WaterFurnace VERSATEC 500 7-30 Water Source Heat Pump Instruction Manual
- June 9, 2024
- WaterFurnace
Table of Contents
VERSATEC 500 7-30 Water Source Heat Pump
Versatec 500 WSHP 7-30 Ton Installation Manual
Formerly Versatec XL Commercial Water Source/Geothermal Heat Pump
· R-410A Refrigerant · 7-30 Tons
Installation Information Water Piping Connections Electrical Startup
Procedures Troubleshooting Preventive Maintenance
IM2770AU 03/22
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Electrical
Availability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General
Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 5 Dimensional Data . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . 6 Installation Notes . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 12 Duct System, Water Piping . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 15 Condensate Drain . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 16 Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 17 System Cleaning and Flushing . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Open Loop
Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 19 Freeze Detection . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 19 Electrical Connections . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .20 Electrical Data . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 21 Blower Performance Data. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22 Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Controls – Aurora Controls . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Unit Startup .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .56 Operating Limits .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 57 Operating Parameters . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 57 Pressure Drop . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 58 Reference Calculations and Legend . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . .59 Refrigerant Circuit Guideline . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 61 Troubleshooting . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 62 Startup/Troubleshooting Form . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .63 Preventive Maintenance . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.65 Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65 Revision
Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Model Nomenclature
1-2 3 4-6 7 UD V 096 T
8 9 10 11 12 13 14 15 16 17 18 19 20 21 22-23 24 L 3 N 5 0 D A N A N 0 A 1 N SS *
Model Type Versatec XL Series
Cabinet Configuration V Vertical (084-360) H Horizontal (084-180) T
Vertical Take-a-Part (240-360)
Unit Capacity 084, 096, 120, 150, 180. 240, 300, 360
Discharge Configuration T Top/Side (Vertical) E End/Side (Horizontal)
Return Air Configuration L Left R Right
Voltage 3 208-230/60/3 4 460/60/3 5 575/60/31
Refrigeration Option N Standard, None G Hot Gas Bypass M Modulating Hot
Gas Reheat²³ P Modulating Hot Gas Reheat with Hot Gas Bypass²³
Blower Option 5 Variable Speed ECM- Backward Inclined, Standard
Future Option 0 Future
Water Coil Option C Copper, Uninsulated D Insulated Copper
Sound Kit Option A None B Sound Kit
Vintage * Factory Use
Non-Standard Options SS Standard
Economizer Option N None W Waterside Economizer²
Air Coil Option 1 All Aluminum, Uncoated 2 All Aluminum, AlumiSeal
Future Option N Standard
Cabinet Option 2 Unpainted Cabinet, 4-Sided Rack (Horizontal) 3 Painted
Cabinet, 4-Sided Rack (Vertical)
Electrical Option N Standard D Non-Fused Disconnect
Control Option A Standard, None C AuroraTM Advanced D AuroraTM Premium E
AuroraTM with BACnet G AuroraTM Advanced with BACnet H AuroraTM Premium
with BACnet
Water Control Option N Standard, None V 2-Way Valve M- Head Pressure4
Note: 1- 575V option includes factory installed step down transformer on plenum fan. 2- Requires Advanced or Premium Controls. 3- Not available on UDH180 4- Head Pressure Control requires Premium Controls and Modulating Hot Gas Reheat.
Electrical Availability
Voltage
208-230/60/3 460/60/3 575/60/3
Voltage
208-230/60/3 460/60/3 575/60/3
– Available
Dual Capacity Compressor
084
096
120
Two Compressor
150
180
240
300
360
3/30/21
4
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
General Installation Information
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn
off main power switches to the indoor unit. If applicable, turn off the
accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be
hazardous due to system pressure and electrical components. Only trained and
qualified service personnel should install, repair or service heating and air
conditioning equipment. Untrained personnel can perform the basic maintenance
functions of cleaning coils and cleaning and replacing filters. All other
operations should be performed by trained service personnel. When working on
heating and air conditioning equipment, observe precautions in the literature,
tags and labels attached to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching
cloth for brazing operations and have a fire extinguisher available.
Unit Location Locate the unit in an indoor area that allows for easy removal
of the filter and access panels. Location should have enough space for service
personnel to perform maintenance or repair. Provide sufficient room to make
water, electrical and duct connection(s). If the unit is located in a confined
space, such as a closet, provisions must be made for return air to freely
enter the space by means of a louvered door, etc. Any access panel screws that
would be difficult to remove after the unit is installed should be removed
prior to setting the unit. On horizontal units, allow adequate room below the
unit for a condensate drain trap and do not locate the unit above supply
piping. Care should be taken when units are located in unconditioned spaces to
prevent damage from frozen water lines and excessive heat that could damage
electrical components.
WARNING: To avoid equipment damage and possible voiding of warranty, be sure
that properly sized strainers are installed upstream of both brazed plate heat
exchangers to protect them against particles in the fluid.
Moving and Storage
Move units in the normal “up” orientation. Horizontal units may be moved and
stored per the information on the packaging. Do not stack more than three
units in total height. When the equipment is received, all items should be
carefully checked against the bill of lading to be sure all crates and cartons
have been received. Examine units for shipping damage, removing the units from
the packaging if necessary. Units in question should also be internally
inspected. If any damage is noted, the carrier should make the proper notation
on the delivery receipt, acknowledging the damage.
Installing Vertical Units
Prior to setting the unit in place, remove and discard the compressor hold
down shipping bolt located at the front of the compressor mounting bracket.
Vertical units are available in left or right air return configurations. Top
flow vertical units should be mounted level on a vibration absorbing pad
slightly larger than the base to provide isolation between the unit and the
floor. It is not necessary to anchor the unit to the floor (see figure below).
Vertical Unit Mounting
2 in. PEX Foam
5
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Dimensional Data
LEFT RETURN SHOWN
“N”
1.0
“J”
“M”
“B”
“H”
“L”
TOP DISCHARGE FIELD REMOVABLE
BLOWER PANEL INSERT
2.1
“G”
1.00
“L”
“M”
2.3
BLOWER ACCESS PANEL “K”
“C”
DRAIN CONNECTION
1.8 (4)
“P” BOTH SIDES
BLOWER ACCESS PANEL
“N”
SIDE DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT
“F” “E” “D”
CONTROL BOX ACCESS DOOR
“R” BOTH SIDES
“A”
Vertical Dimensional Data
Overall Cabinet
Water Connections
Return Connection*
Vertical Models A
Width
084-096 in. 34.0 cm. 86.4
120 in. 34.0 cm. 86.4
150-180 in. 34.0 cm. 86.4
B
Depth
36.3 92.2 36.3 92.2 46.3 117.5
12 3
C DE
F
Loop
Cond- Water Height In Out
ensate FPT
72.5 8.1 15.1 22.1 1 1/4″
184.2 20.6 38.4 56.1 31.8 mm
72.5 8.1 15.1 22.1 2″
184.2 20.6 38.4 56.1 50.8 mm
72.5 8.1 15.1 22.1 2″
184.2 20.6 38.4 56.1 50.8 mm
using delux e filter rack
G
H
J
K
Filter From Return Return
Rack Edge Depth Height
3.1
3.2 29.9 37.8
7.9
8.1 75.9 96.0
3.1
3.2 29.9 37.8
7.9
8.1 75.9 96.0
3.1
2.2 39.9 37.8
7.9
5.6 101.3 96.0
*Dimensions for return connnections are for the deluxe filter rack that is suitable for ducted return applications
Discharge Connection Electrical Connections
L
M
N
P
R
From Supply Supply From H eight
Edge Width Height Edge
4.1 28.0 16.0 3.9 27.4
10.4 71.1 40.6 9.9 69.6
4.1 28.0 16.0 3.9 27.4
10.4 71.1 40.6 9.9 69.6
4.1 38.0 16.0 3.9 27.4
10.4 96.5 40.6 9.9 69.6
6
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Dimensional Data cont.
LEFT RETURN SHOWN
1.4 “F”
DRAIN CONNECTION “J”
“N”
2.1
1.7
“K”
“G”
“L”
“H”
END DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES
SIDE DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES
1.7
“J”
1.0
DUCT FLANGE
“H”
“K”
AIR COIL “M”
“B”
“V”
BLOWER ACCESS
PANEL
“A”
“U”
40.00
“P” “R”
“P”
“T”
“R”
1 5/8″ UNISTRUT
42″ CUT LENGTH
3 REQUIRED NOT SUPPLIED
BY WFI
1.8 (3)
CONTROL BOX
“C”
ACCESS DOOR
“E”
“D”
42.00
Horizontal Dimensional Data
Overall Cabinet
Water Connections
Discharge Connection
Horizontal
12 5
Models
A
B
C DE F
Loop
G
H
J
K
Width Depth Height In Out Cond- Water Filter Rack From Supply Supply ensate FPT Width Edge Height Width
084-096 in. 34.0 89.0 29.9 8.1 15.1 3.2 1 1/4″
3.1
5.0 24.0 24.0
cm. 86.4 226.1 75.9 20.6 38.4 8.1 31.8 mm 7.9
12.7 61.0 61.0
120 in. 34.0 89.0 29.9 8.1 15.1 3.2
2″
3.1
5.0 24.0 24.0
cm. 86.4 226.1 75.9 20.6 38.4 8.1 50.8 mm 7.9
12.7 61.0 61.0
150-180 in. 34.0 110.0 29.9 8.1 15.1 3.2
2″
3.1
5.0 24.0 24.0
cm. 86.4 279.4 75.9 20.6 38.4 8.1 50.8 mm 7.9
12.7 61.0 61.0
*Dimensions for return connnections are for the deluxe filter rack that is suitable for ducted return applications
Return Connection*
using delux e filter rack
L
M
N
From Return Return
Edge Depth Height 4.3 47.6 23.5
10.9 120.9 59.7
4.3 47.6 23.5
10.9 120.9 59.7
4.3 65.6 23.5
10.9 166.6 59.7
Electrical Connections
P
R
From Height Edge 3.9 25.9
9.9 65.8
3.9 25.9
9.9 65.8
3.9 25.9
9.8 65.8
Unistrut Hanging
T
U
V
From Unistrut/ Unistrut/
Edge Unistrut Unistrut
1.7 24.6 61.0
4.3 62.5 154.9
1.7 24.6 61.0
4.3 62.5 154.9
1.7 35.1 71.5
4.3 89.2 181.6
7
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Dimensional Data cont.
16.88 3.40
1.50
16.08
POWER SUPPLY LEFT RETURN
8.10
240-360 RIGHT RETURN
SHOWN
48.08
71.90
20.00 3.40
POWER SUPPLY RIGHT RETURN
7.00 34.00
8.10 REF
36.90
1.00
1.70
TOP DISCHARGE FIELD REMOVABLE
BLOWER PANEL INSERT
88.00
CONTROL BOX ACCESS DOOR
46.00 80.00
7/8″ O.D. DRAIN CONNECTION
WATER OUT 2″ FPT
WATER IN 2″ FPT
31.30 7.00
8.00
6.60
20.80
1.90 (3)
1.80
32.62
8
22.75 REF
32.62
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Dimensional Data cont.
UDV084-180 TOP FLOW ECONOMIZER OPTION LR
“N”
1.0
“J” “M” “B”
“H”
“L”
4.5
TOP DISCHARGE
FIELD REMOVABLE
BLOWER PANEL
INSERT
“G”
2.1
“A”
1.00
“L”
“M”
2.3
“K”
DRAIN CONNECTION
“E” “D”
BLOWER ACCESS PANEL
1.8 CONTROL BOX ACCESS DOOR
“F”
TOP DISCHARGE FIELD REMOVABLE
BLOWER PANEL INSERT
“C”
“P”
BOTH
SIDES
“R” BOTH SIDES
“N”
BLOWER ACCESS PANEL
4.1
34.0
VERSATEC XL – Vertical Dimensional Data
Overall Cabinet
Water Connections
Vertical Models A
Width
084-096 in. 41.2 cm. 104.6
120 in. 41.2 cm. 104.6
150-180 in. 41.2 cm. 104.6
B
Depth
36.3 92.2 36.3 92.2 46.3 117.5
12 3
C DE
F
Loop
Cond- Water Height In Out
ensate FPT
72.5 13.9 23.5 22.1 1 1/4″
184.2 35.3 59.7 56.1 31.8 mm
72.5 13.9 23.5 22.1 2″
184.2 35.3 59.7 56.1 50.8 mm
72.5 14.7 24.2 22.1 2″
184.2 37.3 61.5 56.1 50.8 mm
Return Connection*
using delux e filter rack
G
H
J
K
Filter From Return Return
Rack Edge Depth Height
3.1
3.2 29.9 37.8
7.9
8.1 75.9 96.0
3.1
3.2 29.9 37.8
7.9
8.1 75.9 96.0
3.1
2.2 39.9 37.8
7.9
5.6 101.3 96.0
Discharge Connection Electrical Connections
L
M
N
P
R
From Supply Supply From H eight
Edge Width Height Edge
4.1 28.0 16.0 3.9 27.4
10.4 71.1 40.6 9.9 69.6
4.1 28.0 16.0 3.9 27.4
10.4 71.1 40.6 9.9 69.6
4.1 38.0 16.0 3.9 27.4
10.4 96.5 40.6 9.9 69.6
9
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Dimensional Data cont.
UDV084-180 TOP FLOW ECONOMIZER OPTION RR
1.0
“N”
2.2
“B” “M”
“J”
“M”
BLOWER ACCESS PANEL
“L” 2.3
“N”
“L” 1.0
TOP DISCHARGE FIELD REMOVABLE
BLOWER PANEL INSERT
“A”
BLOWER ACCESS PANEL
TOP DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT “P” BOTH SIDES
“R” BOTH SIDES
“C”
1.8
CONTROL BOX ACCESS DOOR
“F”
8.1 “G”
2.1
“K”
DRAIN CONNECTION
“E” “D”
VERSATEC XL – Vertical Dimensional Data
34.0 4.2
Overall Cabinet
Water Connections
Return Connection*
Vertical
12 3
using delux e filter rack
Models
A
B
C DE F
Loop
G
H
J
K
Cond- Water Filter Width Depth Height In Out
ensate FPT Rack
From Return Return Edge Depth Height
084-096 in. 41.2 36.3 72.5 16.9 23.5 22.1 1 1/4″ 3.1
3.2 29.9 37.8
cm. 104.6 92.2 184.2 42.9 59.7 56.1 31.8 mm 7.9
8.1 75.9 96.0
120 in. 41.2 36.3 72.5 16.9 23.5 22.1 2″
3.1
3.2 29.9 37.8
cm. 104.6 92.2 184.2 42.9 59.7 56.1 50.8 mm 7.9
8.1 75.9 96.0
150-180 in. 41.2 46.3 72.5 17.7 24.2 22.1 2″
3.1
2.2 39.9 37.8
cm. 104.6 117.5 184.2 45.0 61.5 56.1 50.8 mm 7.9
5.6 101.3 96.0
Discharge Connection Electrical Connections
L
M
N
P
R
From Supply Supply From H eight
Edge Width Height Edge
4.1 28.0 16.0 3.9 27.4
10.4 71.1 40.6 9.9 69.6
4.1 28.0 16.0 3.9 27.4
10.4 71.1 40.6 9.9 69.6
4.1 38.0 16.0 3.9 27.4
10.4 96.5 40.6 9.9 69.6
10
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Dimensional Data cont.
LEFT RETURN SHOWN
2.1
1.4
“F”
DRAIN CONNECTIONS “J”
“N”
2.1 1.7
“K”
“G”
“H”
END DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES SIDE DISCHARGE
FIELD REMOVABLE BRACKETS AND DUCT FLANGES
“J”
1.7 1.0 DUCT FLANGE
AIR COIL
“M”
“V”
“B” “A”
50.00 (2)
BLOWER ACCESS
PANEL
22.8 “R”
20.4 “P”
1.8 “E”
“D”
40.00
“U”
“P”
“T”
“R”
CONTROL BOX
“C”
ACCESS DOOR
VERSATEC XL – Horizontal Dimensional Data
Overall Cabinet
Water Connections
Discharge Connection
Horizontal
12 5
Models
A
B
C DE F
Loop
G
H
J
K
Width Depth Height In Out Cond- Water Filter Rack From Supply Supply ensate FPT Width Edge Height Width
084-096 in. 41.1 89.0 29.9 6.9 25.1 3.2 1 1/4″
3.1
5.0 24.0 24.0
cm. 104.4 226.1 75.9 17.5 63.8 8.1 31.8 mm 7.9
12.7 61.0 61.0
120 in. 41.1 89.0 29.9 6.9 25.1 3.2
2″
3.1
5.0 24.0 24.0
cm. 104.4 226.1 75.9 17.5 63.8 8.1 50.8 mm 7.9
12.7 61.0 61.0
150-180 in. 41.1 110.0 29.9 6.9 25.1 3.2
2″
3.1
5.0 24.0 24.0
cm. 104.4 279.4 75.9 17.5 63.8 8.1 50.8 mm 7.9
12.7 61.0 61.0
*Dimensions for return connnections are for the deluxe filter rack that is suitable for ducted return applications
Return Connection*
using delux e filter rack
L
M
N
From Return Return
Edge Depth Height 4.3 47.6 23.5
10.9 120.9 59.7
4.3 47.6 23.5
10.9 120.9 59.7
4.3 65.6 23.5
10.9 166.6 59.7
Electrical Connections
P
R
From Height Edge
3.9 25.9
9.9 65.8
3.9 25.9
9.9 65.8
3.9 25.9
9.8 65.8
Unistrut Hanging
T
U
V
From Unistrut/ Unistrut/
Edge Unistrut Unistrut
1.7 24.6 61.0
4.3 62.5 154.9
1.7 24.6 61.0
4.3 62.5 154.9
1.7 35.1 71.5
4.3 89.2 181.6
11
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Dimensional Data cont.
