1 19.9 13.6 6.1 26.4 16.0 7.8 28.3 19.2 8.7 11.7 9.1 6.5 3.5 15.3 13.0 11.6 5.7 15.3 13.0 11.6 5.7 21.1 14.0 6.4 21.1 14.0 6.4 27.1 16.5 7.2 29.7 17.6 8.5
21.0 22.0 25.0 22.0 29.0 28.0 33.5 28.0 58.3 54.0 55.4 28.0 58.0 54.0 55.4 28.0 73.0 60.0 58.0 28.0 73.0 60.0 58.0 28.0 79.0 73.0 38.0 79.0 73.0 38.0 109.0 83.1 41.0 109.0 83.1 41.0 134.0 110.0 52.0 178.0 136.0 66.1 58.3 54.0 55.4 28.0 83.0 72.0 73.0 38.0 83.0 72.0 73.0 38.0 104.0 83.1 41.0 104.0 83.1 41.0 152.9 110.0 52.0 179.2 136.0 66.1
LRA**
n/a n/a n/a n/a n/a n/a 13.4 n/a 23.3 n/a 33.2 16.8 23.2 n/a 33.2 16.8 29.2
n/a 34.8 16.8 29.2 n/a 34.8 16.8 31.6 43.8 22.8 31.6 43.8 22.8 43.6 49.9 24.6
43.6 49.9 24.6 53.6 66.0 31.2 71.2 81.6 39.7 23.3 n/a 33.2 16.8 33.2 n/a 43.8
22.8 33.2 n/a 43.8 22.8 41.6 49.9 24.6 41.6 49.9 24.6 61.2 66.0 31.2 71.7 81.6
39.7
Blower Motor FLA
0.94 0.94 0.94 0.94 4.0
4.1 4.0 4.1 4.0 4.1 4.0 4.1 4.0 4.1 4.0 4.1 4.0 4.1 4.0 4.1 7.0 6.9 7.0 6.9
4.0 4.0 4.1 7.0 7.0 6.9 4.0 4.0 4.1 7.0 7.0 6.9 7.0 7.0 6.9 7.0 7.0 6.9 4.0
4.1 4.0 4.1 4.0 4.1 4.0 4.1 7.0 7.0 7.0 6.9 4.0 4.0 4.1 7.0 7.0 6.9 7.0 7.0
6.9 7.0 7.0 6.9
Total Unit FLA
5.04 5.24 5.84 5.42 10.2 9.1 12.4 9.7 17.5 13.1 11.1 7.6 16.8 13.7 11.7 7.7
18.1 15.3 12.9 8.3 21.1 18.1 15.9 11.1 20.7 14.4 9.9 23.6 17.4 12.7 23.9 17.6
10.2 26.9 20.6 13.0 33.4 23.0 14.7 35.3 26.2 15.6 15.7 13.2 10.5 7.6 19.3 17.1
15.6 9.8 22.3 20.0 18.6 12.6 25.1 18.0 10.5 28.1 21.0 13.3 34.1 23.5 14.1 36.7
24.6 15.4
Min Circ Amp
6.1 6.3 7.1 6.5 11.8 10.4 14.5 11.1 20.9 15.4 12.9 8.5 20.0 16.1 13.6 8.6 21.6
18.1 15.1 9.4 24.6 20.9 18.1 12.2 24.9 17.0 11.3 27.8 20.0 14.1 28.9 21.0 11.7
31.9 24.0 14.5 40.0 27.0 16.7 42.4 31.0 17.8 18.6 15.5 12.1 8.4 23.1 20.4 18.5
11.2 26.1 23.3 21.5 14.0 30.4 21.5 12.1 33.4 24.5 14.9 40.9 27.6 15.9 44.1
29.0 17.5
Max Fuse/ HACR Breaker
10/15 10/15 10/15 10/15
15 15 20 15 30 20 20 10/15 30 25 20 10/15 35 25 20 10/15 35 30 25 15 40 25 15
40 30 15 45 30 15 50 35 20 60 40 20 70 50 25 30 20 15 10/15 35 30 30 15 40 35
30 15 50 35 15 50 35 20 60 40 20 70 45 25
5/18/2018
CAUTION: When installing a unit with a variable speed ECM blower motor in
460/60/3 voltage, a neutral wire is required to allow proper unit operation.
20
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Blower Performance Data
Standard PSC Motor
Model
Blower Blower Spd Size
Motor HP
H
009
MH ML*
6 x 8
1/10
L
H
012
MH* ML
6 x 8
1/10
L
H
015 M 9 x 7 1/6
L
H
018 M 9 x 7 1/6
L
H
024 M 9 x 7 1/5
L
H
030 M 9 x 7 1/3
L
H
036 M 10 x 10 1/2
L
H
042 M 10 x 10 1/2
L
H
048 M 10 x 10 1/2
L
H
060 M 11 x 10 1
L
H
070 M 11 x 10 1
L
0 480 440 395 325 480 440 395 325 845 735 620 845 735 620 1085 915 845 1290 1100 910 1665 1465 1130 2010 1670 1220 2010 1670 1220 2430 2265 2075 2430 2265 2075
0.05 450 410 370 310 450 410 370 310 835 730 615 835 730 615 1055 895 830 1270 1090 905 1640 1445 1115 1975 1650 1215 1975 1650 1215 2400 2235 2050 2400 2235 2050
0.10 440 400 360 300 440 400 360 300 825 725 610 825 725 610 1030 875 815 1245 1075 900 1610 1425 1100 1940 1630 1210 1940 1630 1210 2365 2205 2020 2365 2205 2020
0.15 420 380 340 280 420 380 340 280 815 715 605 815 715 605 1005 855 795 1220 1060 895 1580 1400 1090 1905 1610 1295 1905 1610 1295 2330 2175 1995 2330 2175 1995
Airflow (cfm) at External Static Pressure (in. wg)
0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60
410 380 360 340 330 310 300 –
370 350 330 310 300 280 270
–
330 310 290 280 270 250 240 –
270 250 240 230 220 210 200 –
410 380 360 340 330 310 300 –
370 350 330 310 300 280 270
–
330 310 290 280 270 250 240 –
270 250 240 230 220 210 200 –
800 790 775 755 735 710 680 565
705 700 690 675 660 630 600 485
600 590 580 565 550 520 490 –
800 790 775 755 735 710 680 565
705 700 690 675 660 630 600 485
600 590 580 565 550 520 490 –
980 950 925 895 870 830 795 735
835 815 795 765 735 705 675 590
775 750 725 702.5 680 650 625 505
1190 1160 1125 1090 1055 1020 985 880
1045 1020 995 970 940 910 875 785
885 875 865 850 835 810 780 710
1550 1515 1480 1450 1415 1315 1215 1090
1375 1350 1325 1260 1190 1140 1090 990
1075 1035 995 965 930 895 860 795
1870 1825 1780 1735 1690 1640 1590 1470
1590 1560 1530 1495 1460 1425 1390 1190
1200 1180 1160 1130 1100 1060 1020 930
1870 1825 1780 1735 1690 1640 1590 1470
1590 1560 1530 1495 1460 1425 1390 1190
1200 1180 1160 1130 1100 1060 1020 930
2290 2255 2215 2180 2140 2095 2045 1945
2145 2110 2070 2035 2000 1960 1915 1825
1965 1940 1915 1885 1850 1820 1785 1720
2290 2255 2215 2180 2140 2095 2045 1945
2145 2110 2070 2035 2000 1960 1915 1825
1965 1940 1915 1885 1850 1820 1785 1720
0.70 –
555 520
760 625 560 980 890 730 1210 1080
1210 1080
1835 1730 1610 1835 1730 1610
0.80 –
1715 1605 1505 1715 1605 1505
Optional High Static PSC Motor
Model
Blower Blower Spd Size
Motor HP
0
Airflow (cfm) at External Static Pressure (in. wg) 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80
H
1290 1270 1245 1220 1190 1160 1125 1090 1055 1020 985 880 760 –
024 M 9 x 7 1/3 1100 1090 1075 1060 1045 1020 995 970 940 910 875 785 625
–
L
910 905 900 895 885 875 865 850 835 810 780 710 560 –
H
1365 1340 1325 1305 1280 1250 1215 1180 1140 1100 1055 960 850 –
030 M 9 x 7 1/2 1040 1040 1035 1030 1020 1005 990 970 945 915 885 810 735
–
L
880 880 880 880 875 870 860 840 820 800 775 730 480 –
H
1930 1905 1875 1840 1805 1765 1725 1680 1635 1530 1425 1270 1150 1025
036 M 10 x 10 1/2 1635 1620 1600 1580 1555 1530 1505 1465 1425 1335 1240 1135 1035 775
L
1230 1230 1225 1215 1200 1165 1130 1095 1060 1035 1005 935 795 675
H
2115 2075 2035 1980 1920 1900 1880 1840 1795 1730 1660 1390 1225 1070
042 M 10 x 10 3/4 2005 1980 1950 1910 1865 1815 1765 1725 1685 1585 1485 1315 1140 1025
L
1860 1835 1805 1780 1750 1715 1675 1635 1590 1540 1490 1260 1115 980
H
2115 2075 2035 1980 1920 1900 1880 1840 1795 1730 1660 1390 1225 1070
048 M 10 x 10 3/4 2005 1980 1950 1910 1865 1815 1765 1725 1685 1585 1485 1315 1140 1025
L
1860 1835 1805 1780 1750 1715 1675 1635 1590 1540 1490 1260 1115 980
Factory settings are in Bold
Air flow values are with dry coil and 1 in. MERV 4.
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500
fpm by 0.16 in. wg.
- Denotes setting for 265 V operation.
0.90 1.00
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
1510 1330
1440 1260
1335 1175
1510 1330
1440 1260
1335 1175
3/16/12
0.90 1.00
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
3/16/12
Setting Blower Speed – PSC
RE
HIGH MEDIUM LOW
CAUTION: Disconnect all power before performing this operation.
PSC BLOWER MOTOR BODY
BLOWER SPEED WI
21
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Blower Performance Data cont.
