WaterFurnace VERSATEC 500 7-30 Water Source Heat Pump Instruction Manual

June 9, 2024
WaterFurnace

VERSATEC 500 7-30 Water Source Heat Pump

Versatec 500 WSHP 7-30 Ton Installation Manual

Formerly Versatec XL Commercial Water Source/Geothermal Heat Pump
· R-410A Refrigerant · 7-30 Tons
Installation Information Water Piping Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance
IM2770AU 03/22

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Electrical Availability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Installation Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Duct System, Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 System Cleaning and Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Open Loop Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Freeze Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Blower Performance Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Controls – Aurora Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Unit Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56 Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Operating Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Reference Calculations and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59 Refrigerant Circuit Guideline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Startup/Troubleshooting Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63 Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65 Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65 Revision Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Model Nomenclature

1-2 3 4-6 7 UD V 096 T

8 9 10 11 12 13 14 15 16 17 18 19 20 21 22-23 24 L 3 N 5 0 D A N A N 0 A 1 N SS *

Model Type Versatec XL Series
Cabinet Configuration V ­ Vertical (084-360) H ­ Horizontal (084-180) T ­ Vertical Take-a-Part (240-360)
Unit Capacity 084, 096, 120, 150, 180. 240, 300, 360
Discharge Configuration T ­ Top/Side (Vertical) E ­ End/Side (Horizontal)
Return Air Configuration L ­ Left R ­ Right
Voltage 3 ­ 208-230/60/3 4 ­ 460/60/3 5 ­ 575/60/31
Refrigeration Option N ­ Standard, None G ­ Hot Gas Bypass M ­ Modulating Hot Gas Reheat²³ P ­ Modulating Hot Gas Reheat with Hot Gas Bypass²³
Blower Option 5 ­ Variable Speed ECM- Backward Inclined, Standard
Future Option 0 ­ Future
Water Coil Option C ­ Copper, Uninsulated D ­ Insulated Copper
Sound Kit Option A ­ None B ­ Sound Kit

Vintage *­ Factory Use
Non-Standard Options SS ­ Standard
Economizer Option N ­ None W ­ Waterside Economizer²
Air Coil Option 1 ­ All Aluminum, Uncoated 2 ­ All Aluminum, AlumiSeal
Future Option N ­ Standard
Cabinet Option 2 ­ Unpainted Cabinet, 4-Sided Rack (Horizontal) 3 ­ Painted Cabinet, 4-Sided Rack (Vertical)
Electrical Option N ­ Standard D ­ Non-Fused Disconnect
Control Option A ­ Standard, None C ­ AuroraTM Advanced D ­ AuroraTM Premium E ­ AuroraTM with BACnet G ­ AuroraTM Advanced with BACnet H ­ AuroraTM Premium with BACnet
Water Control Option N ­ Standard, None V ­ 2-Way Valve M- Head Pressure4

Note: 1- 575V option includes factory installed step down transformer on plenum fan. 2- Requires Advanced or Premium Controls. 3- Not available on UDH180 4- Head Pressure Control requires Premium Controls and Modulating Hot Gas Reheat.

Electrical Availability

Voltage
208-230/60/3 460/60/3 575/60/3
Voltage
208-230/60/3 460/60/3 575/60/3
– Available

Dual Capacity Compressor

084

096

120

Two Compressor

150

180

240

300

360
3/30/21

4

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

General Installation Information

Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available.

Unit Location Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
WARNING: To avoid equipment damage and possible voiding of warranty, be sure that properly sized strainers are installed upstream of both brazed plate heat exchangers to protect them against particles in the fluid.

Moving and Storage
Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.

Installing Vertical Units
Prior to setting the unit in place, remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket.
Vertical units are available in left or right air return configurations. Top flow vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor (see figure below).

Vertical Unit Mounting

2 in. PEX Foam

5

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Dimensional Data

LEFT RETURN SHOWN

“N”

1.0

“J”

“M”

“B”

“H”

“L”

TOP DISCHARGE FIELD REMOVABLE
BLOWER PANEL INSERT

2.1

“G”

1.00

“L”

“M”

2.3

BLOWER ACCESS PANEL “K”

“C”

DRAIN CONNECTION

1.8 (4)

“P” BOTH SIDES

BLOWER ACCESS PANEL

“N”
SIDE DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT

“F” “E” “D”

CONTROL BOX ACCESS DOOR

“R” BOTH SIDES

“A”

Vertical Dimensional Data

Overall Cabinet

Water Connections

Return Connection*

Vertical Models A
Width
084-096 in. 34.0 cm. 86.4
120 in. 34.0 cm. 86.4
150-180 in. 34.0 cm. 86.4

B
Depth
36.3 92.2 36.3 92.2 46.3 117.5

12 3

C DE

F

Loop

Cond- Water Height In Out
ensate FPT

72.5 8.1 15.1 22.1 1 1/4″

184.2 20.6 38.4 56.1 31.8 mm

72.5 8.1 15.1 22.1 2″

184.2 20.6 38.4 56.1 50.8 mm

72.5 8.1 15.1 22.1 2″

184.2 20.6 38.4 56.1 50.8 mm

using delux e filter rack

G

H

J

K

Filter From Return Return

Rack Edge Depth Height

3.1

3.2 29.9 37.8

7.9

8.1 75.9 96.0

3.1

3.2 29.9 37.8

7.9

8.1 75.9 96.0

3.1

2.2 39.9 37.8

7.9

5.6 101.3 96.0

*Dimensions for return connnections are for the deluxe filter rack that is suitable for ducted return applications

Discharge Connection Electrical Connections

L

M

N

P

R

From Supply Supply From H eight
Edge Width Height Edge

4.1 28.0 16.0 3.9 27.4

10.4 71.1 40.6 9.9 69.6

4.1 28.0 16.0 3.9 27.4

10.4 71.1 40.6 9.9 69.6

4.1 38.0 16.0 3.9 27.4

10.4 96.5 40.6 9.9 69.6

6

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Dimensional Data cont.

LEFT RETURN SHOWN

1.4 “F”

DRAIN CONNECTION “J”

“N”

2.1

1.7

“K”

“G”

“L”

“H”
END DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES

SIDE DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES

1.7

“J”

1.0

DUCT FLANGE

“H”

“K”

AIR COIL “M”
“B”

“V”
BLOWER ACCESS
PANEL

“A”

“U”

40.00

“P” “R”

“P”

“T”

“R”

1 5/8″ UNISTRUT

42″ CUT LENGTH

3 REQUIRED NOT SUPPLIED
BY WFI

1.8 (3)

CONTROL BOX

“C”

ACCESS DOOR

“E”

“D”

42.00
Horizontal Dimensional Data

Overall Cabinet

Water Connections

Discharge Connection

Horizontal

12 5

Models

A

B

C DE F

Loop

G

H

J

K

Width Depth Height In Out Cond- Water Filter Rack From Supply Supply ensate FPT Width Edge Height Width

084-096 in. 34.0 89.0 29.9 8.1 15.1 3.2 1 1/4″

3.1

5.0 24.0 24.0

cm. 86.4 226.1 75.9 20.6 38.4 8.1 31.8 mm 7.9

12.7 61.0 61.0

120 in. 34.0 89.0 29.9 8.1 15.1 3.2

2″

3.1

5.0 24.0 24.0

cm. 86.4 226.1 75.9 20.6 38.4 8.1 50.8 mm 7.9

12.7 61.0 61.0

150-180 in. 34.0 110.0 29.9 8.1 15.1 3.2

2″

3.1

5.0 24.0 24.0

cm. 86.4 279.4 75.9 20.6 38.4 8.1 50.8 mm 7.9

12.7 61.0 61.0

*Dimensions for return connnections are for the deluxe filter rack that is suitable for ducted return applications

Return Connection*

using delux e filter rack

L

M

N

From Return Return

Edge Depth Height 4.3 47.6 23.5

10.9 120.9 59.7

4.3 47.6 23.5

10.9 120.9 59.7

4.3 65.6 23.5

10.9 166.6 59.7

Electrical Connections

P

R

From Height Edge 3.9 25.9

9.9 65.8

3.9 25.9

9.9 65.8

3.9 25.9

9.8 65.8

Unistrut Hanging

T

U

V

From Unistrut/ Unistrut/

Edge Unistrut Unistrut

1.7 24.6 61.0

4.3 62.5 154.9

1.7 24.6 61.0

4.3 62.5 154.9

1.7 35.1 71.5

4.3 89.2 181.6

7

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Dimensional Data cont.

16.88 3.40

1.50

16.08

POWER SUPPLY LEFT RETURN
8.10

240-360 RIGHT RETURN
SHOWN

48.08

71.90

20.00 3.40

POWER SUPPLY RIGHT RETURN
7.00 34.00

8.10 REF

36.90

1.00

1.70

TOP DISCHARGE FIELD REMOVABLE
BLOWER PANEL INSERT

88.00

CONTROL BOX ACCESS DOOR

46.00 80.00

7/8″ O.D. DRAIN CONNECTION
WATER OUT 2″ FPT
WATER IN 2″ FPT

31.30 7.00
8.00

6.60

20.80

1.90 (3)

1.80
32.62
8

22.75 REF

32.62

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Dimensional Data cont.

UDV084-180 TOP FLOW ECONOMIZER OPTION LR

“N”

1.0

“J” “M” “B”

“H”

“L”

4.5

TOP DISCHARGE

FIELD REMOVABLE

BLOWER PANEL

INSERT

“G”

2.1

“A”

1.00

“L”

“M”

2.3

“K”
DRAIN CONNECTION
“E” “D”

BLOWER ACCESS PANEL
1.8 CONTROL BOX ACCESS DOOR
“F”

TOP DISCHARGE FIELD REMOVABLE
BLOWER PANEL INSERT

“C”

“P”

BOTH

SIDES

“R” BOTH SIDES

“N”
BLOWER ACCESS PANEL

4.1

34.0

VERSATEC XL – Vertical Dimensional Data

Overall Cabinet

Water Connections

Vertical Models A
Width
084-096 in. 41.2 cm. 104.6
120 in. 41.2 cm. 104.6
150-180 in. 41.2 cm. 104.6

B
Depth
36.3 92.2 36.3 92.2 46.3 117.5

12 3

C DE

F

Loop

Cond- Water Height In Out
ensate FPT

72.5 13.9 23.5 22.1 1 1/4″

184.2 35.3 59.7 56.1 31.8 mm

72.5 13.9 23.5 22.1 2″

184.2 35.3 59.7 56.1 50.8 mm

72.5 14.7 24.2 22.1 2″

184.2 37.3 61.5 56.1 50.8 mm

Return Connection*

using delux e filter rack

G

H

J

K

Filter From Return Return

Rack Edge Depth Height

3.1

3.2 29.9 37.8

7.9

8.1 75.9 96.0

3.1

3.2 29.9 37.8

7.9

8.1 75.9 96.0

3.1

2.2 39.9 37.8

7.9

5.6 101.3 96.0

Discharge Connection Electrical Connections

L

M

N

P

R

From Supply Supply From H eight
Edge Width Height Edge

4.1 28.0 16.0 3.9 27.4

10.4 71.1 40.6 9.9 69.6

4.1 28.0 16.0 3.9 27.4

10.4 71.1 40.6 9.9 69.6

4.1 38.0 16.0 3.9 27.4

10.4 96.5 40.6 9.9 69.6

9

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Dimensional Data cont.

UDV084-180 TOP FLOW ECONOMIZER OPTION RR

1.0

“N”

2.2

“B” “M”

“J”

“M”
BLOWER ACCESS PANEL

“L” 2.3
“N”

“L” 1.0

TOP DISCHARGE FIELD REMOVABLE
BLOWER PANEL INSERT
“A”

BLOWER ACCESS PANEL

TOP DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT “P” BOTH SIDES
“R” BOTH SIDES

“C”
1.8
CONTROL BOX ACCESS DOOR
“F”

8.1 “G”
2.1
“K”
DRAIN CONNECTION
“E” “D”

VERSATEC XL – Vertical Dimensional Data

34.0 4.2

Overall Cabinet

Water Connections

Return Connection*

Vertical

12 3

using delux e filter rack

Models

A

B

C DE F

Loop

G

H

J

K

Cond- Water Filter Width Depth Height In Out
ensate FPT Rack

From Return Return Edge Depth Height

084-096 in. 41.2 36.3 72.5 16.9 23.5 22.1 1 1/4″ 3.1

3.2 29.9 37.8

cm. 104.6 92.2 184.2 42.9 59.7 56.1 31.8 mm 7.9

8.1 75.9 96.0

120 in. 41.2 36.3 72.5 16.9 23.5 22.1 2″

3.1

3.2 29.9 37.8

cm. 104.6 92.2 184.2 42.9 59.7 56.1 50.8 mm 7.9

8.1 75.9 96.0

150-180 in. 41.2 46.3 72.5 17.7 24.2 22.1 2″

3.1

2.2 39.9 37.8

cm. 104.6 117.5 184.2 45.0 61.5 56.1 50.8 mm 7.9

5.6 101.3 96.0

Discharge Connection Electrical Connections

L

M

N

P

R

From Supply Supply From H eight
Edge Width Height Edge

4.1 28.0 16.0 3.9 27.4

10.4 71.1 40.6 9.9 69.6

4.1 28.0 16.0 3.9 27.4

10.4 71.1 40.6 9.9 69.6

4.1 38.0 16.0 3.9 27.4

10.4 96.5 40.6 9.9 69.6

10

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Dimensional Data cont.

LEFT RETURN SHOWN

2.1

1.4

“F”

DRAIN CONNECTIONS “J”

“N”

2.1 1.7

“K”

“G”

“H”
END DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES SIDE DISCHARGE
FIELD REMOVABLE BRACKETS AND DUCT FLANGES
“J”
1.7 1.0 DUCT FLANGE

AIR COIL

“M”

“V”

“B” “A”
50.00 (2)

BLOWER ACCESS
PANEL

22.8 “R”

20.4 “P”
1.8 “E”
“D”

40.00

“U”

“P”

“T”

“R”

CONTROL BOX

“C”

ACCESS DOOR

VERSATEC XL – Horizontal Dimensional Data

Overall Cabinet

Water Connections

Discharge Connection

Horizontal

12 5

Models

A

B

C DE F

Loop

G

H

J

K

Width Depth Height In Out Cond- Water Filter Rack From Supply Supply ensate FPT Width Edge Height Width

084-096 in. 41.1 89.0 29.9 6.9 25.1 3.2 1 1/4″

3.1

5.0 24.0 24.0

cm. 104.4 226.1 75.9 17.5 63.8 8.1 31.8 mm 7.9

12.7 61.0 61.0

120 in. 41.1 89.0 29.9 6.9 25.1 3.2

2″

3.1

5.0 24.0 24.0

cm. 104.4 226.1 75.9 17.5 63.8 8.1 50.8 mm 7.9

12.7 61.0 61.0

150-180 in. 41.1 110.0 29.9 6.9 25.1 3.2

2″

3.1

5.0 24.0 24.0

cm. 104.4 279.4 75.9 17.5 63.8 8.1 50.8 mm 7.9

12.7 61.0 61.0

*Dimensions for return connnections are for the deluxe filter rack that is suitable for ducted return applications

Return Connection*

using delux e filter rack

L

M

N

From Return Return

Edge Depth Height 4.3 47.6 23.5

10.9 120.9 59.7

4.3 47.6 23.5

10.9 120.9 59.7

4.3 65.6 23.5

10.9 166.6 59.7

Electrical Connections

P

R

From Height Edge

3.9 25.9

9.9 65.8

3.9 25.9

9.9 65.8

3.9 25.9

9.8 65.8

Unistrut Hanging

T

U

V

From Unistrut/ Unistrut/

Edge Unistrut Unistrut

1.7 24.6 61.0

4.3 62.5 154.9

1.7 24.6 61.0

4.3 62.5 154.9

1.7 35.1 71.5

4.3 89.2 181.6

11

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Dimensional Data cont.