RIGHT RETURN SHOWN
SIDE DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES
“J”
1.7
“H” “J”
1.7
“K”
2.1 1.5
END DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES
“K” “G”
1.0
2.1
“N”
DUCT
FLANGE “H”
BLOWER
ACCESS
“B”
PANEL
50.00 (2) “A”
“V”
“M”
AIR COIL
“P” “R”
40.00
“C”
CONTROL BOX
ACCESS DOOR
“U” 22.9 “P”
“T”
“E” “D”
20.3 “R”
VERSATEC XL – Horizontal Dimensional Data
Overall Cabinet
Water Connections
Discharge Connection
Horizontal
12 5
Models
A
B
C DE F
Loop
G
H
J
K
Width Depth Height In Out Cond- Water Filter Rack From Supply Supply ensate FPT Width Edge Height Width
084-096 in. 41.1 89.0 29.9 6.9 25.1 3.2 1 1/4″
3.1
5.0 24.0 24.0
cm. 104.4 226.1 75.9 17.5 63.8 8.1 31.8 mm 7.9
12.7 61.0 61.0
120 in. 41.1 89.0 29.9 6.9 25.1 3.2
2″
3.1
5.0 24.0 24.0
cm. 104.4 226.1 75.9 17.5 63.8 8.1 50.8 mm 7.9
12.7 61.0 61.0
150-180 in. 41.1 110.0 29.9 6.9 25.1 3.2
2″
3.1
5.0 24.0 24.0
cm. 104.4 279.4 75.9 17.5 63.8 8.1 50.8 mm 7.9
12.7 61.0 61.0
*Dimensions for return connnections are for the deluxe filter rack that is suitable for ducted return applications
Return Connection*
using delux e filter rack
L
M
N
From Return Return
Edge Depth Height 4.3 47.6 23.5
10.9 120.9 59.7
4.3 47.6 23.5
10.9 120.9 59.7
4.3 65.6 23.5
10.9 166.6 59.7
Electrical Connections
P
R
From Height Edge
3.9 25.9
9.9 65.8
3.9 25.9
9.9 65.8
3.9 25.9
9.8 65.8
Unistrut Hanging
T
U
V
From Unistrut/ Unistrut/
Edge Unistrut Unistrut
1.7 24.6 61.0
4.3 62.5 154.9
1.7 24.6 61.0
4.3 62.5 154.9
1.7 35.1 71.5
4.3 89.2 181.6
12
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Dimensional Data cont.
16.88 3.40
1.50
16.08
POWER SUPPLY LEFT RETURN
8.10
UDV240-360 RIGHT RETURN
SHOWN
48.08
71.90
20.00 3.40
POWER SUPPLY RIGHT RETURN
7.00 34.00
44.88 1.00
8.10 REF
TOP DISCHARGE FIELD REMOVABLE
BLOWER PANEL INSERT
1.70
88.00
CONTROL BOX ACCESS DOOR
46.00 80.00
WATER OUT 2″ FPT
WATER IN 2″ FPT
6.60
20.80
31.30 7.00
8.00 1.90 (3)
1.80 32.62
22.75 REF
32.62
13
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Installation Notes
Typical Unit Installation
Unit Location
Locate the unit in an indoor area that allows for easy removal of the filter
and access panels. Location should have enough space for service personnel to
perform maintenance or repair. Provide sufficient room to make water,
electrical and duct connection(s). If the unit is located in a confined space,
such as a closet, provisions must be made for return air to freely enter the
space by means of a louvered door, etc. Any access panel screws that would be
difficult to remove after the unit is installed should be removed prior to
setting the unit. On horizontal units, allow adequate room below the unit for
a condensate drain trap and do not locate the unit above supply piping. Care
should be taken when units are located in unconditioned spaces to prevent
damage from frozen water lines and excessive heat that could damage electrical
components.
Water Piping
Piping is usually design as `reverse return’ to equalize flow paths through
each unit. A short flexible pressure rated hose is used to make connection to
the fixed building
piping system. This hose is typically stainless steel braid and includes a
swivel fitting on one end for easy removal and is flexible to help isolate the
unit for quieter operation. Isolation valves for servicing, y-strainers for
filtering and memory-stop flow valve or a balancing valve can be provided for
consistent water flow through the unit.
All unit source water connections are fittings that accept a male pipe thread
(MPT). Insert the connectors by hand, then tighten the fitting with a wrench
to provide a leakproof joint. The open and closed loop piping system should
include pressure/temperature ports for serviceability. The proper water flow
must be provided to each unit whenever the unit operates. To assure proper
flow, use pressure/ temperature ports to determine the flow rate. These ports
should be located at the supply and return water connections on the unit. The
proper flow rate cannot be accurately set without measuring the water pressure
drop through the refrigerant-to-water heat exchanger. Never use flexible hoses
smaller than the inside diameter of the water connection at the unit. Limit
hose length to 10 feet per connection. Check carefully for water leaks.
90 deg elbow with vanes on supply
Sealed low velocity ductwork
Acoustic lining to elbow
Canvas connector
Vibration absorbing pad
Flexible water and electrical connections
14
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Installation Notes cont.
Installing Horizontal Units Remove and discard the compressor hold down
shipping bolt located at the front of the compressor mounting bracket prior to
setting the unit in place. Horizontal units are available with side or end
discharge.
NOTE: Left (Right) Return Side Discharge can be converted to Left (Right)
Return End Discharge or vice versa, without additional custom sheet metal
parts. Horizontal units are normally suspended from a ceiling by six 1/2 in.
diameter threaded rods. The rods are usually attached to the unit by hanger
bracket kits furnished with each unit.
Lay out and install the threaded rods and 1 5/8″ strut
channel as shown in the Horizontal Dimensional Data. The unit should be
pitched approximately 1/4 in. toward the drain in both directions to
facilitate the removal of condensate.
Some applications require the installation of horizontal units on an attic
floor. In this case, the unit should be set in a full size secondary drain pan
on top of a vibration absorbing pad. The secondary drain pan prevents possible
condensate overflow or water leakage damage to the ceiling. The secondary
drain pan is usually placed on a plywood base isolated from the ceiling joists
by additional layers of vibration absorbing material.
CAUTION: Do not use rods smaller than 1/2 in. diameter since they may not be
strong enough to support the unit. The rods must be securely anchored to the
ceiling.
Insulated first 4″ of supply plenum & provide one 90″
elbow
Disconnect Threaded rod
Building water loop Hose Kit
Acoustic lining to elbow
Flexible duct collar Strut Channels
Line Voltage
Optional insultated Return Air
15
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Installation Notes cont.
Acoustical Considerations and Equipment Sound Performance
Sound Performance The unit is third party sound rated in accordance with ARI
260. Please consult the manufacture’sr Sound Performance Data Catalog for
details on the AHRI standard and sound performance data.
Recommendations for Noise Reduction Horizontal Unit Location · Specify
equipment with quietest sound power ratings · Do not locate units above areas
with a required NC 40
or less · Space WSHP at least 10 ft (3m) apart to avoid noise
summing of multiple units in a space. · Maximize the height of the unit above
the
ceiling (horizontal). · Suspend unit with isolation grommets that are
appropriately rated to reduce vibrations (horizontal).
Vertical Unit Location · Specify equipment with quietest sound power ratings ·
Space WSHP at least 10 ft (3m) apart to avoid noise
summing of multiple units in a space. · Acoustic ceiling coatings can greatly
reduce noise levels
in mechanical rooms. · Mount unit on a sound absorbing pad, extruded
polystyrene, rubber or cork pad.
Ductwork · Ensure return air grilles will not allow line of site noise to
transfer to adjacent space. Use a sound barrier or some other material to
isolate the grille from the unit. A supply grille, boot and short piece of
flex duct pointed away from the unit can greatly attenuate equipment noise. ·
Use a canvas isolation duct connector at the supply and return duct connection
of the unit. · Internally line the discharge and return duct within the first
4-8 feet of unit with acoustic insulation. Install an internally lined L’ shaped return duct elbow at return grille. Face the elbow away from adjacent units. · Always install at least one 90° elbow in the discharge duct to eliminate line of sight noise transmission of the blower. · Use turning vanes at all elbows and tees to reduce turbulence. · Limit supply duct velocities to less than 1,000 fpm · Design and install ductwork as stiff as possible · Allow 3 duct diameters both up and down stream of the unit before any fittings or transitions are installed. · Use duct sealant on all duct joints. · Install a short (2-4′) of flex duct on all branch ducts just prior to discharge boot or diffuser to reduce vibration and duct sound prior to delivery in the room. · Locate the branch duct balancing damper as far away from the diffuser as possible. · In ceiling plenum systems, install an internally lined
L’ shaped
return duct elbow at unit. Face the elbow away from adjacent units
(horizontal).
Locate return grille 6 ft [1.8 m] from unit
Sealed low velocity ductwork
Turning vanes at elbows and Tees
Branch damper upstream
90 deg elbow on supply
Acoustic lining to elbow
Locate units over hallways where
possible
Canvas connector
Flex duct at diffuser
2-4 ft. [0.6-1.2 m]
Supply grille with 2-3 ft [0.6-0.9 m] of flex loft
open for return air
Flexible water and electrical connections
16
Insulated Return (optional)
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Duct System
An air outlet collar is provided on vertical top flow units and all horizontal
units to facilitate a duct connection. A flexible connector is recommended for
discharge and return air duct connections on metal duct systems. Uninsulated
duct should be insulated with a minimum of 1-inch duct insulation. Application
of the unit to uninsulated ductwork in an unconditioned space is not
recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure
that it has the capacity to accommodate the air required for the unit
application. If the duct is too small, as in the replacement of heating only
systems, larger ductwork should be installed. All existing ductwork should be
checked for leaks and repaired if necessary.
The duct system should be sized to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed.
Water Piping
The proper water flow must be provided to each unit whenever the unit
operates. To assure proper flow, use pressure/temperature ports to determine
the flow rate. These ports should be located at the supply and return water
connections on the unit. The proper flow rate cannot be accurately set without
measuring the water pressure drop through the refrigerant-to-water heat
exchanger.
All source water connections on commercial units are fittings that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fitting with a wrench to provide a leakproof joint. When connecting to an open loop (groundwater) system, thread any copper MPT fitting into the connector and tighten in the same manner as described above.
17
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Condensate Drain
On vertical units, the internal condensate drain assembly consists of a drain
tube which is connected to the drain pan, a 3/4 in. PVC female adapter and a
flexible connecting hose. The female adapter may exit either the front or the
side of the cabinet. The adapter should be glued to the field-installed PVC
condensate piping. On vertical units, a condensate hose is inside all cabinets
as a trapping loop; therefore, an external trap is not necessary.
On horizontal and bottom flow units, a PVC stub or stainless steel tube is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the field-installed condensate piping.
Horizontal Drain Connection (Composite Drain Pan) Unit Pitch for Drain
3/4″ Tube Stub
3/4″ PVC Coupling
1.5 in. Tube Stub
1.5 in.
Vent (if needed)
3/4″ PVC 1/8 in. per foot
1/2” Pitch Drain
18
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas
with extremely hard water, the owner should be informed that the heat
exchanger may require occasional flushing. Failure to adhere to the guidelines
in the water quality table could result in loss of warranty.
Units with cupronickel heat exchangers are recommended for open loop
applications due to the increased resistance to build-up and corrosion, along
with reduced wear caused by acid cleaning.
Material pH
Scaling
Corrosion
Iron Fouling (Biological Growth)
Acidity/Alkalinity Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Sulfates Chlorine Chlorides Carbon Dioxide Ammonia Ammonia Chloride Ammonia
Nitrate Ammonia Hydroxide Ammonia Sulfate Total Dissolved Solids (TDS) LSI
Index Iron, FE2+ (Ferrous) Bacterial Iron Potential
Iron Oxide
Suspended Solids
Erosion
Threshold Velocity (Fresh Water)
NOTES: Grains = ppm divided by 17 mg/L is equivalent to ppm
Copper 7 – 9
(Total Hardness) less than 350 ppm Less than 0.5 ppm (rotten egg smell appears
at 0.5 ppm) Less than 125 ppm Less than 0.5 ppm Less than 20 ppm Less than 50
ppm Less than 2 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Less
than 0.5 ppm Less than 1000 ppm
+0.5 to -0.5
90/10 Cupronickel 7 – 9
(Total Hardness) less than 350 ppm
10 – 50 ppm
Less than 125 ppm Less than 0.5 ppm Less than 125 ppm
10 – 50 ppm Less than 2 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5
ppm Less than 0.5 ppm 1000 – 1500 ppm
+0.5 to -0.5
< 0.2 ppm
< 0.2 ppm
Less than 1 ppm, above this level deposition will occur
Less than 10 ppm and filtered for max. of 600 micron size
Less than 1 ppm, above this level deposition will occur
Less than 10 ppm and filtered for max. of 600 micron size
< 6 ft/sec
< 6 ft/sec
316 Stainless Steel 7 – 9
(Total Hardness) less than 350 ppm
Less than 1 ppm
Less than 200 ppm Less than 0.5 ppm Less than 300 ppm
10 – 50 ppm Less than 20 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5
ppm Less than 0.5 ppm 1000 – 1500 ppm
+0.5 to -0.5
< 0.2 ppm
Less than 1 ppm, above this level deposition will occur Less than 10 ppm and
filtered for max. of 600 micron size
< 6 ft/sec
2/22/12
19
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
System Cleaning and Flushing
Cleaning and Flushing
Prior to start up of any heat pump, the water circulating system must be
cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the supply and return
runouts must be connected together at each unit location (This will prevent
the introduction of dirt into the unit, see Flushing with Water Shutoff Valve
Equipped Systems illustration). The system should be filled at the water make-
up connection with all air vents open. After filling, vents should be closed.
Flushing with Water Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Rubber Hose
Mains
Runouts Initially Connected Together
The contractor should start the main circulator with the pressure reducing
valve makeup open. Vents should be checked in sequence to bleed off any
trapped air and to verify circulation through all components of the system.
As water circulates through the system, the contractor should check and repair
any leaks found in the piping system. Drain(s) at the lowest point(s) in the
system should be opened for initial flush and blowdown, making sure water fill
valves are set at the same rate. Check the pressure gauge at the pump suction
and manually adjust the makeup water valve to hold the same positive pressure
both before and after opening the drain valves. Flushing should continue for
at least two hours, or longer if required, until drain water is clean and
clear.
The supplemental heater and/or circulator pump, if used, should be shut off.
All drains and vents should be opened to completely drain the system. Short-
circuited supply and return runouts should now be connected to the unit supply
and return connections.
Refill the system with clean water. Test the system water for acidity and
treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The
specified percentage of antifreeze may also be added at this time. Use
commercial grade antifreeze designed for HVAC systems only. EnvironolTM brand
antifreeze is recommended.
Once the system has been filled with clean water and antifreeze (if used),
precautions should be taken to protect the system from dirty water conditions.
Dirty water will result in system-wide degradation of performance, and solids
may clog valves, strainers, flow regulators, etc. Additionally, the heat
exchanger may become clogged which reduces compressor service life and can
cause premature unit failure.
In boiler/tower application, set the loop control panel set points to desired
temperatures. Supply power to all motors and start the circulating pumps.
After full flow has been established through all components including the heat
rejector (regardless of season), air vented and loop temperatures stabilized,
each of the units will be ready for check, test and start up and for air and
water balancing.
Ground Source Loop System Checkout
Once piping is completed between the unit pumping system and ground loop,
final purging and charging of the loop is needed. A high pressure pump is
needed to achieve adequate flow velocity in the loop to purge air and dirt
particles from the loop itself. Antifreeze solution is used in most areas to
prevent freezing. Flush the system adequately to remove as much air as
possible; then pressurize the loop to a static pressure of 40-50 PSI (summer)
or 50-75 PSI (winter). This is normally adequate for good system operation.