5-Speed ECM – Single Speed
Model
Motor Spd
Motor Tap
High
5
Med High 4
015
Med
3
Med Low 2
Low
1
High
5
Med High 4
018
Med
3
Med Low 2
Low
1
High
5
Med High 4
024 Med
3
Med Low 2
Low
1
High
5
Med High 4
030 Med
3
Med Low 2
Low
1
High
5
Med High 4
036 Med
3
Med Low 2
Low
1
High
5
Med High 4
042 Med
3
Med Low 2
Low
1
High
5
Med High 4
048 Med
3
Med Low 2
Low
1
High
5
Med High 4
060 Med
3
Med Low 2
Low
1
High
5
Med High 4
070 Med
3
Med Low 2
Low
1
T’Stat Blower Motor Cnct. Size HP
W 9 x 7 1/2
Y1 G
W 9 x 7 1/2
Y1 G W Y1
9 x 7 1/2 G
W Y1 9 x 7 1/2
G W Y1
11 x 10 1/2
G
W 11 x 10 1
Y1 G
W Y1 11 x 10 1
G W Y1
11 x 10 1
G W Y1
11 x 10 1
G
0 916 809 727 699 656 916 809 727 699 656 1015 935 865 810 695 1407 1146 1023 978 795 1530 1413 1355 1336 1243 1934 1799 1694 1575 1454 1934 1799 1694 1575 1454 2230 2081 1951 1812 1668 2472 2271 2133 2008 1806
Factory settings are in Bold Air flow values are with dry coil and standard 1 in. filter
0.05 898 787 715 675 604 898 787 715 675 604 1003 915 855 790 645 1381 1134 1012 962 777 1503 1388 1325 1299 1182 1910 1783 1680 1560 1406 1910 1783 1680 1560 1406 2212 2065 1931 1790 1651 2454 2248 2115 1985 1784
0.10 881 765 703 652 552 881 765 703 652 552 990 895 845 770 595 1354 1122 1001 946 759 1476 1363 1294 1261 1121 1886 1767 1666 1540 1358 1886 1767 1666 1540 1358 2193 2048 1910 1767 1633 2435 2225 2096 1962 1761
0.15 866 754 682 631 530 866 754 682 631 530 975 880 825 755 575 1327 1111 985 934 748 1453 1342 1276 1242 1061 1871 1744 1642 1520 1333 1871 1744 1642 1520 1333 2173 2032 1889 1748 1612 2414 2205 2072 1939 1742
Airflow (cfm) at External Static Pressure (in. wg)
0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60
851 679 813 804 795 774 754 731
743 725 707 688 669 654 639 606
661 638 616 601 587 561 536 485
611 594 577 551 525 490 455
–
508 493 479 436 394 350
–
–
851 679 813 804 795 774 754 731
743 725 707 688 669 654 639 606
661 638 616 601 587 561 536 485
611 594 577 551 525 490 455
–
508 493 479 436 394 350
–
–
955 945 935 920 905 890 880 850
875 855 840 825 815 800 785 755
810 795 780 765 750 735 720 675
740 725 710 695 680 660 640 560
550 520 495 455 420 400
–
–
1300 1267 1233 1201 1168 1131 1094 1009
1099 1085 1071 1062 1052 1042 1031 966
969 959 949 937 925 913 901
–
922 907 891 882 872 858 843
–
737 718 698 686 673 650 626
–
1429 1413 1397 1376 1355 1342 1329 1276
1321 1303 1285 1263 1240 1226 1212 1173
1258 1235 1212 1188 1164 1144 1123 982
1222 1202 1181 1157 1132 1111 1090 937
1000 964 928 856 784 744 703 647
1855 1827 1799 1780 1760 1747 1734 1700
1720 1693 1666 1649 1631 1617 1603 1560
1617 1592 1567 1552 1537 1519 1500 1453
1502 1487 1471 1448 1424 1409 1393 1351
1308 1285 1261 1239 1217 1198 1179 1072
1855 1827 1799 1780 1760 1747 1734 1700
1720 1693 1666 1649 1631 1617 1603 1560
1617 1592 1567 1552 1537 1519 1500 1453
1502 1487 1471 1448 1424 1409 1393 1351
1308 1285 1261 1239 1217 1198 1179 1072
2152 2139 2125 2109 2092 2076 2059 2026
2015 1998 1980 1963 1946 1928 1910 1880
1868 1850 1831 1812 1793 1774 1755 1722
1728 1708 1688 1671 1654 1640 1626 1584
1591 1566 1540 1525 1510 1491 1472 1433
2393 2371 2349 2328 2306 2289 2271 2236
2184 2166 2147 2129 2110 2094 2078 2039
2047 2030 2013 1996 1979 1965 1950 1909
1915 1898 1880 1862 1843 1828 1812 1774
1722 1696 1669 1656 1642 1625 1607 1564
0.70 695 536
695 536 825 720 610 530 1231 1016 909 874 592 1659 1530 1421 1308 1002 1659
1530 1421 1308 1002 1992 1849 1688 1547 1400 2189 2011 1873 1742 1527
0.80 643
643 745 580 570 1173 946 883 830 1617 1492 1372 1266 988 1617 1492 1372 1266
988 1951 1806 1654 1510 1351 2121 1977 1837 1703 1490
0.90 –
1892 1767 1612 1472 1299 2033 1930 1793 1669 1443
1.00 –
1806 1728 1562 1417 1208 1936 1846 1748 1635 1404
11/20/12
About 5-Speed ECM Constant Torque Motors
The 5-speed ECM is a Constant Torque’ ECM motor and delivers air flow similar to a PSC but operates as efficiently as a variable speed ECM motor. Because it is an ECM motor, the 5-speed ECM can ramp slowly up or down like the variable speed ECM motor. There are 5 possible speed taps available on the 5-speed ECM motor with #1 being the lowest airflow and #5 being the highest airflow. These speed selections are preset at the time of manufacture and are easily changed in the field if necessary. If more than one tap are energized at the same time, built in logic gives precedence to the highest tap number and allows air flow to change with G, Y1, Y2 and W signals. Each of those 5 speeds has a specific
Torque’ value
programmed into the motor for each speed selection. As static pressure
increases,
airflow decreases resulting in less torque on the rotor. The motor responds
only to changes in torque and adjusts its speed accordingly.
The 5-speed ECM motor is powered by line voltage but the motor speed is
energized by 24VAC.
5-Speed ECM Benefits: – High efficiency – Soft start – 5 speeds with up to 4
speeds on-line – Built in logic allows air flow to change with G, Y1, Y2 and W
signals – Super efficient low airflow continuous blower setting (G)
22
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Blower Performance Data cont.
5-Speed ECM – Dual Capacity
Model
Motor Speed
Motor T’stat Blower Motor Tap Cnct. Size HP
0
Airflow (cfm) at External Static Pressure (in. wg) 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80
High
5
W
1120 1109 1097 1082 1066 1055 1044 1028 1011 1001 991 932 839
–
Med High 4
Y2
1020 1006 991 980 968 950 932 922 911 894 876 849 812
–
026 Med
3
9 x 7 1/2 917 906 895 884 872 854 836 824 812 792 772 754 719
–
Med Low 2
Y1
836 824 812 794 776 765 754 735 715 703 691 653 631
–
Low
1
G
735 721 707 687 666 653 640 622 603 589 574 533
–
–
High
5
W
1530 1503 1476 1453 1429 1413 1397 1376 1355 1342 1329 1276 1231 1173
Med High 4
Y2
1413 1388 1363 1342 1321 1303 1285 1263 1240 1226 1212 1173 1016 946
038
Med
3
Y1 11 x 10 1/2 1355 1325 1294 1276 1258 1235 1212 1188 1164 1144 1123 982 909 883
Med Low 2
1336 1299 1261 1242 1222 1202 1181 1157 1132 1111 1090 937 874 830
Low
1
G
1243 1182 1121 1061 1000 964 928 856 784 744 703 647 592
High
5
W
1934 1910 1886 1871 1855 1827 1799 1780 1760 1747 1734 1700 1659 1617
Med High 4
1799 1783 1767 1744 1720 1693 1666 1649 1631 1617 1603 1560 1530 1492
049 Med
3
Y2 11 x 10 1 1694 1680 1666 1642 1617 1592 1567 1552 1537 1519 1500 1453 1421 1372
Med Low 2
Y1
1575 1560 1540 1520 1502 1487 1471 1448 1424 1409 1393 1351 1308 1266
Low
1
G
1454 1406 1358 1333 1308 1285 1261 1239 1217 1198 1179 1072 1002 988
High
5
W
2245 2230 2214 2194 2173 2155 2136 2120 2103 2087 2070 2032 1998 1957
Med High 4
Y2
2092 2073 2054 2035 2015 1995 1975 1958 1940 1922 1904 1880 1843 1806
064 Med
3
11 x 10 1
1951 1931 1910 1889 1868 1850 1831 1812 1793 1774 1755 1722 1688 1654
Med Low 2
Y1
1812 1796 1780 1761 1741 1718 1695 1682 1668 1651 1633 1591 1555 1518
Low
1
G
1682 1661 1640 1616 1591 1573 1555 1533 1510 1495 1480 1441 1400 1351
High
5
W
2472 2454 2435 2414 2393 2371 2349 2328 2306 2289 2271 2230 2189 2121
Med High 4
Y2
2271 2248 2225 2205 2184 2166 2147 2129 2110 2094 2078 2039 2011 1977
072
Med
3
11 x 10 1
2133 2115 2096 2072 2047 2030 2013 1996 1979 1965 1950 1909 1873 1837
Med Low 2
Y1
2008 1985 1962 1939 1915 1898 1880 1862 1843 1828 1812 1774 1742 1703
Low
1
G
1806 1784 1761 1742 1722 1696 1669 1656 1642 1625 1607 1564 1527 1490
Factory speed settings are in Bold Air flow values are with dry coil and standard filter For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg., and 500 fpm by 0.16 in. wg. Highest setting is for auxiliary heat (W) and lowest setting is for constant blower (G). The “Y1” and “Y2” settings must be between the “G” and “W” settings.
0.90 1.00
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
1910 1825
1767 1728
1612 1562
1480 1433
1316 1263
2033 1936
1930 1846
1793 1748
1669 1635
1443 1404
7/30/15
Setting Blower Speed – 5-Speed ECM
5-speed ECM blower motors have five (5) speeds of which three (3) are
selectable on single speed and four (4) are selectable on dual capacity.
CAUTION: Disconnect all power before performing this operation.
5-Speed ECM Motor Connections – Single Speed
C – Black
L – Orange G – Green
High Voltage Connections
3/16 in.
CLGN
N – Brown
G – Blue Y1 – Red
12345
Low Voltage Connections 1/4 in.
AUX – Gray
5-Speed ECM Motor Connections – Dual Capacity
C – Black
L – Orange G – Green
High Voltage Connections
3/16 in.
CLGN
N – Brown
G – Blue Y1 – Red
12345
Low Voltage Connections 1/4 in.
AUX – Gray Y2 – Tan
23
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Blower Performance Data cont.