RIGHT RETURN SHOWN

SIDE DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES

“J”

1.7

“H” “J”
1.7

“K”

2.1 1.5
END DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES

“K” “G”

1.0

2.1

“N”

DUCT

FLANGE “H”

BLOWER

ACCESS

“B”

PANEL

50.00 (2) “A”

“V”

“M”

AIR COIL

“P” “R”

40.00

“C”

CONTROL BOX

ACCESS DOOR

“U” 22.9 “P”
“T”
“E” “D”

20.3 “R”

VERSATEC XL – Horizontal Dimensional Data

Overall Cabinet

Water Connections

Discharge Connection

Horizontal

12 5

Models

A

B

C DE F

Loop

G

H

J

K

Width Depth Height In Out Cond- Water Filter Rack From Supply Supply ensate FPT Width Edge Height Width

084-096 in. 41.1 89.0 29.9 6.9 25.1 3.2 1 1/4″

3.1

5.0 24.0 24.0

cm. 104.4 226.1 75.9 17.5 63.8 8.1 31.8 mm 7.9

12.7 61.0 61.0

120 in. 41.1 89.0 29.9 6.9 25.1 3.2

2″

3.1

5.0 24.0 24.0

cm. 104.4 226.1 75.9 17.5 63.8 8.1 50.8 mm 7.9

12.7 61.0 61.0

150-180 in. 41.1 110.0 29.9 6.9 25.1 3.2

2″

3.1

5.0 24.0 24.0

cm. 104.4 279.4 75.9 17.5 63.8 8.1 50.8 mm 7.9

12.7 61.0 61.0

*Dimensions for return connnections are for the deluxe filter rack that is suitable for ducted return applications

Return Connection*

using delux e filter rack

L

M

N

From Return Return

Edge Depth Height 4.3 47.6 23.5

10.9 120.9 59.7

4.3 47.6 23.5

10.9 120.9 59.7

4.3 65.6 23.5

10.9 166.6 59.7

Electrical Connections

P

R

From Height Edge

3.9 25.9

9.9 65.8

3.9 25.9

9.9 65.8

3.9 25.9

9.8 65.8

Unistrut Hanging

T

U

V

From Unistrut/ Unistrut/

Edge Unistrut Unistrut

1.7 24.6 61.0

4.3 62.5 154.9

1.7 24.6 61.0

4.3 62.5 154.9

1.7 35.1 71.5

4.3 89.2 181.6

12

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Dimensional Data cont.

16.88 3.40

1.50

16.08

POWER SUPPLY LEFT RETURN
8.10

UDV240-360 RIGHT RETURN
SHOWN

48.08

71.90

20.00 3.40

POWER SUPPLY RIGHT RETURN
7.00 34.00

44.88 1.00

8.10 REF
TOP DISCHARGE FIELD REMOVABLE
BLOWER PANEL INSERT
1.70

88.00

CONTROL BOX ACCESS DOOR

46.00 80.00

WATER OUT 2″ FPT
WATER IN 2″ FPT

6.60

20.80

31.30 7.00
8.00 1.90 (3)

1.80 32.62

22.75 REF

32.62

13

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Installation Notes

Typical Unit Installation
Unit Location
Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
Water Piping
Piping is usually design as `reverse return’ to equalize flow paths through each unit. A short flexible pressure rated hose is used to make connection to the fixed building

piping system. This hose is typically stainless steel braid and includes a swivel fitting on one end for easy removal and is flexible to help isolate the unit for quieter operation. Isolation valves for servicing, y-strainers for filtering and memory-stop flow valve or a balancing valve can be provided for consistent water flow through the unit.
All unit source water connections are fittings that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fitting with a wrench to provide a leakproof joint. The open and closed loop piping system should include pressure/temperature ports for serviceability. The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/ temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger. Never use flexible hoses smaller than the inside diameter of the water connection at the unit. Limit hose length to 10 feet per connection. Check carefully for water leaks.

90 deg elbow with vanes on supply

Sealed low velocity ductwork

Acoustic lining to elbow
Canvas connector

Vibration absorbing pad

Flexible water and electrical connections

14

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Installation Notes cont.
Installing Horizontal Units Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge.
NOTE: Left (Right) Return Side Discharge can be converted to Left (Right) Return End Discharge or vice versa, without additional custom sheet metal parts. Horizontal units are normally suspended from a ceiling by six 1/2 in. diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit.
Lay out and install the threaded rods and 1 5/8″ strut

channel as shown in the Horizontal Dimensional Data. The unit should be pitched approximately 1/4 in. toward the drain in both directions to facilitate the removal of condensate.
Some applications require the installation of horizontal units on an attic floor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material.
CAUTION: Do not use rods smaller than 1/2 in. diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling.

Insulated first 4″ of supply plenum & provide one 90″
elbow

Disconnect Threaded rod

Building water loop Hose Kit

Acoustic lining to elbow

Flexible duct collar Strut Channels

Line Voltage

Optional insultated Return Air

15

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Installation Notes cont.

Acoustical Considerations and Equipment Sound Performance
Sound Performance The unit is third party sound rated in accordance with ARI 260. Please consult the manufacture’sr Sound Performance Data Catalog for details on the AHRI standard and sound performance data.
Recommendations for Noise Reduction Horizontal Unit Location · Specify equipment with quietest sound power ratings · Do not locate units above areas with a required NC 40
or less · Space WSHP at least 10 ft (3m) apart to avoid noise
summing of multiple units in a space. · Maximize the height of the unit above the
ceiling (horizontal). · Suspend unit with isolation grommets that are
appropriately rated to reduce vibrations (horizontal).
Vertical Unit Location · Specify equipment with quietest sound power ratings · Space WSHP at least 10 ft (3m) apart to avoid noise
summing of multiple units in a space. · Acoustic ceiling coatings can greatly reduce noise levels
in mechanical rooms. · Mount unit on a sound absorbing pad, extruded
polystyrene, rubber or cork pad.

Ductwork · Ensure return air grilles will not allow line of site noise to
transfer to adjacent space. Use a sound barrier or some other material to isolate the grille from the unit. A supply grille, boot and short piece of flex duct pointed away from the unit can greatly attenuate equipment noise. · Use a canvas isolation duct connector at the supply and return duct connection of the unit. · Internally line the discharge and return duct within the first 4-8 feet of unit with acoustic insulation. Install an internally lined L’ shaped return duct elbow at return grille. Face the elbow away from adjacent units. · Always install at least one 90° elbow in the discharge duct to eliminate line of sight noise transmission of the blower. · Use turning vanes at all elbows and tees to reduce turbulence. · Limit supply duct velocities to less than 1,000 fpm · Design and install ductwork as stiff as possible · Allow 3 duct diameters both up and down stream of the unit before any fittings or transitions are installed. · Use duct sealant on all duct joints. · Install a short (2-4′) of flex duct on all branch ducts just prior to discharge boot or diffuser to reduce vibration and duct sound prior to delivery in the room. · Locate the branch duct balancing damper as far away from the diffuser as possible. · In ceiling plenum systems, install an internally linedL’ shaped return duct elbow at unit. Face the elbow away from adjacent units (horizontal).

Locate return grille 6 ft [1.8 m] from unit

Sealed low velocity ductwork

Turning vanes at elbows and Tees
Branch damper upstream

90 deg elbow on supply

Acoustic lining to elbow

Locate units over hallways where
possible

Canvas connector

Flex duct at diffuser
2-4 ft. [0.6-1.2 m]

Supply grille with 2-3 ft [0.6-0.9 m] of flex loft
open for return air

Flexible water and electrical connections

16

Insulated Return (optional)

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Duct System
An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a duct connection. A flexible connector is recommended for discharge and return air duct connections on metal duct systems. Uninsulated duct should be insulated with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired if necessary.

The duct system should be sized to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed.

Water Piping
The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.

All source water connections on commercial units are fittings that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fitting with a wrench to provide a leakproof joint. When connecting to an open loop (groundwater) system, thread any copper MPT fitting into the connector and tighten in the same manner as described above.

17

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Condensate Drain
On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a 3/4 in. PVC female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PVC condensate piping. On vertical units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary.

On horizontal and bottom flow units, a PVC stub or stainless steel tube is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the field-installed condensate piping.

Horizontal Drain Connection (Composite Drain Pan) Unit Pitch for Drain

3/4″ Tube Stub

3/4″ PVC Coupling

1.5 in. Tube Stub

1.5 in.

Vent (if needed)
3/4″ PVC 1/8 in. per foot

1/2” Pitch Drain

18

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Water Quality

In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas

with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing. Failure to adhere to the guidelines in the water quality table could result in loss of warranty.
Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning.

Material pH
Scaling
Corrosion
Iron Fouling (Biological Growth)

Acidity/Alkalinity Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Sulfates Chlorine Chlorides Carbon Dioxide Ammonia Ammonia Chloride Ammonia Nitrate Ammonia Hydroxide Ammonia Sulfate Total Dissolved Solids (TDS) LSI Index Iron, FE2+ (Ferrous) Bacterial Iron Potential
Iron Oxide

Suspended Solids

Erosion

Threshold Velocity (Fresh Water)

NOTES: Grains = ppm divided by 17 mg/L is equivalent to ppm

Copper 7 – 9
(Total Hardness) less than 350 ppm Less than 0.5 ppm (rotten egg smell appears at 0.5 ppm) Less than 125 ppm Less than 0.5 ppm Less than 20 ppm Less than 50 ppm Less than 2 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 1000 ppm
+0.5 to -0.5

90/10 Cupronickel 7 – 9
(Total Hardness) less than 350 ppm
10 – 50 ppm
Less than 125 ppm Less than 0.5 ppm Less than 125 ppm
10 – 50 ppm Less than 2 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm 1000 – 1500 ppm
+0.5 to -0.5

< 0.2 ppm

< 0.2 ppm

Less than 1 ppm, above this level deposition will occur
Less than 10 ppm and filtered for max. of 600 micron size

Less than 1 ppm, above this level deposition will occur
Less than 10 ppm and filtered for max. of 600 micron size

< 6 ft/sec

< 6 ft/sec

316 Stainless Steel 7 – 9
(Total Hardness) less than 350 ppm
Less than 1 ppm
Less than 200 ppm Less than 0.5 ppm Less than 300 ppm
10 – 50 ppm Less than 20 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm 1000 – 1500 ppm
+0.5 to -0.5
< 0.2 ppm
Less than 1 ppm, above this level deposition will occur Less than 10 ppm and filtered for max. of 600 micron size
< 6 ft/sec
2/22/12

19

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

System Cleaning and Flushing
Cleaning and Flushing
Prior to start up of any heat pump, the water circulating system must be cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the supply and return runouts must be connected together at each unit location (This will prevent the introduction of dirt into the unit, see Flushing with Water Shutoff Valve Equipped Systems illustration). The system should be filled at the water make- up connection with all air vents open. After filling, vents should be closed.
Flushing with Water Shutoff Valve Equipped Systems
Return Runout

Supply Runout

Rubber Hose

Mains

Runouts Initially Connected Together

The contractor should start the main circulator with the pressure reducing valve makeup open. Vents should be checked in sequence to bleed off any trapped air and to verify circulation through all components of the system.
As water circulates through the system, the contractor should check and repair any leaks found in the piping system. Drain(s) at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure water fill valves are set at the same rate. Check the pressure gauge at the pump suction and manually adjust the makeup water valve to hold the same positive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if required, until drain water is clean and clear.
The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to completely drain the system. Short- circuited supply and return runouts should now be connected to the unit supply and return connections.

Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. EnvironolTM brand antifreeze is recommended.
Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure.
In boiler/tower application, set the loop control panel set points to desired temperatures. Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up and for air and water balancing.
Ground Source Loop System Checkout
Once piping is completed between the unit pumping system and ground loop, final purging and charging of the loop is needed. A high pressure pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible; then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is normally adequate for good system operation. Loop static pressure may decrease soon after initial installation, due to pipe expansion and loop temperature change. Running the unit for at least 30 minutes after the system has been completely purged of air will allow for the “break-in” period. It may be necessary to adjust static loop pressure (by adding water) after the unit has run for the first time. Loop static pressure will also fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially.
Ensure the pump provides adequate flow through the unit by checking pressure drop across the heat exchanger. Usually 2.25-3.0 gpm of flow per ton of cooling capacity is recommended in earth loop applications.

20

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Open Loop Ground Water Systems

Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 1.5-2 gpm of flow per ton of cooling capacity is recommended in open loop applications. Due to only minor differences in flow rate from low to high, only one solenoid valve should be used. The valve should be sized for full flow.

Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.

Open System – Groundwater Application

Unit Supply Aux. Heat Supply

Flexible Duct Collar

Rubber Bladder Expansion Tank

Hot Water Generator Connections

Drain

Solenoid Valve

Flow Control Valve
(on outlet of Solenoid Valve)
Water Out Water In

Disconnects (If Applicable)

Shut Off Valves
Shut Off Valves (to isolate solenoid valve while acid flushing)

Compressor Line Voltage

Low Voltage to Thermostat
and Valve

P/T Plugs
Vibration Absorbing Pad

Strainer

Boiler Drains For HX Flushing

Freeze Detection
For Aurora Base Control, set SW2-1, FP1, on the printed circuit board for applications using a closed loop antifreeze solution to 15°F [-9.4°C]. On applications using an open loop/ground water system (or closed loop no antifreeze), set this dip switch to 30°F [-1.1°C], the factory default setting. (Refer to the Dip Switch Field Selection table).

21

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Electrical Connections
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.

208 Volt Operation
All 208/230 volt units are factory wired for 230 volt operation. For 208 volt operation, the red and blue transformer wires must be switched on terminal strip PS.

Aurora Base Control Box

Aurora Advanced Control Board (AXB)

Aurora Base Control Board (ABC)

Transformers

Contactors

EEV/Power Supply UPC DDC Controls

22

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Electrical Data

Electrical Table 7-30 Ton Plenum Fan

Model

Rated Voltage

208-230/60/3

084

460/60/3

Dual Capacity Compressor

575/60/3

208-230/60/3

096

460/60/3

575/60/3

208-230/60/3

120

460/60/3

575/60/3

Tw o Compressors & Plenum Fan

208-230/60/3

150

460/60/3

575/60/3

208-230/60/3

180

460/60/3

575/60/3

Two Compressors & Two Plenum Fans

208-230/60/3

240

460/60/3

575/60/3

208-230/60/3

300

460/60/3

575/60/3

208-230/60/3

360

460/60/3

575/60/3

HACR circuit breaker in USA only

Voltage Min/Max
187/253 414/506 518/632 187/253 414/506 518/632 187/253 414/506 518/632 187/253 414/506 518/632 187/253 414/506 518/632 187/253 414/506 518/632 187/253 414/506 518/632 187/253 414/506 518/632

Compressor (each)

MCC RLA LRA

39.5 15.0 13.1 41.9 18.7 14.0 50.8 23.1 17.3 29.7 15.2 11.6 39.0 20.0 15.0 44.0 23.0 17.6 75.0 29.0 23.0 75.0 38.6 35.0

23.3 8.8 8.4 24.7 11.0 9.0 30.0 13.6 11.1 19.0 9.7 7.4 25.0 12.8 9.6 28.2 14.7 11.3 48.1 18.6 14.7 48.1 24.7 22.4

184.0 84.0 60.0 164.0 94.0 65.0 240.0 130.0 93.7 123.0 62.0 50.0 164.0 100.0 78.0 240.0 130.0 93.7 245.0 125.0 100.0 351.0 197.0 135.0

Blower Motor (each) FLA
5.3 3.0 2.4 7.0 4.0 3.2 7.0 4.0 3.2 9.2 6.8 5.4 9.2 6.8 5.4 9.2 6.8 5.4 9.2 6.8 5.4 9.2 6.8 5.4

Total Unit FLA
28.6 11.8 10.8 31.7 15.0 12.2 37.0 17.6 14.3 47.2 26.2 20.2 59.2 32.4 24.6 74.8 43.0 33.5 114.6 50.8 40.3 114.6 63.0 55.7

Min Circ Amp
34.4 14.0 12.9 37.9 17.8 14.5 44.5 21.0 17.1 52.0 28.6 22.1 65.5 35.6 27.0 81.9 46.7 36.3 126.6 55.5 44.0 126.6 69.2 61.3

Max Fuse/ HACR Breaker
55 20 20 60 25 20 70 30 25 70 35 25 90 45 35 110 60 45 175 70 55 175 90 80 3/30/2021

23

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Blower Performance Data

Integrated EC Backward Curved Plenum Fan Performance

Model 084 Fan Fan

Airflow [cfm] at External Static Pressure [in. wg.]

Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

1 900 1395 1315 1215 1090 940 775 495

2 1100 1725 1640 1570 1485 1400 1280 1150 1015 870 620

3 1300 2055 1985 1925 1865 1800 1725 1645 1550 1435 1315 1190 1060 1055 870

4 1400 2220 2165 2100 2045 1990 1915 1850 1770 1685 1595 1490 1375 1260 1105 955

5 1600 2555 2505 2435 2390 2335 2285 2230 2175 2110 2045 1970 1885 1800 1705 1605 1510 1375 1265

6 1700 2715 2660 2610 2545 2505 2460 2415 2365 2305 2250 2180 2125 2050 1970 1885 1800 1695 1600 1495 1350 1275

7 1800 2810 2785 2705 2655 2600 2540 2495 2415 2355 2305 2265 2210 2175 2120 2085 2015 1965 1905 1855 1795 1705

8 1900 2970 2910 2865 2805 2775 2715 2665 2615 2575 2520 2460 2405 2360 2300 2245 2185 2130 2075 2020 1965 1895

9 2000 3145 3105 3075 3015 2945 2900 2855 2805 2745 2695 2655 2585 2520 2475 2430 2380 2305 2245 2175 2100 2030

10 2100 3320 3300 3285 3225 3115 3085 3045 2995 2915 2870 2850 2765 2680 2650 2615 2575 2480 2415 2330 2235 2165

11 2200 3460 3415 3380 3315 2475 3240 3195 3120 3085 3050 3020 2985 2915 2865 2805 2780 2715 2635 2575 2520 2475

12 2300 3625 3575 3505 3460 3425 3395 3345 3245 3255 3230 3190 3165 3120 3075 3025 2990 2950 2855 2820 2785 2715

Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1),

3/30/21

H = stage 2 (Y2), and Aux = electric heat.