Loop static pressure may decrease soon after initial installation, due to pipe
expansion and loop temperature change. Running the unit for at least 30
minutes after the system has been completely purged of air will allow for the
“break-in” period. It may be necessary to adjust static loop pressure (by
adding water) after the unit has run for the first time. Loop static pressure
will also fluctuate with the seasons. Pressures will be higher in the winter
months than during the cooling season. This fluctuation is normal and should
be considered when charging the system initially.
Ensure the pump provides adequate flow through the unit by checking pressure
drop across the heat exchanger. Usually 2.25-3.0 gpm of flow per ton of
cooling capacity is recommended in earth loop applications.
20
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Open Loop Ground Water Systems
Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 1.5-2 gpm of flow per ton of cooling capacity is recommended in open loop applications. Due to only minor differences in flow rate from low to high, only one solenoid valve should be used. The valve should be sized for full flow.
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.
Open System – Groundwater Application
Unit Supply Aux. Heat Supply
Flexible Duct Collar
Rubber Bladder Expansion Tank
Hot Water Generator Connections
Drain
Solenoid Valve
Flow Control Valve
(on outlet of Solenoid Valve)
Water Out Water In
Disconnects (If Applicable)
Shut Off Valves
Shut Off Valves (to isolate solenoid valve while acid flushing)
Compressor Line Voltage
Low Voltage to Thermostat
and Valve
P/T Plugs
Vibration Absorbing Pad
Strainer
Boiler Drains For HX Flushing
Freeze Detection
For Aurora Base Control, set SW2-1, FP1, on the printed circuit board for
applications using a closed loop antifreeze solution to 15°F [-9.4°C]. On
applications using an open loop/ground water system (or closed loop no
antifreeze), set this dip switch to 30°F [-1.1°C], the factory default
setting. (Refer to the Dip Switch Field Selection table).
21
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Electrical Connections
General
Be sure the available power is the same voltage and phase as that shown on the
unit serial plate. Line and low voltage wiring must be done in accordance with
local codes or the National Electric Code, whichever is applicable.
208 Volt Operation
All 208/230 volt units are factory wired for 230 volt operation. For 208 volt
operation, the red and blue transformer wires must be switched on terminal
strip PS.
Aurora Base Control Box
Aurora Advanced Control Board (AXB)
Aurora Base Control Board (ABC)
Transformers
Contactors
EEV/Power Supply UPC DDC Controls
22
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Electrical Data
Electrical Table 7-30 Ton Plenum Fan
Model
Rated Voltage
208-230/60/3
084
460/60/3
Dual Capacity Compressor
575/60/3
208-230/60/3
096
460/60/3
575/60/3
208-230/60/3
120
460/60/3
575/60/3
Tw o Compressors & Plenum Fan
208-230/60/3
150
460/60/3
575/60/3
208-230/60/3
180
460/60/3
575/60/3
Two Compressors & Two Plenum Fans
208-230/60/3
240
460/60/3
575/60/3
208-230/60/3
300
460/60/3
575/60/3
208-230/60/3
360
460/60/3
575/60/3
HACR circuit breaker in USA only
Voltage Min/Max
187/253 414/506 518/632 187/253 414/506 518/632 187/253 414/506 518/632
187/253 414/506 518/632 187/253 414/506 518/632 187/253 414/506 518/632
187/253 414/506 518/632 187/253 414/506 518/632
Compressor (each)
MCC RLA LRA
39.5 15.0 13.1 41.9 18.7 14.0 50.8 23.1 17.3 29.7 15.2 11.6 39.0 20.0 15.0 44.0 23.0 17.6 75.0 29.0 23.0 75.0 38.6 35.0
23.3 8.8 8.4 24.7 11.0 9.0 30.0 13.6 11.1 19.0 9.7 7.4 25.0 12.8 9.6 28.2 14.7 11.3 48.1 18.6 14.7 48.1 24.7 22.4
184.0 84.0 60.0 164.0 94.0 65.0 240.0 130.0 93.7 123.0 62.0 50.0 164.0 100.0 78.0 240.0 130.0 93.7 245.0 125.0 100.0 351.0 197.0 135.0
Blower Motor (each) FLA
5.3 3.0 2.4 7.0 4.0 3.2 7.0 4.0 3.2 9.2 6.8 5.4 9.2 6.8 5.4 9.2 6.8 5.4 9.2
6.8 5.4 9.2 6.8 5.4
Total Unit FLA
28.6 11.8 10.8 31.7 15.0 12.2 37.0 17.6 14.3 47.2 26.2 20.2 59.2 32.4 24.6
74.8 43.0 33.5 114.6 50.8 40.3 114.6 63.0 55.7
Min Circ Amp
34.4 14.0 12.9 37.9 17.8 14.5 44.5 21.0 17.1 52.0 28.6 22.1 65.5 35.6 27.0
81.9 46.7 36.3 126.6 55.5 44.0 126.6 69.2 61.3
Max Fuse/ HACR Breaker
55 20 20 60 25 20 70 30 25 70 35 25 90 45 35 110 60 45 175 70 55 175 90 80
3/30/2021
23
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Blower Performance Data
Integrated EC Backward Curved Plenum Fan Performance
Model 084 Fan Fan
Airflow [cfm] at External Static Pressure [in. wg.]
Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
1 900 1395 1315 1215 1090 940 775 495
2 1100 1725 1640 1570 1485 1400 1280 1150 1015 870 620
3 1300 2055 1985 1925 1865 1800 1725 1645 1550 1435 1315 1190 1060 1055 870
4 1400 2220 2165 2100 2045 1990 1915 1850 1770 1685 1595 1490 1375 1260 1105 955
5 1600 2555 2505 2435 2390 2335 2285 2230 2175 2110 2045 1970 1885 1800 1705 1605 1510 1375 1265
6 1700 2715 2660 2610 2545 2505 2460 2415 2365 2305 2250 2180 2125 2050 1970 1885 1800 1695 1600 1495 1350 1275
7 1800 2810 2785 2705 2655 2600 2540 2495 2415 2355 2305 2265 2210 2175 2120 2085 2015 1965 1905 1855 1795 1705
8 1900 2970 2910 2865 2805 2775 2715 2665 2615 2575 2520 2460 2405 2360 2300 2245 2185 2130 2075 2020 1965 1895
9 2000 3145 3105 3075 3015 2945 2900 2855 2805 2745 2695 2655 2585 2520 2475 2430 2380 2305 2245 2175 2100 2030
10 2100 3320 3300 3285 3225 3115 3085 3045 2995 2915 2870 2850 2765 2680 2650 2615 2575 2480 2415 2330 2235 2165
11 2200 3460 3415 3380 3315 2475 3240 3195 3120 3085 3050 3020 2985 2915 2865 2805 2780 2715 2635 2575 2520 2475
12 2300 3625 3575 3505 3460 3425 3395 3345 3245 3255 3230 3190 3165 3120 3075 3025 2990 2950 2855 2820 2785 2715
Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1),
3/30/21
H = stage 2 (Y2), and Aux = electric heat.
Continuous Fan (G) can be set at any airflow. Factory setting is 1.
L = Stage 1 (Y1) factory setting is 3.
H = Stage 2 (Y2) factory setting is 8.
Electric Heat Operation (AUX) = Stage 3 factory setting is 10.
Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.
Model 096
Fan Fan
Airflow [cfm] at External Static Pressure [in. wg.]
Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
1 600 1530 1430 1205 915 525 420 2 700 1835 1710 1530 1410 1165 870 495 3 800 2145 2030 1895 1740 1565 1385 1125 825 570 4 900 2530 2415 2290 2145 1985 1825 1665 1440 1200 920 5 1000 2815 2720 2620 2505 2365 2235 2085 1915 1755 1555 1325 1115 780 6 1100 3135 3045 2955 2830 2735 2615 2470 2335 2195 2045 1915 1745 1490 1315 7 1200 3440 3360 3275 3195 3095 2985 2895 2750 2645 2505 2375 2225 2085 1915 1730 1525 1235 8 1300 3745 3685 3595 3505 3415 3335 3235 3120 3035 2910 2795 2680 2555 2420 2305 2150 1955 1770 1575 9 1400 4045 3995 3905 3830 3775 3680 3580 3500 3415 3310 3195 3165 2985 2875 2750 2630 2505 2375 2255 2070 1905 10 1500 4370 4285 4220 4150 4085 4010 3920 3850 3775 3680 3595 3505 3400 3305 3195 3075 2940 2830 2750 2645 2525 11 1600 4875 4575 4545 4480 4400 4335 4250 4200 4115 4065 3975 3865 3795 3695 3600 3500 3395 3290 3180 3085 2970 12 1700 5200 5120 5060 5000 4935 4665 4575 4510 4415 4345 4280 4210 4130 4040 3960 3875 3795 3680 3605 3515 3425
Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1),
3/30/21
H = stage 2 (Y2), and Aux = electric heat.
Continuous Fan (G) can be set at any airflow. Factory setting is 1.
L = Stage 1 (Y1) factory setting is 4.
H = Stage 2 (Y2) factory setting is 7.
Electric Heat Operation (AUX) = Stage 3 factory setting is 10.
Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.
Model 120
Fan Fan
Airflow [cfm] at External Static Pressure [in. wg.]
Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
1 700 1835 1710 1530 1410 1165 870 495 2 800 2145 2030 1895 1740 1565 1385 1125 825 570 3 900 2530 2415 2290 2145 1985 1825 1665 1440 1200 920 4 1000 2815 2720 2620 2505 2365 2235 2085 1915 1755 1555 1325 1115 780 5 1100 3135 3045 2955 2830 2735 2615 2470 2335 2195 2045 1915 1745 1490 1315 6 1200 3440 3360 3275 3195 3095 2985 2895 2750 2645 2505 2375 2225 2085 1915 1730 1525 1235 7 1300 3745 3685 3595 3505 3415 3335 3235 3120 3035 2910 2795 2680 2555 2420 2305 2150 1955 1770 1575 8 1400 4045 3995 3905 3830 3775 3680 3580 3500 3415 3310 3195 3165 2985 2875 2750 2630 2505 2375 2255 2070 1905 9 1500 4370 4285 4220 4150 4085 4010 3920 3850 3775 3680 3595 3505 3400 3305 3195 3075 2940 2830 2750 2645 2525 10 1600 4875 4775 4545 4480 4400 4335 4250 4200 4115 4065 3975 3865 3795 3695 3600 3500 3395 3290 3180 3085 2970 11 1700 5200 5120 5060 5000 4935 4665 4575 4510 4415 4345 4280 4210 4130 4040 3960 3875 3795 3680 3605 3515 3425 12 1800 5525 5405 5310 5200 5105 4995 4860 4755 4695 4625 4555 4480 4410 4350 4295 4225 4160 4070 3985 3900 3820
Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1),
3/30/21
H = stage 2 (Y2), and Aux = electric heat.
Continuous Fan (G) can be set at any airflow. Factory setting is 1.
L = Stage 1 (Y1) factory setting is 4.
H = Stage 2 (Y2) factory setting is 8.
Electric Heat Operation (AUX) = Stage 3 factory setting is 10.
Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.
24
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Blower Performance Data cont.
Model 150
Fan Fan
Airflow [cfm] at External Static Pressure [in. wg.]
Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
1 900 2780 2665 2545 2400 2230 2055 1880 1650
2 1000 3095 2990 2885 2780 2675 2515 2345 2175 2005 1830 1590
3 1100 3415 3325 3230 3135 3045 2905 2795 2680 2570 2460 2155 1985
4 1200 3750 3660 3565 3470 3370 3275 3165 3055 2935 2805 2680 2530 2375 2195 1995
5 1300 4055 3980 3905 3815 3725 3635 3540 3445 3335 3215 3100 2975 2845 2700 2545 2385 2190 1995 1802
6 1400 4375 4305 4230 4155 4070 3985 3900 3815 3720 3620 3520 3395 3275 3160 3040 2925 2765 2605 2445 2285 2120
7 1500 4810 4700 4585 4495 4420 4345 4255 4170 4090 4015 3945 3840 3735 3635 3530 3425 3295 3165 3035 2895 2765
8 1600 5245 5095 4940 4835 4770 4685 4605 4525 4450 4385 4320 4225 4135 4035 3945 3855 3745 3640 3530 3415 3300
9 1700 5680 5490 5295 5175 5120 5025 4955 4880 4810 4755 4680 4600 4520 4435 4345 4255 4175 4090 4000 3895 3795
10 1800 6115 5885 5650 5515 5470 5365 5305 5235 5170 5125 5040 4975 4905 4835 4730 4650 4570 4490 4405 4315 4220
11 1900 6550 6280 6005 5855 5820 5705 5655 5590 5530 5495 5400 5350 5290 5235 5115 5045 4965 4890 4810 4735 4645
12 2000 6985 6675 6360 6195 6155 6045 6005 5945 5890 5865 5760 5725 5675 5635 5500 5440 5360 5290 5215 5155 5070
Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1), H = stage 2 (Y2), and Aux = electric heat.
3/30/21
Continuous Fan (G) can be set at any airflow. Factory setting is 1.
L = Stage 1 (Y1) factory setting is 2.
H = Stage 2 (Y2) factory setting is 9.
Electric Heat Operation (AUX) = Stage 3 factory setting is 10.
Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.
Model 180
Fan Fan
Airflow [cfm] at External Static Pressure [in. wg.]
Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
1 900 2454 2341 2214 2075 1923 1758 1580 1389
2 1000 2978 2881 2773 2669 2531 2407 2253 2087 1908 1679 1432
3 1100 3288 3202 3121 3012 2908 2800 2679 2521 2385 2230 2050 1839 1617 1281
4 1200 3587 3507 3433 3343 3249 3145 3037 2926 2791 2659 2490 2364 2218 2037 1825 1568
5 1300 3901 3835 3761 3664 3594 3507 3418 3319 3202 3104 2969 2864 2735 2581 2417 2230 2098 1928
6 1400 4244 4182 4120 4057 3974 3896 3809 3727 3629 3536 3455 3326 3224 3110 2983 2833 2718 2581 2440 2293
7 1550 4812 4738 4664 4587 4504 4438 4372 4291 4226 4134 4046 3962 3870 3780 3707 3579 3501 3404 3305 3204 3101
8 1700 5329 5262 5195 5139 5082 5020 4958 4895 4831 4752 4673 4601 4529 4455 4380 4294 4222 4145 4068 3990 3911
9 1800 5666 5607 5548 5481 5414 5353 5291 5221 5151 5086 5020 4953 4886 4811 4735 4671 4596 4523 4450 4375 4300
10 1900 6018 5957 5895 5833 5770 5712 5654 5589 5524 5463 5402 5340 5278 5208 5138 5047 4976 4907 4837 4766 4695
11 2000 6350 6287 6224 6165 6105 6045 5985 5923 5861 5799 5736 5672 5607 5541 5475 5414 5347 5281 5214 5148 5080
12 2160 6862 6805 6748 6698 6647 6588 6529 6477 6425 6364 6303 6249 6194 6131 6068 5987 5920 5854 5787 5721 5653
Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1),
3/30/21
H = stage 2 (Y2), and Aux = electric heat.
Continuous Fan (G) can be set at any airflow. Factory setting is 1.
L = Stage 1 (Y1) factory setting is 3.
H = Stage 2 (Y2) factory setting is 9.
Electric Heat Operation (AUX) = Stage 3 factory setting is 10.
Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.
25
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Blower Performance Data cont.
Model 240
Fan Fan
Airflow [cfm] at External Static Pressure [in. wg.]
Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
1 900 5755 5525 5290 5005 4725 5045 4075 3645 3205 2635 2 1000 6610 6345 6080 5815 5550 5285 5020 4725 4425 4035 3640 3155
3 1100 7465 7165 6870 6625 6375 5525 5965 5805 5400 5105 4810 4440 4075 3495 2915
4 1200 7815 7650 7485 7295 7105 6915 6725 6540 6355 6095 5835 5540 5245 4755 4265 3995 3730 3075
5 1300 8505 8355 8205 8040 7875 7705 7530 7335 7145 6925 6710 6505 6300 5975 5655 5165 4681 4568 4455 3870 3285
6 1400 9195 9020 8850 8705 8565 8395 8225 8060 7895 7710 7525 7355 7190 6975 6760 6380 6000 5500 5000 4600 4200
7 1500 9885 9785 9605 9470 9335 9180 9025 8895 8770 8575 8385 8215 8045 7850 7655 7415 7175 6740 6305 5870 5435
8 1600 10575 10545 10360 10235 10105 9930 9760 9605 9450 9325 9205 9045 8890 8725 8565 8385 8205 8005 7810 7565 7325
9 1700 11265 11105 11055 11000 10875 10680 10570 10435 10300 10160 10025 9880 9740 9590 9445 9275 9110 8880 8655 8275 7900
10 1800 11955 11860 11750 11695 11645 11430 11380 11265 11150 10995 10715 10595 10480 10340 10205 10065 9930 9770 9610 9305 9005
11 1900 12645 12615 12445 12390 12285 12180 12105 12085 12000 11830 11405 11310 11220 11090 10975 10845 10715 10565 10420 10280 10145
12 2000 13335 13230 13140 13085 12925 12885 12830 12755 12705 12665 12395 12025 11960 11840 11745 11625 11500 11360 11225 11085 10945
Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1),
3/30/21
H = stage 2 (Y2), and Aux = electric heat.