Variable Speed ECM Motor
Single Speed
Model
Max Blower Motor
ESP
Size
hp
1
2
015
0.50 9 x 7
1/2
018
0.50 9 x 7
1/2
024
0.50 9 x 7
1/2
300 300
400 L
400 L
400
030 0.50 9 x 7
1/2
400
036 0.50 11 x 10 1/2
650
750
036 w/1hp*
0.75
11 x 10
1
042 0.50 11 x 10 1/2
042 w/1hp*
0.75
11 x 10
1
048 0.50 11 x 10 1/2
048 w/1hp*
0.75
11 x 10
1
060 0.75 11 x 10
1
800 650 800 650 800 800
1000 L
800
900 L
800
900
950
070 0.75 11 x 10
1
800
950
3 500
500
500 L
500 L
850 L
1100 M
900 L
1000
900
1000 L
1100 L
1100
L
4 600
M 600
M 600
M 600
1000
1300 H
1050
1200 M
1050 L
1200
1300
1300
Airflow DIP Switch Settings
5
6
7
8
700 H
700 H
700
700 M
1100 M
800
800 H
800
1200
900
900 H
1300 H
1000 1000 1400
1500 1600 1800
1150 M
1400 H
1150
1400 M
1500 M
1500
1250
1600
1250
1600 H
1750
1750 M
1350
1700
1350 M
1700
1950 H
1950
1450 H
1850
1450
1850
2100
2100 H
9
1100 1100 1500
1550 2000 1550
H 2000 2300 2300
Dual Capacity
Model
Max Blower Motor
ESP
Size
hp
1
2
3
4
Air Flow DIP Switch Settings
5
6
7
8
026
0.50 9 x 7
1/2
400
500 L
600
700 M
800
900 H
1000
038 0.50 11 x 10 1/2
650
750
850 1000 1100 1200 1300 1400
L
M
H
038 w/1hp*
0.75
11 x 10
1
800 L
1000
1100 M
1300 H
1500
1600
1800
049 0.50 11 x 10 1/2
049 w/1hp*
0.75
11 x 10
1
650
800 L
800 L
900
900 1000
1050 1200
1150
1400 M
1250
1600 H
1350 M
1700
1450 1850
064 0.75 11 x 10
1
800
950
1100 1300 1500 1750 1950 2100
L
M
H
072
0.75 11 x 10
1
800
950
1100 1300 1500
L
Factory settings are at recommended L-M-H DIP switch locations
M-H settings MUST be located within boldface cfm range
Lowest and Highest DIP switch settings are assumed to be L and H respectively
cfm is controlled within ±5% up to the maximum ESP
Max ESP includes allowance for wet coil and 1 in. MERV 4
1750 M
1950
2100 H
9 1100 1500
1550 H
2000
2300 2300
Variable Speed Constant Torque ECM
Fan Speed Fan RPM
0.0
0.1
1
0
2
514
190
3
630
245
50
4
800
330
230
5
950
405
320
6
1100
485
420
7
1200
540
485
8
1300
560
535
9
1400
560
535
10
1500
560
535
11
1600
560
535
12
1700
560
535
Air flow values are with dry coil and standard 1″ filter
Airflow [cfm] at External Static Pressure [in. wg.]
0.2
0.3
0.4
0.5
0.6
175
335
180
405
320
490
415
305
510
475
445
340
510
475
450
425
390
510
475
450
425
390
510
475
450
425
390
24
10
11
12
1200 1200
2200 2300 2400 2200 2300 2400
3/16/12
10
11
12
1200
2200 2300 2400 3/16/12
0.7
0.8
270
365
365
320
4/12/19
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Blower Performance Data cont.
Setting Blower Speed – Variable Speed ECM
The ABC board’s Yellow Config LED will flash the current variable speed ECM
blower speed selections for low, med, and high continuously with a short pause
in between. The speeds can also be confirmed with the AID Tool under the
Setup/ECM Setup screen. The variable speed ECM blower motor speeds can be
field adjusted with or without using an AID Tool.
Variable Speed ECM Setup with an AID Tool cont.
ECM SPEED INFO
LOW SPEED: 3 MED SPEED: 5 HIGH SPEED: 7
Selecting YES will enter variable speed ECM speed setup, while selecting NO will return to the previous screen.
Variable Speed ECM Setup without an AID Tool
The blower speeds for Low (G only), Med (Y1), and High (Y2/Aux) can be
adjusted directly at the Aurora ABC board which utilizes the push button (SW1)
on the ABC board. This procedure is outlined in the Variable Speed ECM
Configuration Mode portion of the Aurora `Base’ Control System section.
Variable Speed ECM Setup with an AID Tool
A much easier method utilizes the AID Tool to change the airflow using the
procedure below. First navigate to the Setup screen and then select ECM Setup.
This screen displays the current variable speed ECM settings. It allows the
technician to enter the setup screens to change the variable speed ECM
settings. Change the highlighted item using the and buttons and then press the
button to select the item.
WANT TO CHANGE?
YES
NO
OPTION ENTER
Variable Speed ECM Speed Setup – These screens allow the technician to select the low, medium, and high blower speed for the variable speed ECM blower motor. Change the highlighted item using the and buttons. Press the button to select the speed.
ECM SPEED INFO
1 2 < LOW 3 4 5 6 7 8 9 10 11 12
ECM SPEED INFO
1 2 LOW 3 4 5 6 7 8 9 10 11 12
< MED
ECM SPEED INFO
1 2 LOW 3 4 5 6 7 8 9 10 11 12
MED < HIGH
OPTION ENTER OPTION ENTER OPTION ENTER
After the high speed setting is selected the AID Tool will automatically
transfer back to the ECM Setup screen.
25
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Wiring Schematics
Aurora Control 460/60/3 Variable Speed ECM
Compressor
Note 4 PGM Y-OUT
Y C
Black/White (92) Yellow (91)
Note 2 Isolation
Valve
213
T3
T1
T2
Red
Yellow
Black
T3
T2
T1
CC
L3
L2
L1
Note 3
Phase Guard Monitor (PGM) L1 L2 L3
Black (7) White (8) Red (9)
Yellow
Blue
Black
460V
Transformer
24V Black/White
Black (54) Blue (55) Red (56)
CC
Dual Capacity Units Only
UltraTech
CS
RCP
Orange
Brown
PB3
N
Black (54)
L1
Blue (55)
L2
Red (56)
L3
Unit Power Supply 460/60/3 w/Neutral
G
Note 1
Green (93) Gray (94)
Ground
Neutral Disconnect
Black (95)
L1
L1
Yellow (96) L2
L2
Red (97)
L3
L3
T
RV
Resistor
RV FD
LP HP
Green
Orange Brown
1 2 3 4 5 P11
Variable Speed ECM
Blower Motor
R G PWM CFM C1 C2
12 15 10 16 1 3 P12
Black (15)
Violet (14)
Black (10) Black (09) Blue (08) Blue (07)
Yellow Yellow Orange (02) Orange (01)
Red (51)
Green (50)
White (52)
Red (53) Note 2
DH W Y2 Y1 G O/B C R LO P9
P2 ES LS ALM ALG ACC COM ACC NO ACC NC
K5 K6
LO R C O/B G Y1 Y2 W DH P1
F1
R
RS485 NET
C
P8
JW2
Blue(16) Blue(18)
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
K3 K4
K2
CC 24V
REV REV FP1 FP1 FP2 FP2 LPS LPS HPS HPS P4
P12
C
K1
R
F
Aurora Base Control
SW1
(ABC)
LED5 RS485 NET C R A- B+ P7
LED4 RS485 EXP C R A- B+ P6 N/A CO C EH1 C EH2 P3
Status G
PWM CFM
C
Fault
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 1
4
Acc Dip 2
5
CC Dual/Single
6
L Pulse/Continuous
7
Reheat/Normal
8
SW2
Config Y
Y1 G CC
Black/White Yellow Violet (42) Blue (24) Yellow (25)
Green/Yellow (28)
Notes
1 Optional, factory installed unit mounted disconnect. 2 Optional, factory
installed internal isolation valve. 3 Optional, factory installed phase
guard 4 Optional, factory installed phase guard. The yellow
transformer wire shall be connected directly to the CPU board, if this option
is not installed.
Brown (23)
Green
Gray
RH
Gray (60)
(61)
Accessory Relay
Operation
SW2-4 SW2-5
Cycle with Blower
On On
Cycle with Compressor
Off Off
Water Valve Slow Open
On Off
Outdoor Air Damper
Off On
Aurora Timing Events
Event
Normal Mode Test Mode
Random Start Delay
5 to 80 seconds
1 second
Compressor On Delay
5 seconds
< 1 second
Compressor Minimum On Time
2 minutes
5 seconds
Compressor Short Cycle Delay
4 minutes
15 seconds
Blower Off Delay
30 seconds
2 seconds
Fault Recognition Delay High Pressure
Less than 1 second Less than 1 second
Start-Up Bypass Low Pressure
2 minutes
30 seconds
Fault Recognition Delay Low Pressure
30 seconds
30 seconds
Start-Up Bypass Low Water/Air Coil Limit
2 minutes
30 seconds
Fault Recognition Delay Low Water/Air Coil Limit
30 seconds
30 seconds
Fault Recognition Delay Condensate Overflow
30 seconds
30 seconds
Thermostat Call Recognition Time
2 seconds
2 seconds
Auxiliary Heat Staging Delay
5 minutes
20 seconds
Emergency Heat Staging Delay
2 minutes
7.5 seconds
Water Valve Slow Open Delay
90 seconds
90 seconds
Reheat Delay
30 seconds
30 seconds
Condensate
Aurora LED Flash Codes
Slow Flash 1 second on and 1 second off
Fast Flash 100 milliseconds on and 100 milliseconds off
Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Random Start Delay
Status LED (LED1, Green)
Fast Flash
Configuration LED (LED2, Yellow)
Fast Flash
Fault LED (LED3, Red)
Fast Flash
Status LED (LED1, Green) Configuration LED (LED2, Yellow)
Fault LED (LED3, Red)
Normal Mode
ON
No Software Overide Flash ECM Setting Normal Mode
OFF
Control is Non-Functional
OFF DIP Switch Overide
Slow Flash Input Fault Lockout
Flash Code 1
Test Mode
Slow Flash ECM Configure Mode
Fast Flash High Pressure Lockout
Flash Code 2
Lockout Active
Fast Flash Reset Configure Mode
Off
Low Pressure Lockout
Flash Code 3
Dehumidification Mode
Flash Code 2
Low Air Coil Limit Lockout – FP2 Flash Code 4
Reserved
Flash Code 3
Low Water Coil Limit Lockout – FP1 Flash Code 5
Reserved
Flash Code 4
Reserved
Flash Code 6
Load Shed
Flash Code 5
Condensate Overflow Lockout
Flash Code 7
ESD
Flash Code 6
Over/Under Voltage Shutdown
Flash Code 8
Reserved
Flash Code 7
Reserved
Flash Code 9
Reserved
Flash Code 10
Air/Water Coil Limit Sensor Error Flash Code 11
Legend
Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Junction Quick Connect Terminal
L1
Field Wiring Lug
Ground
Relay Contacts N.O., N.C.