Continuous Fan (G) can be set at any airflow. Factory setting is 1.

L = Stage 1 (Y1) factory setting is 3.

H = Stage 2 (Y2) factory setting is 8.

Electric Heat Operation (AUX) = Stage 3 factory setting is 10.

Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.

Model 096

Fan Fan

Airflow [cfm] at External Static Pressure [in. wg.]

Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

1 600 1530 1430 1205 915 525 420 2 700 1835 1710 1530 1410 1165 870 495 3 800 2145 2030 1895 1740 1565 1385 1125 825 570 4 900 2530 2415 2290 2145 1985 1825 1665 1440 1200 920 5 1000 2815 2720 2620 2505 2365 2235 2085 1915 1755 1555 1325 1115 780 6 1100 3135 3045 2955 2830 2735 2615 2470 2335 2195 2045 1915 1745 1490 1315 7 1200 3440 3360 3275 3195 3095 2985 2895 2750 2645 2505 2375 2225 2085 1915 1730 1525 1235 8 1300 3745 3685 3595 3505 3415 3335 3235 3120 3035 2910 2795 2680 2555 2420 2305 2150 1955 1770 1575 9 1400 4045 3995 3905 3830 3775 3680 3580 3500 3415 3310 3195 3165 2985 2875 2750 2630 2505 2375 2255 2070 1905 10 1500 4370 4285 4220 4150 4085 4010 3920 3850 3775 3680 3595 3505 3400 3305 3195 3075 2940 2830 2750 2645 2525 11 1600 4875 4575 4545 4480 4400 4335 4250 4200 4115 4065 3975 3865 3795 3695 3600 3500 3395 3290 3180 3085 2970 12 1700 5200 5120 5060 5000 4935 4665 4575 4510 4415 4345 4280 4210 4130 4040 3960 3875 3795 3680 3605 3515 3425

Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1),

3/30/21

H = stage 2 (Y2), and Aux = electric heat.

Continuous Fan (G) can be set at any airflow. Factory setting is 1.

L = Stage 1 (Y1) factory setting is 4.

H = Stage 2 (Y2) factory setting is 7.

Electric Heat Operation (AUX) = Stage 3 factory setting is 10.

Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.

Model 120

Fan Fan

Airflow [cfm] at External Static Pressure [in. wg.]

Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

1 700 1835 1710 1530 1410 1165 870 495 2 800 2145 2030 1895 1740 1565 1385 1125 825 570 3 900 2530 2415 2290 2145 1985 1825 1665 1440 1200 920 4 1000 2815 2720 2620 2505 2365 2235 2085 1915 1755 1555 1325 1115 780 5 1100 3135 3045 2955 2830 2735 2615 2470 2335 2195 2045 1915 1745 1490 1315 6 1200 3440 3360 3275 3195 3095 2985 2895 2750 2645 2505 2375 2225 2085 1915 1730 1525 1235 7 1300 3745 3685 3595 3505 3415 3335 3235 3120 3035 2910 2795 2680 2555 2420 2305 2150 1955 1770 1575 8 1400 4045 3995 3905 3830 3775 3680 3580 3500 3415 3310 3195 3165 2985 2875 2750 2630 2505 2375 2255 2070 1905 9 1500 4370 4285 4220 4150 4085 4010 3920 3850 3775 3680 3595 3505 3400 3305 3195 3075 2940 2830 2750 2645 2525 10 1600 4875 4775 4545 4480 4400 4335 4250 4200 4115 4065 3975 3865 3795 3695 3600 3500 3395 3290 3180 3085 2970 11 1700 5200 5120 5060 5000 4935 4665 4575 4510 4415 4345 4280 4210 4130 4040 3960 3875 3795 3680 3605 3515 3425 12 1800 5525 5405 5310 5200 5105 4995 4860 4755 4695 4625 4555 4480 4410 4350 4295 4225 4160 4070 3985 3900 3820

Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1),

3/30/21

H = stage 2 (Y2), and Aux = electric heat.

Continuous Fan (G) can be set at any airflow. Factory setting is 1.

L = Stage 1 (Y1) factory setting is 4.

H = Stage 2 (Y2) factory setting is 8.

Electric Heat Operation (AUX) = Stage 3 factory setting is 10.

Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.

24

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Blower Performance Data cont.

Model 150

Fan Fan

Airflow [cfm] at External Static Pressure [in. wg.]

Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

1 900 2780 2665 2545 2400 2230 2055 1880 1650

2 1000 3095 2990 2885 2780 2675 2515 2345 2175 2005 1830 1590

3 1100 3415 3325 3230 3135 3045 2905 2795 2680 2570 2460 2155 1985

4 1200 3750 3660 3565 3470 3370 3275 3165 3055 2935 2805 2680 2530 2375 2195 1995

5 1300 4055 3980 3905 3815 3725 3635 3540 3445 3335 3215 3100 2975 2845 2700 2545 2385 2190 1995 1802

6 1400 4375 4305 4230 4155 4070 3985 3900 3815 3720 3620 3520 3395 3275 3160 3040 2925 2765 2605 2445 2285 2120

7 1500 4810 4700 4585 4495 4420 4345 4255 4170 4090 4015 3945 3840 3735 3635 3530 3425 3295 3165 3035 2895 2765

8 1600 5245 5095 4940 4835 4770 4685 4605 4525 4450 4385 4320 4225 4135 4035 3945 3855 3745 3640 3530 3415 3300

9 1700 5680 5490 5295 5175 5120 5025 4955 4880 4810 4755 4680 4600 4520 4435 4345 4255 4175 4090 4000 3895 3795

10 1800 6115 5885 5650 5515 5470 5365 5305 5235 5170 5125 5040 4975 4905 4835 4730 4650 4570 4490 4405 4315 4220

11 1900 6550 6280 6005 5855 5820 5705 5655 5590 5530 5495 5400 5350 5290 5235 5115 5045 4965 4890 4810 4735 4645

12 2000 6985 6675 6360 6195 6155 6045 6005 5945 5890 5865 5760 5725 5675 5635 5500 5440 5360 5290 5215 5155 5070

Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1), H = stage 2 (Y2), and Aux = electric heat.

3/30/21

Continuous Fan (G) can be set at any airflow. Factory setting is 1.

L = Stage 1 (Y1) factory setting is 2.

H = Stage 2 (Y2) factory setting is 9.

Electric Heat Operation (AUX) = Stage 3 factory setting is 10.

Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.

Model 180

Fan Fan

Airflow [cfm] at External Static Pressure [in. wg.]

Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

1 900 2454 2341 2214 2075 1923 1758 1580 1389

2 1000 2978 2881 2773 2669 2531 2407 2253 2087 1908 1679 1432

3 1100 3288 3202 3121 3012 2908 2800 2679 2521 2385 2230 2050 1839 1617 1281

4 1200 3587 3507 3433 3343 3249 3145 3037 2926 2791 2659 2490 2364 2218 2037 1825 1568

5 1300 3901 3835 3761 3664 3594 3507 3418 3319 3202 3104 2969 2864 2735 2581 2417 2230 2098 1928

6 1400 4244 4182 4120 4057 3974 3896 3809 3727 3629 3536 3455 3326 3224 3110 2983 2833 2718 2581 2440 2293

7 1550 4812 4738 4664 4587 4504 4438 4372 4291 4226 4134 4046 3962 3870 3780 3707 3579 3501 3404 3305 3204 3101

8 1700 5329 5262 5195 5139 5082 5020 4958 4895 4831 4752 4673 4601 4529 4455 4380 4294 4222 4145 4068 3990 3911

9 1800 5666 5607 5548 5481 5414 5353 5291 5221 5151 5086 5020 4953 4886 4811 4735 4671 4596 4523 4450 4375 4300

10 1900 6018 5957 5895 5833 5770 5712 5654 5589 5524 5463 5402 5340 5278 5208 5138 5047 4976 4907 4837 4766 4695

11 2000 6350 6287 6224 6165 6105 6045 5985 5923 5861 5799 5736 5672 5607 5541 5475 5414 5347 5281 5214 5148 5080

12 2160 6862 6805 6748 6698 6647 6588 6529 6477 6425 6364 6303 6249 6194 6131 6068 5987 5920 5854 5787 5721 5653

Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1),

3/30/21

H = stage 2 (Y2), and Aux = electric heat.

Continuous Fan (G) can be set at any airflow. Factory setting is 1.

L = Stage 1 (Y1) factory setting is 3.

H = Stage 2 (Y2) factory setting is 9.

Electric Heat Operation (AUX) = Stage 3 factory setting is 10.

Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.

25

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Blower Performance Data cont.

Model 240

Fan Fan

Airflow [cfm] at External Static Pressure [in. wg.]

Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

1 900 5755 5525 5290 5005 4725 5045 4075 3645 3205 2635 2 1000 6610 6345 6080 5815 5550 5285 5020 4725 4425 4035 3640 3155

3 1100 7465 7165 6870 6625 6375 5525 5965 5805 5400 5105 4810 4440 4075 3495 2915

4 1200 7815 7650 7485 7295 7105 6915 6725 6540 6355 6095 5835 5540 5245 4755 4265 3995 3730 3075

5 1300 8505 8355 8205 8040 7875 7705 7530 7335 7145 6925 6710 6505 6300 5975 5655 5165 4681 4568 4455 3870 3285

6 1400 9195 9020 8850 8705 8565 8395 8225 8060 7895 7710 7525 7355 7190 6975 6760 6380 6000 5500 5000 4600 4200

7 1500 9885 9785 9605 9470 9335 9180 9025 8895 8770 8575 8385 8215 8045 7850 7655 7415 7175 6740 6305 5870 5435

8 1600 10575 10545 10360 10235 10105 9930 9760 9605 9450 9325 9205 9045 8890 8725 8565 8385 8205 8005 7810 7565 7325

9 1700 11265 11105 11055 11000 10875 10680 10570 10435 10300 10160 10025 9880 9740 9590 9445 9275 9110 8880 8655 8275 7900

10 1800 11955 11860 11750 11695 11645 11430 11380 11265 11150 10995 10715 10595 10480 10340 10205 10065 9930 9770 9610 9305 9005

11 1900 12645 12615 12445 12390 12285 12180 12105 12085 12000 11830 11405 11310 11220 11090 10975 10845 10715 10565 10420 10280 10145

12 2000 13335 13230 13140 13085 12925 12885 12830 12755 12705 12665 12395 12025 11960 11840 11745 11625 11500 11360 11225 11085 10945

Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1),

3/30/21

H = stage 2 (Y2), and Aux = electric heat.

Continuous Fan (G) can be set at any airflow. Factory setting is 1.

L = Stage 1 (Y1) factory setting is 3.

H = Stage 2 (Y2) factory setting is 6.

Electric Heat Operation (AUX) = Stage 3 factory setting is 8.

Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.

Model 300

Fan Fan

Airflow [cfm] at External Static Pressure [in. wg.]

Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

1 900 5755 5525 5290 5005 4725 5045 4075 3645 3205 2635

2 1000 6610 6345 6080 5815 5550 5285 5020 4725 4425 4035 3640 3155

3 1100 7465 7165 6870 6625 6375 5525 5965 5805 5400 5105 4810 4440 4075 3495 2915

4 1200 7815 7650 7485 7295 7105 6915 6725 6540 6355 6095 5835 5540 5245 4755 4265 3995 3730 3075

5 1300 8505 8355 8205 8040 7875 7705 7530 7335 7145 6925 6710 6505 6300 5975 5655 5165 4681 4568 4455 3870 3285

6 1400 9195 9020 8850 8705 8565 8395 8225 8060 7895 7710 7525 7355 7190 6975 6760 6380 6000 5500 5000 4600 4200

7 1500 9885 9785 9605 9470 9335 9180 9025 8895 8770 8575 8385 8215 8045 7850 7655 7415 7175 6740 6305 5870 5435

8 1600 10575 10545 10360 10235 10105 9930 9760 9605 9450 9325 9205 9045 8890 8725 8565 8385 8205 8005 7810 7565 7325

9 1700 11265 11105 11055 11000 10875 10680 10570 10435 10300 10160 10025 9880 9740 9590 9445 9275 9110 8880 8655 8275 7900

10 1800 11955 11860 11750 11695 11645 11430 11380 11265 11150 10995 10715 10595 10480 10340 10205 10065 9930 9770 9610 9305 9005

11 1900 12645 12615 12445 12390 12285 12180 12105 12085 12000 11830 11405 11310 11220 11090 10975 10845 10715 10565 10420 10280 10145

12 2000 13335 13230 13140 13085 12925 12885 12830 12755 12705 12665 12395 12025 11960 11840 11745 11625 11500 11360 11225 11085 10945

Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1), H = stage 2 (Y2), and Aux = electric heat.

3/30/21

Continuous Fan (G) can be set at any airflow. Factory setting is 1.

L = Stage 1 (Y1) factory setting is 3.

H = Stage 2 (Y2) factory setting is 8.

Electric Heat Operation (AUX) = Stage 3 factory setting is 9.

Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.

Model 360

Fan Fan

Airflow [cfm] at External Static Pressure [in. wg.]

Speed RPM 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

1 900 5755 5525 5290 5005 4725 5045 4075 3645 3205 2635

2 1000 6610 6345 6080 5815 5550 5285 5020 4725 4425 4035 3640 3155

3 1100 7465 7165 6870 6625 6375 5525 5965 5805 5400 5105 4810 4440 4075 3495 2915

4 1200 7815 7650 7485 7295 7105 6915 6725 6540 6355 6095 5835 5540 5245 4755 4265 3995 3730 3075

5 1300 8505 8355 8205 8040 7875 7705 7530 7335 7145 6925 6710 6505 6300 5975 5655 5165 4681 4568 4455 3870 3285

6 1400 9195 9020 8850 8705 8565 8395 8225 8060 7895 7710 7525 7355 7190 6975 6760 6380 6000 5500 5000 4600 4200

7 1500 9885 9785 9605 9470 9335 9180 9025 8895 8770 8575 8385 8215 8045 7850 7655 7415 7175 6740 6305 5870 5435

8 1600 10575 10545 10360 10235 10105 9930 9760 9605 9450 9325 9205 9045 8890 8725 8565 8385 8205 8005 7810 7565 7325

9 1700 11265 11105 11055 11000 10875 10680 10570 10435 10300 10160 10025 9880 9740 9590 9445 9275 9110 8880 8655 8275 7900

10 1800 11955 11860 11750 11695 11645 11430 11380 11265 11150 10995 10715 10595 10480 10340 10205 10065 9930 9770 9610 9305 9005

11 1900 12645 12615 12445 12390 12285 12180 12105 12085 12000 11830 11405 11310 11220 11090 10975 10845 10715 10565 10420 10280 10145

12 2000 13335 13230 13140 13085 12925 12885 12830 12755 12705 12665 12395 12025 11960 11840 11745 11625 11500 11360 11225 11085 10945

Fan selection is accomplished through the Aurora Controls and allows four online selections of continuous fan (G), L = stage 1 (Y1), H = stage 2 (Y2), and Aux = electric heat.

3/30/21

Continuous Fan (G) can be set at any airflow. Factory setting is 1.

L = Stage 1 (Y1) factory setting is 4.

H = Stage 2 (Y2) factory setting is 9.

Electric Heat Operation (AUX) = Stage 3 factory setting is 10.

Elect heat Airflow (AUX) airflow setting should be configured for the minimum airflow needed to support the heater. Please consult heater manual.

26

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Blower Performance Data cont.
Setting Blower Speed – Variable Speed ECM
The ABC board’s Yellow Config LED will flash the current ECM blower speed selections for G, low, and high continuously with a short pause in between. The speeds can also be confirmed with the AID Tool under the Setup/ ECM Setup screen. The Aux will not be flashed but can be viewed in the AID Tool. The ECM blower motor speeds can be field adjusted with or without using an AID Tool.