Continuous Fan (G) can be set at any airflow. Factory setting is 1.
L = Stage 1 (Y1) factory setting is 3.
H = Stage 2 (Y2) factory setting is 6.
Electric Heat Operation (AUX) = Stage 3 factory setting is 8.
Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.
Model 300
Fan Fan
Airflow [cfm] at External Static Pressure [in. wg.]
Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
1 900 5755 5525 5290 5005 4725 5045 4075 3645 3205 2635
2 1000 6610 6345 6080 5815 5550 5285 5020 4725 4425 4035 3640 3155
3 1100 7465 7165 6870 6625 6375 5525 5965 5805 5400 5105 4810 4440 4075 3495 2915
4 1200 7815 7650 7485 7295 7105 6915 6725 6540 6355 6095 5835 5540 5245 4755 4265 3995 3730 3075
5 1300 8505 8355 8205 8040 7875 7705 7530 7335 7145 6925 6710 6505 6300 5975 5655 5165 4681 4568 4455 3870 3285
6 1400 9195 9020 8850 8705 8565 8395 8225 8060 7895 7710 7525 7355 7190 6975 6760 6380 6000 5500 5000 4600 4200
7 1500 9885 9785 9605 9470 9335 9180 9025 8895 8770 8575 8385 8215 8045 7850 7655 7415 7175 6740 6305 5870 5435
8 1600 10575 10545 10360 10235 10105 9930 9760 9605 9450 9325 9205 9045 8890 8725 8565 8385 8205 8005 7810 7565 7325
9 1700 11265 11105 11055 11000 10875 10680 10570 10435 10300 10160 10025 9880 9740 9590 9445 9275 9110 8880 8655 8275 7900
10 1800 11955 11860 11750 11695 11645 11430 11380 11265 11150 10995 10715 10595 10480 10340 10205 10065 9930 9770 9610 9305 9005
11 1900 12645 12615 12445 12390 12285 12180 12105 12085 12000 11830 11405 11310 11220 11090 10975 10845 10715 10565 10420 10280 10145
12 2000 13335 13230 13140 13085 12925 12885 12830 12755 12705 12665 12395 12025 11960 11840 11745 11625 11500 11360 11225 11085 10945
Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1), H = stage 2 (Y2), and Aux = electric heat.
3/30/21
Continuous Fan (G) can be set at any airflow. Factory setting is 1.
L = Stage 1 (Y1) factory setting is 3.
H = Stage 2 (Y2) factory setting is 8.
Electric Heat Operation (AUX) = Stage 3 factory setting is 9.
Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.
Model 360
Fan Fan
Airflow [cfm] at External Static Pressure [in. wg.]
Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
1 900 5755 5525 5290 5005 4725 5045 4075 3645 3205 2635
2 1000 6610 6345 6080 5815 5550 5285 5020 4725 4425 4035 3640 3155
3 1100 7465 7165 6870 6625 6375 5525 5965 5805 5400 5105 4810 4440 4075 3495 2915
4 1200 7815 7650 7485 7295 7105 6915 6725 6540 6355 6095 5835 5540 5245 4755 4265 3995 3730 3075
5 1300 8505 8355 8205 8040 7875 7705 7530 7335 7145 6925 6710 6505 6300 5975 5655 5165 4681 4568 4455 3870 3285
6 1400 9195 9020 8850 8705 8565 8395 8225 8060 7895 7710 7525 7355 7190 6975 6760 6380 6000 5500 5000 4600 4200
7 1500 9885 9785 9605 9470 9335 9180 9025 8895 8770 8575 8385 8215 8045 7850 7655 7415 7175 6740 6305 5870 5435
8 1600 10575 10545 10360 10235 10105 9930 9760 9605 9450 9325 9205 9045 8890 8725 8565 8385 8205 8005 7810 7565 7325
9 1700 11265 11105 11055 11000 10875 10680 10570 10435 10300 10160 10025 9880 9740 9590 9445 9275 9110 8880 8655 8275 7900
10 1800 11955 11860 11750 11695 11645 11430 11380 11265 11150 10995 10715 10595 10480 10340 10205 10065 9930 9770 9610 9305 9005
11 1900 12645 12615 12445 12390 12285 12180 12105 12085 12000 11830 11405 11310 11220 11090 10975 10845 10715 10565 10420 10280 10145
12 2000 13335 13230 13140 13085 12925 12885 12830 12755 12705 12665 12395 12025 11960 11840 11745 11625 11500 11360 11225 11085 10945
Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1), H = stage 2 (Y2), and Aux = electric heat.
3/30/21
Continuous Fan (G) can be set at any airflow. Factory setting is 1.
L = Stage 1 (Y1) factory setting is 4.
H = Stage 2 (Y2) factory setting is 9.
Electric Heat Operation (AUX) = Stage 3 factory setting is 10.
Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.
26
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Blower Performance Data cont.
Setting Blower Speed – Variable Speed ECM
The ABC board’s Yellow Config LED will flash the current ECM blower speed
selections for G, low, and high continuously with a short pause in between.
The speeds can also be confirmed with the AID Tool under the Setup/ ECM Setup
screen. The Aux will not be flashed but can be viewed in the AID Tool. The ECM
blower motor speeds can be field adjusted with or without using an AID Tool.
Variable speed ECM Setup without an AID Tool
The blower speeds for G only, Low (Y1), and High (Y2/ Aux) can be adjusted
directly at the Aurora ABC board which utilizes the push button (SW1) on the
ABC board. This procedure is outlined in the ECM Configuration Mode portion of
the Aurora `Base’ Control System section. The Aux cannot be set manually
without an AID Tool.
Variable speed ECM Setup with an AID Tool
A much easier method utilizes the AID Tool to change
the airflow using the procedure below. First navigate to
the Setup screen and then select ECM Setup. This screen
displays the current ECM settings. It allows the technician
ECM Speed Info
to enter the setup screens to change the ECM settings. Change
Blower Only Speed 3
Lo Compressor
6
Hi Compressor
9
Aux Heat
10
the highlighted item using the and buttons and then press the button to select the item.
Want To Change?
Yes Option
No Enter
Selecting YES will enter ECM speed setup, while selecting NO will return to the previous screen.
ECM Speed Setup – These screens allow the technician to select the G, low, high, and auxiliary heat blower speed for the ECM blower motor. Change the highlighted item using the and buttons. Press the button to select the speed.
ECM Speed Info
1 2 G
3 4 5 6 7 8 9 10 11 12
ECM Speed Info
1 2 G 3 Lo 4 5 6 7 8 9 10 11 12
ECM Speed Info
1
2 G
3 Lo
4
5
6
Hi
7
8
9
10
11
12
ECM Speed Info
1
2 G
3 Lo
4
5
6
Hi
7
8
9 10
11
12
Aux
Option
Enter
Option
Enter
Option
Enter
Option
Enter
After the auxiliary heat speed setting is selected the AID Tool will automatically transfer back to the ECM Setup screen.
Cooling Airflow Setup – These screens allow the technician to select -15%, -10%, -5%, None or +5% change from the heating airflow. Change the adjustment percentage using the and buttons. Press the button to save the change.
Cooling Airflow Setup
Cooling Airflow Setup
— ECM Only –The airflow will be adjusted by the chosen amount in cooling mode.
Adjustment: -15%
— ECM Only –The airflow will be adjusted by the chosen amount in cooling mode.
Adjustment: -15%
Want To Change?
Yes Option
No Enter
Change Enter
Setting Blower Speed – Variable Speed ECM – UPC Controls
Variable speed ECM blower motors have 12 selectable speeds and are factory set
for optimum performance. When applicable, the speed settings may also be
adjusted through the Building Automation System (BAS).
CAUTION: Disconnect all power before performing this operation.
27
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics
Single Compressor 208-230/60/3
CC
Ultra Tech CS RCP
Blue Blue
See N ote 6
FP2/ RV FP1 LAT LP HP
Orange (1)
Yellow Black
Blue (7)
Black (9)
RV T
T
Black (19)
Violet (18)
Gray Red Red
Blue (22) Blue (23)
Orange Yellow (2)
Black
Blue (8)
Black (10)
See N ote 3
K1-RV Relay
K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay
JW2
P9 EH1 CC2 CC F C
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C
P2 ES LS
R F1-3A
ALM ALG ACC COM ACC NO ACC NC
LO
K5-Alarm Relay
K6-Acc Relay
F
PWM
Aurora Base Control
SW1
Status
LED3
CFM
(ABC)
Test Mode
G
R C O/B G Y1 Y2 W DH P1
R Red
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
Com2 LED5
Com1 LED5
SW2 Config LED2
G RS485 NET
G RS485 NET
RS485 EXP
Y
C
P8
C R – + P7
C R – + P6 CO C EH1 C EH2 P3
Y1 G CC
Black
Black
Reh eat Valve See N ote 2
To UPC
See N ote 5
Aurora Advanced and Premiu m Opon
Red Heat Shrink
White Gr een
T T
Gr ay Gr ay Gr een White
Brown Vio le t Vio le t White White
GND 3 OUT 2 5DC 4
Brown Brown
Bro wn (25) Bro wn (24)
Condensate
FLOW
T
METER
DISCH ARGE PRESSU RE TRANSDUCER
T
Black White Red
GND 1 OUT 2 5DC 3
MOTOR RX
TX
R
C
V+ P8
RS485 (+)
(-)
R
C P6 ZO NE (+)
(-)
R
C P7 ABC (+)
(-)
R
C
+5 P9
P4
P2
HA2 HA1 SGI P3 C S +5 C S +5 2 1 C OUT C IN LOOP VS DATA VS PUMP PUMP SLAVE
EWT LWT FLOW LAT P1
LLT P16
Status G
AXBTM
(Aurora Expansion Board)
Modbus Add. ID Future Use Future Use
Acc 2 Dip 1 Acc 2 Dip 2
OFF ON 1 2 3 4 5
SW1
P17 HHWW 21
P18 SCT 321
P12 SCP
321
P10 STEPPER
K3 K2 K1
P15 CT2 CT1 4321
P5 CT2 CT1 4321
P11 ANA ACC2 DH DIV
Pink T
Pink
Blue
T
Blue
Black White Red
1 GND 2 OUT 3 5DC
SU CTI ON PRES SU RE T RA NSD UCE R
DISCH P14 C
R
L1
L1 K6
COM
NO
K5
COM
NO L2
L2
28
Black (16) Black
Yellow (17 )
Modulang Water Valve
Gray
Y
321
Red
~
Black
CO M
24V G
0-10V Y
G ND
U
Red Gr ay Black
Hot Gas Reheat Valve Note 2
Red Black
Note 4
Blue
Compressor T1
Blue
Red Compressor T2
Red
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Single Compressor 208-230/60/3
Black (A) Black (K) Red (B) White (L) Blue (C) Red (M) Black (AG) Red (AH) Blue (AJ)
Unit Power Supply
Non-Fuse d Di sconne ct or T ermi na l Bl oc k
G
L1
L2
L3
L1
L2
L3
Green / Yel low (G1) Compressor
T3
T1
T2
Blue (AC) Red (AB)
Black (AA)
CC
T3
T2
T1
L3
L2
L1
97P8 95-01 03/01/21
Phase Guard Monitor (PG M)
L1 L2 L3
Aurora LED Flash Codes
SlowFlash 1 second on and 1 second off
Fast Flash 100 mil liseconds on and 100 mi lliseconds off
Flash Code 100 mil liseconds on and 400 mi lliseconds off with a 2 second pause before re peating
Random Start Delay
Status LED (LED3, Green)
Fast Fl ash
Configuration LED (LED2, Yel low)
Fast Fl ash
Faul t LED (LED1, Red)
Fast Fl ash
Sta tus LED (LED3, Green)
Configuration LED (LED2, Yellow)
Fault LED (LED1, Red)
Normal Mode
ON
No Software Overi de Fl ash ECM Settin g Normal Mode
OFF
Control is Non-Functional
OFF DIP Switch Overide
Slow Flash Input Fault Lockout
Flash Code 1
Test Mode
Slow Flash ECM Configu re Mod e
Fast Fl ash High Pressure Lockout
Fl ash Code 2
Lockout Active
Fast Fl ash Reset Confi gure Mode
Off
Low Pressure Locko ut
Fl ash Code 3
Dehumidification Mo de
Fl ash Code 2
Low Air Coil Limit Lockout – FP2 Fl ash Code 4
Reserved
Fl ash Code 3
Low Water Coil Limi t Lockout – FP1 Fl ash Code 5
Reserved
Fl ash Code 4
Loss of Charge Lockout
Fl ash Code 6
Load Shed
Fl ash Code 5
Condensate Overfl ow Lockout
Fl ash Code 7
ESD
Fl ash Code 6
Over/Under Vol tage Sh utdown
Fl ash Code 8
Reserved
Fl ash Code 7
Reserved
Fl ash Code 9
Compressor Monitor Lockout
Fl ash Code 1 0
Air/Water Coil Limit Sensor Error Fl ash Code 1 1
L2
L1
L3
GN D A ( D+) B ( D-)
Blower Motor
ID
GN D
A ( D+)
B ( D-)
ID
Green/Yel low (29)
Control Box
Control Box
fo ut
Base Panel
Door
GN D
PB1
2 Green/Yel low (14)
3 Black (13)
Black/White
1 C
Yellow (12 )
Y-OUT
Y
PGM
Yellow
Accessor y Relay
Operation
SW2-4 SW2-5
Cycl e with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
Aurora Timing Events
Event
Normal Mode
Random Start Delay
5 to 80 seconds
Compressor On Delay
5 seconds
Compressor Minimum On Time
2 minutes
Compressor Short Cycl e Delay
4 minutes
Blower Off Delay
30 seconds
Faul t Recogn itio n Delay High Pressure
Less than 1 second
Start-Up Bypass Low Pressure
2 minutes
Faul t Recogn itio n Delay Low Pressure
30 seconds
Start-Up Bypass Low Water/Ai r Coil Limit
2 minutes
Faul t Recogn itio n Delay Low Water/Ai r Coil Limit 30 seconds
Faul t Recogn itio n Delay Condensate Overfl ow
30 seconds
Thermostat Call Recognition Time
2 seconds
Auxi liary Heat Stagi ng Del ay
5 minutes
Emergency Heat Stagi ng Dela y
2 minutes
Water Valve Slow Open Delay
90 seconds
Reheat Delay
30 seconds
Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds
Tra nsformer
Cla ss 2
Black Red See N ote 7
Blue
Notes:
1 P1 (screw ter minals) and P9 (Molex connector ) are adjacent and share
common terminals in the same order. 2 Optional factor y installed hot gas
reheat or modulating hot gas r eheat. 3 Optional factor y installed internal
isolation valve. 4 Optional waters ide economizer. 5 See supplemental
schematic for AXB and/or UPC connections. 6 LAT location with Aurora Base
Controls, FP2 with Auror a Advanced and Premium Controls. 7 Swap blue and
red leads for 208V operation.
Green/ Yellow (15 )
Factory PWM CFM C
1 2 3
24V
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
CC2 Factory
G P5 LO HI CCG CC FG F R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1
JW2 Alarm
P2 Fi eld Connections
LED1 R
Off FP1 15oF/30oF
FP2 15oF/30oF
On 1 LED2
2Y
Faul t
RV B/O
ACC Dip 4
3 Config 4
LED3
ACC Dip 5
CC Dual/Si ngle
G L Pulse/Continuous
Status
Reheat/Normal
5 6 7 8 SW2
AURORA BASE CONTROLTM
Com1 G
RS485 Exp
Factory
EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7
RS 485
Factory Use
RS485 NET
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
CC C
Legend
Factory Low Voltage Wiring Factory Line Voltage Wiring Fi eld Low Voltage Wiring Field Line Voltage Wiri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ring Internal Ju nction Qui ck Con nect Terminal
L1
Field Wiring Lug
T
Thermistor
Relay Coi l
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
EX-XX
Ground Relay Con tacts N.O., N.C.