Capacitor
Fuse
CC Compressor Contactor CO Condensate Overflow Sensor ES Emergency
Shutdown HP High Pressure Switch LP Low Pressure Switch FD Freeze
Detection Sensor F1 Fuse
1 2 3
T
Thermistor
Relay Coil
Switch – Condensate Overflow Switch – High pressure Switch – Low pressure
Polarized connector
G
Light Emitting Diode – Green
Y
Light Emitting Diode – Yellow
R
Light Emitting Diode – Red
SW1 Push button SW2 DIP package 8 position RB Blower Relay RV Reversing Valve Coil PGM Phase Guard Monitor RH Reheat Valve Coil
97P818-08 3/19/12
26
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Wiring Schematics cont.
Aurora Base Control 460/60/3 5-Speed ECM with Reheat
Note 4
Phase Guard Monitor (PGM) L1 L2 L3
Red (9) White (8) Black (7)
T3
T1
Red
T2
Black
Yellow
T3
T2
T1
CC
L3
L2
L1
Note 1 Green (93)
Ground
Neutral Disconnect
Black (95)
L1
L1
Unit Power Supply 460/60/3
G
Yellow (96)
L2
L2
Red (97)
L3
L3
Blue
Black
460V
Brown Orange
Note 5
PGM Y-OUT
Y C
Black/White (92) Yellow (91)
Yellow
Transformer
24V Black/White
Note 2 Isolation
Valve
213
CC
Dual Capacity Units Only
UltraTech CS
RCP
470 T
RV
Gray
Tan
Red Blue
Black 470 Resistor
RV FD
LP HP
Black (10) Black (09) Blue (08) Blue (07)
Yellow Yellow Orange (02) Orange (01)
Black (15)
Violet (14)
Red (51)
Green (50)
White (52)
Red (53) Note 2
Blue(16) Blue(18)
P9 EH1 CC2 CC F C
P2
ES
LS
ALM ALG ACC COM
K5-Alarm Relay
ACC NO ACC NC
K6-Acc Relay
LO R C O/B G Y1 Y2 W DH P1
R
Com2 LED5
G RS485 NET
C
P8
K1-RV Relay
K3-CC2 Relay K2-CC Relay K4-Fan Relay
JW2
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REV REV FP1 FP1 FP2 FP2 LPS LPS HPS HPS P4
C
R F1-3A
F
Aurora Base Control (ABC)
SW1 Test Mode
Com1 LED5
G RS485 NET
C R – + P7
RS485 EXP C R – + P6 CO C EH1 C EH2 P3
Status LED3
G
PWM CFM
Fault
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Single
6
L Output Type
7
Future Use
8
SW2
Config
LED2
Y
Y1 G CC
Black/White Yellow
GN L
Green
5-Speed ECM Fan Motor
54321C
Note 5
Accessory Relay
Operation
SW2-4 SW2-5
Cycle with Blower
On On
Cycle with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
Aurora Timing Events
Event
Normal Mode
Random Start Delay
5 to 80 seconds
Compressor On Delay
5 seconds
Compressor Minimum On Time
2 minutes
Compressor Short Cycle Delay
4 minutes
Blower Off Delay
30 seconds
Fault Recognition Delay High Pressure
Less than 1 second
Start-Up Bypass Low Pressure
2 minutes
Fault Recognition Delay Low Pressure
30 seconds
Start-Up Bypass Low Water/Air Coil Limit
2 minutes
Fault Recognition Delay Low Water/Air Coil Limit
30 seconds
Fault Recognition Delay Condensate Overflow
30 seconds
Thermostat Call Recognition Time
2 seconds
Auxiliary Heat Staging Delay
5 minutes
Emergency Heat Staging Delay
2 minutes
Water Valve Slow Open Delay
90 seconds
Reheat Delay
30 seconds
Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds
Notes:
1 Optional, factory installed unit mounted disconnect. 2 Optional, factory
installed internal isolation valve. 3 Optional, factory installed phase
guard 4 Optional, factory installed phase guard. The yellow transformer wire
shall be connected directly to the CPU board, if this option is not installed.
5 Wire is provided with the unit but only connected to the 5 Speed ECM
motor on dual capacity units.
Gray (61)
RH
Gray (60)
Green
Brown (23) Condensate
Aurora LED Flash Codes
Slow Flash 1 second on and 1 second off
Fast Flash 100 milliseconds on and 100 milliseconds off
Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Random Start Delay
Status LED (LED1, Green)
Fast Flash
Configuration LED (LED2, Yellow)
Fast Flash
Fault LED (LED3, Red)
Fast Flash
Status LED (LED1, Green)
Configuration LED (LED2, Yellow)
Fault LED (LED3, Red)
Normal Mode
ON
No Software Overide Flash ECM Setting Normal Mode
OFF
Control is Non-Functional
OFF DIP Switch Overide
Slow Flash Input Fault Lockout
Flash Code 1
Test Mode
Slow Flash ECM Configure Mode
Fast Flash High Pressure Lockout
Flash Code 2
Lockout Active
Fast Flash Reset Configure Mode
Off
Low Pressure Lockout
Flash Code 3
Dehumidification Mode
Flash Code 2
Low Air Coil Limit Lockout – FP2 Flash Code 4
Reserved
Flash Code 3
Low Water Coil Limit Lockout – FP1 Flash Code 5
Reserved
Flash Code 4
Reserved
Flash Code 6
Load Shed
Flash Code 5
Condensate Overflow Lockout
Flash Code 7
ESD
Flash Code 6
Over/Under Voltage Shutdown
Flash Code 8
Reserved
Flash Code 7
Reserved
Flash Code 9
Reserved
Flash Code 10
Air/Water Coil Limit Sensor Error Flash Code 11
Legend
Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Junction Quick Connect Terminal
L1
Field Wiring Lug
Ground
Relay Contacts N.O., N.C.
Capacitor
Fuse
CC Compressor Contactor CO Condensate Overflow Sensor ES Emergency
Shutdown HP High Pressure Switch LP Low Pressure Switch FD Freeze
Detection Sensor F1 Fuse
1 2 3
T
Thermistor
Relay Coil
Switch – Condensate Overflow Switch – High pressure Switch – Low pressure
Polarized connector
G
Light Emitting Diode – Green
Y
Light Emitting Diode – Yellow
R
Light Emitting Diode – Red
SW1 Push button SW2 DIP package 8 position RB Blower Relay RV Reversing Valve Coil PGM Phase Guard Monitor RH Reheat Valve Coil
97P819-16 10/30/12
27
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Wiring Schematics cont.
Commercial Aurora UPC with Variable Speed ECM Motor 208-230/60/1
Compressor S
Blue Cap
Tan
C
R Black
Red
T2
T1
CC
L2
L1
Red 208V
Blue 230V
Black
Class 2
Transfo rmer 24V
Yellow Black/White
Green (93) Black (95)
Ground
Neutral Disconnect
L1
L1
Red (97)
L2
L2
L3
L3
Unit Power Supply 208-230/60/1 G
Black Red
Red (51)
Green (50)
White (52)
Red (53) Note 3
Dual Capacity Units Only
Ultra Tech CS
RCP
Gray T
Gray T RV
RV FP LAT LP HP
CC
Black (10) Black (09) Blue (08) Blue (07)
Black Black Yellow Yellow Orange (02) Orange (01)
Black (15)
Violet (14)
Blue(16) Blue(18)
P9 EH1 CC2 CC F C
P2
ES
LS
ALM ALG ACC COM
K5-Alarm Relay
ACC NO ACC NC
K6-Acc Relay
LO R C O/B G Y1 Y2 W DH P1
R
Com2 LED5
G RS485 NET
C
P8
K1-RV Relay
K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
JW2
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F
Aurora Base Control (ABC)
SW1 Test Mode
Com1 LED5
G RS485 NET
C R – + P7
RS485 EXP C R – + P6 CO C EH1 C EH2 P3
PWM
Status
CFM
LED3
G
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Single
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
Y1 G CC
Black/White Yellow Yellow
Blue
Bro wn (23)
Condensate
Green
Gray (61)
RH Gray (60) Note 4
From UPC
28
ECM Fan Mo tor
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Wiring Schematics cont.
Commercial Aurora UPC with Variable Speed ECM Motor 208-230/60/1
Notes:
1 Optional, fac tory installed unit mounted dis connec t. 2 Swap blue and
red leads for 208V operation. 3 Optional, fac tory installed internal
isolation valve . 4 Optional, factory installed reheat.
Legend
Factory Low Voltage Wiring Factory Line Vol tage Wiring Field Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Ju nction Qui ck Con nect Terminal
L1
Field Wiring Lug
Ground
Relay Con tacts N.O., N.C.