Variable speed ECM Setup without an AID Tool
The blower speeds for G only, Low (Y1), and High (Y2/ Aux) can be adjusted directly at the Aurora ABC board which utilizes the push button (SW1) on the ABC board. This procedure is outlined in the ECM Configuration Mode portion of the Aurora `Base’ Control System section. The Aux cannot be set manually without an AID Tool.

Variable speed ECM Setup with an AID Tool

A much easier method utilizes the AID Tool to change

the airflow using the procedure below. First navigate to

the Setup screen and then select ECM Setup. This screen

displays the current ECM settings. It allows the technician

ECM Speed Info

to enter the setup screens to change the ECM settings. Change

Blower Only Speed 3

Lo Compressor

6

Hi Compressor

9

Aux Heat

10

the highlighted item using the and buttons and then press the button to select the item.

Want To Change?

Yes Option

No Enter

Selecting YES will enter ECM speed setup, while selecting NO will return to the previous screen.

ECM Speed Setup – These screens allow the technician to select the G, low, high, and auxiliary heat blower speed for the ECM blower motor. Change the highlighted item using the and buttons. Press the button to select the speed.

ECM Speed Info
1 2 G
3 4 5 6 7 8 9 10 11 12

ECM Speed Info
1 2 G 3 Lo 4 5 6 7 8 9 10 11 12

ECM Speed Info

1

2 G

3 Lo

4

5

6

Hi

7

8

9

10

11

12

ECM Speed Info

1

2 G

3 Lo

4

5

6

Hi

7

8

9 10

11

12

Aux

Option

Enter

Option

Enter

Option

Enter

Option

Enter

After the auxiliary heat speed setting is selected the AID Tool will automatically transfer back to the ECM Setup screen.

Cooling Airflow Setup – These screens allow the technician to select -15%, -10%, -5%, None or +5% change from the heating airflow. Change the adjustment percentage using the and buttons. Press the button to save the change.

Cooling Airflow Setup

Cooling Airflow Setup

— ECM Only –The airflow will be adjusted by the chosen amount in cooling mode.
Adjustment: -15%

— ECM Only –The airflow will be adjusted by the chosen amount in cooling mode.
Adjustment: -15%

Want To Change?

Yes Option

No Enter

Change Enter

Setting Blower Speed – Variable Speed ECM – UPC Controls
Variable speed ECM blower motors have 12 selectable speeds and are factory set for optimum performance. When applicable, the speed settings may also be adjusted through the Building Automation System (BAS).
CAUTION: Disconnect all power before performing this operation.

27

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics
Single Compressor 208-230/60/3

CC

Ultra Tech CS RCP
Blue Blue

See N ote 6
FP2/ RV FP1 LAT LP HP

Orange (1)

Yellow Black

Blue (7)

Black (9)

RV T

T

Black (19)

Violet (18)

Gray Red Red
Blue (22) Blue (23)

Orange Yellow (2)

Black

Blue (8)

Black (10)

See N ote 3

K1-RV Relay

K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay
JW2

P9 EH1 CC2 CC F C

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C

P2 ES LS

R F1-3A

ALM ALG ACC COM ACC NO ACC NC
LO

K5-Alarm Relay
K6-Acc Relay

F

PWM

Aurora Base Control

SW1

Status

LED3

CFM

(ABC)

Test Mode

G

R C O/B G Y1 Y2 W DH P1
R Red

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

Com2 LED5

Com1 LED5

SW2 Config LED2

G RS485 NET

G RS485 NET

RS485 EXP

Y

C

P8

C R – + P7

C R – + P6 CO C EH1 C EH2 P3

Y1 G CC

Black

Black
Reh eat Valve See N ote 2

To UPC
See N ote 5

Aurora Advanced and Premiu m Opon

Red Heat Shrink
White Gr een

T T

Gr ay Gr ay Gr een White
Brown Vio le t Vio le t White White

GND 3 OUT 2 5DC 4

Brown Brown

Bro wn (25) Bro wn (24)
Condensate

FLOW

T

METER

DISCH ARGE PRESSU RE TRANSDUCER
T

Black White Red

GND 1 OUT 2 5DC 3

MOTOR RX
TX
R
C
V+ P8
RS485 (+)
(-)
R
C P6 ZO NE (+)
(-)
R
C P7 ABC (+)
(-)
R
C
+5 P9

P4

P2

HA2 HA1 SGI P3 C S +5 C S +5 2 1 C OUT C IN LOOP VS DATA VS PUMP PUMP SLAVE

EWT LWT FLOW LAT P1

LLT P16

Status G

AXBTM
(Aurora Expansion Board)

Modbus Add. ID Future Use Future Use
Acc 2 ­ Dip 1 Acc 2 ­ Dip 2

OFF ON 1 2 3 4 5
SW1

P17 HHWW 21

P18 SCT 321

P12 SCP
321

P10 STEPPER

K3 K2 K1

P15 CT2 CT1 4321

P5 CT2 CT1 4321

P11 ANA ACC2 DH DIV

Pink T
Pink

Blue

T

Blue

Black White Red

1 GND 2 OUT 3 5DC

SU CTI ON PRES SU RE T RA NSD UCE R

DISCH P14 C
R
L1
L1 K6

COM

NO

K5

COM

NO L2

L2

28

Black (16) Black
Yellow (17 )

Modulang Water Valve

Gray

Y

321

Red

~

Black

CO M

24V G

0-10V Y

G ND

U

Red Gr ay Black
Hot Gas Reheat Valve Note 2
Red Black

Note 4

Blue

Compressor T1

Blue

Red Compressor T2
Red

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.

Single Compressor 208-230/60/3

Black (A) Black (K) Red (B) White (L) Blue (C) Red (M) Black (AG) Red (AH) Blue (AJ)

Unit Power Supply

Non-Fuse d Di sconne ct or T ermi na l Bl oc k

G

L1

L2

L3

L1

L2

L3

Green / Yel low (G1) Compressor

T3

T1

T2

Blue (AC) Red (AB)

Black (AA)

CC

T3

T2

T1

L3

L2

L1

97P8 95-01 03/01/21

Phase Guard Monitor (PG M)
L1 L2 L3

Aurora LED Flash Codes

SlowFlash 1 second on and 1 second off

Fast Flash 100 mil liseconds on and 100 mi lliseconds off

Flash Code 100 mil liseconds on and 400 mi lliseconds off with a 2 second pause before re peating

Random Start Delay

Status LED (LED3, Green)

Fast Fl ash

Configuration LED (LED2, Yel low)

Fast Fl ash

Faul t LED (LED1, Red)

Fast Fl ash

Sta tus LED (LED3, Green)

Configuration LED (LED2, Yellow)

Fault LED (LED1, Red)

Normal Mode

ON

No Software Overi de Fl ash ECM Settin g Normal Mode

OFF

Control is Non-Functional

OFF DIP Switch Overide

Slow Flash Input Fault Lockout

Flash Code 1

Test Mode

Slow Flash ECM Configu re Mod e

Fast Fl ash High Pressure Lockout

Fl ash Code 2

Lockout Active

Fast Fl ash Reset Confi gure Mode

Off

Low Pressure Locko ut

Fl ash Code 3

Dehumidification Mo de

Fl ash Code 2

Low Air Coil Limit Lockout – FP2 Fl ash Code 4

Reserved

Fl ash Code 3

Low Water Coil Limi t Lockout – FP1 Fl ash Code 5

Reserved

Fl ash Code 4

Loss of Charge Lockout

Fl ash Code 6

Load Shed

Fl ash Code 5

Condensate Overfl ow Lockout

Fl ash Code 7

ESD

Fl ash Code 6

Over/Under Vol tage Sh utdown

Fl ash Code 8

Reserved

Fl ash Code 7

Reserved

Fl ash Code 9

Compressor Monitor Lockout

Fl ash Code 1 0

Air/Water Coil Limit Sensor Error Fl ash Code 1 1

L2

L1

L3

GN D A ( D+) B ( D-)

Blower Motor

ID

GN D

A ( D+)

B ( D-)

ID

Green/Yel low (29)

Control Box

Control Box

fo ut

Base Panel

Door

GN D

PB1

2 Green/Yel low (14)
3 Black (13)

Black/White

1 C

Yellow (12 )

Y-OUT

Y

PGM

Yellow

Accessor y Relay

Operation

SW2-4 SW2-5

Cycl e with Blower

On On

Cycl e with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

Aurora Timing Events

Event

Normal Mode

Random Start Delay

5 to 80 seconds

Compressor On Delay

5 seconds

Compressor Minimum On Time

2 minutes

Compressor Short Cycl e Delay

4 minutes

Blower Off Delay

30 seconds

Faul t Recogn itio n Delay ­ High Pressure

Less than 1 second

Start-Up Bypass ­ Low Pressure

2 minutes

Faul t Recogn itio n Delay ­ Low Pressure

30 seconds

Start-Up Bypass ­ Low Water/Ai r Coil Limit

2 minutes

Faul t Recogn itio n Delay ­ Low Water/Ai r Coil Limit 30 seconds

Faul t Recogn itio n Delay ­ Condensate Overfl ow

30 seconds

Thermostat Call Recognition Time

2 seconds

Auxi liary Heat Stagi ng Del ay

5 minutes

Emergency Heat Stagi ng Dela y

2 minutes

Water Valve Slow Open Delay

90 seconds

Reheat Delay

30 seconds

Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds

Tra nsformer

Cla ss 2

Black Red See N ote 7
Blue

Notes:
1 ­ P1 (screw ter minals) and P9 (Molex connector ) are adjacent and share common terminals in the same order. 2 ­ Optional factor y installed hot gas reheat or modulating hot gas r eheat. 3 ­ Optional factor y installed internal isolation valve. 4 ­ Optional waters ide economizer. 5 ­ See supplemental schematic for AXB and/or UPC connections. 6 ­ LAT location with Aurora Base Controls, FP2 with Auror a Advanced and Premium Controls. 7 ­ Swap blue and red leads for 208V operation.

Green/ Yellow (15 )

Factory PWM CFM C

1 2 3
24V

HP P4

ECM PWM

HP

P13

LP

LP

FP2

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

CC2 Factory

G P5 LO HI CCG CC FG F R
F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1
JW2 Alarm
P2 Fi eld Connections

LED1 R

Off FP1 ­ 15oF/30oF
FP2 ­ 15oF/30oF

On 1 LED2
2Y

Faul t

RV ­ B/O

ACC ­ Dip 4

3 Config 4

LED3

ACC ­ Dip 5

CC ­ Dual/Si ngle

G L ­ Pulse/Continuous

Status

Reheat/Normal

5 6 7 8 SW2

AURORA BASE CONTROLTM
Com1 G

RS485 Exp

Factory

EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7

RS 485

Factory Use

RS485 NET

P11

P9

Factory Fan Connection

P8 Com2 G

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Fi eld Connections

3A-Fuse

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

RR

CC C

Legend

Factory Low Voltage Wiring Factory Line Voltage Wiring Fi eld Low Voltage Wiring Field Line Voltage Wiri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ring Internal Ju nction Qui ck Con nect Terminal

L1

Field Wiring Lug

T

Thermistor

Relay Coi l

Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure

Polarized connector

EX-XX

Ground Relay Con tacts ­ N.O., N.C.

Pin Number Designation on Twist-Lock Connector

Capacitor Fuse

G

Light Emitti ng Diode – Green

Current Transducer

Y

Light Emitti ng Diode – Yellow

CC ­ Compressor Contactor CO ­ Condensate Overfl ow Sensor ES ­ Emergency Shutdown EWT ­ Entering Water Temp Sensor HP ­ High Pressure Switch LAT ­ Leaving Ai r Temp LLT ­ Liqui d Line Temp LP ­ Low Pressure Switch LWT ­ Leaving Water Temp

R

Light Emitti ng Diode – Red

FP1 ­ Freeze Protection Sensor 1 FP2 ­ Freeze Protection Sensor 2 SW1 ­ Push button SW2 ­ DIP package 8 position RV ­ Reversi ng Valve Coi l PGM ­ Phase Guard Moni tor RH ­ Reheat Valve Coi l

29

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
Single Compressor 460/60/3

CC

Ultra Tech CS RCP
Blue Blue

See N ote 6
FP2/ RV FP1 LAT LP HP

Orange (1)

Yellow Black

Blue (7)

Black (9)

RV T

T

Black (19)

Violet (18)

Gray Red Red
Blue (22) Blue (23)

Orange Yellow (2)

Black

Blue (8)

Black (10)

See N ote 3

K1-RV Relay

K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
JW2

P9 EH1 CC2 CC F C

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C

P2 ES LS

R F1-3A

ALM ALG ACC COM ACC NO ACC NC
LO

K5-Alarm Relay
K6-Acc Relay

F

PWM

Aurora Base Control

SW1

Status

LED3

CFM

(ABC)

Test Mode

G

R C O/B G Y1 Y2 W DH P1
R Red

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

Com2 LED5

Com1 LED5

SW2 Config LED2

G RS485 NET

G RS485 NET

RS485 EXP

Y

C

P8

C R – + P7

C R – + P6 CO C EH1 C EH2 P3

Y1 G CC

Black

Black
Reh eat Valve See N ote 2

To UPC
See N ote 5

Aurora Advanced and Premiu m Opon

Red Heat Shrink
White Gr een

T T

Gr ay Gr ay Gr een White
Brown Vio le t Vio le t White White

GND 3 OUT 2 5DC 4

Brown Brown

Bro wn (25) Bro wn (24)
Condensate

FLOW

T

METER

DISCH ARGE PRESSU RE TRANSDUCER
T

Black White Red

GND 1 OUT 2 5DC 3

MOTOR RX
TX
R
C
V+ P8
RS485 (+)
(-)
R
C P6 ZO NE (+)
(-)
R
C P7 ABC (+)
(-)
R
C
+5 P9

P4

P2

HA2 HA1 SGI P3 C S +5 C S +5 2 1 C OUT C IN LOOP VS DATA VS PUMP PUMP SLAVE

EWT LWT FLOW LAT P1

LLT P16

Status G

AX BTM
(Aurora Expansion Board)

Modbus Add. ID Future Use Future Use
Acc 2 ­ Dip 1 Acc 2 ­ Dip 2

OFF ON 1 2 3 4 5
SW1

P17 HHWW 21

P18 SCT 321

P12 SCP
321

P10 STEPPER

K3 K2 K1

P15 CT2 CT1 4321

P5 CT2 CT1 4321

P11 ANA ACC2 DH DIV

Pink T Pink

Blue

T

Blue

Black White Red

1 GND SU CTI ON 2 OUT PRES SU RE 3 5DC T RA NSD UCE R

DISCH P14 C
R
L1
L1 K6

COM

NO

K5

COM

NO L2

L2

Black (16) Black
Yellow (17 )

Modulang Water Valve

Gray

Y

321

Red

~

Black

CO M

24V G

0-10V Y

G ND

U

Red Gr ay Black
Hot Gas Reheat Valve Note 2
Red Black

Note 4

Blue

Compressor T1

Blue

Red Compressor T2
Red

30

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
Single Compressor 460/60/3

Unit Power Supply

Non-Fuse d Di sconne ct or T ermi na l Bl oc k

G

L1

L2

L3

L1

L2

L3

Green / Yel low (G1) Compressor

T3

T1

T2

Yellow (AC) Orange (AB) Bro wn (AA)

CC

T3

T2

T1

L3

L2

L1

Phase Guard Monitor (PG M)
L1 L2 L3

Bro wn (A) Black (K) Orange (B) White (L) Yellow (C) Red (M) Bro wn (AG) Orange (AH) Yellow (AJ)

L2

L1

L3

GN D A ( D+) B ( D-)

Blower Motor

ID

GN D

A ( D+)

B ( D-)

ID

Green/Yel low (29)

Control Box

Control Box

fo ut

Base Panel

Door

GN D

PB1

2 Green/Yel low (14)
3 Black (13)

Black/White

1 C

Yellow (12 )

Y-OUT

Y

PGM

Yellow

Tra nsformer

Black
Blue Cla ss 2

Green/ Yellow (15 )

97P8 95-02 03/01/21

Aurora LED Flash Codes

SlowFlash 1 second on and 1 second off

Fast Flash 100 milliseconds on and 100 mi lliseconds off

Flash Code 100 mil liseconds on and 400 mi lliseconds off with a 2 second pause before re peating

Random Start Delay

Status LED (LED3, Green)

Fast Fl ash

Configuration LED (LED2, Yel low)

Fast Fl ash

Faul t LED (LED1, Red)

Fast Fl ash

Sta tus LED (LED3, Green)

Configuration LED (LED2, Yellow)

Fault LED (LED1, Red)