Pin Number Designation on Twist-Lock Connector
Capacitor Fuse
G
Light Emitti ng Diode – Green
Current Transducer
Y
Light Emitti ng Diode – Yellow
CC Compressor Contactor CO Condensate Overfl ow Sensor ES Emergency Shutdown EWT Entering Water Temp Sensor HP High Pressure Switch LAT Leaving Ai r Temp LLT Liqui d Line Temp LP Low Pressure Switch LWT Leaving Water Temp
R
Light Emitti ng Diode – Red
FP1 Freeze Protection Sensor 1 FP2 Freeze Protection Sensor 2 SW1 Push button SW2 DIP package 8 position RV Reversi ng Valve Coi l PGM Phase Guard Moni tor RH Reheat Valve Coi l
29
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Single Compressor 460/60/3
CC
Ultra Tech CS RCP
Blue Blue
See N ote 6
FP2/ RV FP1 LAT LP HP
Orange (1)
Yellow Black
Blue (7)
Black (9)
RV T
T
Black (19)
Violet (18)
Gray Red Red
Blue (22) Blue (23)
Orange Yellow (2)
Black
Blue (8)
Black (10)
See N ote 3
K1-RV Relay
K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
JW2
P9 EH1 CC2 CC F C
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C
P2 ES LS
R F1-3A
ALM ALG ACC COM ACC NO ACC NC
LO
K5-Alarm Relay
K6-Acc Relay
F
PWM
Aurora Base Control
SW1
Status
LED3
CFM
(ABC)
Test Mode
G
R C O/B G Y1 Y2 W DH P1
R Red
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
Com2 LED5
Com1 LED5
SW2 Config LED2
G RS485 NET
G RS485 NET
RS485 EXP
Y
C
P8
C R – + P7
C R – + P6 CO C EH1 C EH2 P3
Y1 G CC
Black
Black
Reh eat Valve See N ote 2
To UPC
See N ote 5
Aurora Advanced and Premiu m Opon
Red Heat Shrink
White Gr een
T T
Gr ay Gr ay Gr een White
Brown Vio le t Vio le t White White
GND 3 OUT 2 5DC 4
Brown Brown
Bro wn (25) Bro wn (24)
Condensate
FLOW
T
METER
DISCH ARGE PRESSU RE TRANSDUCER
T
Black White Red
GND 1 OUT 2 5DC 3
MOTOR RX
TX
R
C
V+ P8
RS485 (+)
(-)
R
C P6 ZO NE (+)
(-)
R
C P7 ABC (+)
(-)
R
C
+5 P9
P4
P2
HA2 HA1 SGI P3 C S +5 C S +5 2 1 C OUT C IN LOOP VS DATA VS PUMP PUMP SLAVE
EWT LWT FLOW LAT P1
LLT P16
Status G
AX BTM
(Aurora Expansion Board)
Modbus Add. ID Future Use Future Use
Acc 2 Dip 1 Acc 2 Dip 2
OFF ON 1 2 3 4 5
SW1
P17 HHWW 21
P18 SCT 321
P12 SCP
321
P10 STEPPER
K3 K2 K1
P15 CT2 CT1 4321
P5 CT2 CT1 4321
P11 ANA ACC2 DH DIV
Pink T Pink
Blue
T
Blue
Black White Red
1 GND SU CTI ON 2 OUT PRES SU RE 3 5DC T RA NSD UCE R
DISCH P14 C
R
L1
L1 K6
COM
NO
K5
COM
NO L2
L2
Black (16) Black
Yellow (17 )
Modulang Water Valve
Gray
Y
321
Red
~
Black
CO M
24V G
0-10V Y
G ND
U
Red Gr ay Black
Hot Gas Reheat Valve Note 2
Red Black
Note 4
Blue
Compressor T1
Blue
Red Compressor T2
Red
30
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Single Compressor 460/60/3
Unit Power Supply
Non-Fuse d Di sconne ct or T ermi na l Bl oc k
G
L1
L2
L3
L1
L2
L3
Green / Yel low (G1) Compressor
T3
T1
T2
Yellow (AC) Orange (AB) Bro wn (AA)
CC
T3
T2
T1
L3
L2
L1
Phase Guard Monitor (PG M)
L1 L2 L3
Bro wn (A) Black (K) Orange (B) White (L) Yellow (C) Red (M) Bro wn (AG) Orange (AH) Yellow (AJ)
L2
L1
L3
GN D A ( D+) B ( D-)
Blower Motor
ID
GN D
A ( D+)
B ( D-)
ID
Green/Yel low (29)
Control Box
Control Box
fo ut
Base Panel
Door
GN D
PB1
2 Green/Yel low (14)
3 Black (13)
Black/White
1 C
Yellow (12 )
Y-OUT
Y
PGM
Yellow
Tra nsformer
Black
Blue Cla ss 2
Green/ Yellow (15 )
97P8 95-02 03/01/21
Aurora LED Flash Codes
SlowFlash 1 second on and 1 second off
Fast Flash 100 milliseconds on and 100 mi lliseconds off
Flash Code 100 mil liseconds on and 400 mi lliseconds off with a 2 second pause before re peating
Random Start Delay
Status LED (LED3, Green)
Fast Fl ash
Configuration LED (LED2, Yel low)
Fast Fl ash
Faul t LED (LED1, Red)
Fast Fl ash
Sta tus LED (LED3, Green)
Configuration LED (LED2, Yellow)
Fault LED (LED1, Red)
Normal Mode
ON
No Software Overi de Fl ash ECM Settin g Normal Mode
OFF
Control is Non-Functional
OFF DIP Switch Overide
Slow Flash Input Fault Lockout
Flash Code 1
Test Mode
Slow Flash ECM Configu re Mod e
Fast Fl ash High Pressure Lockout
Fl ash Code 2
Lockout Active
Fast Fl ash Reset Confi gure Mode
Off
Low Pressure Locko ut
Fl ash Code 3
Dehumidification Mo de
Fl ash Code 2
Low Air Coil Limi t Lockout – FP2 Fl ash Code 4
Reserved
Fl ash Code 3
Low Water Coil Limi t Lockout – FP1 Fl ash Code 5
Reserved
Fl ash Code 4
Loss of Charge Lockout
Fl ash Code 6
Load Shed
Fl ash Code 5
Condensate Overfl ow Lockout
Fl ash Code 7
ESD
Fl ash Code 6
Over/Under Vol tage Sh utdown
Fl ash Code 8
Reserved
Flash Code 7
Reserved
Fl ash Code 9
Compressor Monitor Lockout
Fl ash Code 1 0
Air/Water Coil Limit Sensor Error Fl ash Code 1 1
Accessor y Relay
Operation
SW2-4 SW2-5
Cycl e with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
Aurora Timing Events
Event
Normal Mode
Random Start Delay
5 to 80 seconds
Compressor On Delay
5 seconds
Compressor Minimum On Time
2 minutes
Compressor Short Cycl e Delay
4 minutes
Blower Off Delay
30 seconds
Faul t Recogn itio n Delay High Pressure
Less than 1 second
Start-Up Bypass Low Pressure
2 minutes
Faul t Recogn itio n Delay Low Pressure
30 seconds
Start-Up Bypass Low Water/Ai r Coil Limit
2 minutes
Faul t Recogn itio n Delay Low Water/Ai r Coil Limit 30 seconds
Faul t Recogn itio n Delay Condensate Overfl ow
30 seconds
Thermostat Call Recognition Time
2 seconds
Auxi liary Heat Stagi ng Del ay
5 minutes
Emergency Heat Stagi ng Dela y
2 minutes
Water Valve Slow Open Delay
90 seconds
Reheat Delay
30 seconds
Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds
Notes:
1 P1 (screw ter minals) and P9 (Molex connector ) are adjacent and share
common terminals in the same order. 2 Optional factor y installed hot gas
reheat. 3 Optional factor y installed internal isolation valve. 4 Optional
waters ide economizer . 5 See supplemental schematic for AXB and/or UPC
connections. 6 LAT location with Aurora Base Controls, FP2 with Auror a
Advanced and Premium Controls.
Factory PWM CFM C
1 2 3
24V
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
CC2 Factory
G P5 LO HI CCG CC FG F R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1
JW2 Alarm
P2 Fi eld Connections
LED1 R
Off FP1 15oF/30oF
FP2 15oF/30oF
On 1 LED2
2Y
Faul t
RV B/O
ACC Dip 4
3 Config 4
LED3
ACC Dip 5
CC Dual/Si ngle
G L Pulse/Continuous
Status
Reheat/Normal
5 6 7 8 SW2
AURORA BASE CONTROLTM
Com1 G
RS485 Exp
Factory
EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7
RS 485
Factory Use
RS485 NET
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
3A-Fuse
CC C
Legend
Factory Low Voltage Wiring Factory Line Vol tage Wiring Field Low Voltage Wiring Fi eld Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Ju nction Quick Con nect Terminal
L1
Field Wiring Lug
T
Thermistor
Relay Coi l
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
EX-XX
Ground Relay Con tacts N.O., N.C.
Pin Number Designation on Twist-Lock Connector
Capacitor Fuse
G
Light Emitti ng Diode – Green
Current Transducer
Y
Light Emitti ng Diode – Yellow
CC Compressor Contactor CO Condensate Overfl ow Sensor ES Emergency Shutdown EWT Entering Water Temp Sensor HP High Pressure Switch LAT Leaving Ai r Temp LLT Liqui d Line Temp LP Low Pressure Switch LWT Leaving Water Temp
R
Light Emitting Diode – Red
FP1 Freeze Protection Sensor 1 FP2 Freeze Protection Sensor 2 SW1 Push button SW2 DIP package 8 position RV Reversi ng Valve Coi l PGM Phase Guard Moni tor RH Reheat Valve Coi l
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
2
RR
31
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor 208-230/60/3
Note 2 Isol ation Valve
RV-A FP1-A
LP-A HP-A RV-B FP1-B LP-B HP-B RH-A RH-B
Black (32) CCCCA Violet (31)
RV-A FP1-A LAT LP-A HP-A
Orange Yellow
Blue Black
(28) 30 Gray (32) (34)
RV T
T
Yellow
Orange (31) Gray Blue Black
(29)
(33) (35)
JW2
P9 EH1 CC2 CC F C
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C
K1-RV Relay
P2 ES LS
R F1-3A
K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay
ALM ALG ACC COM
K5-Alarm Relay
Gray
ACC NO
K6-Acc
ACC NC
Relay
LO
F
PWM
Aurora Base Control A
SW1
Status LED3
CFM
(ABC-A)
Test Mode
G
R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
Com1 LED5
G RS485 NET
RS485 EXP
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
C
P8
C R – + P7
C R – + P6 CO C EH1 C EH2P3
Y1 G CC
Black Red
Red Red Note 2
Valve RHA Note 3
“EX” Con nector (twist lock)
1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 19 20 22 23 25 26 27
Red/White
Black
To UPC
Bro wn (38)
Bro wn (37)
Condensate
470
RV-B
Resistor FP1-B
LP-B
HP-B
Orange/ White (38)
Yellow (40)
Blue/ Black/ White White (42) (44)
RV T
Black (36) CCCCB Violet (35)
Orange/ White
Yellow (41)
(39)
Blue/ Black/ White White (43) (45)
P9 EH1 CC2 CC F C
P2
ES
LS
ALM ALG ACC COM
K5-Alarm Relay
ACC NO ACC NC
K6-Acc Relay
LO R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
C
P8
JW2
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F
K1-RV Relay
K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
Aurora Base Control B (ABC-B)
SW1 Test Mode
Com1 LED5
G RS485 NET
C R – + P7
RS485 EXP C R – + P6 CO C EH1 C EH2P3
PWM
Status
CFM
LED3
G
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
Y1 G CC
Valve RHB Note 3
Black/White
To UPC
Bro wn (41)
Bro wn (40)
Condensate
Black/White (18)
Yellow (17 )
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
White
32
Note 3
Note 2 Isol ation Valve
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor 208-230/60/3
Unit Power Input 208-230/60/3
G
L1
L2
L3
L1
L2
L3
Green / Yel low (G1) Compressor A
Green / Yel low (G2) Compressor B
Phase Gu ard Monitor (PG M)
L1 L2 L3
Blue (AC)
T3
T1
T2
Red (AB)
Black (AA) Blue (AF)
T3
T1
T2
Red (AE)
Black (AD)
CCA
T3
T2
T1
CCB
T3
T2
T1
Black (AG) Red (AH) Blue (AJ)
Black (X) White (Y) Red (Z)
PB1
2 Black/White (20)
Green/Yel low (15)
3
1
Green/Yel low (16)
Blue (C) Red (B) Black (A)
Blue (F) Red (E) Black (D)
Black (G) Red (H)
Blue (J)
Black (U)
Red (V) Blue (W)
Black/White
24V Tra nsformer
Black (14)
Yellow (13 ) Y-OUT
Yellow
Cla ss 2
C
Y
Yellow (11 )
PGM
Black/White
Yellow (12 )
L3
L2
L1
Black
Red for 20 8V Blue for 230V
Black
L3
L2
L1
Blower Motor L1 A L3
L2
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Black (K) White (L) Red (M)
See Note 4
Blower
Motor
B
L1
L3
L2
Control Box Base Panel
Green / Yel low (39)
Control Box Door
Accessor y Relay
Operation
SW2-4 SW2-5
Cycl e with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
24V Tra nsformer
Yellow (19 )
Yellow
Cla ss 2
Red for 20 8V Blue for 230V
PWM CFM
C
Factory Factory
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
CC2 Factory
G P5 LO HI CCG CC FG F R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1
JW2 Alarm
P2 Fi eld Connections
LED1 R
Off FP1 15oF/30oF
FP2 15oF/30oF
On 1 LED2
2Y
Faul t
RV B/O
ACC Dip 4
3 Config 4
LED3
ACC Dip 5
CC Dual/Si ngle
G L Pulse/Continuous
Status
Reheat/Normal
5 6 7 8 SW2
AURORA BASE CONTROLTM
Com1 G
RS485 Exp
EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7
RS 485
Factory Use
RS485 NET
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
CC C
Notes:
1 P1 (screw terminals) and P9 (Molex connector) are adjacent and share
common terminals in the same or der. 2 Optional isolation water valv e. 3
Optional hot gas reheat. 4 Sizes 240-360 equipped with two blowers .
Legend
Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal
L1
Fi eld Wiring Lug
1 2 3
T
Thermistor
Relay Coi l
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
Ground
Relay Con tacts N.O., N.C.
Capacitor
Fuse
CCA Compressor A Contactor CCB Compressor B Contactor CO Condensate
Overfl ow Sensor ES Emergency Shutdown HP1 High Pressure Switch 1 HP2
High Pressure Switch 2 LP1 Low Pressure Switch 1 LP2 Low Pressure Switch 2
FP1 Freeze Protection Sensor 1 FP2 Freeze Protection Sensor 2 F1 Fuse
EX-XX
Pin Number Designation on Twist-Lock Connector
G
Light Emitting Diode – Green
Y
Light Emitting Diode – Yellow
R
Light Emitti ng Diode – Red
SW1 Push button SW2 DIP package 8 position RV1 Reversi ng Valve Coi l 1 RV2 Reversi ng Valve Coi l 2 PGM Phase Guard Moni tor RH Reheat Valve Coi l
33
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor 460/60/3
Note 2 Isol ation Valve
RV-A FP1-A
LP-A HP-A RV-B FP1-B LP-B HP-B RH-A RH-B
Black (32) CCCCA Violet (31)
RV-A FP1-A LAT LP-A HP-A
Orange Yellow
Blue Black
(28) 30 Gray (32) (34)
RV T
T
Yellow
Orange (31) Gray Blue Black
(29)
(33) (35)
JW2
P9 EH1 CC2 CC F C
R
F
FG
CC
CCGCHCI2
CC2 CC2 LO G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C
K1-RV Relay
P2 ES LS
R F1-3A
K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay
ALM ALG ACC COM
K5-Alarm Relay
Gray
ACC NO
K6-Acc
ACC NC
Relay
LO
F
PWM
Aurora Base Control A
SW1
Status LED3
CFM
(ABC-A)
Test Mode
G
R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
Com1 LED5
G RS485 NET
RS485 EXP
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
C
P8
C R – + P7
C R – + P6 CO C EH1 C EH2P3
Y1 G CC
Black Red
Red Red Note 2
Valve RHA Note 3
“EX” Con nector (twist lock)
1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 19 20 22 23 25 26 27
Red/White
Black
To UPC
Bro wn (38)
Bro wn (37)
Condensate
470
RV-B
Resistor FP1-B
LP-B
HP-B
Orange/ White (38)
Yellow (40)
Blue/ Black/ White White (42) (44)
RV T
CCCCB
Black (36)
Violet (35)
Orange/ Yellow White (41) (39)
Blue/ Black/ White White (43) (45)
P9 EH1 CC2 CC F C
P2
ES
LS
ALM ALG ACC COM
K5-Alarm Relay
ACC NO ACC NC
K6-Acc Relay
LO R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
C
P8
JW2
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F
K1-RV Relay
K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
Aurora Base Control B (ABC-B)
SW1 Test Mode
Com1 LED5
G RS485 NET
C R – + P7
RS485 EXP C R – + P6 CO C EH1 C EH2P3
PWM
Status
CFM
LED3
G
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
Y1 G CC
Valve RHB Note 3
Black/White
To UPC
Bro wn (41)
Bro wn (40)
Condensate
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
White
34
Note 3
Note 2 Isol ation Valve
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor 460/60/3
Unit Power Input 460/60/3
G
L1
L2
L3
L1
L2
L3
Green / Yel low (G1) Compressor A
Green / Yel low (G2) Compressor B
Phase Gu ard Monitor (PG M)
L1 L2 L3
Blue (AC)
T3
T1
T2
Red (AB)
Black (AA) Blue (AF)
T3
T1
T2
Red (AE)
Black (AD)
CCA
T3
T2
T1
CCB
T3
T2
T1
Bro wn (AG) Orange (AH)
Yellow (AJ)
Black (X) White (Y) Red (Z)
PB1
Black/White (18) 2
Black/White (20)
Green/Yel low (15)
3
Yellow (17 ) 1
Green/Yel low (16)
Yellow (C) Orange (B) Bro wn (A)
Yellow (F) Orange (E) Bro wn (D)
Bro wn (G) Orange (H)
Yellow (J)
Bro wn (U)
Orange (V) Yellow (W)
Black/White
24V Tra nsformer
Black (14)
Yellow (13 ) Y-OUT
Yellow
Cla ss 2
C
Y
Yellow (11 )
PGM
Black/White
Yellow (12 )
L3
L2
L1
Black Blue
Black
L3
L2
L1
Blower Motor L1 A L3
L2
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Black (K) White (L) Red (M)
See Note 4
Blower
Motor
B
L1
L3
L2
Control Box Base Panel
Green / Yel low (39)
Control Box Door
Accessor y Relay
Operation
SW2-4 SW2-5
Cycl e with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
24V Tra nsformer
Yellow (19 )
Yellow
Blue
Cla ss 2
PWM CFM
C
Factory Factory
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
CC2 Factory
G P5 LO HI CCG CC FG F R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1
JW2 Alarm
P2 Fi eld Connections
LED1 R
Off FP1 15oF/30oF
FP2 15oF/30oF
On 1 LED2
2Y
Faul t
RV B/O
ACC Dip 4
3 Config 4
LED3
ACC Dip 5
CC Dual/Si ngle
G L Pulse/Continuous
Status
Reheat/Normal
5 6 7 8 SW2
AURORA BASE CONTROLTM
Com1 G
RS485 Exp
EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7
RS 485
Factory Use
RS485 NET
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
CC C
Notes:
1 P1 (screw terminals) and P9 (Molex connector) are adjacent and share
common terminals in the same or der. 2 Optional isolation water valv e. 3
Optional hot gas reheat. 4 Sizes 240-360 equipped with two blowers .
Legend
Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal
L1
Fi eld Wiring Lug
1 2 3
T
Thermistor
Relay Coi l
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
Ground
Relay Con tacts N.O., N.C.
Capacitor
Fuse
CCA Compressor A Contactor CCB Compressor B Contactor CO Condensate
Overfl ow Sensor ES Emergency Shutdown HP1 High Pressure Switch 1 HP2
High Pressure Switch 2 LP1 Low Pressure Switch 1 LP2 Low Pressure Switch 2
FP1 Freeze Protection Sensor 1 FP2 Freeze Protection Sensor 2 F1 Fuse
EX-XX
Pin Number Designation on Twist-Lock Connector
G
Light Emitting Diode – Green
Y
Light Emitting Diode – Yellow
R
Light Emitti ng Diode – Red
SW1 Push button SW2 DIP package 8 position RV1 Reversi ng Valve Coi l 1 RV2 Reversi ng Valve Coi l 2 PGM Phase Guard Moni tor RH Reheat Valve Coi l
35
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 208-230/60/3
G
Note 2 Isol ation Valve
Black Red
Red Red Note 2
Black (32) CCCCA Violet (31)
RV-A FP1-A FP2-A LP-A HP-A
Orange Yellow
Blue Black
(28) 30 Black (32) (34)
RV T
T
Yellow
Orange (31) Black Blue Black
(29)
(33) (35)
JW2
P9 EH1 CC2 CC F C
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C
K1-RV Relay
P2 ES LS
R F1-3A
K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay
ALM ALG ACC COM
K5-Alarm Relay
Gray
ACC NO
K6-Acc
ACC NC
Relay
LO
F
PWM
Aurora Base Control A
SW1
Status LED3
CFM
(ABC-A)
Test Mode
G
R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
Com1 LED5
G RS485 NET
RS485 EXP
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
C
P8
C R – + P7
C R – + P6 CO C EH1 C EH2P3
Y1 G CC
Valve RHA Note 3
Black
To UPC
Bro wn (38) Bro wn (37)
WSE Condensate Bro wn (113)
RV-A FP1-A LP-A HP-A WSE RV-B FP1-B LP-B HP-B RH-A
RH-B
0-10V G ND 24V 0-10V G ND 24V
Y
GY
G
“EX” Con nector (twist lock)
1
2
3
4
5
6
7
8
White
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Red/White
Valve RHB Note 3
RV-B FP1-B FP1-B LP-B HP-B
Orange/ White (38)
Yellow (40)
Black
Blue/ White (42)
Black/ White (44)
CCCCB
RV T
T
Black (36)
Violet (35)
Orange/ Yellow White (41)
Black
Blue/ White
Black/ White
(39)
(43) (45)
P9 EH1 CC2 CC F C
P2
ES
LS
ALM ALG ACC COM
K5-Alarm Relay
ACC NO ACC NC
K6-Acc Relay
LO R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
C
P8
JW2
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F
K1-RV Relay
K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
Aurora Base Control B (ABC-B)
SW1 Test Mode
Com1 LED5
G RS485 NET
C R – + P7
RS485 EXP C R – + P6 CO C EH1 C EH2P3
Status LED3
G
PWM CFM
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
Y1 G CC
Black/White
To UPC
Bro wn (41) Bro wn (40)
WSE Condensate Bro wn (114)
Black/White (18)
Yellow (17 )
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
White
36
Note 3
Note 2 Isol ation Valve
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 208-230/60/3
G
Black/White (18)
ellow (17 )
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
e
Unit Power Input 208-230/60/3
L1
L2
L3
L1
L2
L3
Green / Yel low (G1) Compressor A
Green / Yel low (G2) Compressor B
Phase Gu ard Monitor (PG M)
L1 L2 L3
Blue (AC)
T3
T1
T2
Red (AB)
Black (AA) Blue (AF)
T3
T1
T2
Red (AE)
Black (AD)
CCA
T3
T2
T1
CCB
T3
T2
T1
Black (AG) Red (AH) Blue (AJ)
Black (X) White (Y) Red (Z)
PB1
2 Black/White (20)
Green/Yel low (15)
3
1
Green/Yel low (16)
Blue (C) Red (B) Black (A)
Blue (F) Red (E) Black (D)
Black (G) Red (H)
Blue (J)
Black (U)
Red (V) Blue (W)
Black/White
24V Tra nsformer
Black (14)
Yellow (13 ) Y-OUT
Yellow
Cla ss 2
C
Y
Yellow (11 )
PGM
Black/White
Yellow (12 )
L3
L2
L1
Black
Red for 20 8V Blue for 230V
Black
L3
L2
L1
Blower Motor L1 A L3
L2
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Black (K) White (L) Red (M)
See Note 4
Blower
Motor
B
L1
L3
L2
Control Box Base Panel
Green / Yel low (39)
Control Box Door
Accessor y Relay
Operation
SW2-4 SW2-5
Cycl e with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
24V Tra nsformer
Yellow (19 )
Yellow
Cla ss 2
Red for 20 8V Blue for 230V
Factory PWM CFM C
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
CC2 Factory
G P5 LO HI CCG CC FG F R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1
JW2 Alarm
P2 Fi eld Connections
LED1 R
Off FP1 15oF/30oF
FP2 15oF/30oF
On 1 LED2
2Y
Faul t
RV B/O
ACC Dip 4
3 Config 4
LED3
ACC Dip 5
CC Dual/Si ngle
G L Pulse/Continuous
Status
Reheat/Normal
5 6 7 8 SW2
AURORA BASE CONTROLTM
Com1 G
RS485 Exp
Factory
EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7
RS 485
Factory Use
RS485 NET
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
CC C
Notes:
1 P1 (screw terminals) and P9 (Molex connector) are adjacent and share
common terminals in the same or der. 2 Optional isolation water valv e. 3
Optional hot gas reheat. 4 Sizes 240-360 equipped with two blowers .
Legend
Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal
L1
Fi eld Wiring Lug
1 2 3
T
Thermistor
Relay Coi l
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
Ground
Relay Con tacts N.O., N.C.
Capacitor
Fuse
Current Transducer
CCA Compressor A Contactor CCB Compressor B Contactor CO Condensate
Overfl ow Sensor ES Emergency Shutdown HP1 High Pressure Switch 1 HP2
High Pressure Switch 2 LP1 Low Pressure Switch 1 LP2 Low Pressure Switch 2
FP1 Freeze Protection Sensor 1 FP2 Freeze Protection Sensor 2 F1 Fuse
EX-XX
Pin Number Designation on Twist-Lock Connector
G
Light Emitting Diode – Green
Y
Light Emitting Diode – Yellow
R
Light Emitti ng Diode – Red
SW1 Push button SW2 DIP package 8 position RV1 Reversi ng Valve Coi l 1 RV2 Reversi ng Valve Coi l 2 PGM Phase Guard Moni tor RH Reheat Valve Coi l
37
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 460/60/3
Note 2 Isol ation Valve
Black Red
Red Red Note 2
Black (32) CCCCA Violet (31)
RV-A FP1-A FP2-A LP-A HP-A
Orange Yellow
Blue Black
(28) 30 Black (32) (34)
RV T
T
Yellow
Orange (31) Black Blue Black
(29)
(33) (35)
JW2
P9 EH1 CC2 CC F C
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C
K1-RV Relay
P2 ES LS
R F1-3A
K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay
ALM ALG ACC COM
K5-Alarm Relay
Gray
ACC NO
K6-Acc
ACC NC
Relay
LO
F
PWM
Aurora Base Control A
SW1
Status LED3
CFM
(ABC-A)
Test Mode
G
R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
Com1 LED5
G RS485 NET
RS485 EXP
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
C
P8
C R – + P7
C R – + P6 CO C EH1 C EH2P3
Y1 G CC
Valve RHA Note 3
Black
To UPC
Bro wn (38) Bro wn (37)
WSE Condensate Bro wn (113)
RV-A FP1-A LP-A HP-A WSE RV-B FP1-B LP-B HP-B RH-A
RH-B
0-10V G ND 24V 0-10V G ND 24V
Y
GY
G
“EX” Con nector (twist lock)
1
2
3
4
5
6
7
8
White
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Red/White
Valve RHB Note 3
RV-B FP1-B FP1-B LP-B HP-B
Orange/ White (38)
Yellow (40)
Black
Blue/ White (42)
Black/ White (44)
CCCCB
RV T
T
Black (36)
Violet (35)
Orange/ Yellow White (41) (39)
Black
Blue/ White (43)
Black/ White (45)
P9 EH1 CC2 CC F C
P2
ES
LS
ALM ALG ACC COM
K5-Alarm Relay
ACC NO ACC NC
K6-Acc Relay
LO R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
C
P8
JW2
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F
K1-RV Relay
K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
Aurora Base Control B (ABC-B)
SW1 Test Mode
Com1 LED5
G RS485 NET
C R – + P7
RS485 EXP C R – + P6 CO C EH1 C EH2P3
Status LED3
G
PWM CFM
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
Y1 G CC
Black/White
To UPC
Bro wn (41) Bro wn (40)
WSE Condensate Bro wn (114)
Black/White (18)
Yellow (17 )
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
White
38
Note 3
Note 2 I sol ation Valve
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 460/60/3
Unit Power Input 460/60/3
G
L1
L2
L3
L1
L2
L3
Green / Yel low (G1) Compressor A
Green / Yel low (G2) Compressor B
Phase Gu ard Monitor (PG M)
L1 L2 L3
Blue (AC)
T3
T1
T2
Red (AB)
Black (AA) Blue (AF)
T3
T1
T2
Red (AE)
Black (AD)
CCA
T3
T2
T1
CCB
T3
T2
T1
Bro wn (AG) Orange (AH)
Yellow (AJ)
Black (X) White (Y) Red (Z)
PB1
2 Black/White (20)
Green/Yel low (15)
3
1
Green/Yel low (16)
Yellow (C) Orange (B) Bro wn (A)
Yellow (F) Orange (E) Bro wn (D)
Bro wn (G) Orange (H)
Yellow (J)
Bro wn (U)
Orange (V) Yellow (W)
Black/White
24V Tra nsformer
Black (14)
Yellow (13 ) Y-OUT
Yellow Cla ss 2 C
Y
Yellow (11 )
PGM
Black/White
Yellow (12 )
L3
L2
L1
Black Blue
Black
L3
L2
L1
Blower Motor L1 A L3
L2
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Black (K) White (L) Red (M)
See Note 4
Blower
Motor
B
L1
L3
L2
Control Box Base Panel
Green / Yel low (39)
Control Box Door
Accessor y Relay
Operation
SW2-4 SW2-5
Cycl e with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
24V Tra nsformer
Yellow (19 )
Yellow
Blue
Cla ss 2
PWM CFM
C
Factory Factory
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
CC2 Factory
G P5 LO HI CCG CC FG F R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1
JW2 Alarm
P2 Fi eld Connections
Off On
LED1 FP1 15oF/30oF
1
R FP2 15oF/30oF
2
Faul t
RV B/O
3
ACC Dip 4
4
LED3
ACC Dip 5
CC Dual/Si ngle
G L Pulse/Continuous
Status
Reheat/Normal
5 6 7 8 SW2
LED2 Y
Config
AURORA BASE CONTROLTM
Com1 G
RS485 Exp
EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7
RS 485
Factory Use
RS485 NET
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
CC C
Notes:
1 P1 (screw terminals) and P9 (Molex connector) are adjacent and share
common terminals in the same or der. 2 Optional isolation water valv e. 3
Optional hot gas reheat. 4 Sizes 240-360 equipped with two blowers .
Legend
Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal
L1
Fi eld Wiring Lug
1 2 3
T
Thermistor
Relay Coi l
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
Ground
Relay Con tacts N.O., N.C.
Capacitor
Fuse
Current Transducer
CCA Compressor A Contactor CCB Compressor B Contactor CO Condensate
Overfl ow Sensor ES Emergency Shutdown HP1 High Pressure Switch 1 HP2
High Pressure Switch 2 LP1 Low Pressure Switch 1 LP2 Low Pressure Switch 2
FP1 Freeze Protection Sensor 1 FP2 Freeze Protection Sensor 2 F1 Fuse
EX-XX
Pin Number Designation on Twist-Lock Connector
G
Light Emitting Diode – Green
Y
Light Emitting Diode – Yellow
R
Light Emitti ng Diode – Red
SW1 Push button SW2 DIP package 8 position RV1 Reversi ng Valve Coi l 1 RV2 Reversi ng Valve Coi l 2 PGM Phase Guard Moni tor RH Reheat Valve Coi l
39
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Aurora Advanced and Premium Controls Add-on
Note 1 Modulang Water Valve
~ Y
CO M
321
Gr ay
Black To PB1-2
Red
To PB1-1
L2
NO L2
NO
K5
DISCH P14 C R L1 L1
K6
SCT-A SUCP-A
LL T-A DISCH-A
HW SCT-B
SUCP-B
LL T-B
DISCH-B
1
EEV-A
2
3
4
1
EEV-B
2
3
4
Blac k
Gr ee n
Blac k
Gr ee n
DISCHARGE GND 1 PRESSURE OUT 2
TRANSDUCER 5DC 3
Black White Red
COM
COM
DISCH ARGE PRESSU RE TRANSDUCER
GND 1 OUT 2 5DC 3
Black White Red
K3 K2 K1
LLT P16
Gr ay Note 4
FL OW M ET E R
Brown T
Brown
Gr ay T
Gr ay
GND 3 3 OUT 2 2 5DC 4 4
Gr een White Brown
Purple T
Purple
White T
White
P2
EWT LWT FLOW LAT P1
Status G
AXBTM-A
(Aurora Expansion Board A)
P5 CT2 CT1 43 21
P11 ANA ACC2 DH DIV
Red Black
Note 3
0-10V Y
24V G
Bro wn/White T
Bro wn/White
Red Gr ay Black
G ND
U
Hot Gas Reheat
Blue
Compressor A T1
Valve Note 2
Blue
Red Compressor A T2
Red
Black Black
Auxi liary Heat CT
P15 CT2 CT1 4321
HA2 HA1 SGI P3 C S +5 C S +5 2 1 C OUT C IN LOOP VS DATA VS PUMP PUMP SLAVE
Red
White
Gr een
Gr ay
1+
Black
2 X1
P10 STEPPER
Heat Shrink “EX” Con nector (twist lock)
1 2 3
Modbus Add. ID Future Use Future Use
Acc 2 Dip 1 Acc 2 Dip 2
OFF ON 1 2 3 4 5
SW1
P12 SUC P
Ye ll ow Red
Or ang e
3 X2 4 Y1 5 Y2
Black 1 GND SUCTION White 2 OUT PRESSURE
Red 3 5DC TRANSDUCER
Blue( 66) T Blue( 67)
SCT
P18
4
5
6
Pink
HW
P17
P4
7
Pink
8
HOT WATER
9
OPTIO N
MOTOR RX TX R C V+ P8
RS485 (+) (-) R C P6
ZO NE (+) (-) R C P7
ABC (+) (-) R C +5 P9
10
11
12
13
To ABC-A
14
15
16
17
Green/Yel low
18
19
20
21
Notes:
22
23
24
1 Optional factor y installed modulating water valve. Requires Auror a Pr emium Controls
2 Optional factor y installed modulating hot gas reheat.
25
3 Optional Waterside Economizer.
26
4 Optional flow meter for field install only.
27
R
C
24V
GN D
P5
P2
+24 GN VD
+5V USB
USB
5A
GN
D
POW ER SUPPLY
BOARD
P1
P4
P3
4321 54321 4321 54321
28
29
AXB Accessory 2 DIP Sengs
30
SW1-4 SW1-5 DESCRIPTION
31
ON
ON Cycles with Blower
OFF
ON Cycles with CC rst stage compressor or compressor spd 1-12
ON
OFF Cycles with CC2 second stage of compressor or comp spd 7-12
OFF
OFF Cycles with DH from ABC board
ELECTRONIC EXPANSION
VALVE A
ELECTRONIC EXPANSION
VALVE B
Black White Gr een Red Or ang e Red Ye ll ow Black Gr ay Black White Gr een Red Orang e Red Ye ll ow Black Gr ay
40
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Aurora Advanced and Premium Controls Add-on
L2
NO L2
NO
K5
DISCH P14 C R L1 L1
K6
COM
COM
P11 ANA ACC2 DH DIV
K3 K2 K1
LLT P16
24V G
EWT LWT FLOW LAT P1
P2
HA2 HA1 SGI P3 C S +5 C S +5 2 1 C OUT C IN LOOP VS DATA VS PUMP PUMP SLAVE
P4
Status G
AXBTM-B
(Aurora Expansion Board B)
Modbus Add. ID Future Use Future Use
Acc 2 Dip 1 Acc 2 Dip 2
OFF ON 1 2 3 4 5
SW1
To ABC-B
P17
P18
P12 SUC P
P10 STEPPER
HW
SCT
P15 CT2 CT1 4321
P5 CT2 CT1 43 21
0-10V Y
Red Gr ay Black
G ND
U
Blue/W hite Blue/W hite Red/White Red/White
Hot Gas Reheat Valve Note 2
Compressor B T1
Compressor B T2
Black Black
Auxi liary Heat CT
Gr ay Black Ye ll ow Red Or ang e
1+ 2 X1 3 X2 4 Y1 5 Y2
Black 1 GND SUCTION White 2 OUT PRESSURE
Red 3 5DC TRANSDUCER
Blue T Blue
Legend
Factory Low Voltage Wiring
Factory Line Vol tage Wiring
T
Fi eld Low Voltage Wiring
Fi eld Li ne Voltage Wi ri ng
Optional Block
DC Voltage PCB Traces
Fi eld Zone Sensor Wi ri ng
Internal Ju nction
Qui ck Con nect Terminal
L1
Fi eld Wiring Lug
Ground Relay Con tacts N.O., N.C.
Capacitor G
Fuse
Current Transducer (CT)
Y
DISCH Discharge Pressure EWT Entering Water Temperature
R
HW Hot Water Gene ration
LAT Leaving Ai r Temperature
LLT Liquid Line Temperature
LWT Leaving Water Temperature
SCT Suction Temperature
SUCP Suction Pressure
1 2 3
EX-XX
Thermistor Relay Coi l Switch – Condensate Overfl ow Switch – High pressure
Switch – Low pressure
Polarized connector
Pin Number Designation on Twist-Lock Connector
Light Emitting Diode – Green Light Emitting Diode – Yellow
Light Emitti ng Diode – Red
Aurora Timing Events
Event
Normal Mode
Random Start Delay
5 to 80 seconds
Compressor On Delay
5 seconds
Compressor Minimum On Time
2 minutes
Compressor Short Cycl e Delay
4 minutes
Blower Off Delay
30 seconds
Faul t Recogn itio n Delay High Pressure
Less than 1 second
Start-Up Bypass Low Pressure
2 minutes
Faul t Recogn itio n Delay Low Pressure
30 seconds
Start-Up Bypass Low Water/Air Coil Limit
2 minutes
Faul t Recogn itio n Delay Low Water/Ai r Coil Limit 30 seconds
Faul t Recogn itio n Delay Condensate Overfl ow
30 seconds
Thermostat Call Recognition Time
2 seconds
Auxi liary Heat Stagi ng Del ay
5 minutes
Emergency Heat Stagi ng Dela y
2 minutes
Water Valve Slow Open Delay
90 seconds
Reheat Delay
30 seconds
Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds
Aurora LED Flash Codes
SlowFlash 1 second on and 1 second off
Fast Flash 100 mil liseconds on and 100 mi lliseconds off
Flash Code 100 mil liseconds on and 400 mi lliseconds off with a 2 second pause before re peating
Random Start Delay
Status LED (LED3, Green)
Fast Fl ash
Configuration LED (LED2, Yel low)
Fast Fl ash
Faul t LED (LED1, Red)
Fast Fl ash
Sta tus LED (LED3, Green)
Configuration LED (LED2, Yellow)
Fault LED (LED1, Red)
Normal Mode
ON
No Software Overi de Fl ash ECM Settin g Normal Mode
OFF
Control is Non-Functional
OFF DIP Switch Overide
Slow Flash Input Fault Lockout
Fl ash Code 1
Test Mode
Slow Flash ECM Configu re Mod e
Fast Fl ash High Pressure Lockout
Fl ash Code 2
Lockout Active
Fast Fl ash Reset Confi gure Mode
Off
Low Pressure Locko ut
Fl ash Code 3
Dehumidification Mo de
Fl ash Code 2
Low Air Coil Limi t Lockout – FP2 Fl ash Code 4
Reserved
Fl ash Code 3
Low Water Coil Limi t Lockout – FP1 Fl ash Code 5
Reserved
Flash Code 4
Loss of Charge Lockout
Fl ash Code 6
Load Shed
Fl ash Code 5
Condensate Overfl ow Lockout
Fl ash Code 7
ESD
Fl ash Code 6
Over/Under Vol tage Sh utdown
Fl ash Code 8
Reserved
Fl ash Code 7
Reserved
Fl ash Code 9
Compressor Monitor Lockout
Fl ash Code 1 0
Air/Water Coil Limit Sensor Error Fl ash Code 1 1
Page 1
41
MOTOR RX TX R C V+ P8
RS485 (+) (-) R C P6
ZO NE (+) (-) R C P7
ABC (+) (-) R C +5 P9
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Single Compressor 575/60/3
CC
Ultra Tech CS RCP
Blue Blue
See N ote 5
FP2/ RV FP1 LAT LP HP
Orange (1)
Yellow Black
Blue (7)
Black (9)
RV T
T
Black (19)
Violet (18)
Gray Red Red
Blue (22) Blue (23)
Orange Yellow (2)
Black
Blue (8)
Black (10)
See N ote 3
K1-RV Relay
K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
JW2
P9 EH1 CC2 CC F C
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C
P2 ES LS
R F1-3A
ALM ALG ACC COM ACC NO ACC NC
LO
K5-Alarm Relay
K6-Acc Relay
F
PWM
Aurora Base Control
SW1
Status
LED3
CFM
(ABC)
Test Mode
G
R C O/B G Y1 Y2 W DH P1
R Red
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
Com2 LED5
Com1 LED5
SW2 Config LED2
G RS485 NET
G RS485 NET
RS485 EXP
Y
C
P8
C R – + P7
C R – + P6 CO C EH1 C EH2 P3
Y1 G CC
Black
Black
Reh eat Valve See N ote 2
To UPC
See N ote 4
Aurora Advanced and Premiu m Opon
Red Heat Shrink
White Gr een
T T
Gr ay Gr ay Gr een White
Brown Vio le t Vio le t White White
GND 3 OUT 2 5DC 4
Brown Brown
Bro wn (25) Bro wn (24)
Condensate
FLOW
T
METER
DISCH ARGE PRESSU RE TRANSDUCER
T
Black White Red
GND 1 OUT 2 5DC 3
MOTOR RX
TX
R
C
V+ P8
RS485 (+)
(-)
R
C P6 ZO NE (+)
(-)
R
C P7 ABC (+)
(-)
R
C
+5 P9
P4
P2
HA2 HA1 SGI P3 C S +5 C S +5 2 1 C OUT C IN LOOP VS DATA VS PUMP PUMP SLAVE
EWT LWT FLOW LAT P1
LLT P16
Status G
AX BTM
(Aurora Expansion Board)
Modbus Add. ID Future Use Future Use
Acc 2 Dip 1 Acc 2 Dip 2
OFF ON 1 2 3 4 5
SW1
P17 HHWW 21
P18 SCT 321
P12 SCP
321
P10 STEPPER
K3 K2 K1
P15 CT2 CT1 4321
P5 CT2 CT1 4321
P11 ANA ACC2 DH DIV
Pink T
Pink
T
Blue Blue
Black White Red
1 GND SU CTI ON 2 OUT PRES SU RE 3 5DC T RA NSD UCE R
DISCH P14 C
R
L1
L1 K6
COM
NO
K5
COM
NO L2
L2
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
L1
Bla Bla Yello
Modulang Water Valve
Gray
Y
321
Red
~
Black
CO M
24V G
0-10V Y
G ND
U
Red Gr ay Black
Hot Gas Reheat Valve Note 2
Red Black
Note 4
Blue
Compressor T1
Blue
Red Compressor T2
Red
42
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Single Compressor 575/60/3
Unit Power Supply
Non-Fuse d Di sconne ct or T ermi na l Bl oc k
G
L1
L2
L3
Green / Yel low (G1) Compressor
L1
L2
L3
T3
T1
T2
Yellow (AC) Orange (AB) Bro wn (AA)
CC
T3
T2
T1
L3
L2
L1
Phase Guard Monitor (PG M)
L1 L2 L3
Bro wn (A) Orange (B) Yellow (C)
Black (K) White (L) Red (M) Bro wn (AG) Orange (AH) Yellow (AJ)
L2
L1
L3
Blower Motor
Black (16) Black
Yellow (17 )
Green/ Yellow (15 )
460V
X1
575V
H1
X2
H2
X3
H3
Class N
Control Box Base Panel
PB1
Green/Yel low (29)
Control Box Door
2 Green/Yel low (14)
3 Black (13)
Black/White
1 C
Yellow (12 )
Y-OUT
Y
PGM
Yellow
Tra nsformer
Black
Blue Cla ss 2
97P8 95-08 03/01/21
Aurora LED Flash Codes
SlowFlash 1 second on and 1 second off
Fast Flash 100 milliseconds on and 100 milliseconds off
Flash Code 100 mil liseconds on and 400 mi lliseconds off with a 2 second pause before re peating
Random Start Delay
Status LED (LED3, Green)
Fast Fl ash
Configuration LED (LED2, Yel low)
Fast Fl ash
Faul t LED (LED1, Red)
Fast Fl ash
Sta tus LED (LED3, Green)
Configuration LED (LED2, Yellow)
Fault LED (LED1, Red)
Normal Mode
ON
No Software Overi de Fl ash ECM Settin g Normal Mode
OFF
Control is Non-Functional
OFF DIP Switch Overide
Slow Flash Input Fault Lockout
Flash Code 1
Test Mode
Slow Flash ECM Configu re Mod e
Fast Fl ash High Pressure Lockout
Fl ash Code 2
Lockout Active
Fast Fl ash Reset Confi gure Mode
Off
Low Pressure Locko ut
Fl ash Code 3
Dehumidification Mo de
Fl ash Code 2
Low Air Coil Limi t Lockout – FP2 Fl ash Code 4
Reserved
Fl ash Code 3
Low Water Coil Limi t Lockout – FP1 Fl ash Code 5
Reserved
Fl ash Code 4
Loss of Charge Lockout
Fl ash Code 6
Load Shed
Fl ash Code 5
Condensate Overfl ow Lockout
Fl ash Code 7
ESD
Fl ash Code 6
Over/Under Vol tage Sh utdown
Fl ash Code 8
Reserved
Flash Code 7
Reserved
Fl ash Code 9
Compressor Monitor Lockout
Fl ash Code 1 0
Air/Water Coil Limit Sensor Error Fl ash Code 1 1
Accessor y Relay
Operation
SW2-4 SW2-5
Cycl e with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
Aurora Timing Events
Event
Normal Mode
Random Start Delay
5 to 80 seconds
Compressor On Delay
5 seconds
Compressor Minimum On Time
2 minutes
Compressor Short Cycl e Delay
4 minutes
Blower Off Delay
30 seconds
Fault Recogn itio n Delay High Pressure
Less than 1 second
Start-Up Bypass Low Pressure
2 minutes
Fault Recogn itio n Delay Low Pressure
30 seconds
Start-Up Bypass Low Water/Ai r Coil Limit
2 minutes
Faul t Recogn itio n Delay Low Water/Ai r Coil Limit 30 seconds
Faul t Recogn itio n Delay Condensate Overfl ow
30 seconds
Thermostat Call Recognition Time
2 seconds
Auxi liary Heat Stagi ng Del ay
5 minutes
Emergency Heat Stagi ng Dela y
2 minutes
Water Valve Slow Open Delay
90 seconds
Reheat Delay
30 seconds
Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds
Notes:
1 P1 (screw ter minals) and P9 (Molex connector ) are adjacent and share
common terminals in the same order. 2 Optional factor y installed hot gas
reheat. 3 Optional factor y installed internal isolation valve. 4 See
supplemental schematic for AXB and/or UPC connections. 5 LAT location with
Aurora Base Controls, FP2 with Aurora Advanced and Premium Controls.
PWM CFM
C
1 2 3
24V
T1 mpressor T2
HP P4
ECM PWM
HP
P13
LP
LP
FP2
Factory
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
CC2 Factory
G P5 LO HI CCG CC FG F R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1
JW2 Alarm
P2 Fi eld Connections
LED1 R
Off FP1 15oF/30oF
FP2 15oF/30oF
On 1 LED2
2Y
Faul t
RV B/O
ACC Dip 4
3 Config 4
LED3
ACC Dip 5
CC Dual/Si ngle
G L Pulse/Continuous
Status
Reheat/Normal
5 6 7 8 SW2
AURORA BASE CONTROLTM
Com1 G
RS485 Exp
Factory
EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7
RS 485
Factory Use
RS485 NET
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
CC C
Legend
Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Ju nction Quick Con nect Terminal
L1
Field Wiring Lug
T
Thermistor
Relay Coi l
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
EX-XX
Ground Relay Con tacts N.O., N.C.
Pin Number Designation on Twist-Lock Connector
Capacitor Fuse
G
Light Emitti ng Diode – Green
Current Transducer
Y
Light Emitti ng Diode – Yellow
CC Compressor Contactor CO Condensate Overfl ow Sensor ES Emergency Shutdown EWT Entering Water Temp Sensor HP High Pressure Switch LAT Leaving Ai r Temp LLT Liqui d Line Temp LP Low Pressure Switch LWT Leaving Water Temp
R
Light Emitting Diode – Red
FP1 Freeze Protection Sensor 1 FP2 Freeze Protection Sensor 2 SW1 Push button SW2 DIP package 8 position RV Reversi ng Valve Coi l PGM Phase Guard Moni tor RH Reheat Valve Coi l
43
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Base 575/60/3
RV-A FP1-A
LP-A HP-A RV-B FP1-B LP-B HP-B RH-A RH-B
Note 2 Isol ation Valve
“EX” Con nector (twist lock)
1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 19 20 22 23 25 26 27
Red/White
Black Red
Red Red Note 2
Black (32) CCCCA Violet (31)
RV-A FP1-A LAT LP-A HP-A
Orange Yellow
Blue Black
(28) 30 Gray (32) (34)
RV T
T
Yellow
Orange (31) Gray Blue Black
(29)
(33) (35)
JW2
P9 EH1 CC2 CC F C
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C
K1-RV Relay
P2 ES LS
R F1-3A
K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay
ALM ALG ACC COM
K5-Alarm Relay
Gray
ACC NO
K6-Acc
ACC NC
Relay
LO
F
PWM
Aurora Base Control A
SW1
Status LED3
CFM
(ABC-A)
Test Mode
G
R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
Com1 LED5
G RS485 NET
RS485 EXP
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
C
P8
C R – + P7
C R – + P6 CO C EH1 C EH2P3
Y1 G CC
Valve RHA Note 3
Black
To UPC
CCCCB
Bro wn (38)
Bro wn (37)
Condensate
470
RV-B
Resistor FP1-B
LP-B
HP-B
Orange/ White (38)
Yellow (40)
Blue/ Black/ White White (42) (44)
RV T
Black (36)
Violet (35)
Orange/ White
Yellow (41)
(39)
Blue/ Black/ White White (43) (45)
JW2
P9 EH1 CC2 CC F C
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C
K1-RV Relay
P2 ES LS
R F1-3A
K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
ALM ALG ACC COM ACC NO ACC NC
LO
K5-Alarm Relay
K6-Acc Relay
Aurora Base Control B
SW1
Status LED3
(ABC-B)
Test Mode
G
F PWM CFM
White
R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
Com1 LED5
G RS485 NET
RS485 EXP
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
C
P8
C R – + P7
C R – + P6 CO C EH1 C EH2P3
Y1 G CC
Valve RHB Note 3
Black/White
To UPC
Bro wn (41)
Bro wn (40)
Condensate
44
Note 3
Note 2 Isol ation Valve
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Base 575/60/3
Unit Power Input 575/60/3
Green / Yel low (G1) Compressor A
Green / Yel low (G2) Compressor B
Yellow Orange Bro wn
Yellow Orange Bro wn
G
L1
L1
L2
L3
L2
L3
Phase Gu ard Monitor (PG M)
L1 L2 L3
Blue (AC)
T3
T1
T2
Red (AB)
Black (AA) Blue (AF)
T3
T1
T2
Red (AE)
Black (AD)
CCA
T3
T2
T1
CCB
T3
T2
T1
Bro wn (AG) Orange (AH)
Yellow (AJ)
57 5V H1
46 0V X1
H2
X2
H3
X3
Class N
57 5V H1
46 0V X1
H2
X2
H3
X3
Class N
PB1
Black/White (18) 2
Black/White (20)
Green/Yel low (15)
3
Yellow (17 )
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
1 Green/Yel low (16)
Yellow (19 )
Yellow (C) Orange (B) Bro wn (A)
Yellow (F) Orange (E) Bro wn (D)
Bro wn (G) Orange (H) Yellow (J)
Bro wn (U)
Orange (V) Yellow (W)
L3
L2
L1
Black/White
24V Tra nsformer
Black (14)
Yellow (13 ) Y-OUT
Yellow
Cla ss 2
C
Y
Yellow (11 )
PGM
Black/White
Yellow (12 )
24V Tra nsformer
Yellow
Cla ss 2
Black Blue
Black Blue
PWM CFM
C
Factory Factory
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
CC2 Factory
G P5 LO HI CCG CC FG F R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1
JW2 Alarm
P2 Fi eld Connections
LED1 R
Off FP1 15oF/30oF
FP2 15oF/30oF
On 1 LED2
2Y
Faul t
RV B/O
ACC Dip 4
3 Config 4
LED3
ACC Dip 5
CC Dual/Si ngle
G L Pulse/Continuous
Status
Reheat/Normal
5 6 7 8 SW2
AURORA BASE CONTROLTM
Com1 G
RS485 Exp
EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7
RS 485
Factory Use
RS485 NET
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
CC C
L3
L2
L1
Blower Motor L1 A L3
L2
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Black (K) White (L) Red (M)
See Note 4
Blower
Motor
B
L1
L3
L2
Black (X) White (Y) Red (Z)
Control Box Base Panel
Green / Yel low (39)
Control Box Door
Accessor y Relay
Operation
SW2-4 SW2-5
Cycl e with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
Notes:
1 P1 (screw terminals) and P9 (Molex connector) are adjacent and share
common terminals in the same or der. 2 Optional isolation water valv e. 3
Optional hot gas reheat. 4 Sizes 240-360 equipped with two blowers .
Legend
Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal
L1
Fi eld Wiring Lug
1 2 3
T
Thermistor
Relay Coi l
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
Ground
Relay Con tacts N.O., N.C.
Capacitor
Fuse
CCA Compressor A Contactor CCB Compressor B Contactor CO Condensate
Overfl ow Sensor ES Emergency Shutdown HP1 High Pressure Switch 1 HP2
High Pressure Switch 2 LP1 Low Pressure Switch 1 LP2 Low Pressure Switch 2
FP1 Freeze Protection Sensor 1 FP2 Freeze Protection Sensor 2 F1 Fuse
EX-XX
Pin Number Designation on Twist-Lock Connector
G
Light Emitting Diode – Green
Y
Light Emitting Diode – Yellow
R
Light Emitti ng Diode – Red
SW1 Push button SW2 DIP package 8 position RV1 Reversi ng Valve Coi l 1 RV2 Reversi ng Valve Coi l 2 PGM Phase Guard Moni tor RH Reheat Valve Coi l
45
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 575/60/3
Note 2 Isol ation Valve
Black Red
Red Red Note 2
Black (32) CCCCA Violet (31)
RV-A FP1-A FP2-A LP-A HP-A
Orange Yellow
Blue Black
(28) 30 Gray (32) (34)
RV T
T
Yellow
Orange (31) Gray Blue Black
(29)
(33) (35)
JW2
P9 EH1 CC2 CC F C
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C
K1-RV Relay
P2 ES LS
R F1-3A
K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay
ALM ALG ACC COM
K5-Alarm Relay
Gray
ACC NO
K6-Acc
ACC NC
Relay
LO
F
PWM
Aurora Base Control A
SW1
Status LED3
CFM
(ABC-A)
Test Mode
G
R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
Com1 LED5
G RS485 NET
RS485 EXP
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
C
P8
C R – + P7
C R – + P6 CO C EH1 C EH2P3
Y1 G CC
Valve RHA Note 3
Black
To UPC
Bro wn (38) Bro wn (37)
WSE Condensate Bro wn (113)
RV-A FP1-A LP-A HP-A WSE RV-B FP1-B LP-B HP-B RH-A
RH-B
0-10V G ND 24V 0-10V G ND 24V
Y
GY
G
“EX” Con nector (twist lock)
1
2
3
4
5
6
7
8
White
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Red/White
Valve RHB Note 3
CCCCB
RV-B FP1-B FP2-B LP-B HP-B
Orange/ White (38)
Yellow (40)
Black
Blue/ White (42)
Black/ White (44)
RV T
T
Black (36)
Violet (35)
Orange/ White
Yellow (41)
(39)
Black
Blue/ White (43)
Black/ White (45)
P9 EH1 CC2 CC F C
P2
ES
LS
ALM ALG ACC COM
K5-Alarm Relay
ACC NO ACC NC
K6-Acc Relay
LO R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R
Com2 LED5
G RS485 NET
C P8
JW2
R
F
FG
CC
CCGCHCI2
CC2 LO
CC2 G
P5
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F
K1-RV Relay
K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
Aurora Base Control B (ABC-B)
SW1 Test Mode
Com1 LED5
G RS485 NET
C R – + P7
RS485 EXP C R – + P6 CO C EH1 C EH2P3
Status LED3
G
PWM CFM
Faul t
C
LED1
P13
R
Off On
FP1 15°F/30°F
1
FP2 15°F/30°F
2
RV B/O
3
Acc Dip 4
4
Acc Dip 5
5
CC Dual/Si ngle
6
L Output Type
7
Reheat/Normal
8
SW2 Config
LED2
Y
Y1 G CC
Black/White
To UPC
Bro wn (41) Bro wn (40)
WSE Condensate Bro wn (114)
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
White
46
Note 3
Note 2 I sol ation Valve
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 575/60/3
Unit Power Input 575/60/3
Green / Yel low (G1) Compressor A
Green / Yel low (G2) Compressor B
Yellow Orange Bro wn
Yellow Orange Bro wn
G
L1
L1
57 5V H1
46 0V X1
H2
X2
H3
X3
Class N
57 5V H1
46 0V X1
H2
X2
H3
X3
Class N
PB1
Black/White (18) 2
Black/White (20)
Green/Yel low (15)
3
Yellow (17 ) 1
Green/Yel low (16)
L2
L3
L2
L3
Phase Gu ard Monitor (PG M)
L1 L2 L3
Blue (AC)
T3
T1
T2
Red (AB)
Black (AA) Blue (AF)
T3
T1
T2
Red (AE)
Black (AD)
CCA
T3
T2
T1
CCB
T3
T2
T1
Bro wn (AG) Orange (AH)
Yellow (AJ)
Yellow (C) Orange (B) Bro wn (A)
Yellow (F) Orange (E) Bro wn (D)
Bro wn (G) Orange (H) Yellow (J)
Bro wn (U)
Orange (V) Yellow (W)
L3
L2
L1
Black/White
Black
L3
L2
L1
Blower Motor L1 A L3
L2
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Gnd Disconnect
L1
L1
L2
L2
L3
L3
Black (K) White (L) Red (M)
See Note 4
Blower
Motor
B
L1
L3
L2
24V Tra nsformer
Black (14)
Yellow (13 ) Y-OUT
Yellow
Cla ss 2
C
Y
Yellow (11 )
PGM
Black/White
Yellow (12 )
Blue Black
Control Box Base Panel
Green / Yel low (39)
Control Box Door
Accessor y Relay
Operation
SW2-4 SW2-5
Cycl e with Blower
On On
Cycl e with Compressor
Off Off
Water Valve Slow Open On Off
Outdoor Air Damper
Off On
Black (X) White (Y) Red (Z)
24V Tra nsformer
Yellow (19 )
Yellow
Blue
Cla ss 2
PWM CFM
C
Factory Factory
HP P4
ECM PWM
HP
P13
LP
LP
FP2
FP2
FP1
FP1
SW1 Test
REV
REV
RV K1
CC2 CC K2
CC2 Factory
G P5 LO HI CCG CC FG F R
F
CC Hi K3 Fan K4 Alarm K5
CC
Acc K6
G
Y1
JW2 Alarm
P2 Fi eld Connections
Off On
LED1 FP1 15oF/30oF
1 LED2
R FP2 15oF/30oF
2Y
Faul t
RV B/O
ACC Dip 4
3 Config 4
LED3
ACC Dip 5
CC Dual/Si ngle
G L Pulse/Continuous
Status
Reheat/Normal
5 6 7 8 SW2
AURORA BASE CONTROLTM
Com1 G
RS485 Exp
EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7
RS 485
Factory Use
RS485 NET
P11
P9
Factory Fan Connection
P8 Com2 G
DH
W
Y2
Y1
G
O/B
C
R
LO
P1
Fi eld Connections
3A-Fuse
DH
W
Y2
Y1
G
O/B
C
R
LO
ES LS ALM ALG ACC c ACC no ACC nc
RR
CC C
Notes:
1 P1 (screw terminals) and P9 (Molex connector) are adjacent and share
common terminals in the same or der. 2 Optional isolation water valv e. 3
Optional hot gas reheat. 4 Sizes 240-360 equipped with two blowers .
Legend
Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal
L1
Fi eld Wiring Lug
1 2 3
T
Thermistor
Relay Coi l
Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
Ground
Relay Con tacts N.O., N.C.
Capacitor
Fuse
Current Transducer
CCA Compressor A Contactor CCB Compressor B Contactor CO Condensate
Overfl ow Sensor ES Emergency Shutdown HP1 High Pressure Switch 1 HP2
High Pressure Switch 2 LP1 Low Pressure Switch 1 LP2 Low Pressure Switch 2
FP1 Freeze Protection Sensor 1 FP2 Freeze Protection Sensor 2 F1 Fuse
EX-XX
Pin Number Designation on Twist-Lock Connector
G
Light Emitting Diode – Green
Y
Light Emitting Diode – Yellow
R
Light Emitti ng Diode – Red
SW1 Push button SW2 DIP package 8 position RV1 Reversi ng Valve Coi l 1 RV2 Reversi ng Valve Coi l 2 PGM Phase Guard Moni tor RH Reheat Valve Coi l
47
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
084-300 Single/Dual Compressor Aurora UPC
Orange Red
White Black
BACnet or N2 Network
Connections
Devices Must Be Wired in Daisy Chain Configuration
Orange Red
White Black
1 2 3 4 5 6 7 8 To ABC-A – P8
Blue Green
Br own Yellow
1 2 3 4 5 6 7 8 To ABC-B – P8 Dual Compressor Only
Blue Green
Br own Yellow
NET+ NETCOM NET+ NETCOM
12345678
ZS Sensor 1 Addr: 0
GND RNET+ RNET-
+12V
ZS Sensor 2 Addr: 1
GND RNET+ RNET-
+12V
ZS Sensor 3 Addr: 2
GND RNET+ RNET-
+12V
NET+ NETCOM
NET+ NETN/C N/C Signal
LE D1 TX
LE D2 RX
LON A DA P TER
P ORT
LE D6 TX
LE D7
2W RX
4W
GND RNET+ RNET+ 12 V
RNET
GND LN+ LN+12
/S
LOCAL ACCESS
ZS Sensor Information
Zone Sensors can be wired in daisy chain as show or in a star or hybrid configuration. Maximum of 5 sensors per UPC. Maximum allowable load 210mA. See the UPC install manual for possible sensor combinations.
DIP Switch Value
1 2 4 8
ON 1 2 34
Each ZS sensor must have a unique address, but the addresses do not need to be sequential. Use the DIP switches on the back of the ZS sensor to set an address from 0 to 4. (0 is the factory default.) Each DIP switch has the value shown in the figure to the left. Turn on as many DIP switches as you need so that their total value equals the address.
48
LE D3 P OWER
P OWER
GND 24 VAC
FORM AT B ATT
Communication Options
NOTE 1
LE D4 RUN
LE D5 E RR
ON
TEN’S
89 0 12 73
654
89 0 12 73
654
ONE’S
MAC Address Setting
Notes
1. Use DIP Switches 5 8 to change communication protocol and DIP switches 1
2 to change BACnet baud rate. 2. DDC functionality available where
specifically indicated in the product controls options.
Legend
Factory Low Voltage Wiring Field Low Voltage Wiring
12345678 RJ45 Connector
VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Aurora Controls
Aurora Controls
The Aurora Control System is a complete commercial comfort system that can
bring all aspects of the HVAC system into one cohesive module network. The
Aurora System is available in two configurations: Aurora Base Control and
Aurora Advanced and Aurora Premium Control both with optional Aurora UPC for
DDC applications.
Control Aurora Base
Control
Aurora Advanced and Premium
Aurora Base/ Aurora Advanced
Control w/UPC BACnet or N2
General Description
Application
The ABC microprocessor provides all the features necessary to operate today’s standard WSHPs that utilize dual capacity compressors and variable speed ECM/5 speed ECM blower motors with hot gas reheat. This control can communicate to a handheld diagnostic tool to help the installing contractor or service technician with equipment setup and service. By utilizing Modbus RTU communication protocol, the ABC board can communicate with additional devices on the Aurora network
Used for residential and commercial applications that use single or dual capacity compressors with PSC, 5-speed ECM, or variable speed ECM blower motors. This base control can also communicate to the AID Tool to display faults, inputs/outputs, and software revision. Commercial features such as hot gas reheat, slow opening water valve, and random start are also capable with the ABC board.
Display/Interface
Optional AID toll can be used for field service.
Protocol Standalone
Aurora Advanced Control adds the Aurora AXB expansion board and provides added I/O and standard features such as refrigerant, performance or energy monitoring.
· Refrigeration Monitoring provides Suction and discharge pressure, Suction,
liquid line temps and superheat and subcooling.
· Performance Monitoring provides entering and leaving loop water
temperatures, loop flow rate as well as heat of extraction or rejection rate
into the loop.
· Energy Monitoring provides realtime power measurement (Watt) of
compressor, fan, auxiliary heat and zone pump.
· Plus many more I/O options
Optional AID tool can be used for field service.
The Aurora Unitary Protocol Converter (UPC) is an integrated solution and communicates directly with the Aurora Heat Pump Controls and allows access/control of a variety of internal Aurora heat pump operations such as sensors, relay operation, faults and other information. In turn, the UPC then converts internal Aurora Modbus protocol to BACnet MS/TP, or N2 protocols and communicates to the BAS system. This provides the great benefit of complete control integration and a myriad of information available to the BAS from the heat pump control. Plus it also allows individual unit configuration such as ECM fan speeds or freeze protection setting directly over the BAS without the need for access to the actual heat pump.
The Aurora UPC is implemented with the Aurora heat pump control into our latest water source heat pumps. All Internal Aurora points are accessible to the UPC via firmware providing an integrated solution. All zone temperatures and zone sensors are connected to the UPC on an RNet bus, simplifying hook up at the unit. RNet sensors can include a combination of zone temperature and humidity, CO2, and VOC sensors. The UPC includes built-in support
References
Read User Manual Online (PDF format)