Capacitor
Fuse
CC Compressor Contactor CO Condensate Overfl ow Sensor ES Emergency
Shutdown HP High Pressure Switch LP Low Pressure Switch FP Freeze
Protection F1 Fuse
1 2 3
T
Thermistor
Relay Coil
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
G
Light Emitting Diode – Green
Y
Light Emitting Diode – Yellow
R
Light Emitti ng Diode – Red
SW1 Push button SW2 DIP package 8 position RB Blower Relay RV Reversi ng Valve Coi l PGM Phase Guard Moni tor RH Reheat Valve Coil
97P92 10/27
Aurora LED Flash Codes
SlowFlash 1 second on and 1 second off
Fast Flash 100 milliseconds on and 100 milliseconds off
Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repe ating
Random Start Delay
Status LED (LED1, Green)
Fast Fl ash
Configuration LED (LED2, Yellow)
Fast Fl ash
Faul t LED (LED3, Red)
Fast Fl ash
Sta tus LED (LED1, Green)
Configuration LED (LED2, Yellow)
Fault LED (LED3, Red)
Normal Mode
ON
No Software Overi de Fl ash ECM Settin g Normal Mode
OFF
Control is Non-Functional
OFF DIP Switch Overide
Slow Flash Input Fault Lockout
Fl ash Code 1
Test Mode
Slow Flash ECM Configu re Mod e
Fast Fl ash High Pressure Lockout
Fl ash Code 2
Lockout Active
Fast Fl ash Reset Confi gure Mode
Off
Low Pressure Locko ut
Fl ash Code 3
Dehumidification Mo de
Fl ash Code 2
Low Air Coil Limi t Lockout – FP2 Fl ash Code 4
Reserved
Fl ash Code 3
Low Water Coil Limi t Lockout – FP1 Fl ash Code 5
Reserved
Fl ash Code 4
Reserved
Fl ash Code 6
Load Shed
Fl ash Code 5
Condensate Overflow Lockout
Fl ash Code 7
ESD
Fl ash Code 6
Over/Under Voltage Shutdown
Fl ash Code 8
Reserved
Fl ash Code 7
Reserved
Fl ash Code 9
Reserved
Fl ash Code 10
Air/Water Coil Limit Sensor Error Fl ash Code 11
Factory PWM CFM C
Accessor y Relay
Operation
SW2-4 SW2-5
Cycle with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
Aurora Timing Events
Event
Normal Mode
Test Mode
Random Start Delay
5 to 80 seconds
1 second
Compressor On Delay
5 seconds
< 1 second
Compressor Minimum On Time
2 minutes
5 seconds
Compressor Short Cycl e Delay
4 minutes
15 seconds
Blower Off Delay
30 seconds
2 seconds
Faul t Recogn itio n Delay High Pressure
Less than 1 second Less than 1 second
Start-Up Bypass Low Pressure
2 minutes
30 seconds
Faul t Recogn itio n Delay Low Pressure
30 seconds
30 seconds
Start-Up Bypass Low Water/Air Coil Limit
2 minutes
30 seconds
Faul t Recogn itio n Delay Low Water/Air Coil Limit 30 seconds
30 seconds
Fault Recogn itio n Delay Condensate Overflow
30 seconds
30 seconds
Thermostat Call Recognition Time
2 seconds
2 seconds
Auxi liary Heat Stagi ng Del ay
5 minutes
20 seconds
Emergency Heat Stagi ng Dela y
2 minutes
7.5 seconds
Water Valve Slow Open Delay
90 seconds
90 seconds
Reheat Delay
30 seconds
30 seconds
29
CC2 Factory Factory Use
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
G
P5
LO
HI
CCG
CC
FG
F
R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1 JW2 Alarm
P2
Fi eld Connections
Off LED1 FP1 15oF/30oF
On 1 LED2
R FP2 15oF/30oF
2Y
Faul t
RV B/O
ACC Dip 4
LED3 G
ACC Dip 5 CC Dual/Single L Pulse/Continuous
Status
Reheat/Normal
3 Config
4 5 6 7 8
SW2
AURORA BASE CONTROLTM
Com1 G
EH1
P3 EH2 C EH1 C CO N/A
Factory
RS485 Exp
P6
(+)
(-)
R
C
P7
RS 485
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
RS485 NET CC C
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
Pa
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Wiring Schematics cont.
Commercial Aurora UPC with Variable Speed ECM Motor 265/60/1
Compressor S
Blue Cap
Tan
C
R Black
Red
T2
T1
CC
L2
L1
Blue 265V
Black
Green (93) Black (95)
Ground
Neutral Disconnect
L1
L1
Red (97)
L2
L2
L3
L3
White
Black
Transfo rmer 24V
Black/White Yellow
Transfo rmer 2 30 V
Unit Power Supply 208-230/60/1 G
Yellow Red
Black Red
Class 2
Red (51)
Green (50)
White (52)
Red (53) Note 2
Dual Capacity Units Only
Ultra Tech CS
RCP
Gray T
Gray T RV
RV FP LAT LP HP
CC
Black (10) Black (09) Blue (08) Blue (07)
Black Black Yellow Yellow Orange (02) Orange (01)
Black (15)
Violet (14)
Blue(16) Blue(18)
P9 EH1 CC2 CC F C
P2
ES
LS
ALM ALG ACC COM
K5-Alarm Relay
ACC NO ACC NC
K6-Acc Relay
LO R C O/B G Y1 Y2 W DH P1
R
Com2 LED5
G RS485 NET
C
P8
K1-RV Relay
K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
JW2
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F
Aurora Base Control (ABC)
SW1 Test Mode
Com1 LED5
G RS485 NET
C R – + P7
RS485 EXP C R – + P6 CO C EH1 C EH2 P3
Status LED3
G
PWM CFM
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Single
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
Y1 G CC
Black/White Yellow Yellow
Blue
Bro wn (23)
Condensate
Green
Gray (61)
RH Gray (60) Note 3
From UPC
30
ECM Fan Mo tor
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Wiring Schematics cont.
Commercial Aurora UPC with Variable Speed ECM Motor 208-230/60/1
Notes:
1 Optional, fac tory installed unit mounted dis connec t. 3 Optional, fac
tory installed internal isolation valve . 4 Optional, factory installed r
eheat.
Legend
Factory Low Voltage Wiring Factory Line Vol tage Wiring Field Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Ju nction Qui ck Con nect Terminal
L1
Field Wiring Lug
Ground
Relay Con tacts N.O., N.C.
Capacitor
Fuse
CC Compressor Contactor CO Condensate Overfl ow Sensor ES Emergency
Shutdown HP High Pressure Switch LP Low Pressure Switch FP Freeze
Protection F1 Fuse
1 2 3
T
Thermistor
Relay Coi l
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
G
Light Emitti ng Diode – Green
Y
Light Emitting Diode – Yellow
R
Light Emitti ng Diode – Red
SW1 Push button SW2 DIP package 8 position RB Blower Relay RV Reversi ng Valve Coi l PGM Phase Guard Moni tor RH Reheat Valve Coil
97P92 11/01
Aurora LED Flash Codes
SlowFlash 1 second on and 1 second off
Fast Flash 100 milliseconds on and 100 milliseconds off
Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repe ating
Random Start Delay
Status LED (LED1, Green)
Fast Fl ash
Configuration LED (LED2, Yellow)
Fast Fl ash
Faul t LED (LED3, Red)
Fast Fl ash
Sta tus LED (LED1, Green)
Configuration LED (LED2, Yellow)
Fault LED (LED3, Red)
Normal Mode
ON
No Software Overi de Fl ash ECM Settin g Normal Mode
OFF
Control is Non-Functional
OFF DIP Switch Overide
Slow Flash Input Fault Lockout
Fl ash Code 1
Test Mode
Slow Flash ECM Configu re Mod e
Fast Fl ash High Pressure Lockout
Fl ash Code 2
Lockout Active
Fast Flash Reset Confi gure Mode
Off
Low Pressure Locko ut
Fl ash Code 3
Dehumidification Mo de
Fl ash Code 2
Low Air Coil Limit Lockout – FP2 Fl ash Code 4
Reserved
Fl ash Code 3
Low Water Coil Limi t Lockout – FP1 Fl ash Code 5
Reserved
Fl ash Code 4
Reserved
Fl ash Code 6
Load Shed
Fl ash Code 5
Condensate Overflow Lockout
Fl ash Code 7
ESD
Fl ash Code 6
Over/Under Voltage Shutdown
Fl ash Code 8
Reserved
Fl ash Code 7
Reserved
Fl ash Code 9
Reserved
Fl ash Code 10
Air/Water Coil Limit Sensor Error Fl ash Code 11
PWM CFM
C
Accessor y Relay
Operation
SW2-4 SW2-5
Cycle with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
Aurora Timing Events
Event
Normal Mode
Random Start Delay
5 to 80 seconds
Compressor On Delay
5 seconds
Compressor Minimum On Time
2 minutes
Compressor Short Cycl e Delay
4 minutes
Blower Off Delay
30 seconds
Faul t Recogn itio n Delay High Pressure
Less than 1 second
Start-Up Bypass Low Pressure
2 minutes
Faul t Recogn itio n Delay Low Pressure
30 seconds
Start-Up Bypass Low Water/Air Coil Limit
2 minutes
Fault Recogn itio n Delay Low Water/Air Coil Limit
30 seconds
Faul t Recogn itio n Delay Condensate Overfl ow
30 seconds
Thermostat Call Recognition Time
2 seconds
Auxi liary Heat Stagi ng Del ay
5 minutes
Emergency Heat Staging Dela y
2 minutes
Water Valve Slow Open Delay
90 seconds
Reheat Delay
30 seconds
Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds
CC2 Factory Factory Use
Factory Factory
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
G
P5
LO
HI
CCG
CC
FG
F
R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1 JW2 Alarm
P2
Fi eld Connections
Off LED1 FP1 15oF/30oF
On 1 LED2
R FP2 15oF/30oF
2Y
Faul t
RV B/O
ACC Dip 4
LED3 G
ACC Dip 5 CC Dual/Single L Pulse/Continuous
Status
Reheat/Normal
3 Config
4 5 6 7 8
SW2
AURORA BASE CONTROLTM
Com1 G
EH1
P3 EH2 C EH1 C CO N/A
RS485 Exp
P6
(+)
(-)
R
C
P7
RS 485
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
31
RS485 NET CC C
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Wiring Schematics cont.
Aurora Control and UPC
To ABC – P8
12345678
BACnet or N2 Network
Connections
Devices Must Be Wired in Daisy Chain Configuration
Orange Red
White Black
Blue Green
Brown Yellow
NET+ NETCOM NET+ NETCOM
Optional LON Add-On Module
LON OC
LON Network Connections
Devices Must Be Wired in Daisy Chain Configuration
Service
LED1
21
LED2
Tx
LED3
Rx
LED4
Net
ECHELON
12
12
GND
ZS Sensor 1 RNET+
Addr: 0
RNET-
+12V
ZS Sensor 2 Addr: 1
GND RNET+ RNET-
+12V
ZS Sensor 3 Addr: 2
GND RNET+ RNET-
+12V
NET+ NETCOM
NET+ NETN/C N/C Signal
LED1 TX
LED2 RX
LON ADAPTER
PORT
LED6 TX
LED7 2W RX
4W
GND RNET+ RNET+12V
RNET
GND LN+ LN+12
/S
LOCAL ACCESS
POWER
GND 24 VAC
LED3 POWER
FORMAT BATT
Communication Options
NOTE 1
12345678
LED4 RUN
LED5 ERR
ON
TEN’S
89 0 12 73
654
89 0 12
76
5
3 4
ONE’S
MAC Address Setting
ZS Sensor Information
Zone Sensors can be wired in daisy chain as show or in a star or hybrid configuration. Maximum of 5 sensors per UPC. Maximum allowable load 210mA. See the UPC install manual for possible sensor combinations.