Normal Mode

ON

No Software Overi de Fl ash ECM Settin g Normal Mode

OFF

Control is Non-Functional

OFF DIP Switch Overide

Slow Flash Input Fault Lockout

Flash Code 1

Test Mode

Slow Flash ECM Configu re Mod e

Fast Fl ash High Pressure Lockout

Fl ash Code 2

Lockout Active

Fast Fl ash Reset Confi gure Mode

Off

Low Pressure Locko ut

Fl ash Code 3

Dehumidification Mo de

Fl ash Code 2

Low Air Coil Limi t Lockout – FP2 Fl ash Code 4

Reserved

Fl ash Code 3

Low Water Coil Limi t Lockout – FP1 Fl ash Code 5

Reserved

Fl ash Code 4

Loss of Charge Lockout

Fl ash Code 6

Load Shed

Fl ash Code 5

Condensate Overfl ow Lockout

Fl ash Code 7

ESD

Fl ash Code 6

Over/Under Vol tage Sh utdown

Fl ash Code 8

Reserved

Flash Code 7

Reserved

Fl ash Code 9

Compressor Monitor Lockout

Fl ash Code 1 0

Air/Water Coil Limit Sensor Error Fl ash Code 1 1

Accessor y Relay

Operation

SW2-4 SW2-5

Cycl e with Blower

On On

Cycl e with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

Aurora Timing Events

Event

Normal Mode

Random Start Delay

5 to 80 seconds

Compressor On Delay

5 seconds

Compressor Minimum On Time

2 minutes

Compressor Short Cycl e Delay

4 minutes

Blower Off Delay

30 seconds

Faul t Recogn itio n Delay ­ High Pressure

Less than 1 second

Start-Up Bypass ­ Low Pressure

2 minutes

Faul t Recogn itio n Delay ­ Low Pressure

30 seconds

Start-Up Bypass ­ Low Water/Ai r Coil Limit

2 minutes

Faul t Recogn itio n Delay ­ Low Water/Ai r Coil Limit 30 seconds

Faul t Recogn itio n Delay ­ Condensate Overfl ow

30 seconds

Thermostat Call Recognition Time

2 seconds

Auxi liary Heat Stagi ng Del ay

5 minutes

Emergency Heat Stagi ng Dela y

2 minutes

Water Valve Slow Open Delay

90 seconds

Reheat Delay

30 seconds

Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds

Notes:
1 ­ P1 (screw ter minals) and P9 (Molex connector ) are adjacent and share common terminals in the same order. 2 ­ Optional factor y installed hot gas reheat. 3 ­ Optional factor y installed internal isolation valve. 4 ­ Optional waters ide economizer . 5 ­ See supplemental schematic for AXB and/or UPC connections. 6 ­ LAT location with Aurora Base Controls, FP2 with Auror a Advanced and Premium Controls.

Factory PWM CFM C

1 2 3
24V

HP P4

ECM PWM

HP

P13

LP

LP

FP2

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

CC2 Factory

G P5 LO HI CCG CC FG F R
F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1
JW2 Alarm
P2 Fi eld Connections

LED1 R

Off FP1 ­ 15oF/30oF
FP2 ­ 15oF/30oF

On 1 LED2
2Y

Faul t

RV ­ B/O

ACC ­ Dip 4

3 Config 4

LED3

ACC ­ Dip 5

CC ­ Dual/Si ngle

G L ­ Pulse/Continuous

Status

Reheat/Normal

5 6 7 8 SW2

AURORA BASE CONTROLTM
Com1 G

RS485 Exp

Factory

EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7

RS 485

Factory Use

RS485 NET

P11

P9

Factory Fan Connection

P8 Com2 G

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Fi eld Connections

3A-Fuse

CC C

Legend

Factory Low Voltage Wiring Factory Line Vol tage Wiring Field Low Voltage Wiring Fi eld Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Ju nction Quick Con nect Terminal

L1

Field Wiring Lug

T

Thermistor

Relay Coi l

Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure

Polarized connector

EX-XX

Ground Relay Con tacts ­ N.O., N.C.

Pin Number Designation on Twist-Lock Connector

Capacitor Fuse

G

Light Emitti ng Diode – Green

Current Transducer

Y

Light Emitti ng Diode – Yellow

CC ­ Compressor Contactor CO ­ Condensate Overfl ow Sensor ES ­ Emergency Shutdown EWT ­ Entering Water Temp Sensor HP ­ High Pressure Switch LAT ­ Leaving Ai r Temp LLT ­ Liqui d Line Temp LP ­ Low Pressure Switch LWT ­ Leaving Water Temp

R

Light Emitting Diode – Red

FP1 ­ Freeze Protection Sensor 1 FP2 ­ Freeze Protection Sensor 2 SW1 ­ Push button SW2 ­ DIP package 8 position RV ­ Reversi ng Valve Coi l PGM ­ Phase Guard Moni tor RH ­ Reheat Valve Coi l

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

2

RR

31

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor 208-230/60/3

Note 2 Isol ation Valve
RV-A FP1-A
LP-A HP-A RV-B FP1-B LP-B HP-B RH-A RH-B

Black (32) CCCCA Violet (31)

RV-A FP1-A LAT LP-A HP-A

Orange Yellow

Blue Black

(28) 30 Gray (32) (34)

RV T

T

Yellow

Orange (31) Gray Blue Black

(29)

(33) (35)

JW2

P9 EH1 CC2 CC F C

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C

K1-RV Relay

P2 ES LS

R F1-3A

K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay

ALM ALG ACC COM

K5-Alarm Relay

Gray

ACC NO

K6-Acc

ACC NC

Relay

LO

F

PWM

Aurora Base Control A

SW1

Status LED3

CFM

(ABC-A)

Test Mode

G

R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

Com1 LED5
G RS485 NET

RS485 EXP

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config

LED2

Y

C

P8

C R – + P7

C R – + P6 CO C EH1 C EH2P3

Y1 G CC

Black Red
Red Red Note 2

Valve RHA Note 3
“EX” Con nector (twist lock)
1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 19 20 22 23 25 26 27

Red/White

Black
To UPC

Bro wn (38)

Bro wn (37)

Condensate

470

RV-B

Resistor FP1-B

LP-B

HP-B

Orange/ White (38)

Yellow (40)

Blue/ Black/ White White (42) (44)

RV T

Black (36) CCCCB Violet (35)

Orange/ White

Yellow (41)

(39)

Blue/ Black/ White White (43) (45)

P9 EH1 CC2 CC F C

P2

ES

LS

ALM ALG ACC COM

K5-Alarm Relay

ACC NO ACC NC

K6-Acc Relay

LO R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

C

P8

JW2

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F

K1-RV Relay

K3-CC2 Relay K2-CC Rel ay K4-Fan Relay

Aurora Base Control B (ABC-B)

SW1 Test Mode

Com1 LED5
G RS485 NET
C R – + P7

RS485 EXP C R – + P6 CO C EH1 C EH2P3

PWM

Status

CFM

LED3

G

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config

LED2

Y

Y1 G CC

Valve RHB Note 3

Black/White
To UPC

Bro wn (41)

Bro wn (40)

Condensate

Black/White (18)
Yellow (17 )
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
White

32

Note 3

Note 2 Isol ation Valve

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
Dual Compressor 208-230/60/3

Unit Power Input 208-230/60/3

G

L1

L2

L3

L1

L2

L3

Green / Yel low (G1) Compressor A

Green / Yel low (G2) Compressor B

Phase Gu ard Monitor (PG M)
L1 L2 L3

Blue (AC)

T3

T1

T2

Red (AB)

Black (AA) Blue (AF)

T3

T1

T2

Red (AE)

Black (AD)

CCA

T3

T2

T1

CCB

T3

T2

T1

Black (AG) Red (AH) Blue (AJ)

Black (X) White (Y) Red (Z)

PB1

2 Black/White (20)

Green/Yel low (15)

3

1

Green/Yel low (16)

Blue (C) Red (B) Black (A)
Blue (F) Red (E) Black (D)
Black (G) Red (H)
Blue (J)
Black (U)
Red (V) Blue (W)

Black/White

24V Tra nsformer

Black (14)

Yellow (13 ) Y-OUT

Yellow

Cla ss 2

C

Y

Yellow (11 )

PGM

Black/White

Yellow (12 )

L3

L2

L1

Black
Red for 20 8V Blue for 230V
Black

L3

L2

L1

Blower Motor L1 A L3
L2

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Black (K) White (L) Red (M)

See Note 4

Blower

Motor

B

L1

L3

L2

Control Box Base Panel

Green / Yel low (39)

Control Box Door

Accessor y Relay

Operation

SW2-4 SW2-5

Cycl e with Blower

On On

Cycl e with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

24V Tra nsformer

Yellow (19 )

Yellow

Cla ss 2

Red for 20 8V Blue for 230V

PWM CFM
C

Factory Factory

HP P4

ECM PWM

HP

P13

LP

LP

FP2

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

CC2 Factory

G P5 LO HI CCG CC FG F R
F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1
JW2 Alarm
P2 Fi eld Connections

LED1 R

Off FP1 ­ 15oF/30oF
FP2 ­ 15oF/30oF

On 1 LED2
2Y

Faul t

RV ­ B/O

ACC ­ Dip 4

3 Config 4

LED3

ACC ­ Dip 5

CC ­ Dual/Si ngle

G L ­ Pulse/Continuous

Status

Reheat/Normal

5 6 7 8 SW2

AURORA BASE CONTROLTM
Com1 G

RS485 Exp

EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7

RS 485

Factory Use

RS485 NET

P11

P9

Factory Fan Connection

P8 Com2 G

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Fi eld Connections

3A-Fuse

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

RR

CC C

Notes:
1 ­ P1 (screw terminals) and P9 (Molex connector) are adjacent and share common terminals in the same or der. 2 ­ Optional isolation water valv e. 3 ­ Optional hot gas reheat. 4 ­ Sizes 240-360 equipped with two blowers .

Legend

Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal

L1

Fi eld Wiring Lug

1 2 3

T

Thermistor

Relay Coi l

Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure

Polarized connector

Ground
Relay Con tacts ­ N.O., N.C.
Capacitor
Fuse
CCA ­ Compressor A Contactor CCB ­ Compressor B Contactor CO ­ Condensate Overfl ow Sensor ES ­ Emergency Shutdown HP1 ­ High Pressure Switch 1 HP2 ­ High Pressure Switch 2 LP1 ­ Low Pressure Switch 1 LP2 ­ Low Pressure Switch 2 FP1 ­ Freeze Protection Sensor 1 FP2 ­ Freeze Protection Sensor 2 F1 ­ Fuse

EX-XX

Pin Number Designation on Twist-Lock Connector

G

Light Emitting Diode – Green

Y

Light Emitting Diode – Yellow

R

Light Emitti ng Diode – Red

SW1 ­ Push button SW2 ­ DIP package 8 position RV1 ­ Reversi ng Valve Coi l 1 RV2 ­ Reversi ng Valve Coi l 2 PGM ­ Phase Guard Moni tor RH ­ Reheat Valve Coi l

33

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor 460/60/3

Note 2 Isol ation Valve
RV-A FP1-A
LP-A HP-A RV-B FP1-B LP-B HP-B RH-A RH-B

Black (32) CCCCA Violet (31)

RV-A FP1-A LAT LP-A HP-A

Orange Yellow

Blue Black

(28) 30 Gray (32) (34)

RV T

T

Yellow

Orange (31) Gray Blue Black

(29)

(33) (35)

JW2

P9 EH1 CC2 CC F C

R

F

FG

CC

CCGCHCI2

CC2 CC2 LO G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C

K1-RV Relay

P2 ES LS

R F1-3A

K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay

ALM ALG ACC COM

K5-Alarm Relay

Gray

ACC NO

K6-Acc

ACC NC

Relay

LO

F

PWM

Aurora Base Control A

SW1

Status LED3

CFM

(ABC-A)

Test Mode

G

R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

Com1 LED5
G RS485 NET

RS485 EXP

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config
LED2

Y

C

P8

C R – + P7

C R – + P6 CO C EH1 C EH2P3

Y1 G CC

Black Red
Red Red Note 2

Valve RHA Note 3
“EX” Con nector (twist lock)
1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 19 20 22 23 25 26 27

Red/White

Black
To UPC

Bro wn (38)

Bro wn (37)

Condensate

470

RV-B

Resistor FP1-B

LP-B

HP-B

Orange/ White (38)

Yellow (40)

Blue/ Black/ White White (42) (44)

RV T

CCCCB

Black (36)

Violet (35)

Orange/ Yellow White (41) (39)

Blue/ Black/ White White (43) (45)

P9 EH1 CC2 CC F C

P2

ES

LS

ALM ALG ACC COM

K5-Alarm Relay

ACC NO ACC NC

K6-Acc Relay

LO R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

C

P8

JW2

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F

K1-RV Relay

K3-CC2 Relay K2-CC Rel ay K4-Fan Relay

Aurora Base Control B (ABC-B)

SW1 Test Mode

Com1 LED5
G RS485 NET
C R – + P7

RS485 EXP C R – + P6 CO C EH1 C EH2P3

PWM

Status

CFM

LED3

G

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config

LED2

Y

Y1 G CC

Valve RHB Note 3

Black/White
To UPC

Bro wn (41)

Bro wn (40)

Condensate

GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
White

34

Note 3

Note 2 Isol ation Valve

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
Dual Compressor 460/60/3

Unit Power Input 460/60/3

G

L1

L2

L3

L1

L2

L3

Green / Yel low (G1) Compressor A

Green / Yel low (G2) Compressor B

Phase Gu ard Monitor (PG M)
L1 L2 L3

Blue (AC)

T3

T1

T2

Red (AB)

Black (AA) Blue (AF)

T3

T1

T2

Red (AE)

Black (AD)

CCA

T3

T2

T1

CCB

T3

T2

T1

Bro wn (AG) Orange (AH)
Yellow (AJ)

Black (X) White (Y) Red (Z)

PB1
Black/White (18) 2
Black/White (20)

Green/Yel low (15)

3

Yellow (17 ) 1

Green/Yel low (16)

Yellow (C) Orange (B) Bro wn (A)
Yellow (F) Orange (E) Bro wn (D)
Bro wn (G) Orange (H)
Yellow (J)
Bro wn (U)
Orange (V) Yellow (W)

Black/White

24V Tra nsformer

Black (14)

Yellow (13 ) Y-OUT

Yellow

Cla ss 2

C

Y

Yellow (11 )

PGM

Black/White

Yellow (12 )

L3

L2

L1

Black Blue
Black

L3

L2

L1

Blower Motor L1 A L3
L2

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Black (K) White (L) Red (M)

See Note 4

Blower

Motor

B

L1

L3

L2

Control Box Base Panel

Green / Yel low (39)

Control Box Door

Accessor y Relay

Operation

SW2-4 SW2-5

Cycl e with Blower

On On

Cycl e with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

24V Tra nsformer

Yellow (19 )

Yellow

Blue

Cla ss 2

PWM CFM
C

Factory Factory

HP P4

ECM PWM

HP

P13

LP

LP

FP2

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

CC2 Factory

G P5 LO HI CCG CC FG F R
F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1
JW2 Alarm
P2 Fi eld Connections

LED1 R

Off FP1 ­ 15oF/30oF
FP2 ­ 15oF/30oF

On 1 LED2
2Y

Faul t

RV ­ B/O

ACC ­ Dip 4

3 Config 4

LED3

ACC ­ Dip 5

CC ­ Dual/Si ngle

G L ­ Pulse/Continuous

Status

Reheat/Normal

5 6 7 8 SW2

AURORA BASE CONTROLTM
Com1 G

RS485 Exp

EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7

RS 485

Factory Use

RS485 NET

P11

P9

Factory Fan Connection

P8 Com2 G

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Fi eld Connections

3A-Fuse

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

RR

CC C

Notes:
1 ­ P1 (screw terminals) and P9 (Molex connector) are adjacent and share common terminals in the same or der. 2 ­ Optional isolation water valv e. 3 ­ Optional hot gas reheat. 4 ­ Sizes 240-360 equipped with two blowers .

Legend

Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal

L1

Fi eld Wiring Lug

1 2 3

T

Thermistor

Relay Coi l

Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure

Polarized connector

Ground
Relay Con tacts ­ N.O., N.C.
Capacitor
Fuse
CCA ­ Compressor A Contactor CCB ­ Compressor B Contactor CO ­ Condensate Overfl ow Sensor ES ­ Emergency Shutdown HP1 ­ High Pressure Switch 1 HP2 ­ High Pressure Switch 2 LP1 ­ Low Pressure Switch 1 LP2 ­ Low Pressure Switch 2 FP1 ­ Freeze Protection Sensor 1 FP2 ­ Freeze Protection Sensor 2 F1 ­ Fuse

EX-XX

Pin Number Designation on Twist-Lock Connector

G

Light Emitting Diode – Green

Y

Light Emitting Diode – Yellow

R

Light Emitti ng Diode – Red

SW1 ­ Push button SW2 ­ DIP package 8 position RV1 ­ Reversi ng Valve Coi l 1 RV2 ­ Reversi ng Valve Coi l 2 PGM ­ Phase Guard Moni tor RH ­ Reheat Valve Coi l

35

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 208-230/60/3

G

Note 2 Isol ation Valve

Black Red
Red Red Note 2

Black (32) CCCCA Violet (31)

RV-A FP1-A FP2-A LP-A HP-A

Orange Yellow

Blue Black

(28) 30 Black (32) (34)

RV T

T

Yellow

Orange (31) Black Blue Black

(29)

(33) (35)

JW2

P9 EH1 CC2 CC F C

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C

K1-RV Relay

P2 ES LS

R F1-3A

K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay

ALM ALG ACC COM

K5-Alarm Relay

Gray

ACC NO

K6-Acc

ACC NC

Relay

LO

F

PWM

Aurora Base Control A

SW1

Status LED3

CFM

(ABC-A)

Test Mode

G

R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

Com1 LED5
G RS485 NET

RS485 EXP

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config
LED2

Y

C

P8

C R – + P7

C R – + P6 CO C EH1 C EH2P3

Y1 G CC

Valve RHA Note 3

Black
To UPC

Bro wn (38) Bro wn (37)

WSE Condensate Bro wn (113)

RV-A FP1-A LP-A HP-A WSE RV-B FP1-B LP-B HP-B RH-A
RH-B

0-10V G ND 24V 0-10V G ND 24V

Y

GY

G

“EX” Con nector (twist lock)

1

2

3

4

5

6

7

8

White

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

Red/White

Valve RHB Note 3

RV-B FP1-B FP1-B LP-B HP-B

Orange/ White (38)

Yellow (40)

Black

Blue/ White (42)

Black/ White (44)

CCCCB

RV T

T

Black (36)

Violet (35)

Orange/ Yellow White (41)

Black

Blue/ White

Black/ White

(39)

(43) (45)

P9 EH1 CC2 CC F C

P2

ES

LS

ALM ALG ACC COM

K5-Alarm Relay

ACC NO ACC NC

K6-Acc Relay

LO R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

C

P8

JW2

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F

K1-RV Relay

K3-CC2 Relay K2-CC Rel ay K4-Fan Relay

Aurora Base Control B (ABC-B)

SW1 Test Mode

Com1 LED5
G RS485 NET
C R – + P7

RS485 EXP C R – + P6 CO C EH1 C EH2P3

Status LED3
G

PWM CFM

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config
LED2

Y

Y1 G CC

Black/White
To UPC

Bro wn (41) Bro wn (40)

WSE Condensate Bro wn (114)

Black/White (18)
Yellow (17 )
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
White

36

Note 3

Note 2 Isol ation Valve

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 208-230/60/3

G
Black/White (18)
ellow (17 )
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
e

Unit Power Input 208-230/60/3

L1

L2

L3

L1

L2

L3

Green / Yel low (G1) Compressor A

Green / Yel low (G2) Compressor B

Phase Gu ard Monitor (PG M)
L1 L2 L3

Blue (AC)

T3

T1

T2

Red (AB)

Black (AA) Blue (AF)

T3

T1

T2

Red (AE)

Black (AD)

CCA

T3

T2

T1

CCB

T3

T2

T1

Black (AG) Red (AH) Blue (AJ)

Black (X) White (Y) Red (Z)

PB1

2 Black/White (20)

Green/Yel low (15)

3

1

Green/Yel low (16)

Blue (C) Red (B) Black (A)
Blue (F) Red (E) Black (D)
Black (G) Red (H)
Blue (J)
Black (U)
Red (V) Blue (W)

Black/White

24V Tra nsformer

Black (14)

Yellow (13 ) Y-OUT

Yellow

Cla ss 2

C

Y

Yellow (11 )

PGM

Black/White

Yellow (12 )

L3

L2

L1

Black
Red for 20 8V Blue for 230V
Black

L3

L2

L1

Blower Motor L1 A L3
L2

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Black (K) White (L) Red (M)

See Note 4

Blower

Motor

B

L1

L3

L2

Control Box Base Panel

Green / Yel low (39)

Control Box Door

Accessor y Relay

Operation

SW2-4 SW2-5

Cycl e with Blower

On On

Cycl e with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

24V Tra nsformer

Yellow (19 )

Yellow

Cla ss 2

Red for 20 8V Blue for 230V

Factory PWM CFM C

HP P4

ECM PWM

HP

P13

LP

LP

FP2

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

CC2 Factory

G P5 LO HI CCG CC FG F R
F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1
JW2 Alarm
P2 Fi eld Connections

LED1 R

Off FP1 ­ 15oF/30oF
FP2 ­ 15oF/30oF

On 1 LED2
2Y

Faul t

RV ­ B/O

ACC ­ Dip 4

3 Config 4

LED3

ACC ­ Dip 5

CC ­ Dual/Si ngle

G L ­ Pulse/Continuous

Status

Reheat/Normal

5 6 7 8 SW2

AURORA BASE CONTROLTM
Com1 G

RS485 Exp

Factory

EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7

RS 485

Factory Use

RS485 NET

P11

P9

Factory Fan Connection

P8 Com2 G

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Fi eld Connections

3A-Fuse

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

RR

CC C

Notes:
1 ­ P1 (screw terminals) and P9 (Molex connector) are adjacent and share common terminals in the same or der. 2 ­ Optional isolation water valv e. 3 ­ Optional hot gas reheat. 4 ­ Sizes 240-360 equipped with two blowers .

Legend

Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal

L1

Fi eld Wiring Lug

1 2 3

T

Thermistor

Relay Coi l

Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure

Polarized connector

Ground
Relay Con tacts ­ N.O., N.C.
Capacitor
Fuse
Current Transducer
CCA ­ Compressor A Contactor CCB ­ Compressor B Contactor CO ­ Condensate Overfl ow Sensor ES ­ Emergency Shutdown HP1 ­ High Pressure Switch 1 HP2 ­ High Pressure Switch 2 LP1 ­ Low Pressure Switch 1 LP2 ­ Low Pressure Switch 2 FP1 ­ Freeze Protection Sensor 1 FP2 ­ Freeze Protection Sensor 2 F1 ­ Fuse

EX-XX

Pin Number Designation on Twist-Lock Connector

G

Light Emitting Diode – Green

Y

Light Emitting Diode – Yellow

R

Light Emitti ng Diode – Red

SW1 ­ Push button SW2 ­ DIP package 8 position RV1 ­ Reversi ng Valve Coi l 1 RV2 ­ Reversi ng Valve Coi l 2 PGM ­ Phase Guard Moni tor RH ­ Reheat Valve Coi l

37

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 460/60/3

Note 2 Isol ation Valve

Black Red
Red Red Note 2

Black (32) CCCCA Violet (31)

RV-A FP1-A FP2-A LP-A HP-A

Orange Yellow

Blue Black

(28) 30 Black (32) (34)

RV T

T

Yellow

Orange (31) Black Blue Black

(29)

(33) (35)

JW2

P9 EH1 CC2 CC F C

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C

K1-RV Relay

P2 ES LS

R F1-3A

K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay

ALM ALG ACC COM

K5-Alarm Relay

Gray

ACC NO

K6-Acc

ACC NC

Relay

LO

F

PWM

Aurora Base Control A

SW1

Status LED3

CFM

(ABC-A)

Test Mode

G

R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

Com1 LED5
G RS485 NET

RS485 EXP

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config
LED2

Y

C

P8

C R – + P7

C R – + P6 CO C EH1 C EH2P3

Y1 G CC

Valve RHA Note 3

Black
To UPC

Bro wn (38) Bro wn (37)

WSE Condensate Bro wn (113)

RV-A FP1-A LP-A HP-A WSE RV-B FP1-B LP-B HP-B RH-A
RH-B

0-10V G ND 24V 0-10V G ND 24V

Y

GY

G

“EX” Con nector (twist lock)

1

2

3

4

5

6

7

8

White

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

Red/White

Valve RHB Note 3

RV-B FP1-B FP1-B LP-B HP-B

Orange/ White (38)

Yellow (40)

Black

Blue/ White (42)

Black/ White (44)

CCCCB

RV T

T

Black (36)

Violet (35)

Orange/ Yellow White (41) (39)

Black

Blue/ White (43)

Black/ White (45)

P9 EH1 CC2 CC F C

P2

ES

LS

ALM ALG ACC COM

K5-Alarm Relay

ACC NO ACC NC

K6-Acc Relay

LO R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

C

P8

JW2

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F

K1-RV Relay

K3-CC2 Relay K2-CC Rel ay K4-Fan Relay

Aurora Base Control B (ABC-B)

SW1 Test Mode

Com1 LED5
G RS485 NET
C R – + P7

RS485 EXP C R – + P6 CO C EH1 C EH2P3

Status LED3
G

PWM CFM

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config
LED2

Y

Y1 G CC

Black/White
To UPC

Bro wn (41) Bro wn (40)

WSE Condensate Bro wn (114)

Black/White (18)
Yellow (17 )
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
White

38

Note 3

Note 2 I sol ation Valve

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 460/60/3

Unit Power Input 460/60/3

G

L1

L2

L3

L1

L2

L3

Green / Yel low (G1) Compressor A

Green / Yel low (G2) Compressor B

Phase Gu ard Monitor (PG M)
L1 L2 L3

Blue (AC)

T3

T1

T2

Red (AB)

Black (AA) Blue (AF)

T3

T1

T2

Red (AE)

Black (AD)

CCA

T3

T2

T1

CCB

T3

T2

T1

Bro wn (AG) Orange (AH)
Yellow (AJ)

Black (X) White (Y) Red (Z)

PB1

2 Black/White (20)

Green/Yel low (15)

3

1

Green/Yel low (16)

Yellow (C) Orange (B) Bro wn (A)
Yellow (F) Orange (E) Bro wn (D)
Bro wn (G) Orange (H)
Yellow (J)
Bro wn (U)
Orange (V) Yellow (W)

Black/White

24V Tra nsformer

Black (14)

Yellow (13 ) Y-OUT

Yellow Cla ss 2 C

Y

Yellow (11 )

PGM

Black/White

Yellow (12 )

L3

L2

L1

Black Blue
Black

L3

L2

L1

Blower Motor L1 A L3
L2

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Black (K) White (L) Red (M)

See Note 4

Blower

Motor

B

L1

L3

L2

Control Box Base Panel

Green / Yel low (39)

Control Box Door

Accessor y Relay

Operation

SW2-4 SW2-5

Cycl e with Blower

On On

Cycl e with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

24V Tra nsformer

Yellow (19 )

Yellow

Blue

Cla ss 2

PWM CFM
C

Factory Factory

HP P4

ECM PWM

HP

P13

LP

LP

FP2

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

CC2 Factory

G P5 LO HI CCG CC FG F R
F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1
JW2 Alarm
P2 Fi eld Connections

Off On

LED1 FP1 ­ 15oF/30oF

1

R FP2 ­ 15oF/30oF

2

Faul t

RV ­ B/O

3

ACC ­ Dip 4

4

LED3

ACC ­ Dip 5

CC ­ Dual/Si ngle

G L ­ Pulse/Continuous

Status

Reheat/Normal

5 6 7 8 SW2

LED2 Y
Config

AURORA BASE CONTROLTM
Com1 G

RS485 Exp

EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7

RS 485

Factory Use

RS485 NET

P11

P9

Factory Fan Connection

P8 Com2 G

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Fi eld Connections

3A-Fuse

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

RR

CC C

Notes:
1 ­ P1 (screw terminals) and P9 (Molex connector) are adjacent and share common terminals in the same or der. 2 ­ Optional isolation water valv e. 3 ­ Optional hot gas reheat. 4 ­ Sizes 240-360 equipped with two blowers .

Legend

Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal

L1

Fi eld Wiring Lug

1 2 3

T

Thermistor

Relay Coi l

Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure

Polarized connector

Ground
Relay Con tacts ­ N.O., N.C.
Capacitor
Fuse
Current Transducer
CCA ­ Compressor A Contactor CCB ­ Compressor B Contactor CO ­ Condensate Overfl ow Sensor ES ­ Emergency Shutdown HP1 ­ High Pressure Switch 1 HP2 ­ High Pressure Switch 2 LP1 ­ Low Pressure Switch 1 LP2 ­ Low Pressure Switch 2 FP1 ­ Freeze Protection Sensor 1 FP2 ­ Freeze Protection Sensor 2 F1 ­ Fuse

EX-XX

Pin Number Designation on Twist-Lock Connector

G

Light Emitting Diode – Green

Y

Light Emitting Diode – Yellow

R

Light Emitti ng Diode – Red

SW1 ­ Push button SW2 ­ DIP package 8 position RV1 ­ Reversi ng Valve Coi l 1 RV2 ­ Reversi ng Valve Coi l 2 PGM ­ Phase Guard Moni tor RH ­ Reheat Valve Coi l

39

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
Aurora Advanced and Premium Controls Add-on

Note 1 Modulang Water Valve

~ Y

CO M

321

Gr ay

Black To PB1-2

Red

To PB1-1

L2

NO L2

NO

K5

DISCH P14 C R L1 L1
K6

SCT-A SUCP-A

LL T-A DISCH-A

HW SCT-B

SUCP-B

LL T-B

DISCH-B

1

EEV-A

2

3

4

1

EEV-B

2

3

4

Blac k

Gr ee n

Blac k

Gr ee n

DISCHARGE GND 1 PRESSURE OUT 2
TRANSDUCER 5DC 3

Black White Red

COM

COM

DISCH ARGE PRESSU RE TRANSDUCER
GND 1 OUT 2 5DC 3

Black White Red

K3 K2 K1

LLT P16

Gr ay Note 4
FL OW M ET E R

Brown T
Brown

Gr ay T
Gr ay

GND 3 3 OUT 2 2 5DC 4 4

Gr een White Brown

Purple T
Purple
White T
White

P2

EWT LWT FLOW LAT P1

Status G
AXBTM-A
(Aurora Expansion Board A)

P5 CT2 CT1 43 21

P11 ANA ACC2 DH DIV

Red Black

Note 3

0-10V Y

24V G

Bro wn/White T
Bro wn/White
Red Gr ay Black

G ND

U

Hot Gas Reheat

Blue

Compressor A T1

Valve Note 2

Blue

Red Compressor A T2
Red

Black Black

Auxi liary Heat CT

P15 CT2 CT1 4321

HA2 HA1 SGI P3 C S +5 C S +5 2 1 C OUT C IN LOOP VS DATA VS PUMP PUMP SLAVE

Red

White

Gr een

Gr ay

1+

Black

2 X1

P10 STEPPER

Heat Shrink “EX” Con nector (twist lock)
1 2 3

Modbus Add. ID Future Use Future Use
Acc 2 ­ Dip 1 Acc 2 ­ Dip 2

OFF ON 1 2 3 4 5
SW1

P12 SUC P

Ye ll ow Red
Or ang e

3 X2 4 Y1 5 Y2

Black 1 GND SUCTION White 2 OUT PRESSURE
Red 3 5DC TRANSDUCER
Blue( 66) T Blue( 67)

SCT

P18

4

5

6

Pink

HW

P17

P4

7

Pink

8

HOT WATER

9

OPTIO N

MOTOR RX TX R C V+ P8
RS485 (+) (-) R C P6
ZO NE (+) (-) R C P7
ABC (+) (-) R C +5 P9

10

11

12

13

To ABC-A

14

15

16

17

Green/Yel low

18

19

20

21

Notes:

22

23

24

1 ­ Optional factor y installed modulating water valve. Requires Auror a Pr emium Controls

2 ­ Optional factor y installed modulating hot gas reheat.

25

3 ­ Optional Waterside Economizer.

26

4 ­ Optional flow meter for field install only.