DIP Switch Value
1 2 4 8
ON 1 2 34
Each ZS sensor must have a unique address, but the addresses do not need to be sequential. Use the DIP switches on the back of the ZS sensor to set an address from 0 to 4. (0 is the factory default.) Each DIP switch has the value shown in the figure to the left. Turn on as many DIP switches as you need so that their total value equals the address.
32
Notes
1. Use DIP Switches 5 8 to change communication protocol and DIP switches 1
2 to change BACnet baud rate
Legend
Factory Low Voltage Wiring Field Low Voltage Wiring 12345678 RJ45 Connector
Page 1
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Controls – Aurora Base Control
Aurora `Base’ Control
Field Selectable Options via Hardware
DIP Switch (SW1) Test/Configuration Button (See SW1 Operation Table)
NOTE: Refer to the Aurora Base Control Application and Troubleshooting Guide
and the Instruction Guide: Aurora Interface and Diagnostics (AID) Tool for
additional information.
Control Features
Software ABC Standard Version 3.0 Single or Dual Capacity Compressors Either
single or dual capacity compressors can be operated.
Variable Speed ECM Blower Motor Option (If Applicable) A Variable Speed ECM
blower motor can be driven directly using the onboard PWM output. Four blower
speeds are available based upon the G, Y1, Y2, and W input signals to the
board. The blower speeds can be changed either by the ECM manual
configurations mode method or by using the Aurora AID Tool directly. All four
blower speeds can be set to the same speed if desired.
5-Speed ECM Blower Motor Option (If Applicable) A 5-Speed ECM blower motor
will be driven directly using the thermostat connections. Any of the G, Y1, or
Y2/W signals can drive any of the 5 available pre-programmed blower speeds on
the motor. All 5 Series “G” vintage units will be wired this way at the
factory.
Other Control Features
· Random start at power up · Anti-short cycle protection · High and low
pressure cutouts · Loss of charge · Water coil freeze detection · Air coil
freeze detection · Over/under voltage protection · Condensate overflow sensor
· Load shed · Dehumidification (where applicable) · Emergency shutdown · Hot
gas reheat operation (where applicable) · Diagnostic LED · Test mode push
button switch · Two auxiliary electric heat outputs · Alarm output · Accessory
output with N.O. and N.C. · Two Modbus communication Ports
Test Mode
The control is placed in the test mode by holding the push button switch SW1
for 2 – 5 seconds. In test mode most of the control timings will be shortened
by a factor of sixteen (16). LED3 (green) will flash at 1 second on and 1
second off. Additionally, when entering test mode LED1 (red) will flash the
last lockout one time. Test mode will automatically time out after 30 minutes.
Test mode can be exited by pressing and holding the SW1 button for 2 to 5
seconds or by cycling the power. NOTE: Test mode will automatically be exited
after 30 minutes.
Variable Speed ECM Configuration Mode
(If Applicable)
The control is placed in the ECM configuration mode by holding the pushbutton
switch SW1 for 5 to 10 seconds, the high, low, and “G” ECM speeds can be
selected by following the LED display lights. LED2 (yellow) will fast flash
when entering the ECM configuration. When setting “G” speed LED3 (green) will
be continuously lit, for low speed LED1 (red) will be continuously lit, and
for high speed both LED3 (green) and LED1 (red) will be continuously lit.
During the ECM configuration mode LED2 (yellow) will flash each of the 12
possible blower speeds 3 times. When the desired speed is flashed press SW1,
LED2 will fast flash until SW1 is released. “G” speed has now been selected.
Next select low speed, and high speed blower selections following the same
process above. After third selection has been made, the control will exit the
ECM configuration mode. Aux fan speed will remain at default or current
setting and requires the AID Tool for adjustment.
Reset Configuration Mode
The control is placed in reset configuration mode by holding the push button
switch SW1 for 50 to 60 seconds. This will reset all configuration settings
and the EEPROM back to the factory default settings. LED3 (green) will turn
off when entering reset configuration mode. Once LED3 (green) turns off,
release SW1 and the control will reset.
DIP Switch (SW2)
SW2-1 FP1 Selection Low water coil temperature limit setting for freeze
detection. On = 30°F; Off = 15°F.
SW2-2 FP2 Selection On = 30°F; Off = N/A SW2-3 RV O/B – thermostat type.
Heat pump
thermostats with “O” output in cooling or “B” output in Heating can be
selected. On = O; Off = B. SW2-4 Access Relay Operation (P2) and 2-5
Access Relay Operation Cycle with Blower
Cycle with Compressor Water Valve Slow Opening Cycle with Comm. T-stat Hum Cmd
SW2-4 ON OFF ON OFF
SW2-5 ON OFF OFF ON
33
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Controls – Aurora Base Control cont.
Cycle with Blower – The accessory relay will cycle with the blower output.
Cycle with Compressor – The accessory relay will cycle with the compressor
output.
Water Valve Slow Opening – The accessory relay will cycle and delay both the
blower and compressor output for 90 seconds.
SW2-6 CC Operation selection of single or dual capacity compressor. On =
Single Stage; Off = Dual Capacity
SW2-7 Lockout and Alarm Outputs (P2) selection of a continuous or pulsed
output for both the LO and ALM Outputs. On = Continuous; Off = Pulsed
SW2-8 Future Use
Alarm Jumper Clip Selection From the factory, ALM is connected to 24 VAC via
JW2. By cutting JW2, ALM becomes a dry contact connected to ALG.
Variable Speed ECM Blower Speeds The blower speeds can be changed either by
using the ECM manual configurations mode method or by using the Aurora AID
Tool directly (see Instruction Guide: Aurora Interface and Diagnostics (AID)
Tool topic).
Field Selectable Options via Software
(Selectable via the Aurora AID Tool) ECM Blower Speeds An ECM blower motor can
be driven directly using the onboard PWM output. Four blower speeds are
available, based upon the “G”, Y1 (low), Y2 (high), and Aux input signals to
the board. The blower speeds can be changed either by the ECM manual
configurations mode method (see ECM Configuration Mode topic) or by using the
Aurora AID Tool directly. All four blower speeds can be set to the same speed
if desired. Aux blower speed will remain at default or current setting and
requires the AID Tool for adjustment.
Lockout when locked out, the blower will operate continuously in “G” speed,
and PSC blower motor output will remain on. The Alarm output (ALM) and Lockout
output (L) will be turned on. The fault type identification display LED1 (Red)
shall flash the fault code. To reset lockout conditions with SW2-8 On,
thermostat inputs “Y1”, “Y2”, and “W” must be removed for at least 3 seconds.
To reset lockout conditions with SW2-8 Off, thermostat inputs “Y1”, “Y2”, “W”,
and “DH” must be removed for at least 3 seconds. Lockout may also be reset by
turning power off for at least 30 seconds or by enabling the emergency
shutdown input for at least 3 seconds.
Lockout With Emergency Heat – if the control is locked out in the heating
mode, and a Y2 or W input is received, the control will operate in the
emergency heat mode while the compressor is locked out. The first emergency
heat output will be energized 10 seconds after the W input is received, and
the blower will shift to high speed. If the control remains locked out, and
the W input is present, additional stage of emergency heat will stage on after
2 minutes. When the W input is removed, all of the emergency heat outputs will
turn off, and the ECM blower will shift to “G” speed and PSC blower motor
output will remain on.
High Pressure fault is recognized when the Normally Closed High Pressure
Switch, P4-9/10 opens, no matter how momentarily. The High Pressure Switch is
electrically in series with the Compressor Contactor and serves as a hardwired
limit switch if an overpressure condition should occur.
Low Pressure – fault is recognized when the Normally Closed Low Pressure
Switch, P4-7/8 is continuously open for 30 seconds. Closure of the LPS any
time during the 30 second recognition time restarts the 30 second continuous
open requirement. A continuously open LPS shall not be recognized during the 2
minute startup bypass time.
Loss of Charge fault is recognized when the Normally Closed Low Pressure
Switch, P4-7/8 is open prior to the compressor starting.
Safety Features
The following safety features are provided to protect the compressor, heat
exchangers, wiring and other components from damage caused by operation
outside of design conditions.
Fuse a 3 amp automotive type plug-in fuse provides protection against short
circuit or overload conditions.
Anti-Short Cycle Protection 4 minute anti-short cycle protection for the
compressor.
Random Start 5 to 80 second random start upon power up.
Fault Retry in the fault condition, the control will stage off the outputs
and then “try again” to satisfy the thermostat Y input call. Once the
thermostat input calls are satisfied, the control will continue on as if no
fault occurred. If 3 consecutive faults occur without satisfying the
thermostat Y input call, then the control will go to Lockout mode.
Condensate Overflow – fault is recognized when the impedance between this line
and 24 VAC common or chassis ground drops below 100K ohms for 30 seconds
continuously.
Freeze Detection (Coax) – set points shall be either 30°F or 15°F. When the
thermistor temperature drops below the selected set point, the control shall
begin counting down the 30 seconds delay. If the thermistor value rises above
the selected set point, then the count should reset. The resistance value must
remain below the selected set point for the entire length of the appropriate
delay to be recognized as a fault. This fault will be ignored for the initial
2 minutes of the compressor run time.
Freeze Detection (Air Coil) – uses the FP2 input to protect against ice
formation on the air coil. The FP2 input will operate exactly like FP1 except
that the set point is 30 degrees and is not field adjustable.
34
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Controls – Aurora Base Control cont.
Over/Under Voltage Shutdown – An over/under voltage condition exists when the
control voltage is outside the range of 18 VAC to 30 VAC. If the over/under
voltage shutdown lasts for 15 minutes, the lockout and alarm relay will be
energized. Over/under voltage shutdown is selfresetting in that if the voltage
comes back within range of 18 VAC to 30 VAC for at least 0.5 seconds, then
normal operation is restored.
Operation Description
Power Up – The unit will not operate until all the inputs and safety controls
are checked for normal conditions. The unit has a 5 to 80 second random start
delay at power up. Then the compressor has a 4 minute anti-short cycle delay
after the random start delay.
Standby In standby mode, Y1, Y2, W, DH, and G are not active. Input O may be
active. The blower and compressor will be off.
Heating Operation Single Compressor Heating, 2nd Stage (Y1, Y2) The compressor
will be staged to full capacity 20 seconds after Y2 input is received. The ECM
blower will shift to high speed seconds after the Y2 input is received.
Dual Compressor Heating, 2nd Stage (Y1, Y2) In dual compressor operation, two
ABC boards used in 24 VAC operation, there will be a Y2 call to the Y1 input
on the second ABC. The compressor will stage to full capacity 30 seconds after
Y1 input is received to the second board.
Single Compressor Heating, 3rd Stage (Y1, Y2, W) The hot water pump is de-
energized and the first stage of electric heat is energized 10 seconds after
the W command is received. If the demand continues the second stage of
electric heat will be energized after 5 minutes.
Dual Compressor Heating, 3rd Stage (Y1, Y2, W) The first stage of electric
heat is energized 10 seconds after the W command is received. If the demand
continues the second stage of electric heat will be energized after 5 minutes
Emergency Heat (W) – The blower will be started on “G” speed, 10 seconds later
the first stage of electric heat will be turned on. 5 seconds after the first
stage of electric heat is energized the blower will shift to Aux speed. If the
emergency heat demand is not satisfied after 2 minutes the second electric
heat stage will be energized.
Cooling Operation In all cooling operations, the reversing valve directly
tracks the O input. Thus, anytime the O input is present, the reversing valve
will be energized.
Single Compressor Cooling, 2nd Stage (Y1, Y2, 0) The compressor will be staged
to full capacity 20 seconds after Y2 input was received. The ECM blower will
shift to high speed 15 seconds after the Y2 input was received.
Dual Compressor Cooling, 2nd Stage (Y1, Y2, O) In dual compressor operation,
two ABC boards used in 24 VAC operation, there will be a Y2 call to the Y1
input on the second ABC. The compressor will stage to full capacity 30 seconds
after Y1 input is received to the second board.
Blower (G) – The blower will start immediately upon receiving a thermostat G
command. If there are no other commands from the thermostat the ECM will run
on “G” speed until the G command is removed. Regardless of blower input (G)
from the thermostat, the blower will remain on for 30 seconds at the end of
each heating, cooling, and emergency heat cycle.
Dehumidification (Y1, O, DH or Y1, Y2, O, DH) – When a DH command is received
from the thermostat during a compressor call for cooling the ECM blower speed
will be reduced by 15% to increase dehumidification.
Emergency Shutdown – Four (4) seconds after a valid ES input, P2-7 is present,
all control outputs will be turned off and remain off until the emergency
shutdown input is no longer present. The first time that the compressor is
started after the control exits the emergency shutdown mode, there will be an
anti-short cycle delay followed by a random start delay. Input must be tied to
common to activate.
Continuous Blower Operation – The blower output will be energized any time the
control has a G input present, unless the control has an emergency shutdown
input present. The blower output will be turned off when G input is removed.
Load Shed – The LS input disables all outputs with the exception of the blower
output. When the LS input has been cleared, the anti-short cycle timer and
random start timer will be initiated. Input must be tied to common to
activate.
Blower (G) – The blower will start immediately upon receiving a thermostat G command. If there are no other commands from the thermostat the ECM will run on “G” speed until the G command is removed. Regardless of blower input (G) from the thermostat, the blower will remain on for 30 seconds at the end of each heating cycle.
35
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Controls – Aurora Base Control cont.
Aurora `Base’ Control LED Displays
These three LEDs display the status, configuration, and fault codes for the
control. These can also be read in plain English via the Aurora AID Tool.
Status LED (LED3, Green)
Description of Operation Normal Mode Control is Non-functional Test Mode
Lockout Active Dehumidification Mode (Future Use) (Future Use) Load Shed ESD
(Future Use)
Fault LED, Green ON OFF
Slow Flash Fast Flash Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5
Flash Code 6 Flash Code 7
Configuration LED (LED2, Yellow)
Description of Operation No Software Overwritten DIP Switch was Overwritten ECM Configuration Mode
Configuration LED, Yellow Flashing ECM Setting Slow Flash Fast Flash
Fault LED (LED1, Red)
Red Fault LED
LED Flash Code*
Lockout
Reset/ Remove
Normal – No Faults
OFF
ABC Basic Faults
Fault – Input
1
No
Auto
Fault – High Pressure
2
Yes Hard or Soft
Fault – Low Pressure
3
Yes Hard or Soft
Fault – Freeze Detection FP2
4
Yes Hard or Soft
Fault – Freeze Detection FP1
5
Yes Hard or Soft
Fault – Condensate Overflow
7
Yes Hard or Soft
Fault – Over/Under Voltage
8
No
Auto
Fault – FP1 & FP2 Sensor Error
11
Yes Hard or Soft
NOTE: All codes >11 use long flash for tens digit and short flash for the ones digit. 20, 30, 40, 50, etc. are skipped.
Aurora Interface and Diagnostics (AID) Tool
The Aurora Interface and Diagnostics (AID) Tool is a device that is a member
of the Aurora network. The AID Tool is used to troubleshoot equipment which
uses the Aurora control via Modbus RTU communication. The AID Tool provides
diagnostics, fault management, ECM setup, and system configuration
capabilities to the Aurora family of controls. An AID Tool is recommended,
although not required, for ECM airflow settings. The AID Tool simply plugs
into the exterior of the cabinet in the AID Tool port.
ABC Control Board Layout
Factory PWM CFM C
CC2 Factory Factory Use
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
G P5 LO HI CCG CC FG F R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1
JW2 Alarm
P2
Field Connections
Off LED1 FP1 15oF/30oF
On 1 LED2
R FP2 15oF/30oF
2Y
Faul t
RV B/O
ACC Dip 4
3 Config 4
LED3
ACC Dip 5
CC Dual/Single
G L Pulse/Continuous
Status
Reheat/Normal
5 6 7 8 SW2
AURORA BASE CONTROLTM
Com1 G
Factory
RS485 Exp
EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7
RS 485
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Field Connections
RS485 NET CC C
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
36
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Controls – Aurora Advanced Control
Aurora Advanced’ Control Features The Aurora
Advanced’ Control system expands on the capability of the Aurora
Base’ Control (ABC) by adding the Aurora Expansion Board (AXB). All of the preceding features of the Aurora
Base’ Control are included. The following
control description is of the additional features and capability of the Aurora
advanced control.
It is highly recommended the installing/servicing contractor obtain an Aurora
Interface and Diagnostic Tool (AID) and specialized training before attempting
to install or service an Aurora `Advanced’ control system.
The additional AXB features include the following:
AXB DIP Switch
DIP 1 – ID: This is the AXB ModBus ID and should always read On.
DIP 2 & 3 – Future Use DIP 4 & 5 – Accessory Relay2: A second, DIP
configurable,
accessory relay is provided that can be cycled with the compressor 1 or 2 ,
blower, or the Dehumidifier (DH) input. This is to complement the Accessory 1
Relay on the ABC board.
Position DIP 4
1
ON
2
OFF
3
ON
4
OFF
DIP 5 ON ON
OFF OFF
Description Cycles with Fan or ECM (or G) Cycles with CC1 first stage of
compressor
or compressor spd 6 Cycles with CC2 second stage of compressor or compressor
spd 7-12 Cycles with DH input from ABC board
Advanced Hot Water Generator Control (Domestic Hot Water Option)
In lieu of the `Base Hot Water Generator Control’, the Advanced features an
AID Tool selectable temperature limit and microprocessor control of the
process. This will maximize hot water generation and prevent undesirable
energy use. An alert will occur when the hot water input temperature is at or
above setpoint (100°F – 140°F) for 30 continuous seconds (130°F is the default
setting). This alert will appear as an E15 on the AID Tool and the hot water
pump de-energizes. Hot water pump operations resume on the next compressor
cycle or after 15 minutes of continuous compressor operation during
the current thermostat demand cycle. Since compressor hot gas temperature is
dependent on loop temperature in cooling mode, loop temperatures may be too
low to allow proper heating of water. The control will monitor water and
refrigerant temperatures to determine if conditions are satisfactory for
heating water. LED1 (red LED) will flash code 15 when the DHW limit is reached
and when conditions are not favorable for water heating. Error code 15 will
also be displayed on the AID Tool in the fault screen. This flash code is a
noncritical alert and does not necessarily indicate a problem.
Compressor Monitoring The AXB includes two current transducers to monitor the
compressor current and starting characteristics. Open circuits or welded
contactor faults will be detected. A fault will produce an E10 code.
IntelliZone2 Zoning Compatibility (Optional IntelliZone2 Zoning) A dedicated
input to connect and communicate with the IntelliZone2 (IZ2) zoning system is
provided on P7. The is a dedicated communication port using a proprietary
ModBus protocol. An AXB can be added to other selected ABC-only systems as
well. Then an advanced communicating IntelliZone2 zoning system can be added
to ABC-only systems. Consult the IntelliZone2 literature for more information.
Variable Speed Pump This input and output are provided to drive and monitor a
variable speed pump. The VS pump output is a PWM signal to drive the variable
speed pump. The minimum and maximum level are set using the AID Tool. 75% and
100% are the default settings respectively. The VS data input allows a
separate PWM signal to return from the pump giving fault and performance
information. Fault received from the variable speed pump will be displayed as
E16.
Modulating Water Valve This output is provided to drive a modulating water
valve. Through advanced design the 0-10VDC valve can be driven directly from
the VS pump output. The minimum and maximum level are set in the same way as
the VS pump using the AID Tool. 75% and 100% are the default settings
respectively.
Loop Pump Linking This input and output are provided so that two units can be
linked together with a common flow center. When either unit has a call for
loop pump, both unit’s loop pump relays and variable speed pumps are
energized. The flow center then can simply be wired to either unit. The output
from one unit should be routed to the input of the other. If daisy chained up
to 16 heat pumps can be wired and linked together in this fashion.
37
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Controls – Aurora Advanced Control cont.
Advanced Communication Ports Communication ports P6 and P8 will provide future
expansion via dedicated protocols. These are for future use.
Smart Grid-On Peak (SG) Input The ‘On Peak’ input was designed to allow
utilities to utilize simple radio controlled switches to control the On
Electric Peak behavior of the 5 and 7 Series Geothermal Heat Pumps. With a
closed contact signal, this input will limit the operation and thus the power
consumption of the unit by one of the below selections. The AID Tool will
allow configuration of this input for the action of:
· No Action · Disable compressor operation until removed · Go to On Peak
thermostat settings until removed
[Requires Com T-Stat] (Future Release) · Compressor limited to 50% or low cap
until removed
[dual capacity or variable speed only] (Future Release) · Disable compressor
operation for 1/2 hr (can be
removed immediately) (Future Release)
Then Flash Code 7 on the Green LED for the ‘On Peak’ mode. And On Peak will
display on communicating thermostats.
Home Automation 1 and 2 Inputs The Home automation inputs are simple closed
contact inputs that will trigger an AID Tool and thermostat alert for the
homeowner. These would require optional sensors and or equipment for
connection to the AXB board. With two inputs two different sensors can be
selected. The selected text will then be displayed on the AID Tool and
communicating thermostats. These events will NOT alter functionality or
operation of the heat pump/accessories and is for homeowner/service
notification only.
Home Automation 1 – E23 HA1 With a closed dry contact signal, this input will
cause an alarm and Alert Code 23 to indicate on the stat or flash on ABC. The
AID Tool will allow configuration of this input between the following
selections:
· No Action · Home Automation Fault [no lockout info only] – Output from home
automation system · Security Alarm [no lockout info only] – Output from home
security · Sump Alarm Fault [no lockout info only] – Switch output from sump
sensor · Smoke/CO Alarm Fault [no lockout info only] – Switch output from
Smoke/CO sensor · Dirty Filter Alarm [no lockout info only] – Output from
dirty filter sensor
Home Automation 2 E24 HA2 With a closed dry contact signal, this input will
cause an alarm and Alert Code 24 to indicate on the stat or flash on ABC. The
AID Tool will allow configuration of this input between the following
selections:
· No Action · Home Automation Fault [no lockout info only] – Output from home
automation system · Security Alarm [no lockout info only] – Output from home
security · Sump Alarm Fault [no lockout info only] – Switch output from sump
sensor · Smoke/CO Alarm Fault [no lockout info only] – Switch output from
Smoke/CO sensor · Dirty Filter Alarm [no lockout info only] – Output from
dirty filter sensor
Monitoring Sensor Kits
Energy Monitoring (Standard Sensor Kit on `Advanced’ models) The Energy
Monitoring Kit includes two current transducers (blower and electric heat)
added to the existing two compressor sensors so that the complete power usage
of the heat pump can be measured. The AID Tool provides configuration detail
for the type of blower motor and a line voltage calibration procedure to
improve the accuracy. This information can be displayed on the AID Tool or
selected communicating thermostats. The TPCM32U03/04 will display
instantaneous energy use while the color touchscreen TPCC32U01 will in
addition display a 13 month history in graph form.
Refrigerant Monitoring (optional sensor kit) The optional Refrigerant
Monitoring Kit includes two pressure transducers, and three temperature
sensors, heating liquid line, suction temperature and existing cooling liquid
line (FP1). These sensors allow the measurement of discharge and suction
pressures, suction and liquid line temperatures as well as superheat and
subcooling. This information will only be displayed on the AID Tool.
Performance Monitoring (optional sensor kit) The optional Performance
Monitoring Kit includes three temperature sensors, entering and leaving water,
leaving air temperature and a water flow rate sensor. With this kit heat of
extraction and rejection will be calculated. This requires configuration using
the AID Tool for selection of water or antifreeze.
38
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Controls – Aurora Advanced Control cont.
Special Modes and Applications
5-Speed ECM Blower Motor Normally the 5-Speed ECM motor can be driven off of
thermostat signals and the ABC connector P9. Communicating thermostats,
however present a special problem in this application since they operate
without 24 VAC thermostat signals. The ABC board is wired to operate these
systems from the alternate relay output signals CC1, CC2, Fan, and EH1 and
should be wired for this.
Communicating Digital Thermostats The Aurora controls system also features
either monochromatic or color touch screen graphic display thermostats for
user interface. These displays not only feature easy to use graphical
interface but display alerts and faults in plain English. Many of the features
discussed here may not be applicable without these thermostats.
Dehumidification Passive In passive dehumidification mode, the airflow is
reduced by 15% from the heating airflow setting. If cooling airflow is set to
+5, -5 or -10% of heating airflow it will automatically be set to -15% of
heating airflow whenever the dehumidification call is present in the
communicating stat or from the thermostat input DH. If the airflow for cooling
is already set to -15% no airflow change will be noticed from normal cooling.
Dehumidification mode will be shown on the ABC and the communicating
thermostats.
Aurora `Advanced’ Control LED Displays
These three LEDs display the status, configuration, and fault codes for the
control. These can also be read in plain English via the Aurora AID Tool.
Status LED (LED3, Green)
Description of Operation Normal Mode Control is Non-functional Test Mode
Lockout Active Dehumidification Mode Load Shed Emergency Shutdown On Peak Mode
(Future Use) (Future Use)
Fault LED, Green ON OFF
Slow Flash Fast Flash Flash Code 2 Flash Code 5 Flash Code 6 Flash Code 7
Flash Code 8 Flach Code 9
Configuration LED (LED2, Yellow)
Description of Operation No Software Overwritten DIP Switch Overwritten ECM Configuration Mode Reset Configuration Mode
Configuration LED, Yellow ECM Setting Slow Flash Fast Flash OFF
Fault LED (LED1, Red)
Red Fault LED
Normal – No Faults Fault-Input Fault-High Pressure
LED Flash Code * Off 1 2
Lockout
No Yes
Reset/ Remove
Auto Hard or Soft
Fault Condition Summary
Tstat input error. Autoreset upon condition removal. HP switch has tripped
(>600 psi)
ABC Basic Faults
Fault-Low Pressure
3
Yes Hard or Soft Low Pressure Switch has tripped (<40 psi for 30 continuous sec.)
Fault-Freeze Detection FP2
4
Yes Hard or Soft Freeze protection sensor has tripped (<15 or 30 degF for 30 continuous sec.)
Fault-Freeze Detection FP1
5
Yes Hard or Soft Freeze protection sensor has tripped (<15 or 30 degF for 30 continuous sec.)
Fault-Condensate Overflow
7
Yes Hard or Soft Condensate switch has shown continuity for 30 continuous sec.
Fault-Over/Under Voltage
8
No
Auto
Instantaneous voltage is out of range. **Controls shut down until resolved.
Fault-FP1 Snsr Error
11
Yes Hard or Soft If FP1 Sensor Error
Fault-Compressor Monitor
10
Yes Hard or Soft Open Crkt, Run, Start or welded cont
ABC & AXB Advanced Faults
Non-CriticAXBSnsrErr
13
No
Auto
Any Other Sensor Error
CriticAXBSnsrErr
14
Yes Hard or Soft Sensor Error for EEV or HW
Alert-HotWtr
15
No
Auto
HW over limit or logic lockout. HW pump deactivated.
Fault-VarSpdPump
16
No
Auto
Alert is read from PWM feedback.
Not Used
17
No
Auto
IZ2 Com Fault. Autoreset upon condition removal.
Non-CritComErr
18
No
Auto
Any non-critical com error
Fault-CritComErr
19
No
Auto
Any critical com error. Auto reset upon condition removal
Alarm – Low Loop Pressure
21
No
Auto
Loop pressure is below 3 psi for more than 3 minutes
Alarm – Home Automation 1
23
No
Auto
Closed contact input is present on Dig 2 input – Text is configurable
Alarm – Home Automation 2
24
No
Auto
Closed contact input is present on Dig 3 input – Text is configurable
NOTES: *All codes >11 use long flash for tens digit and short flash for the ones digit. 20, 30, 40, 50 etc. are skipped! Alert’ is a noncritical sensor or function that has failed. Normal operation of the heat pump is maintained but service is desired at some point.
39
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Controls – UPC DDC Control (optional)
Aurora UPC Controller
ZS Series Sensors
The Aurora Unitary Protocol Converter (UPC) is designed to add-on to any
Aurora based heat pump control. The Aurora Unitary Protocol Convertor (UPC) is
designed to allow water source heat pumps to be integrated into Building
Automation Systems (BAS) with ease. The Aurora UPC is an integrated solution
and communicates directly with the Aurora Heat Pump Controls and allows
access/control of a variety of internal Aurora heat pump operations such as
sensors, relay operation, faults and other information. In turn, the UPC then
converts internal Aurora Modbus protocol to BACnet MS/TP, LON, or N2 protocols
and communicates to the BAS system. This provides the great benefit of
complete control integration and a myriad of information available to the BAS
from the heat pump control. Plus it also allows individual unit configuration
such as ECM fan speeds or freeze protection setting directly over the BAS
without the need for access to the actual heat pump. The Aurora UPC is
programmed using the powerful Eikon object oriented.
The Aurora UPC is implemented with the Aurora Base Controller (ABC) heat pump
control into our latest water source heat pumps. This will allow for a BAS to
integrate
and communicate to the heat pump thru a choice of 3 different communication
protocols. The Aurora UPC has the ability to communicate BACnet MS/TP, N2
open, or LonWorks (requires LON Plugin card). This flexibility is possible due
to the onboard dipswitches which allow for the desired protocol and baud rate
to be selected in the field. All zone temperatures and zone sensors are
connected to the UPC on an RNet bus, simplifying hook up at the unit. RNet
sensors can include a combination of zone temperature and humidity, CO2, and
VOC sensors. The UPC includes built-in support for a custom configurable
keypad/display unit – BACview6 (4-line by 40 character per line display) or
BACview5 (2-line by 16 character per line display). Up to 2 Keypad/display
units can be mounted remotely for configuration and troubleshooting.
There are an extensive number of points that the UPC has available over the
network for integration into the BAS. Control programmers need to carefully
determine which points they want to add into the BAS database. A list of the
BACnet points, N2 points, and LON SNVTs are available along with their
individual point descriptions by contacting the Commercial Solutions Group at
1-877-677-4420.
40
VERSATEC 500 0.75-6 TON INSTALLATION MANUAL – Formerly Envision2 Compact
Controls – UPC DDC Control (optional) cont.
BAS
N2 BACnet
LonWorks
Modbus Rnet
Aurora UPC Features
· Rugged enclosure made of GE C2950 Cycoloy plastic · Built-in surge transient
protection circuitry · Operating range of -20° to 140°F; 10 to 95% relative
hu-
midity, non-condensing · Onboard CR123A battery has a life of 10 years with
720
hours of cumulative power outage · Multi-Protocol field selectable
communication port
that supports: · EIA-485 BACnet MS/TP @ 9600, 19.2k, 38.4k, 76.8k baud ·
Metasys N2 Open · LonWorks TP/FT-10 (Requires optional LON plug-in
communication card) · Status of all unit operating conditions and fault
lockouts · Visual LED’s for status of power, network communication,
processor operation, and errors · Provides gateway into Aurora heat pump
controls for
unsurpassed control flexibility · Network point for commanding unit into load
shed · Network point for commanding unit into
emergency shutdown · Network points to assist in fan speed selection · Network
points for freeze protection settings · Heating and cooling control from a rem
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>