27

R

C

24V

GN D

P5

P2

+24 GN VD

+5V USB

USB

5A

GN

D

POW ER SUPPLY

BOARD

P1

P4

P3

4321 54321 4321 54321

28

29

AXB Accessory 2 DIP Sengs

30

SW1-4 SW1-5 DESCRIPTION

31

ON

ON Cycles with Blower

OFF

ON Cycles with CC rst stage compressor or compressor spd 1-12

ON

OFF Cycles with CC2 second stage of compressor or comp spd 7-12

OFF

OFF Cycles with DH from ABC board

ELECTRONIC EXPANSION
VALVE A

ELECTRONIC EXPANSION
VALVE B

Black White Gr een Red Or ang e Red Ye ll ow Black Gr ay Black White Gr een Red Orang e Red Ye ll ow Black Gr ay

40

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Aurora Advanced and Premium Controls Add-on

L2

NO L2

NO

K5

DISCH P14 C R L1 L1
K6

COM

COM

P11 ANA ACC2 DH DIV

K3 K2 K1

LLT P16

24V G

EWT LWT FLOW LAT P1

P2

HA2 HA1 SGI P3 C S +5 C S +5 2 1 C OUT C IN LOOP VS DATA VS PUMP PUMP SLAVE

P4

Status G
AXBTM-B
(Aurora Expansion Board B)

Modbus Add. ID Future Use Future Use
Acc 2 ­ Dip 1 Acc 2 ­ Dip 2

OFF ON 1 2 3 4 5
SW1

To ABC-B

P17

P18

P12 SUC P

P10 STEPPER

HW

SCT

P15 CT2 CT1 4321

P5 CT2 CT1 43 21

0-10V Y

Red Gr ay Black

G ND

U

Blue/W hite Blue/W hite Red/White Red/White

Hot Gas Reheat Valve Note 2
Compressor B T1
Compressor B T2

Black Black

Auxi liary Heat CT

Gr ay Black Ye ll ow Red Or ang e

1+ 2 X1 3 X2 4 Y1 5 Y2

Black 1 GND SUCTION White 2 OUT PRESSURE
Red 3 5DC TRANSDUCER
Blue T Blue

Legend

Factory Low Voltage Wiring

Factory Line Vol tage Wiring

T

Fi eld Low Voltage Wiring

Fi eld Li ne Voltage Wi ri ng

Optional Block

DC Voltage PCB Traces

Fi eld Zone Sensor Wi ri ng

Internal Ju nction

Qui ck Con nect Terminal

L1

Fi eld Wiring Lug

Ground Relay Con tacts ­ N.O., N.C.

Capacitor G
Fuse

Current Transducer (CT)

Y

DISCH ­ Discharge Pressure EWT ­ Entering Water Temperature

R

HW ­ Hot Water Gene ration

LAT ­ Leaving Ai r Temperature

LLT ­ Liquid Line Temperature

LWT ­ Leaving Water Temperature

SCT ­ Suction Temperature

SUCP ­ Suction Pressure

1 2 3

EX-XX

Thermistor Relay Coi l Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure
Polarized connector
Pin Number Designation on Twist-Lock Connector
Light Emitting Diode – Green Light Emitting Diode – Yellow
Light Emitti ng Diode – Red

Aurora Timing Events

Event

Normal Mode

Random Start Delay

5 to 80 seconds

Compressor On Delay

5 seconds

Compressor Minimum On Time

2 minutes

Compressor Short Cycl e Delay

4 minutes

Blower Off Delay

30 seconds

Faul t Recogn itio n Delay ­ High Pressure

Less than 1 second

Start-Up Bypass ­ Low Pressure

2 minutes

Faul t Recogn itio n Delay ­ Low Pressure

30 seconds

Start-Up Bypass ­ Low Water/Air Coil Limit

2 minutes

Faul t Recogn itio n Delay ­ Low Water/Ai r Coil Limit 30 seconds

Faul t Recogn itio n Delay ­ Condensate Overfl ow

30 seconds

Thermostat Call Recognition Time

2 seconds

Auxi liary Heat Stagi ng Del ay

5 minutes

Emergency Heat Stagi ng Dela y

2 minutes

Water Valve Slow Open Delay

90 seconds

Reheat Delay

30 seconds

Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds

Aurora LED Flash Codes

SlowFlash 1 second on and 1 second off

Fast Flash 100 mil liseconds on and 100 mi lliseconds off

Flash Code 100 mil liseconds on and 400 mi lliseconds off with a 2 second pause before re peating

Random Start Delay

Status LED (LED3, Green)

Fast Fl ash

Configuration LED (LED2, Yel low)

Fast Fl ash

Faul t LED (LED1, Red)

Fast Fl ash

Sta tus LED (LED3, Green)

Configuration LED (LED2, Yellow)

Fault LED (LED1, Red)

Normal Mode

ON

No Software Overi de Fl ash ECM Settin g Normal Mode

OFF

Control is Non-Functional

OFF DIP Switch Overide

Slow Flash Input Fault Lockout

Fl ash Code 1

Test Mode

Slow Flash ECM Configu re Mod e

Fast Fl ash High Pressure Lockout

Fl ash Code 2

Lockout Active

Fast Fl ash Reset Confi gure Mode

Off

Low Pressure Locko ut

Fl ash Code 3

Dehumidification Mo de

Fl ash Code 2

Low Air Coil Limi t Lockout – FP2 Fl ash Code 4

Reserved

Fl ash Code 3

Low Water Coil Limi t Lockout – FP1 Fl ash Code 5

Reserved

Flash Code 4

Loss of Charge Lockout

Fl ash Code 6

Load Shed

Fl ash Code 5

Condensate Overfl ow Lockout

Fl ash Code 7

ESD

Fl ash Code 6

Over/Under Vol tage Sh utdown

Fl ash Code 8

Reserved

Fl ash Code 7

Reserved

Fl ash Code 9

Compressor Monitor Lockout

Fl ash Code 1 0

Air/Water Coil Limit Sensor Error Fl ash Code 1 1

Page 1

41

MOTOR RX TX R C V+ P8
RS485 (+) (-) R C P6
ZO NE (+) (-) R C P7
ABC (+) (-) R C +5 P9

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
Single Compressor 575/60/3

CC

Ultra Tech CS RCP
Blue Blue

See N ote 5
FP2/ RV FP1 LAT LP HP

Orange (1)

Yellow Black

Blue (7)

Black (9)

RV T

T

Black (19)

Violet (18)

Gray Red Red
Blue (22) Blue (23)

Orange Yellow (2)

Black

Blue (8)

Black (10)

See N ote 3

K1-RV Relay

K3-CC2 Relay K2-CC Rel ay K4-Fan Relay
JW2

P9 EH1 CC2 CC F C

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C

P2 ES LS

R F1-3A

ALM ALG ACC COM ACC NO ACC NC
LO

K5-Alarm Relay
K6-Acc Relay

F

PWM

Aurora Base Control

SW1

Status

LED3

CFM

(ABC)

Test Mode

G

R C O/B G Y1 Y2 W DH P1
R Red

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

Com2 LED5

Com1 LED5

SW2 Config LED2

G RS485 NET

G RS485 NET

RS485 EXP

Y

C

P8

C R – + P7

C R – + P6 CO C EH1 C EH2 P3

Y1 G CC

Black

Black
Reh eat Valve See N ote 2

To UPC
See N ote 4

Aurora Advanced and Premiu m Opon

Red Heat Shrink
White Gr een

T T

Gr ay Gr ay Gr een White
Brown Vio le t Vio le t White White

GND 3 OUT 2 5DC 4

Brown Brown

Bro wn (25) Bro wn (24)
Condensate

FLOW

T

METER

DISCH ARGE PRESSU RE TRANSDUCER
T

Black White Red

GND 1 OUT 2 5DC 3

MOTOR RX
TX
R
C
V+ P8
RS485 (+)
(-)
R
C P6 ZO NE (+)
(-)
R
C P7 ABC (+)
(-)
R
C
+5 P9

P4

P2

HA2 HA1 SGI P3 C S +5 C S +5 2 1 C OUT C IN LOOP VS DATA VS PUMP PUMP SLAVE

EWT LWT FLOW LAT P1

LLT P16

Status G

AX BTM
(Aurora Expansion Board)

Modbus Add. ID Future Use Future Use
Acc 2 ­ Dip 1 Acc 2 ­ Dip 2

OFF ON 1 2 3 4 5
SW1

P17 HHWW 21

P18 SCT 321

P12 SCP
321

P10 STEPPER

K3 K2 K1

P15 CT2 CT1 4321

P5 CT2 CT1 4321

P11 ANA ACC2 DH DIV

Pink T
Pink

T

Blue Blue

Black White Red

1 GND SU CTI ON 2 OUT PRES SU RE 3 5DC T RA NSD UCE R

DISCH P14 C
R
L1
L1 K6

COM

NO

K5

COM

NO L2

L2

GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D

L1
Bla Bla Yello

Modulang Water Valve

Gray

Y

321

Red

~

Black

CO M

24V G

0-10V Y

G ND

U

Red Gr ay Black
Hot Gas Reheat Valve Note 2
Red Black

Note 4

Blue

Compressor T1

Blue

Red Compressor T2
Red

42

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.

Single Compressor 575/60/3

Unit Power Supply

Non-Fuse d Di sconne ct or T ermi na l Bl oc k

G

L1

L2

L3

Green / Yel low (G1) Compressor

L1

L2

L3

T3

T1

T2

Yellow (AC) Orange (AB) Bro wn (AA)

CC

T3

T2

T1

L3

L2

L1

Phase Guard Monitor (PG M)
L1 L2 L3

Bro wn (A) Orange (B) Yellow (C)
Black (K) White (L) Red (M) Bro wn (AG) Orange (AH) Yellow (AJ)

L2

L1

L3

Blower Motor

Black (16) Black
Yellow (17 )

Green/ Yellow (15 )

460V
X1

575V
H1

X2

H2

X3

H3

Class N
Control Box Base Panel
PB1

Green/Yel low (29)

Control Box Door

2 Green/Yel low (14)
3 Black (13)

Black/White

1 C

Yellow (12 )

Y-OUT

Y

PGM

Yellow

Tra nsformer

Black
Blue Cla ss 2

97P8 95-08 03/01/21

Aurora LED Flash Codes

SlowFlash 1 second on and 1 second off

Fast Flash 100 milliseconds on and 100 milliseconds off

Flash Code 100 mil liseconds on and 400 mi lliseconds off with a 2 second pause before re peating

Random Start Delay

Status LED (LED3, Green)

Fast Fl ash

Configuration LED (LED2, Yel low)

Fast Fl ash

Faul t LED (LED1, Red)

Fast Fl ash

Sta tus LED (LED3, Green)

Configuration LED (LED2, Yellow)

Fault LED (LED1, Red)

Normal Mode

ON

No Software Overi de Fl ash ECM Settin g Normal Mode

OFF

Control is Non-Functional

OFF DIP Switch Overide

Slow Flash Input Fault Lockout

Flash Code 1

Test Mode

Slow Flash ECM Configu re Mod e

Fast Fl ash High Pressure Lockout

Fl ash Code 2

Lockout Active

Fast Fl ash Reset Confi gure Mode

Off

Low Pressure Locko ut

Fl ash Code 3

Dehumidification Mo de

Fl ash Code 2

Low Air Coil Limi t Lockout – FP2 Fl ash Code 4

Reserved

Fl ash Code 3

Low Water Coil Limi t Lockout – FP1 Fl ash Code 5

Reserved

Fl ash Code 4

Loss of Charge Lockout

Fl ash Code 6

Load Shed

Fl ash Code 5

Condensate Overfl ow Lockout

Fl ash Code 7

ESD

Fl ash Code 6

Over/Under Vol tage Sh utdown

Fl ash Code 8

Reserved

Flash Code 7

Reserved

Fl ash Code 9

Compressor Monitor Lockout

Fl ash Code 1 0

Air/Water Coil Limit Sensor Error Fl ash Code 1 1

Accessor y Relay

Operation

SW2-4 SW2-5

Cycl e with Blower

On On

Cycl e with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

Aurora Timing Events

Event

Normal Mode

Random Start Delay

5 to 80 seconds

Compressor On Delay

5 seconds

Compressor Minimum On Time

2 minutes

Compressor Short Cycl e Delay

4 minutes

Blower Off Delay

30 seconds

Fault Recogn itio n Delay ­ High Pressure

Less than 1 second

Start-Up Bypass ­ Low Pressure

2 minutes

Fault Recogn itio n Delay ­ Low Pressure

30 seconds

Start-Up Bypass ­ Low Water/Ai r Coil Limit

2 minutes

Faul t Recogn itio n Delay ­ Low Water/Ai r Coil Limit 30 seconds

Faul t Recogn itio n Delay ­ Condensate Overfl ow

30 seconds

Thermostat Call Recognition Time

2 seconds

Auxi liary Heat Stagi ng Del ay

5 minutes

Emergency Heat Stagi ng Dela y

2 minutes

Water Valve Slow Open Delay

90 seconds

Reheat Delay

30 seconds

Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds

Notes:
1 ­ P1 (screw ter minals) and P9 (Molex connector ) are adjacent and share common terminals in the same order. 2 ­ Optional factor y installed hot gas reheat. 3 ­ Optional factor y installed internal isolation valve. 4 ­ See supplemental schematic for AXB and/or UPC connections. 5 ­ LAT location with Aurora Base Controls, FP2 with Aurora Advanced and Premium Controls.

PWM CFM
C

1 2 3
24V

T1 mpressor T2

HP P4

ECM PWM

HP

P13

LP

LP

FP2

Factory

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

CC2 Factory

G P5 LO HI CCG CC FG F R
F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1
JW2 Alarm
P2 Fi eld Connections

LED1 R

Off FP1 ­ 15oF/30oF
FP2 ­ 15oF/30oF

On 1 LED2
2Y

Faul t

RV ­ B/O

ACC ­ Dip 4

3 Config 4

LED3

ACC ­ Dip 5

CC ­ Dual/Si ngle

G L ­ Pulse/Continuous

Status

Reheat/Normal

5 6 7 8 SW2

AURORA BASE CONTROLTM
Com1 G

RS485 Exp

Factory

EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7

RS 485

Factory Use

RS485 NET

P11

P9

Factory Fan Connection

P8 Com2 G

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Fi eld Connections

3A-Fuse

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

RR

CC C

Legend

Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Ju nction Quick Con nect Terminal

L1

Field Wiring Lug

T

Thermistor

Relay Coi l

Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure

Polarized connector

EX-XX

Ground Relay Con tacts ­ N.O., N.C.

Pin Number Designation on Twist-Lock Connector

Capacitor Fuse

G

Light Emitti ng Diode – Green

Current Transducer

Y

Light Emitti ng Diode – Yellow

CC ­ Compressor Contactor CO ­ Condensate Overfl ow Sensor ES ­ Emergency Shutdown EWT ­ Entering Water Temp Sensor HP ­ High Pressure Switch LAT ­ Leaving Ai r Temp LLT ­ Liqui d Line Temp LP ­ Low Pressure Switch LWT ­ Leaving Water Temp

R

Light Emitting Diode – Red

FP1 ­ Freeze Protection Sensor 1 FP2 ­ Freeze Protection Sensor 2 SW1 ­ Push button SW2 ­ DIP package 8 position RV ­ Reversi ng Valve Coi l PGM ­ Phase Guard Moni tor RH ­ Reheat Valve Coi l

43

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Base 575/60/3

RV-A FP1-A
LP-A HP-A RV-B FP1-B LP-B HP-B RH-A RH-B

Note 2 Isol ation Valve
“EX” Con nector (twist lock)
1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 19 20 22 23 25 26 27

Red/White

Black Red
Red Red Note 2

Black (32) CCCCA Violet (31)

RV-A FP1-A LAT LP-A HP-A

Orange Yellow

Blue Black

(28) 30 Gray (32) (34)

RV T

T

Yellow

Orange (31) Gray Blue Black

(29)

(33) (35)

JW2

P9 EH1 CC2 CC F C

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C

K1-RV Relay

P2 ES LS

R F1-3A

K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay

ALM ALG ACC COM

K5-Alarm Relay

Gray

ACC NO

K6-Acc

ACC NC

Relay

LO

F

PWM

Aurora Base Control A

SW1

Status LED3

CFM

(ABC-A)

Test Mode

G

R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

Com1 LED5
G RS485 NET

RS485 EXP

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config

LED2

Y

C

P8

C R – + P7

C R – + P6 CO C EH1 C EH2P3

Y1 G CC

Valve RHA Note 3

Black
To UPC

CCCCB

Bro wn (38)

Bro wn (37)

Condensate

470

RV-B

Resistor FP1-B

LP-B

HP-B

Orange/ White (38)

Yellow (40)

Blue/ Black/ White White (42) (44)

RV T

Black (36)

Violet (35)

Orange/ White

Yellow (41)

(39)

Blue/ Black/ White White (43) (45)

JW2

P9 EH1 CC2 CC F C

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C

K1-RV Relay

P2 ES LS

R F1-3A

K3-CC2 Relay K2-CC Rel ay K4-Fan Relay

ALM ALG ACC COM ACC NO ACC NC
LO

K5-Alarm Relay
K6-Acc Relay

Aurora Base Control B

SW1

Status LED3

(ABC-B)

Test Mode

G

F PWM CFM
White

R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

Com1 LED5
G RS485 NET

RS485 EXP

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config

LED2

Y

C

P8

C R – + P7

C R – + P6 CO C EH1 C EH2P3

Y1 G CC

Valve RHB Note 3

Black/White
To UPC

Bro wn (41)

Bro wn (40)

Condensate

44

Note 3

Note 2 Isol ation Valve

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
Dual Compressor Aurora Base 575/60/3

Unit Power Input 575/60/3

Green / Yel low (G1) Compressor A

Green / Yel low (G2) Compressor B

Yellow Orange Bro wn

Yellow Orange Bro wn

G

L1

L1

L2

L3

L2

L3

Phase Gu ard Monitor (PG M)
L1 L2 L3

Blue (AC)

T3

T1

T2

Red (AB)

Black (AA) Blue (AF)

T3

T1

T2

Red (AE)

Black (AD)

CCA

T3

T2

T1

CCB

T3

T2

T1

Bro wn (AG) Orange (AH)
Yellow (AJ)

57 5V H1

46 0V X1

H2

X2

H3

X3

Class N

57 5V H1

46 0V X1

H2

X2

H3

X3

Class N

PB1
Black/White (18) 2
Black/White (20)

Green/Yel low (15)

3

Yellow (17 )
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4

1 Green/Yel low (16)
Yellow (19 )

Yellow (C) Orange (B) Bro wn (A)
Yellow (F) Orange (E) Bro wn (D)
Bro wn (G) Orange (H) Yellow (J)
Bro wn (U)
Orange (V) Yellow (W)

L3

L2

L1

Black/White

24V Tra nsformer

Black (14)

Yellow (13 ) Y-OUT

Yellow

Cla ss 2

C

Y

Yellow (11 )

PGM

Black/White

Yellow (12 )

24V Tra nsformer

Yellow

Cla ss 2

Black Blue
Black Blue

PWM CFM
C

Factory Factory

HP P4

ECM PWM

HP

P13

LP

LP

FP2

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

CC2 Factory

G P5 LO HI CCG CC FG F R
F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1
JW2 Alarm
P2 Fi eld Connections

LED1 R

Off FP1 ­ 15oF/30oF
FP2 ­ 15oF/30oF

On 1 LED2
2Y

Faul t

RV ­ B/O

ACC ­ Dip 4

3 Config 4

LED3

ACC ­ Dip 5

CC ­ Dual/Si ngle

G L ­ Pulse/Continuous

Status

Reheat/Normal

5 6 7 8 SW2

AURORA BASE CONTROLTM
Com1 G

RS485 Exp

EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7

RS 485

Factory Use

RS485 NET

P11

P9

Factory Fan Connection

P8 Com2 G

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Fi eld Connections

3A-Fuse

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

RR

CC C

L3

L2

L1

Blower Motor L1 A L3
L2

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Black (K) White (L) Red (M)

See Note 4

Blower

Motor

B

L1

L3

L2

Black (X) White (Y) Red (Z)

Control Box Base Panel

Green / Yel low (39)

Control Box Door

Accessor y Relay

Operation

SW2-4 SW2-5

Cycl e with Blower

On On

Cycl e with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

Notes:
1 ­ P1 (screw terminals) and P9 (Molex connector) are adjacent and share common terminals in the same or der. 2 ­ Optional isolation water valv e. 3 ­ Optional hot gas reheat. 4 ­ Sizes 240-360 equipped with two blowers .

Legend

Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal

L1

Fi eld Wiring Lug

1 2 3

T

Thermistor

Relay Coi l

Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure

Polarized connector

Ground
Relay Con tacts ­ N.O., N.C.
Capacitor
Fuse
CCA ­ Compressor A Contactor CCB ­ Compressor B Contactor CO ­ Condensate Overfl ow Sensor ES ­ Emergency Shutdown HP1 ­ High Pressure Switch 1 HP2 ­ High Pressure Switch 2 LP1 ­ Low Pressure Switch 1 LP2 ­ Low Pressure Switch 2 FP1 ­ Freeze Protection Sensor 1 FP2 ­ Freeze Protection Sensor 2 F1 ­ Fuse

EX-XX

Pin Number Designation on Twist-Lock Connector

G

Light Emitting Diode – Green

Y

Light Emitting Diode – Yellow

R

Light Emitti ng Diode – Red

SW1 ­ Push button SW2 ­ DIP package 8 position RV1 ­ Reversi ng Valve Coi l 1 RV2 ­ Reversi ng Valve Coi l 2 PGM ­ Phase Guard Moni tor RH ­ Reheat Valve Coi l

45

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL
Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 575/60/3

Note 2 Isol ation Valve

Black Red
Red Red Note 2

Black (32) CCCCA Violet (31)

RV-A FP1-A FP2-A LP-A HP-A

Orange Yellow

Blue Black

(28) 30 Gray (32) (34)

RV T

T

Yellow

Orange (31) Gray Blue Black

(29)

(33) (35)

JW2

P9 EH1 CC2 CC F C

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C

K1-RV Relay

P2 ES LS

R F1-3A

K3-CC2 Rel ay K2-CC Rel ay K4-Fan Relay

ALM ALG ACC COM

K5-Alarm Relay

Gray

ACC NO

K6-Acc

ACC NC

Relay

LO

F

PWM

Aurora Base Control A

SW1

Status LED3

CFM

(ABC-A)

Test Mode

G

R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET

Com1 LED5
G RS485 NET

RS485 EXP

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config

LED2

Y

C

P8

C R – + P7

C R – + P6 CO C EH1 C EH2P3

Y1 G CC

Valve RHA Note 3

Black
To UPC

Bro wn (38) Bro wn (37)

WSE Condensate Bro wn (113)

RV-A FP1-A LP-A HP-A WSE RV-B FP1-B LP-B HP-B RH-A
RH-B

0-10V G ND 24V 0-10V G ND 24V

Y

GY

G

“EX” Con nector (twist lock)

1

2

3

4

5

6

7

8

White

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

Red/White

Valve RHB Note 3

CCCCB

RV-B FP1-B FP2-B LP-B HP-B

Orange/ White (38)

Yellow (40)

Black

Blue/ White (42)

Black/ White (44)

RV T

T

Black (36)

Violet (35)

Orange/ White

Yellow (41)

(39)

Black

Blue/ White (43)

Black/ White (45)

P9 EH1 CC2 CC F C

P2

ES

LS

ALM ALG ACC COM

K5-Alarm Relay

ACC NO ACC NC

K6-Acc Relay

LO R C O/B G Y1 Y2 W DH P1/P9 (Note 1)
R

Com2 LED5
G RS485 NET
C P8

JW2

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPSP4 C R
F1-3A F

K1-RV Relay

K3-CC2 Relay K2-CC Rel ay K4-Fan Relay

Aurora Base Control B (ABC-B)

SW1 Test Mode

Com1 LED5
G RS485 NET
C R – + P7

RS485 EXP C R – + P6 CO C EH1 C EH2P3

Status LED3
G

PWM CFM

Faul t

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Si ngle

6

L Output Type

7

Reheat/Normal

8

SW2 Config

LED2

Y

Y1 G CC

Black/White
To UPC

Bro wn (41) Bro wn (40)

WSE Condensate Bro wn (114)

GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor A
GN D A ( D+) B ( D-)
ID GN D A ( D+) B ( D-) ID fo ut GN D
Blower Motor B Note 4
White

46

Note 3

Note 2 I sol ation Valve

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
Dual Compressor Aurora Advanced and Premium 575/60/3

Unit Power Input 575/60/3

Green / Yel low (G1) Compressor A

Green / Yel low (G2) Compressor B

Yellow Orange Bro wn

Yellow Orange Bro wn

G

L1

L1

57 5V H1

46 0V X1

H2

X2

H3

X3

Class N

57 5V H1

46 0V X1

H2

X2

H3

X3

Class N

PB1
Black/White (18) 2
Black/White (20)

Green/Yel low (15)

3

Yellow (17 ) 1

Green/Yel low (16)

L2

L3

L2

L3

Phase Gu ard Monitor (PG M)
L1 L2 L3

Blue (AC)

T3

T1

T2

Red (AB)

Black (AA) Blue (AF)

T3

T1

T2

Red (AE)

Black (AD)

CCA

T3

T2

T1

CCB

T3

T2

T1

Bro wn (AG) Orange (AH)
Yellow (AJ)

Yellow (C) Orange (B) Bro wn (A)
Yellow (F) Orange (E) Bro wn (D)
Bro wn (G) Orange (H) Yellow (J)
Bro wn (U)
Orange (V) Yellow (W)

L3

L2

L1

Black/White

Black

L3

L2

L1

Blower Motor L1 A L3
L2

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Gnd Disconnect

L1

L1

L2

L2

L3

L3

Black (K) White (L) Red (M)

See Note 4

Blower

Motor

B

L1

L3

L2

24V Tra nsformer

Black (14)

Yellow (13 ) Y-OUT

Yellow

Cla ss 2

C

Y

Yellow (11 )

PGM

Black/White

Yellow (12 )

Blue Black

Control Box Base Panel

Green / Yel low (39)

Control Box Door

Accessor y Relay

Operation

SW2-4 SW2-5

Cycl e with Blower

On On

Cycl e with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

Black (X) White (Y) Red (Z)

24V Tra nsformer

Yellow (19 )

Yellow

Blue

Cla ss 2

PWM CFM
C

Factory Factory

HP P4

ECM PWM

HP

P13

LP

LP

FP2

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

CC2 Factory

G P5 LO HI CCG CC FG F R
F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1
JW2 Alarm
P2 Fi eld Connections

Off On

LED1 FP1 ­ 15oF/30oF

1 LED2

R FP2 ­ 15oF/30oF

2Y

Faul t

RV ­ B/O

ACC ­ Dip 4

3 Config 4

LED3

ACC ­ Dip 5

CC ­ Dual/Si ngle

G L ­ Pulse/Continuous

Status

Reheat/Normal

5 6 7 8 SW2

AURORA BASE CONTROLTM
Com1 G

RS485 Exp

EH1
P3 EH2 C EH1 C CO N/A
P6 (+) (-) R C
P7

RS 485

Factory Use

RS485 NET

P11

P9

Factory Fan Connection

P8 Com2 G

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Fi eld Connections

3A-Fuse

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

RR

CC C

Notes:
1 ­ P1 (screw terminals) and P9 (Molex connector) are adjacent and share common terminals in the same or der. 2 ­ Optional isolation water valv e. 3 ­ Optional hot gas reheat. 4 ­ Sizes 240-360 equipped with two blowers .

Legend

Factory Low Voltage Wiring Factory Line Vol tage Wiring Fi eld Low Voltage Wiring Fi eld Li ne Voltage Wi ri ng Optional Block DC Voltage PCB Traces Fi eld Zone Sensor Wi ri ng Internal Ju nction Qui ck Con nect Terminal

L1

Fi eld Wiring Lug

1 2 3

T

Thermistor

Relay Coi l

Switch – Condensate Overfl ow Switch – High pressure Switch – Low pressure

Polarized connector

Ground
Relay Con tacts ­ N.O., N.C.
Capacitor
Fuse
Current Transducer
CCA ­ Compressor A Contactor CCB ­ Compressor B Contactor CO ­ Condensate Overfl ow Sensor ES ­ Emergency Shutdown HP1 ­ High Pressure Switch 1 HP2 ­ High Pressure Switch 2 LP1 ­ Low Pressure Switch 1 LP2 ­ Low Pressure Switch 2 FP1 ­ Freeze Protection Sensor 1 FP2 ­ Freeze Protection Sensor 2 F1 ­ Fuse

EX-XX

Pin Number Designation on Twist-Lock Connector

G

Light Emitting Diode – Green

Y

Light Emitting Diode – Yellow

R

Light Emitti ng Diode – Red

SW1 ­ Push button SW2 ­ DIP package 8 position RV1 ­ Reversi ng Valve Coi l 1 RV2 ­ Reversi ng Valve Coi l 2 PGM ­ Phase Guard Moni tor RH ­ Reheat Valve Coi l

47

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Wiring Schematics cont.
084-300 Single/Dual Compressor Aurora UPC

Orange Red
White Black

BACnet or N2 Network
Connections
Devices Must Be Wired in Daisy Chain Configuration

Orange Red
White Black

1 2 3 4 5 6 7 8 To ABC-A – P8
Blue Green
Br own Yellow

1 2 3 4 5 6 7 8 To ABC-B – P8 Dual Compressor Only

Blue Green
Br own Yellow

NET+ NETCOM NET+ NETCOM
12345678

ZS Sensor 1 Addr: 0

GND RNET+ RNET-
+12V

ZS Sensor 2 Addr: 1

GND RNET+ RNET-
+12V

ZS Sensor 3 Addr: 2

GND RNET+ RNET-
+12V

NET+ NETCOM
NET+ NETN/C N/C Signal

LE D1 TX
LE D2 RX
LON A DA P TER
P ORT
LE D6 TX
LE D7
2W RX

4W

GND RNET+ RNET+ 12 V
RNET

GND LN+ LN+12
/S
LOCAL ACCESS

ZS Sensor Information

Zone Sensors can be wired in daisy chain as show or in a star or hybrid configuration. Maximum of 5 sensors per UPC. Maximum allowable load 210mA. See the UPC install manual for possible sensor combinations.

DIP Switch Value
1 2 4 8

ON 1 2 34

Each ZS sensor must have a unique address, but the addresses do not need to be sequential. Use the DIP switches on the back of the ZS sensor to set an address from 0 to 4. (0 is the factory default.) Each DIP switch has the value shown in the figure to the left. Turn on as many DIP switches as you need so that their total value equals the address.

48

LE D3 P OWER

P OWER
GND 24 VAC

FORM AT B ATT

Communication Options
NOTE 1

LE D4 RUN
LE D5 E RR

ON
TEN’S
89 0 12 73
654
89 0 12 73
654
ONE’S

MAC Address Setting

Notes
1. Use DIP Switches 5 ­ 8 to change communication protocol and DIP switches 1 ­ 2 to change BACnet baud rate. 2. DDC functionality available where specifically indicated in the product controls options.
Legend
Factory Low Voltage Wiring Field Low Voltage Wiring
12345678 RJ45 Connector

VERSATEC 500 7-30 TON INSTALLATION MANUAL – Formerly Versatec XL

Aurora Controls
Aurora Controls
The Aurora Control System is a complete commercial comfort system that can bring all aspects of the HVAC system into one cohesive module network. The Aurora System is available in two configurations: Aurora Base Control and Aurora Advanced and Aurora Premium Control both with optional Aurora UPC for DDC applications.

Control Aurora Base
Control
Aurora Advanced and Premium
Aurora Base/ Aurora Advanced
Control w/UPC BACnet or N2

General Description

Application

The ABC microprocessor provides all the features necessary to operate today’s standard WSHPs that utilize dual capacity compressors and variable speed ECM/5 speed ECM blower motors with hot gas reheat. This control can communicate to a handheld diagnostic tool to help the installing contractor or service technician with equipment setup and service. By utilizing Modbus RTU communication protocol, the ABC board can communicate with additional devices on the Aurora network

Used for residential and commercial applications that use single or dual capacity compressors with PSC, 5-speed ECM, or variable speed ECM blower motors. This base control can also communicate to the AID Tool to display faults, inputs/outputs, and software revision. Commercial features such as hot gas reheat, slow opening water valve, and random start are also capable with the ABC board.

Display/Interface
Optional AID toll can be used for field service.

Protocol Standalone

Aurora Advanced Control adds the Aurora AXB expansion board and provides added I/O and standard features such as refrigerant, performance or energy monitoring.

· Refrigeration Monitoring ­ provides Suction and discharge pressure, Suction, liquid line temps and superheat and subcooling.
· Performance Monitoring ­ provides entering and leaving loop water temperatures, loop flow rate as well as heat of extraction or rejection rate into the loop.
· Energy Monitoring ­ provides realtime power measurement (Watt) of compressor, fan, auxiliary heat and zone pump.
· Plus many more I/O options

Optional AID tool can be used for field service.

The Aurora Unitary Protocol Converter (UPC) is an integrated solution and communicates directly with the Aurora Heat Pump Controls and allows access/control of a variety of internal Aurora heat pump operations such as sensors, relay operation, faults and other information. In turn, the UPC then converts internal Aurora Modbus protocol to BACnet MS/TP, or N2 protocols and communicates to the BAS system. This provides the great benefit of complete control integration and a myriad of information available to the BAS from the heat pump control. Plus it also allows individual unit configuration such as ECM fan speeds or freeze protection setting directly over the BAS without the need for access to the actual heat pump.

The Aurora UPC is implemented with the Aurora heat pump control into our latest water source heat pumps. All Internal Aurora points are accessible to the UPC via firmware providing an integrated solution. All zone temperatures and zone sensors are connected to the UPC on an RNet bus, simplifying hook up at the unit. RNet sensors can include a combination of zone temperature and humidity, CO2, and VOC sensors. The UPC includes built-in support

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals