WaterFurnace 700R11 Indoor Split Geothermal Heat Pump User Manual

June 9, 2024
WaterFurnace

WaterFurnace Logo 700R11 Indoor Split Geothermal Heat Pump
033, 042, 050 Variable Speed
User Manual
Submittal Data
English Language/IP Units
SD2703SNA 01/23

Contractor: P.O.: —————
Engineer: ———————–
Project Name: —————–
Unit Tag: ———————-

Unit Nomenclature (Compressor Section)

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
1

Unit Nomenclature (Air Handler)

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
2

Notes:
1 – Air flow on the 050 unit in the horizontal configurations should be limited to 1900 cfm in cooling mode, or condensate blow off may occur.
2 – Compressor section mus t be matched with identical model SVH air handler section. See Compatibility Table
3 – To field convert the SVH to bottom flow air discharge. The SAHBCK kit must be ordered separately.
4 – UPC is not compatible with Symphony or IntelliZone2.

AHRI/ISO 13256-1 Performance Ratings
7 Series Indoor Split Residential Series AHRI Data ECM Motor
AHRI/ASHRAE/ISO 13256-1

**Model| ****Capacity Modulation| **

Flow Rate Clg/Htg

| Water Loop Heat Pump| Ground Water Heat Pump| Ground Loop Heat Pump
---|---|---|---|---|---
Cooling EWT 86°F| Heating EWT 68°F| Cooling EWT 59°F| Heating EWT 50°F| Cooling Full Load 77°F Part Load 68°F| Heating Full Load 32°F Part Load 41°F
cfm| Capacity Btuh| EER

Btuh/W

| Capacity Btuh| COP| Capacity Btuh| EER

Btuh/W

| Capacity Btuh| COP| Capacity Btuh| EER

Btuh/W

| Capacity Btuh| COP
033| Full| 1200/1500| 31,600| 16.8| 49,800| 5.2| 37,000| 29.2| 40,700| 4.5| 33,300| 20.3| 31,700| 3.4
Part| 650/800| 10,900| 20.9| 16,800| 7.3| 12,900| 46.0| 13,900| 5.7| 13,700| 36.0| 12,000| 5.2
042| Full| 1500/1800| 39,500| 16.4| 66,100| 4.9| 46,200| 28.2| 54,100| 4.2| 41,600| 19.7| 42,700| 3.5
Part| 900/1100| 15,600| 22.4| 23,800| 7.5| 17,300| 52.0| 18,800| 5.8| 17,500| 40.8| 15,800| 5.1
050| Full| 1800/2200| 46,700| 14.4| 77,800| 4.3| 55,200| 24.3| 64,900| 3.8| 49,800| 17.1| 50,800| 3.2
Part| 950/1200| 19,400| 20.9| 28,900| 7.4| 21,200| 45.6| 22,800| 5.8| 22,000| 35.5| 19,800| 5.0

3/20/20
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Heating capacities based upon 68°F DB, 59°F WB entering air temperature All ratings based upon 208V operation

Energy Star Compliance Table

Model Tier 3
Ground Water Ground Loop
033 Yes
042 Yes
050 Yes

10/31/19

Energy Star Rating Criteria
In order for water-source heat pumps to be Energy Star rated they must meet or exceed the minimum efficiency requirements listed below. Tier 3 represents the current minimum efficiency water source heat pumps must have in order to be Energy Start rated.

Tier 3: 1/1/2012 – No Effective End Date Published

Water-to-Air EER C COP
Ground Loop 17.1 3.6
Ground Water 21.1 4.1

Water-to-Water
Ground Loop| 16.1| 3.1
Ground Water| 20.1| 3.5

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump -
Logo

Compressor Section Dimensional Data

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
3

**Models| ****Height| ****Width| ****Depth| Water In| Water Out| Service Valve| HWG**

In

| HWG

Out

| Low| External| Line| KNOCK OUT| KNOCK OUT
---|---|---|---|---|---|---|---|---|---|---|---|---|---
Liquid| Gas| Voltage| Pump| Voltage
A| B| C| D| E| F| G| H| J| K| L| M| N| P
033-050| in.| 21.25| 25.62| 31.60| 2.30| 7.21| 16.40| 18.30| 10.30| 13.30| 12.10| 14.30| 9.50| 4.70| 9.10
cm.| 54.00| 65.10| 80.30| 5.80| 18.50| 41.70| 46.50| 26.20| 33.80| 30.70| 36.30| 24.10| 11.90| 23.10

Air Handler Dimensional Data – SVH Air Handler
Top Flow/Horizontal Unit Configuration

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
4

SVH Air Handler – Topflow/Horizontal

Condensate is plastic 3/4″ FPT Discharge flange is field installed and extends 1″ (25.4 mm) from cabinet NOTE: Clearance for maintenance and servicing access – minimum 30″ from front of unit recommended for blower motor/coil replacement. Condensate drain lines routed to clear filter and panel access. Filter removal – minimum 30″ recommended.

Air Handler Dimensional Data – SVH Air Handler
Bottom Flow Unit Configuration

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
5

Condensate is plastic 3/4″ FPT Discharge lange is kid installed and extends 1″ (25.4 mm) from cabinet NOTE: Clearance for maintenance and servicing access – minimum 30° from front of unit recommended for blower motor/coil replacement. Condensate drain lines routed to clear filter and panel access. Filter removal – minimum 30° recommended.

Compressor Section Physical Data

Model NVZ033 NVZ042 NVZ050
Compressor (1 each) Variable Speed Scroll
Factory Charge R410a, oz [kg] 68 [1.93] 90 [2.55] 92 [2.61]

Coax and Water Piping
Water Connections Size – Swivel – in [mm]| 1” [25.4]| 1” [25.4]| 1” [25.4]
HWG Connection Size – Female Sweat I.D. – in [mm]| 1/2” [12.7]| 1/2” [12.7]| 1/2” [12.7]
| Brass Service Valve – Liquid Line – in [mm]| 3/8” [9.45]
| Brass Service Valve – Suction Line – in [mm]| 3/4” [19.1]| 7/8” [22.23]
Coax & Piping Water Volume – gal [l]| 1.3 [4.9]| 2.3 [8.7]| 2.3 [8.7]
| Weight – Operating, lb [kg]| 241 [109]| 302 [137]| 302 [137]
| Weight – Packaged, lb [kg]| 261 [118]| 322 [146]| 322 [146]

03/18/20
Notes:
All units have an EEV and 1/2 in. [12.7mm], and 3/4 in. [19.1] electrical knockouts Brass services valves are sweat type valves

Air Handler Physical Data

Air Handler Model Number (Refrigerant) 033 042 050


Evaporator Coil

| Air Coil Total Face Area, ft2 [m2]| 6.81 [0.63]
Tube outside diameter – in. [mm]| 3/8 [9.52]
Number of rows| 3
Fins per inch| 12
Suction line connection – in. [mm] sweat| 7/8 [22.23]
Liquid line connection – in. [mm] sweat| 3/8 [9.45]
Refrigerant| R-410a
Condensate drain connection – (FPT) in. [mm]| 3/4 [19.05]
Blower Wheel Size (Dia x W), in. [mm]| 11 x 10 [279 x 254]
Blower motor type/speeds| Variable Speed ECM
Blower motor output – hp [W]| 1 [746]
Filter Standard – 1” [51mm] Field Supplied.| 22 X 20 [559 x 508]
Electrical characteristics (60hz)| 208/230 – 1ph
Shipping weight – lbs. [kg]| 206 [93.4]
Operating weight – lbs. [kg]| 188 [85.3]

Auxiliary Heat Compatibility

Model| kW| Stages| Min CFM|
---|---|---|---|---
033| 042| 050
19P659-02| 10| 2| 1300| ●| ●| ●
19P659-03| 15| 2| 1700| | ●| ●
19P659-04| 20| 2| 2000| | | ●

03/12/20

Air Handler Auxiliary Heat Blower Settings

Model Variable Speed ECM DIP Setting
SVH033 10
SVH042 11
SVH050 11

6/6/2019

Electrical Data

Variable speed with external loop pump


Model

| ****

Rated Voltage

| ****

Voltage Min/Max

| ****

COMP LRA

| ****

COMP MCC

| ****

Drive RLA

| Drive Internal Fuse| HWG

Pump FLA

| Ext Loop FLA| Total Unit FLA| Minimum Circuit Amp| Max Fuse HACR

Breaker

---|---|---|---|---|---|---|---|---|---|---|---
033| 208-230/60/1| 187/253| 10.2| 18.0| 22.0| 30.0| 0.4| 5.4| 27.8| 33.3| 35
042| 208-230/60/1| 187/253| 12.0| 23.5| 28.0| 35.0| 0.4| 5.4| 33.8| 40.8| 45
050| 208-230/60/1| 187/253| 12.0| 30.0| 33.0| 40.0| 0.4| 5.4| 38.8| 47.1| 50

8/21/19
Rated Voltage of 208/230/60/1 HACR circuit breaker in USA only All fuses Class RK-5

Air Handler Electrical Data


Model

| Electric Heat

Capacity

| ****

Supply Circuit

| Aux. Heat Minimum CFM| ****

Rated Voltage

| ****

Voltage Min/Max

| Fan Motor FLA| Heater Am- pacity| Total Unit FLA| Minimum Circuit Am-

pacity

| Maximum Fuse/HACR
---|---|---|---|---|---|---|---|---|---|---
KW| BTUH
240v| 240v| 208v| 240v| 208v| 240v| 208v| 240v| 208v| 240v
033| 0| 0| –| | ****






208- 30/60/1

| ****






197/253

| 7.0| –| –| 7.0| 7.0| 8.8| 8.8| 15| 15
9.6| 32,765| single| 1,300| 7.0| 34.7| 40.0| 41.7| 47.0| 52.1| 58.8| 60| 60



042

| 0| 0| –| | 7.0| –| –| 7.0| 7.0| 8.8| 8.8| 15| 15
9.6| 32,765| single| 1,300| 7.0| 34.7| 40.0| 41.7| 47.0| 52.1| 58.8| 60| 60
14.4| 49,147| single| ****

1,700

| 7.0| 52.0| 60.0| 59.0| 67.0| 73.8| 83.8| 80| 90
14.4| 49,147| L1/L2| 7.0| 34.7| 40.0| 41.7| 47.0| 52.1| 58.8| 60| 60
L3/L4| –| 17.3| 20.0| 17.3| 20.0| 21.6| 25.0| 25| 25




050

| 0| 0| –| | 7.0| –| –| 7.0| 7.0| 8.8| 8.8| 15| 15
9.6| 32,765| single| 1,300| 7.0| 34.7| 40.0| 41.7| 47.0| 52.1| 58.8| 60| 60
14.4| 49,147| single| ****

1,700

| 7.0| 52.0| 60.0| 59.0| 67.0| 73.8| 83.8| 80| 90
14.4| 49,147| L1/L2| 7.0| 34.7| 40.0| 41.7| 47.0| 52.1| 58.8| 60| 60
L3/L4| –| 17.3| 20.0| 17.3| 20.0| 21.6| 25.0| 25| 25
19.2| 65,530| single| ****

2,000

| 7.0| 69.3| 80.0| 76.3| 87.0| 95.4| 108.8| 100| 110
19.2| 65,530| L1/L2| 7.0| 34.7| 40.0| 41.7| 47.0| 52.1| 58.8| 60| 60
L3/L4| –| 34.7| 40.0| 34.7| 40.0| 43.4| 50.0| 50| 50

1/29/20
Rated Voltage of 208/230/60/1 HACR circuit breaker in USA only

SVH Blower Performance Data

Variable Speed ECM

Model| Max ESP| Speed 1| Speed 2| Speed 3| Speed 4| Speed 5| Speed 6| Speed 7| Speed 8| Speed 9| Speed 10| Speed 11| Speed 12
---|---|---|---|---|---|---|---|---|---|---|---|---|---
033| 0.75| 250| 400 G| 550 L| 650| 750| 850| 1000| 1150| 1250 H| 1350 Aux| 1450| 1600
042| 0.75| 250| 450 G| 650 L| 800| 950| 1050| 1200| 1350| 1450| 1600 H| 1750 Aux| 1850
050| 0.75| 300| 550 G| 800 L| 1000| 1150| 1300| 1450| 1600| 1750| 1900 H| 2050 Aux| 2200
VS Com- pressor Speed| | | | **

1-2

| ****

3-4

| | ****

5-6

| ****

7-8

| | ****

9-10

| ****

11-12

| |

4/15/2020

** VS Compressor speed is given for the factory default cfm settings. When the cfm default settings are changed it will change the relationship to the compressor speed that is shown in the table. In cooling mode compressor speeds 10-12 are only available when SuperBoost mode is selected at the thermostat.
Factory settings are at recommended G, L , H and Aux positions
“G” may be located anywhere within the airflow table.
“L” setting should be located within the boldface CFM range
“H” setting MUST be located within the shaded CFM range
“Aux” setting MUST be equal to or higher than factory setting shown in the table above CFM is controlled within 5% up to the maximum ESP

Line Set Sizes

NOTE: Manufacturer recommends the standard total line set length not to exceed 80 ft with no more than 25 ft of vertical separation between the compressor section and the air handler. For installations that exceed the standard range refer to the Long Line Set Application Guide AG2200EW for further installation requirements.

Unit| Air| 20 feet| 40 feet| 60 feet| 80 feet| NZ Factory Charge (oz.)| *Charge Amount with SVH Air Handler (oz.)
---|---|---|---|---|---|---|---

Size

|

Handler

|

Suction

|

Liquid

|

Suction

|

Liquid

|

Suction

|

Liquid

|

Suction

|

Liquid

NVZ033| SVH033| 3/4” OD| 3/8” OD| 3/4” OD| 3/8” OD| 3/4” OD| 3/8” OD| 3/4” OD| 3/8” OD| 68| 118
NVZ042| SVH042| 3/4” OD| 3/8” OD| 3/4” OD| 3/8” OD| 3/4” OD| 3/8” OD| 3/4” OD| 3/8” OD| 90| 142
NVZ050| SVH050| 3/4” OD| 3/8” OD| 3/4” OD| 3/8” OD| 3/4” OD| 3/8” OD| 7/8” OD| 3/8” OD| 92| 152
CAPACITY MULTIPLIER| 1.00| 0.985| 0.97| 0.955| |

Notes: * The “Charge Amount with SVH Air Handler” column is based on the charge amount for a SVH Air Handler + Compressor Section/Split. Additional charge will need to be added accordingly for line set length. After charge is added, additional adjustments can be made to get appropriate subcooling and superheat measurements. Additional charge for R410A is 0.50 oz. per ft. for 3/8” and 1.0 oz. per ft. for 1/2” tube. Longer line sets will significantly reduce capacity and efficiency of the system as well as adversely effect the system reliability due to poor oil return.

Operating Limits

Operating Limits Cooling Heating
(°F) (°C) (°F)
Air Limits
Min. Ambient Air 45 7.2
Rated Ambient Air 80 26.7
Max. Ambient Air 100 37.8
Min. Entering Air 50 10.0
Rated Entering Air db/wb 80.6/66.2 27/19
Max. Entering Air db/wb 110/83 43/28.3
Water Limits
Min. Entering Water 30 -1.1
Normal Entering Water 50-110 10-43.3
Max. Entering Water 120 48.9

NOTE: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependent upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.

Definitions

Abbreviations and Definitions

cfm = airflow, cubic feet/minute
EWT = entering water temperature, Fahrenheit
gpm = water flow in gallons/minute
WPD = water pressure drop, psi and feet of water
EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)
HC = air heating capacity, MBtu/h
TC = total cooling capacity, MBtu/h
SC = sensible cooling capacity, MBtu/h
kW = total power unit input, kilowatts
HR = total heat of rejection, MBtu/h
HE = total heat of extraction, MBtu/h
HWC = hot water generator capacity, MBtu/h
EER = Energy Efficient Ratio
= Btu output/Watt input
COP = Coefficient of Performance
= Btu output/Btu input
LWT = leaving water temperature, °F
LAT = leaving air temperature, °F
TH = total heating capacity, MBtu/h
LC = latent cooling capacity, MBtu/h
S/T = sensible to total cooling ratio

Compressor Section Pressure Drop

Model GPM Pressure Drop (psi)
30° F 50° F 70°

033

| 11.5| 3.60| 3.30| 3.10| 2.90| 2.70
9.0| 2.30| 2.10| 2.00| 1.90| 1.70
7.0| 2.10| 2.00| 1.80| 1.80| 1.60
6.0| 1.10| 1.05| 1.00| 0.90| 0.85
4.5| 0.70| 0.66| 0.64| 0.60| 0.55


042

| 13.5| 4.10| 3.80| 3.60| 3.40| 3.10
10.5| 1.90| 1.80| 1.70| 1.60| 1.50
7.5| 1.70| 1.50| 1.40| 1.30| 1.20
6.0| 1.00| 0.90| 0.80| 0..7| 0.60
4.0| 0.40| 0.38| 0.36| 0.34| 0.30


050

| 17.0| 6.20| 5.80| 5.40| 5.00| 4.60
13.5| 3.90| 3.70| 3.50| 3.10| 2.90
9.5| 1.90| 1.80| 1.70| 1.60| 1.50
7.5| 1.40| 1.30| 1.20| 1.10| 0.90
5.0| 0.60| 0.55| 0.50| 0.45| 0.40

8/21/2019

Thermistor Resistance

Thermistor Resistance (10k Ohm) for FP1, FP2, HWL, LWT and LLT

(EWT with Performance Option)

| Thermistor Resistance (1k Ohm) for compressor discharge line, suction line, LAT, compressor ambient and EWT
---|---
Thermistor Temperature (°F)| Thermistor Resistance (Ohms)| Thermistor Temperature (°F)| Thermistor Resistance (Ohms)
5| 75757-70117| 20| 974.4-973.4
14| 57392-53234| 25| 985.4-984.4
23| 43865-40771| 30| 996.1-995.1
32| 33809-31487| 35| 1007.0-1006.0
41| 26269-24513| 40| 1017.8-1016.8
50| 20570-19230| 45| 1028.6-1027.6
59| 16226-15196| 50| 1039.5-1038.5
68| 12889-12093| 55| 1050.2-1049.2
77| 10310-9688| 60| 1061.2-1060.2
86| 8300-7812| 65| 1072.9-1071.9
95| 6723-6337| 70| 1082.7-1081.7
104| 5480-5172| 75| 1093.4-1092.4
113| 4490-4246| 80| 1103.0-1102.0
122| 3700-3504| 85| 1115.5-1114.5
131| 3067-2907| 90| 1126.2-1125.2
140| 2554-2424| 95| 1136.6-1135.6
149| 2149-2019| 100| 1147.2-1146.2
4/24/12| 105| 1158.1-1157.1
110| 1168.8-1167.8
115| 1179.4-1178.4
120| 1190.1-1189.1
125| 1200.3-1199.3
130| 1212.2-1211.2

Correction Factor Tables

Air Flow Corrections (Compressor Speeds 1-3)

Airflow Cooling Heating

CFM Per Ton

of Clg

| % of Nominal| Total Cap| Sens Cap| Power| Heat of Rej| Htg Cap| Power| Heat of Ext
240| 60| 0.940| 0.740| 0.967| 0.951| 0.943| 1.106| 0.902
275| 69| 0.950| 0.783| 0.973| 0.959| 0.953| 1.088| 0.918
300| 75| 0.960| 0.827| 0.978| 0.967| 0.962| 1.070| 0.935
325| 81| 0.970| 0.870| 0.984| 0.975| 0.972| 1.053| 0.951
350| 88| 0.980| 0.913| 0.989| 0.984| 0.981| 1.035| 0.967
375| 94| 0.990| 0.957| 0.995| 0.992| 0.991| 1.018| 0.984
400| 100| 1.000| 1.000| 1.000| 1.000| 1.000| 1.000| 1.000
425| 106| 1.030| 1.022| 1.024| 1.026| 1.009| 0.982| 1.016
450| 113| 1.060| 1.045| 1.048| 1.051| 1.019| 0.965| 1.033
475| 119| 1.091| 1.067| 1.071| 1.077| 1.028| 0.947| 1.049
500| 125| 1.121| 1.089| 1.095| 1.103| 1.038| 0.930| 1.065
520| 130| 1.151| 1.111| 1.110| 1.129| 1.047| 0.912| 1.082

6/29/12

Air Flow Corrections (Compressor Speeds 4-12)

Airflow Cooling Heating

CFM Per Ton

of Clg

| % of Nominal| Total Cap| Sens Cap| Power| Heat of Rej| Htg Cap| Power| Heat of Ext
240| 60| 0.928| 0.747| 0.936| 0.929| 0.961| 1.097| 0.938
275| 69| 0.940| 0.789| 0.946| 0.941| 0.967| 1.081| 0.948
300| 75| 0.952| 0.831| 0.957| 0.953| 0.974| 1.064| 0.959
325| 81| 0.964| 0.873| 0.968| 0.965| 0.980| 1.048| 0.969
350| 88| 0.976| 0.916| 0.979| 0.976| 0.987| 1.032| 0.979
375| 94| 0.988| 0.958| 0.989| 0.988| 0.993| 1.016| 0.990
400| 100| 1.000| 1.000| 1.000| 1.000| 1.000| 1.000| 1.000
425| 106| 1.020| 1.023| 1.004| 1.018| 1.010| 0.966| 1.018
450| 113| 1.056| 1.042| 1.008| 1.035| 1.020| 0.932| 1.036
475| 119| 1.072| 1.079| 1.011| 1.053| 1.029| 0.898| 1.054
500| 125| 1.087| 1.095| 1.015| 1.070| 1.039| 0.865| 1.071
520| 130| 1.099| 1.113| 1.019| 1.088| 1.049| 0.831| 1.089

6/14/12

Cooling Capacity Corrections

Entering Air

WB ° F

| Total Clg

Cap

| Sensible Cooling Capacity Multipliers – Entering DB ° F| Power

Input

| Heat of

Rejection

---|---|---|---|---
60| 65| 70| 75| 80| 80.6| 85| 90| 95| 100
55| 0.898| 0.723| 0.866| 1.048| 1.185| | | | | | | 0.985| 0.913
60| 0.912| | 0.632| 0.880| 1.078| 1.244| 1.260| | | | | 0.994| 0.927
63| 0.945| | | 0.768| 0.960| 1.150| 1.175| | | | | 0.996| 0.954
65| 0.976| | | 0.694| 0.881| 1.079| 1.085| 1.270| | | | 0.997| 0.972
66.2| 0.983| | | 0.655| 0.842| 1.040| 1.060| 1.232|
| | | 0.999| 0.986
67| 1.000| | | 0.616| 0.806| 1.000| 1.023| 1.193| 1.330| 1.480| ***| 1.000| 1.000*
70| 1.053| | | | 0.693| 0.879| 0.900| 1.075| 1.205| 1.404|
| 1.003| 1.044
75| 1.168| | | | | 0.687| 0.715| 0.875| 1.040| 1.261| 1.476| 1.007| 1.141

1/5/2017

NOTE: *Sensible capacity equals total capacity at conditions shown.

Heating Capacity Corrections

Ent Air DB °F Heating Corrections
Htg Cap Power
45 1.062
50 1.050
55 1.037
60 1.025
65 1.012
68 1.005
70 1.000
75 0.987
80 0.975

Antifreeze Corrections

Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given.

Antifreeze Type| Antifreeze % by wt| Heating| Cooling| Pressure Drop
---|---|---|---|---
EWT – °F [°C]| | 30 [-1.1]| 90 [32.2]| 30 [-1.1]
Water| 0| 1.000| 1.000| 1.000

Ethylene Glycol

| 10| 0.973| 0.991| 1.075
20| 0.943| 0.979| 1.163
30| 0.917| 0.965| 1.225
40| 0.890| 0.955| 1.324
50| 0.865| 0.943| 1.419

Propylene Glycol

| 10| 0.958| 0.981| 1.130
20| 0.913| 0.969| 1.270
30| 0.854| 0.950| 1.433
40| 0.813| 0.937| 1.614
50| 0.770| 0.922| 1.816

Ethanol

| 10| 0.927| 0.991| 1.242
20| 0.887| 0.972| 1.343
30| 0.856| 0.947| 1.383
40| 0.815| 0.930| 1.523
50| 0.779| 0.911| 1.639

Methanol

| 10| 0.957| 0.986| 1.127
20| 0.924| 0.970| 1.197
30| 0.895| 0.951| 1.235
40| 0.863| 0.936| 1.323
50| 0.833| 0.920| 1.399

WARNING: Gray area represents antifreeze concentrations greater than 35% by weight and should be avoided due to the extreme performance penalty they represent.
Antifreeze Correction Example
Antifreeze solution is Propylene Glycol 20% by weight. Determine the corrected heating and cooling performance at 30°F and 90°F respectively as well as pressure drop at 30°F for a 033 operating at 100% capacity.
The corrected cooling capacity at 90°F would be: 30,500 Btu/h x 0.969 = 29,554 Btu/h
The corrected heating capacity at 30°F would be: 34,100 Btu/h x 0.913 = 31,133 Btu/h
The corrected pressure drop at 30°F and 11.5 gpm would be: 7.9 feet of head x 1.270 = 10.03 feet of head

Performance Data

NVZ033 – 50% Part Load


EWT

°F

| ****

Flow gpm

| WPD| HEATING – EAT 70°F| ****

EWT

°F

| ****

Flow gpm

| WPD| COOLING – EAT 80/67 °F
---|---|---|---|---|---|---|---
PSI| FT| Airflow cfm| HC

MBtuh

| Power kW| HE

MBtuh

| LAT

°F

| COP| HWC

MBtuh

| PSI| FT| Airflow cfm| TC

MBtuh

| SC

MBtuh

| S/T Ratio| Power kW| HR

MBtuh

| EER| HWC

MBtuh


20

| 3.0| 0.5| 1.1| Operation not recommended| ****

20

| 2.5| 0.2| 0.5| **** Operation not recommended
4.5| 0.7| 1.6| 3.5| 0.5| 1.1
6.0| 1.2| 2.7| 550| 12.4| 1.48| 7.2| 90.6| 2.43| 2.2| 4.5| 0.7| 1.6
750| 12.7| 1.37| 8.0| 85.7| 2.72| 1.9



30

| 3.0| 0.5| 1.1| 550| 13.1| 1.22| 8.3| 91.0| 3.00| 2.0| ****


30

| 2.5| 0.2| 0.5| 500| 17.8| 12.8| 0.72| 0.54| 18.8| 31.6| –
750| 13.6| 1.25| 8.7| 86.1| 3.04| 1.7| 650| 18.1| 14.0| 0.77| 0.56| 19.2| 30.9| –
4.5| 0.7| 1.6| 550| 13.4| 1.23| 8.6| 91.6| 3.06| 2.1| 3.5| 0.5| 1.1| 500| 18.0| 12.9| 0.71| 0.51| 18.9| 33.7| –
750| 14.0| 1.26| 9.0| 86.5| 3.11| 1.8| 650| 18.3| 14.1| 0.77| 0.54| 19.3| 32.5| –
6.0| 1.1| 2.6| 550| 14.6| 1.39| 9.0| 93.1| 2.89| 2.2| 4.5| 0.7| 1.6| 500| 18.1| 12.9| 0.71| 0.50| 19.0| 34.9| –
750| 14.9| 1.29| 9.8| 87.5| 3.23| 1.9| 650| 18.6| 14.1| 0.76| 0.52| 19.5| 34.0| –



40

| 3.0| 0.4| 1.0| 550| 15.6| 1.27| 11.0| 95.8| 3.55| 2.0| ****


40

| 2.5| 0.2| 0.5| 500| 19.3| 13.2| 0.68| 0.59| 20.4| 31.1| –
750| 16.2| 1.29| 11.5| 89.6| 3.60| 1.8| 650| 19.7| 14.5| 0.73| 0.62| 20.9| 30.5| –
4.5| 0.7| 1.5| 550| 16.1| 1.27| 11.5| 96.6| 3.65| 2.1| 3.5| 0.4| 1.0| 500| 19.6| 13.4| 0.68| 0.56| 20.6| 33.2| –
750| 16.7| 1.29| 12.0| 90.2| 3.71| 1.9| 650| 19.9| 14.6| 0.73| 0.59| 21.0| 32.2| –
6.0| 1.1| 2.5| 550| 17.0| 1.30| 12.2| 98.1| 3.76| 2.2| 4.5| 0.7| 1.5| 500| 19.7| 13.4| 0.68| 0.55| 20.6| 34.5| –
750| 17.6| 1.33| 12.7| 91.3| 3.82| 2.0| 650| 20.2| 14.6| 0.72| 0.57| 21.1| 33.7| –



50

| 3.0| 0.4| 1.0| 550| 18.2| 1.31| 13.7| 100.6| 4.06| 2.5| ****


50

| 2.5| 0.2| 0.5| 500| 20.6| 13.2| 0.64| 0.63| 21.8| 31.2| –
750| 18.8| 1.33| 14.2| 93.2| 4.13| 2.2| 650| 21.2| 14.7| 0.69| 0.64| 22.4| 31.4| –
4.5| 0.6| 1.5| 550| 18.8| 1.31| 14.4| 101.7| 4.20| 2.5| 3.5| 0.4| 1.0| 500| 20.8| 13.3| 0.64| 0.61| 21.9| 32.3| –
750| 19.4| 1.33| 14.9| 94.0| 4.28| 2.3| 650| 21.4| 14.7| 0.69| 0.63| 22.5| 32.6| –
6.0| 1.1| 2.5| 550| 19.7| 1.34| 15.1| 103.2| 4.30| 2.6| 4.5| 0.6| 1.5| 500| 21.1| 13.7| 0.65| 0.61| 22.2| 33.1| –
750| 20.3| 1.36| 15.7| 95.1| 4.37| 2.4| 650| 21.7| 15.1| 0.70| 0.62| 22.8| 33.4| –



60

| 3.0| 0.4| 1.0| 550| 20.7| 1.33| 16.1| 104.8| 4.55| 2.7| ****


60

| 2.5| 0.2| 0.5| 500| 20.0| 13.2| 0.66| 0.74| 21.6| 25.6| 1.3
750| 21.2| 1.34| 16.6| 96.2| 4.63| 2.5| 650| 20.5| 14.6| 0.71| 0.76| 22.1| 25.9| 1.4
4.5| 0.6| 1.4| 550| 21.5| 1.33| 17.0| 106.2| 4.74| 2.8| 3.5| 0.4| 1.0| 500| 20.2| 13.3| 0.66| 0.72| 21.7| 26.6| 1.2
750| 22.0| 1.34| 17.4| 97.2| 4.83| 2.6| 650| 20.7| 14.7| 0.71| 0.74| 22.2| 26.8| 1.3
6.0| 1.0| 2.4| 550| 22.3| 1.36| 17.6| 107.5| 4.80| 2.9| 4.5| 0.6| 1.4| 500| 20.5| 13.6| 0.66| 0.72| 22.0| 27.2| 1.1
750| 22.8| 1.37| 18.1| 98.1| 4.88| 2.7| 650| 21.1| 15.1| 0.72| 0.73| 22.5| 27.5| 1.2



70

| 3.0| 0.4| 0.9| 550| 23.1| 1.35| 18.5| 108.9| 5.03| 3.1| ****


70

| 2.5| 0.2| 0.5| 500| 19.3| 13.2| 0.68| 0.85| 21.3| 21.6| 1.7
750| 23.6| 1.32| 19.1| 99.1| 5.24| 2.8| 650| 19.9| 14.6| 0.73| 0.87| 21.9| 21.7| 1.8
4.5| 0.6| 1.4| 550| 24.1| 1.34| 19.6| 110.6| 5.27| 3.2| 3.5| 0.4| 0.9| 500| 19.5| 13.2| 0.68| 0.83| 21.4| 22.3| 1.6
750| 24.6| 1.34| 20.0| 100.4| 5.37| 2.9| 650| 20.0| 14.6| 0.73| 0.85| 22.0| 22.5| 1.7
6.0| 1.0| 2.3| 550| 24.8| 1.37| 20.1| 111.7| 5.29| 3.3| 4.5| 0.6| 1.4| 500| 19.8| 13.6| 0.68| 0.82| 21.7| 22.9| 1.5
750| 25.2| 1.37| 20.5| 101.1| 5.39| 2.7| 650| 20.4| 15.0| 0.74| 0.84| 22.3| 23.1| 1.7



80

| 3.0| 0.4| 0.9| 550| 25.4| 1.34| 20.9| 112.8| 5.57| 3.7| ****


80

| 2.5| 0.2| 0.4| 500| 18.5| 12.9| 0.70| 0.93| 20.8| 18.8| 2.3
750| 25.8| 1.33| 21.2| 101.8| 5.68| 3.4| 650| 19.0| 14.3| 0.75| 0.95| 21.3| 19.0| 2.5
4.5| 0.6| 1.3| 550| 26.6| 1.33| 22.1| 114.9| 5.87| 3.9| 3.5| 0.4| 0.9| 500| 18.6| 13.0| 0.69| 0.91| 20.9| 19.5| 2.2
750| 27.0| 1.32| 22.5| 103.3| 5.99| 3.5| 650| 19.2| 14.3| 0.75| 0.93| 21.4| 19.7| 2.4
6.0| 1.0| 2.2| 550| 27.0| 1.36| 22.4| 115.5| 5.84| 4.0| 4.5| 0.6| 1.3| 500| 19.0| 13.3| 0.70| 0.90| 21.1| 20.0| 2.0
750| 27.3| 1.35| 22.7| 103.7| 5.95| 3.7| 650| 19.5| 14.7| 0.75| 0.92| 21.7| 20.2| 2.2



90

| 3.0| 0.4| 0.9| 550| 27.7| 1.33| 23.2| 116.7| 6.12| 4.3| ****


90

| 2.5| 0.2| 0.4| 500| 17.6| 12.6| 0.71| 1.02| 20.3| 16.5| 3.0
750| 27.9| 1.31| 23.5| 104.5| 6.25| 4.0| 650| 18.1| 13.9| 0.77| 1.04| 20.8| 16.7| 3.2
4.5| 0.6| 1.3| 550| 29.1| 1.32| 24.7| 119.1| 6.49| 4.5| 3.5| 0.4| 0.9| 500| 17.8| 12.7| 0.71| 0.99| 20.3| 17.1| 2.9
750| 29.3| 1.30| 24.9| 106.2| 6.63| 4.1| 650| 18.3| 14.0| 0.77| 1.01| 20.9| 17.3| 3.1
6.0| 0.9| 2.2| 550| 29.3| 1.34| 24.7| 119.3| 6.40| 4.6| 4.5| 0.6| 1.3| 500| 17.6| 12.3| 0.70| 1.17| 20.8| 14.4| 2.8
750| 29.4| 1.32| 24.9| 106.3| 6.53| 4.3| 650| 18.6| 14.4| 0.77| 1.00| 21.1| 17.7| 2.6



100

| 3.0| 0.4| 0.8| ****







Operation not recommended

| ****


100

| 2.5| 0.2| 0.4| 500| 16.7| 12.4| 0.74| 1.34| 20.5| 11.9| 3.6
650| 17.2| 13.7| 0.80| 1.36| 21.0| 12.0| 3.8
4.5| 0.5| 1.2| 3.5| 0.4| 0.8| 500| 16.9| 12.4| 0.74| 1.30| 20.5| 12.4| 3.3
650| 17.4| 13.8| 0.79| 1.33| 21.1| 12.5| 3.6
6.0| 0.9| 2.1| 4.5| 0.5| 1.2| 500| 17.2| 12.8| 0.74| 1.29| 20.7| 12.7| 3.0
650| 17.6| 14.1| 0.80| 1.32| 21.3| 12.8| 3.4



110

| 3.0| 0.3| 0.8| ****


110

| 2.5| 0.2| 0.4| 500| 15.8| 12.1| 0.77| 1.66| 20.7| 9.1| 4.7
650| 16.3| 13.4| 0.83| 1.69| 21.3| 9.2| 5.0
4.5| 0.5| 1.2| 3.5| 0.3| 0.8| 500| 16.0| 12.2| 0.76| 1.61| 20.7| 9.4| 4.4
650| 16.4| 13.5| 0.82| 1.64| 21.3| 9.5| 4.8
6.0| 0.9| 2.0| 4.5| 0.5| 1.2| 500| 16.2| 12.5| 0.77| 1.60| 20.9| 9.7| 4.1
650| 16.7| 13.9| 0.83| 1.63| 21.5| 9.8| 4.6



120

| 3.0| 0.3| 0.8| ****


120

| 2.5| 0.2| 0.4| 500| 13.2| 12.1| 0.92| 1.95| 19.2| 6.4| 6.2
650| 13.5| 13.2| 0.98| 2.00| 19.6| 6.4| 6.0
4.5| 0.5| 1.2| 3.5| 0.3| 0.8| 500| 13.4| 12.2| 0.91| 1.84| 19.0| 6.9| 5.5
650| 13.6| 13.2| 0.97| 1.89| 19.4| 6.8| 5.9
6.0| 0.8| 1.9| 4.5| 0.5| 1.2| 500| 13.5| 12.2| 0.90| 1.78| 18.9| 7.2| 5.0
650| 13.8| 13.2| 0.96| 1.84| 19.4| 7.1| 5.6

3/27/2020

Performance Data cont.
NVZ033 – 100% Full Load


EWT

°F

| ****

Flow gpm

| WPD| HEATING – EAT 70°F| ****

EWT

°F

| ****

Flow gpm

| WPD| COOLING – EAT 80/67 °F|
---|---|---|---|---|---|---|---|---
PSI| FT| Airflow cfm| HC

MBtuh

| Power kW| HE

MBtuh

| LAT

°F

| COP| HWC

MBtuh

| PSI| FT| Airflow cfm| TC

MBtuh

| SC

MBtuh

| S/T Ratio| Power kW| HR

MBtuh

| EER| HWC

MBtuh


20

| 6.0| 1.5| 3.5| Operation not recommended| ****

20

| 4.5| 0.7| 1.6| ****

Operation not recommended

9.0| 2.3| 5.4| 6.5| 1.5| 3.5
12.0| 4.1| 9.5| 1150| 27.6| 2.94| 17.6| 92.2| 2.75| 3.0| 9.0| 2.3| 5.4
1500| 28.7| 2.80| 19.1| 87.7| 3.00| 2.7



30

| 6.0| 1.5| 3.4| 1150| 31.7| 2.70| 22.5| 95.5| 3.44| 3.1| ****


30

| 4.5| 0.7| 1.6| 1000| 34.6| 22.1| 0.64| 1.14| 38.5| 30.4| –
1500| 32.6| 2.79| 23.1| 90.1| 3.42| 2.8| 1200| 35.2| 24.3| 0.69| 1.18| 39.3| 29.8| –
9.0| 2.3| 5.3| 1150| 32.5| 2.74| 23.1| 96.2| 3.48| 3.2| 6.5| 1.5| 3.4| 1000| 35.1| 22.3| 0.64| 1.08| 38.7| 32.5| –
1500| 33.4| 2.82| 23.8| 90.6| 3.47| 2.9| 1200| 35.6| 24.4| 0.68| 1.14| 39.5| 31.3| –
12.0| 4.0| 9.2| 1150| 32.8| 2.99| 22.6| 96.4| 3.22| 3.2| 9.0| 2.3| 5.3| 1000| 35.2| 22.3| 0.63| 1.05| 38.8| 33.6| –
1500| 34.1| 2.85| 24.4| 91.0| 3.51| 2.9| 1200| 36.1| 24.4| 0.68| 1.10| 39.9| 32.8| –



40

| 6.0| 1.4| 3.3| 1150| 35.4| 2.84| 25.7| 98.5| 3.66| 3.3| ****


40

| 4.5| 0.7| 1.5| 1000| 35.4| 23.6| 0.67| 1.31| 39.9| 27.1| –
1500| 36.5| 2.91| 26.5| 92.5| 3.67| 3.1| 1200| 36.1| 25.9| 0.72| 1.36| 40.7| 26.5| –
9.0| 2.2| 5.1| 1150| 36.5| 2.89| 26.7| 99.4| 3.70| 3.4| 6.5| 1.4| 3.3| 1000| 35.8| 23.9| 0.67| 1.24| 40.1| 28.8| –
1500| 37.7| 2.96| 27.6| 93.2| 3.73| 3.1| 1200| 36.5| 26.1| 0.71| 1.30| 40.9| 28.0| –
12.0| 3.9| 8.9| 1150| 37.3| 2.92| 27.3| 100.0| 3.74| 3.5| 9.0| 2.2| 5.1| 1000| 36.1| 23.9| 0.66| 1.20| 40.2| 30.0| –
1500| 38.5| 2.99| 28.3| 93.7| 3.78| 3.2| 1200| 36.9| 26.1| 0.71| 1.26| 41.2| 29.3| –



50

| 6.0| 1.4| 3.2| 1150| 39.2| 2.98| 29.0| 101.5| 3.85| 3.7| ****


50

| 4.5| 0.6| 1.5| 1000| 34.7| 23.1| 0.66| 1.47| 39.7| 23.6| –
1500| 40.3| 3.02| 30.0| 94.9| 3.91| 3.4| 1200| 36.5| 25.7| 0.70| 1.55| 41.8| 23.6| –
9.0| 2.1| 4.9| 1150| 40.6| 3.05| 30.2| 102.7| 3.90| 3.8| 6.5| 1.4| 3.2| 1000| 35.5| 23.4| 0.66| 1.39| 40.2| 25.6| –
1500| 41.9| 3.09| 31.3| 95.9| 3.97| 3.5| 1200| 37.3| 25.9| 0.70| 1.45| 42.2| 25.6| –
12.0| 3.7| 8.6| 1150| 41.5| 3.08| 31.0| 103.4| 3.95| 3.9| 9.0| 2.1| 4.9| 1000| 35.8| 24.9| 0.70| 1.35| 40.4| 26.5| –
1500| 42.8| 3.12| 32.2| 96.4| 4.02| 3.6| 1200| 37.7| 27.7| 0.73| 1.42| 42.5| 26.5| –



60

| 6.0| 1.3| 3.1| 1150| 43.4| 3.03| 33.1| 105.0| 4.20| 4.1| ****


60

| 4.5| 0.6| 1.4| 1000| 32.9| 23.4| 0.71| 1.68| 38.6| 19.6| 1.9
1500| 44.8| 3.05| 34.4| 97.7| 4.31| 3.8| 1200| 34.5| 26.0| 0.75| 1.75| 40.4| 19.7| 2.1
9.0| 2.1| 4.8| 1150| 45.4| 3.11| 34.7| 106.5| 4.27| 4.3| 6.5| 1.3| 3.1| 1000| 33.6| 23.7| 0.70| 1.59| 39.1| 21.1| 1.8
1500| 46.8| 3.13| 36.1| 98.9| 4.38| 3.9| 1200| 35.2| 26.2| 0.74| 1.66| 40.9| 21.2| 2.0
12.0| 3.6| 8.4| 1150| 46.5| 3.15| 35.7| 107.4| 4.33| 4.4| 9.0| 2.1| 4.8| 1000| 34.0| 24.9| 0.73| 1.55| 39.3| 21.9| 1.7
1500| 48.0| 3.16| 37.2| 99.6| 4.45| 4.0| 1200| 35.7| 27.7| 0.78| 1.63| 41.2| 21.9| 1.9



70

| 6.0| 1.3| 3.0| 1150| 47.7| 3.07| 37.2| 108.4| 4.55| 4.6| ****


70

| 4.5| 0.6| 1.4| 1000| 31.0| 23.7| 0.76| 1.92| 37.6| 16.2| 2.4
1500| 49.1| 3.15| 38.4| 100.3| 4.57| 4.3| 1200| 32.1| 25.4| 0.79| 1.98| 38.9| 16.2| 2.5
9.0| 2.0| 4.6| 1150| 50.2| 3.17| 39.3| 110.4| 4.63| 4.8| 6.5| 1.3| 3.0| 1000| 31.8| 24.0| 0.75| 1.80| 38.0| 17.7| 2.2
1500| 51.8| 3.17| 41.0| 102.0| 4.78| 4.4| 1200| 33.2| 26.5| 0.80| 1.87| 39.6| 17.8| 2.4
12.0| 3.5| 8.1| 1150| 51.4| 3.21| 40.5| 111.4| 4.69| 4.9| 9.0| 2.0| 4.6| 1000| 32.2| 24.9| 0.77| 1.76| 38.2| 18.3| 2.0
1500| 53.2| 3.20| 42.3| 102.8| 4.87| 4.5| 1200| 33.6| 27.6| 0.82| 1.83| 39.8| 18.4| 2.3



80

| 6.0| 1.3| 2.9| 1150| 51.0| 3.18| 40.1| 111.1| 4.70| 5.2| ****


80

| 4.5| 0.6| 1.3| 1000| 29.6| 23.5| 0.79| 2.14| 36.9| 13.8| 2.9
1500| 52.8| 3.16| 42.0| 102.6| 4.90| 4.9| 1200| 30.8| 26.2| 0.85| 2.21| 38.4| 14.0| 3.1
9.0| 1.9| 4.5| 1150| 53.9| 3.31| 42.7| 113.4| 4.78| 5.4| 6.5| 1.3| 2.9| 1000| 30.5| 23.8| 0.78| 2.07| 37.5| 14.7| 2.7
1500| 55.8| 3.27| 44.6| 104.4| 4.99| 5.0| 1200| 31.7| 26.4| 0.83| 2.13| 38.9| 14.9| 3.0
12.0| 3.4| 7.8| 1150| 55.5| 3.35| 44.1| 114.7| 4.86| 5.6| 9.0| 1.9| 4.5| 1000| 30.8| 24.4| 0.79| 2.02| 37.7| 15.2| 2.5
1500| 57.4| 3.30| 46.1| 105.4| 5.10| 5.1| 1200| 32.1| 27.1| 0.84| 2.09| 39.2| 15.4| 2.8



90

| 6.0| 1.2| 2.8| 1150| 54.3| 3.29| 43.1| 113.7| 4.84| 5.9| ****


90

| 4.5| 0.6| 1.3| 1000| 28.3| 23.4| 0.83| 2.40| 36.4| 11.8| 3.7
1500| 56.2| 3.24| 45.2| 104.7| 5.09| 5.5| 1200| 29.3| 26.0| 0.89| 2.46| 37.6| 11.9| 3.9
9.0| 1.9| 4.3| 1150| 57.7| 3.44| 46.0| 116.5| 4.92| 6.1| 6.5| 1.2| 2.8| 1000| 29.1| 23.7| 0.82| 2.33| 37.0| 12.5| 3.4
1500| 59.8| 3.38| 48.3| 106.9| 5.19| 5.7| 1200| 30.2| 26.3| 0.87| 2.39| 38.3| 12.6| 3.7
12.0| 3.3| 7.5| 1150| 59.6| 3.49| 47.7| 117.9| 5.01| 6.3| 9.0| 1.9| 4.3| 1000| 29.8| 24.0| 0.81| 2.33| 37.7| 12.8| 3.2
1500| 61.6| 3.40| 50.0| 108.0| 5.31| 5.8| 1200| 30.5| 26.5| 0.87| 2.34| 38.5| 13.0| 4.1



100

| 6.0| 1.2| 2.7| ****







Operation not recommended

| ****


100

| 4.5| 0.5| 1.2| 1000| 26.8| 23.2| 0.87| 2.73| 36.1| 9.8| 4.4
1200| 27.6| 25.7| 0.93| 2.78| 37.1| 9.9| 4.8
9.0| 1.8| 4.2| 6.5| 1.2| 2.7| 1000| 27.7| 23.5| 0.85| 2.68| 36.8| 10.3| 4.1
1200| 28.6| 26.1| 0.91| 2.72| 37.9| 10.5| 4.5
12.0| 3.1| 7.3| 9.0| 1.8| 4.2| 1000| 28.0| 23.4| 0.84| 2.63| 37.0| 10.6| 3.8
1200| 28.9| 25.9| 0.90| 2.68| 38.0| 10.8| 4.3



110

| 6.0| 1.1| 2.6| ****


110

| 4.5| 0.5| 1.2| 1000| 25.3| 23.0| 0.91| 3.06| 35.8| 8.3| 5.6
1200| 26.0| 25.5| 0.98| 3.10| 36.6| 8.4| 5.9
9.0| 1.7| 4.0| 6.5| 1.1| 2.6| 1000| 26.3| 23.2| 0.88| 3.03| 36.7| 8.7| 5.2
1200| 27.0| 25.8| 0.96| 3.05| 37.4| 8.9| 5.6
12.0| 3.0| 7.0| 9.0| 1.7| 4.0| 1000| 26.6| 22.9| 0.86| 2.98| 36.7| 8.9| 4.8
1200| 27.3| 25.3| 0.93| 3.01| 37.6| 9.1| 5.3



120

| 6.0| 1.1| 2.5| ****


120

| 4.5| 0.5| 1.2| 1000| 24.4| 22.1| 0.90| 3.60| 36.7| 6.8| 6.7
1200| 25.0| 24.1| 0.97| 3.69| 37.5| 6.8| 7.1
9.0| 1.7| 3.8| 6.5| 1.1| 2.5| 1000| 24.7| 22.3| 0.90| 3.41| 36.4| 7.3| 6.2
1200| 25.2| 24.2| 0.96| 3.49| 37.1| 7.2| 6.7
12.0| 2.9| 6.7| 9.0| 1.7| 3.8| 1000| 25.0| 22.3| 0.89| 3.30| 36.2| 7.6| 6.4
1200| 25.5| 24.2| 0.95| 3.40| 37.1| 7.5| 7.1

Performance Data cont.
NVZ042 – 50% Part Load


EWT

°F

| ****

Flow gpm

| WPD| HEATING – EAT 70°F| ****

EWT

°F

| ****

Flow gpm

| WPD| COOLING – EAT 80/67 °F
---|---|---|---|---|---|---|---
PSI| FT| Airflow cfm| HC

MBtuh

| Power kW| HE

MBtuh

| LAT

°F

| COP| HWC

MBtuh

| PSI| FT| Airflow cfm| TC

MBtuh

| SC

MBtuh

| S/T Ratio| Power kW| HR

MBtuh

| EER| HWC

MBtuh


20

| 3.7| 0.4| 0.8| Operation not recommended| ****

20

| 3.0| 0.2| 0.5| **** Operation not recommended
5.2| 0.7| 1.6| 4.4| 0.6| 1.4
6.7| 1.2| 2.7| 700| 16.6| 1.73| 10.7| 91.9| 2.81| 2.7| 5.8| 0.9| 2.2
900| 16.9| 1.66| 11.2| 87.4| 2.98| 2.3



30

| 3.7| 0.3| 0.8| 700| 17.1| 1.56| 11.8| 92.6| 3.20| 2.6| ****


30

| 3.0| 0.2| 0.5| 650| 23.3| 15.7| 0.67| 0.59| 24.2| 37.8| –
900| 17.7| 1.59| 12.2| 88.2| 3.26| 2.2| 750| 23.8| 17.2| 0.73| 0.61| 24.7| 36.9| –
5.2| 0.7| 1.6| 700| 18.5| 1.63| 12.9| 94.4| 3.31| 2.7| 4.4| 0.6| 1.3| 650| 23.7| 15.9| 0.67| 0.56| 24.4| 40.3| –
900| 19.0| 1.65| 13.4| 89.6| 3.39| 2.3| 750| 24.0| 17.3| 0.72| 0.59| 24.9| 38.8| –
6.7| 1.1| 2.6| 700| 19.2| 1.74| 13.3| 95.4| 3.23| 2.8| 5.8| 0.9| 2.1| 650| 23.8| 15.9| 0.67| 0.54| 24.5| 41.7| –
900| 19.6| 1.67| 13.9| 90.2| 3.44| 2.4| 750| 24.4| 17.3| 0.71| 0.57| 25.1| 40.7| –



40

| 3.7| 0.3| 0.8| 700| 19.9| 1.60| 14.4| 96.3| 3.64| 2.8| ****


40

| 3.0| 0.2| 0.5| 650| 24.4| 16.1| 0.66| 0.67| 25.5| 34.4| –
900| 20.5| 1.61| 15.0| 91.1| 3.73| 2.4| 750| 24.9| 17.6| 0.71| 0.70| 26.1| 33.7| –
5.2| 0.7| 1.5| 700| 21.4| 1.66| 15.8| 98.4| 3.78| 2.9| 4.4| 0.6| 1.3| 650| 24.7| 16.2| 0.66| 0.64| 25.7| 36.7| –
900| 22.2| 1.66| 16.5| 92.8| 3.91| 2.5| 750| 25.1| 17.7| 0.70| 0.67| 26.2| 35.6| –
6.7| 1.1| 2.5| 700| 22.1| 1.67| 16.4| 99.3| 3.88| 3.0| 5.8| 0.9| 2.0| 650| 24.9| 16.2| 0.65| 0.62| 25.8| 38.1| –
900| 22.9| 1.69| 17.2| 93.6| 3.98| 2.6| 750| 25.4| 17.7| 0.70| 0.65| 26.4| 37.2| –



50

| 3.7| 0.3| 0.7| 700| 22.7| 1.64| 17.1| 100.0| 4.06| 3.1| ****


50

| 3.0| 0.2| 0.5| 650| 25.0| 15.3| 0.61| 0.85| 26.7| 27.9| –
900| 23.4| 1.64| 17.8| 94.1| 4.19| 2.8| 750| 25.8| 18.0| 0.70| 0.89| 27.6| 27.6| –
5.2| 0.6| 1.5| 700| 24.4| 1.69| 18.7| 102.3| 4.24| 3.3| 4.4| 0.5| 1.2| 650| 25.5| 15.3| 0.60| 0.74| 26.8| 33.0| –
900| 25.4| 1.68| 19.6| 96.1| 4.43| 2.9| 750| 26.3| 18.1| 0.69| 0.77| 27.7| 32.4| –
6.7| 1.1| 2.5| 700| 25.4| 1.70| 19.6| 103.6| 4.37| 3.4| 5.8| 0.9| 2.0| 650| 25.7| 15.3| 0.60| 0.69| 26.8| 35.2| –
900| 26.2| 1.70| 20.4| 97.0| 4.52| 3.0| 750| 26.5| 18.1| 0.68| 0.73| 27.7| 34.5| –



60

| 3.7| 0.3| 0.7| 700| 25.2| 1.68| 19.4| 103.3| 4.39| 2.9| ****


60

| 3.0| 0.2| 0.5| 650| 23.6| 15.0| 0.64| 0.99| 25.9| 22.8| 1.3
900| 26.1| 1.67| 20.4| 96.8| 4.58| 2.5| 750| 24.4| 17.7| 0.73| 1.03| 26.7| 22.5| 1.5
5.2| 0.6| 1.4| 700| 27.2| 1.72| 21.4| 106.0| 4.64| 3.0| 4.4| 0.5| 1.2| 650| 24.0| 15.1| 0.63| 0.88| 25.9| 26.1| 1.2
900| 28.3| 1.70| 22.5| 99.1| 4.88| 2.6| 750| 24.8| 17.8| 0.72| 0.92| 26.7| 25.7| 1.4
6.7| 1.0| 2.4| 700| 28.4| 1.74| 22.5| 107.6| 4.79| 3.2| 5.8| 0.8| 1.9| 650| 24.3| 15.2| 0.62| 0.83| 26.0| 27.8| 1.1
900| 29.4| 1.72| 23.5| 100.2| 5.02| 2.7| 750| 25.0| 17.9| 0.71| 0.87| 26.8| 27.4| 1.3



70

| 3.7| 0.3| 0.7| 700| 27.7| 1.72| 21.8| 106.6| 4.72| 3.4| ****


70

| 3.0| 0.2| 0.5| 650| 22.3| 14.8| 0.66| 1.12| 25.1| 18.9| 2.2
900| 30.5| 1.72| 24.6| 101.4| 5.20| 3.0| 750| 22.9| 16.5| 0.72| 1.18| 25.8| 18.5| 2.3
5.2| 0.6| 1.4| 700| 30.0| 1.75| 24.1| 109.7| 5.03| 3.6| 4.4| 0.5| 1.2| 650| 22.5| 14.9| 0.66| 1.02| 24.9| 21.1| 2.0
900| 31.2| 1.72| 25.4| 102.1| 5.32| 3.2| 750| 23.2| 17.6| 0.76| 1.06| 25.8| 20.8| 2.2
6.7| 1.0| 2.3| 700| 31.4| 1.77| 25.4| 111.6| 5.20| 3.8| 5.8| 0.8| 1.8| 650| 22.9| 15.0| 0.66| 0.97| 25.1| 22.5| 1.8
900| 32.6| 1.73| 26.7| 103.5| 5.52| 3.5| 750| 23.6| 17.6| 0.75| 1.01| 25.9| 22.3| 2.0



80

| 3.7| 0.3| 0.7| 700| 29.7| 1.77| 23.6| 109.2| 4.91| 4.2| ****


80

| 3.0| 0.2| 0.4| 650| 20.8| 13.7| 0.66| 1.30| 24.2| 15.3| 2.3
900| 30.8| 1.74| 24.9| 101.7| 5.19| 3.7| 750| 21.5| 16.1| 0.75| 1.35| 25.1| 15.1| 2.6
5.2| 0.6| 1.3| 700| 32.2| 1.79| 26.1| 112.6| 5.27| 4.4| 4.4| 0.5| 1.1| 650| 20.9| 13.9| 0.66| 1.20| 24.0| 16.6| 2.0
900| 33.5| 1.74| 27.6| 104.5| 5.63| 3.9| 750| 21.5| 16.3| 0.76| 1.25| 24.8| 16.4| 2.4
6.7| 1.0| 2.2| 700| 33.8| 1.81| 27.7| 114.8| 5.48| 4.6| 5.8| 0.8| 1.8| 650| 21.4| 14.0| 0.65| 1.15| 24.3| 17.7| 1.8
900| 35.2| 1.76| 29.2| 106.2| 5.86| 4.1| 750| 22.1| 16.4| 0.75| 1.20| 25.1| 17.5| 2.2



90

| 3.7| 0.3| 0.6| 700| 31.6| 1.82| 25.4| 111.8| 5.09| 5.1| ****


90

| 3.0| 0.2| 0.4| 650| 19.3| 12.7| 0.66| 1.47| 23.4| 12.6| 3.7
900| 32.9| 1.78| 26.8| 103.8| 5.41| 4.6| 750| 19.9| 14.9| 0.75| 1.52| 24.2| 12.5| 4.0
5.2| 0.6| 1.3| 700| 34.4| 1.83| 28.1| 115.5| 5.51| 5.4| 4.4| 0.5| 1.1| 650| 19.3| 12.8| 0.66| 1.39| 23.1| 13.2| 3.3
900| 35.8| 1.77| 29.8| 106.8| 5.93| 4.8| 750| 19.9| 15.1| 0.76| 1.44| 23.8| 13.1| 3.8
6.7| 0.9| 2.2| 700| 36.3| 1.85| 30.0| 118.0| 5.75| 5.6| 5.8| 0.7| 1.7| 650| 19.8| 14.1| 0.71| 1.37| 23.6| 13.8| 3.0
900| 37.8| 1.79| 31.7| 108.9| 6.19| 5.0| 750| 20.5| 15.2| 0.74| 1.39| 24.2| 14.0| 3.5



100

| 3.7| 0.3| 0.6| ****







Operation not recommended

| ****


100

| 3.0| 0.2| 0.4| 650| 17.8| 12.0| 0.67| 1.68| 22.7| 10.1| 5.1
750| 18.4| 14.1| 0.77| 1.75| 23.5| 10.0| 5.7
5.2| 0.5| 1.2| 4.4| 0.4| 1.0| 650| 17.7| 12.2| 0.69| 1.64| 22.4| 10.3| 4.7
750| 18.2| 14.3| 0.78| 1.70| 23.2| 10.2| 5.3
6.7| 0.9| 2.1| 5.8| 0.7| 1.7| 650| 18.4| 12.3| 0.67| 1.58| 22.9| 11.1| 4.3
750| 18.9| 14.5| 0.77| 1.65| 23.6| 10.9| 4.9



110

| 3.7| 0.3| 0.6| ****


110

| 3.0| 0.2| 0.4| 650| 16.3| 11.4| 0.70| 1.89| 22.0| 8.2| 7.3
750| 16.8| 13.3| 0.79| 1.97| 22.7| 8.1| 7.8
5.2| 0.5| 1.2| 4.4| 0.4| 1.0| 650| 16.1| 11.5| 0.72| 1.88| 21.7| 8.1| 6.8
750| 16.6| 13.5| 0.81| 1.96| 22.5| 8.1| 7.5
6.7| 0.9| 2.0| 5.8| 0.7| 1.6| 650| 16.9| 11.7| 0.70| 1.82| 22.3| 8.8| 6.2
750| 17.3| 13.8| 0.79| 1.90| 23.0| 8.7| 7.0



120

| 3.7| 0.2| 0.6| ****


120

| 3.0| 0.2| 0.4| 650| 14.2| 12.3| 0.86| 2.32| 21.4| 5.8| 10.4
750| 14.5| 13.4| 0.92| 2.38| 21.9| 5.8| 10.9
5.2| 0.5| 1.2| 4.4| 0.4| 1.0| 650| 14.4| 12.4| 0.86| 2.19| 21.2| 6.2| 9.3
750| 14.6| 13.4| 0.92| 2.25| 21.6| 6.2| 10.0
6.7| 0.8| 1.9| 5.8| 0.7| 1.5| 650| 14.5| 12.4| 0.85| 2.12| 21.1| 6.5| 8.0
750| 14.8| 13.4| 0.91| 2.19| 21.6| 6.4| 9.1

NVZ042 – 100% Full Load


EWT

°F

| ****

Flow gpm

| WPD| HEATING – EAT 70°F| ****

EWT

°F

| ****

Flow gpm

| WPD| COOLING – EAT 80/67 °F
---|---|---|---|---|---|---|---
PSI| FT| Airflow cfm| HC

MBtuh

| Power kW| HE

MBtuh

| LAT

°F

| COP| HWC

MBtuh

| PSI| FT| Airflow cfm| TC

MBtuh

| SC

MBtuh

| S/T Ratio| Power kW| HR

MBtuh

| EER| HWC

MBtuh


20

| 9.0| 1.9| 4.3| Operation not recommended| ****

20

| 6.0| 0.9| 2.2| ****

Operation not recommended

12.0| 3.5| 8.1| 8.5| 1.6| 3.8
15.0| 5.0| 11.6| 1600| 36.8| 3.84| 23.7| 91.3| 2.81| 3.5| 11.0| 2.5| 5.7
1800| 37.4| 3.84| 24.3| 89.2| 2.85| 3.1



30

| 9.0| 1.8| 4.2| 1600| 37.8| 3.68| 25.3| 91.9| 3.01| 3.5| ****


30

| 6.0| 0.9| 2.1| 1200| 38.7| 24.1| 0.62| 1.40| 43.5| 27.6| –
1800| 39.1| 3.74| 26.4| 90.1| 3.07| 3.2| 1400| 39.4| 26.5| 0.67| 1.46| 44.4| 27.0| –
12.0| 3.4| 7.9| 1600| 40.9| 3.85| 27.7| 93.7| 3.11| 3.7| 8.5| 1.6| 3.7| 1200| 39.2| 24.3| 0.62| 1.34| 43.8| 29.4| –
1800| 42.1| 3.88| 28.9| 91.7| 3.19| 3.2| 1400| 39.9| 26.6| 0.67| 1.41| 44.7| 28.3| –
15.0| 4.9| 11.3| 1600| 42.7| 3.93| 29.3| 94.7| 3.18| 3.9| 11.0| 2.4| 5.5| 1200| 39.4| 24.3| 0.62| 1.30| 43.9| 30.4| –
1800| 43.4| 3.93| 30.0| 92.3| 3.24| 3.4| 1400| 40.4| 26.6| 0.66| 1.36| 45.0| 29.7| –



40

| 9.0| 1.8| 4.1| 1600| 43.0| 3.81| 30.0| 94.9| 3.31| 3.8| ****


40

| 6.0| 0.9| 2.0| 1200| 42.3| 28.0| 0.66| 1.61| 47.8| 26.2| –
1800| 44.4| 3.84| 31.3| 92.8| 3.39| 3.5| 1400| 43.1| 30.6| 0.71| 1.68| 48.9| 25.7| –
12.0| 3.3| 7.6| 1600| 46.4| 3.96| 32.9| 96.8| 3.44| 4.2| 8.5| 1.5| 3.6| 1200| 42.8| 28.3| 0.66| 1.53| 48.0| 27.9| –
1800| 48.0| 3.96| 34.5| 94.7| 3.56| 3.7| 1400| 43.6| 30.9| 0.71| 1.61| 49.1| 27.1| –
15.0| 4.7| 11.0| 1600| 47.9| 3.98| 34.3| 97.7| 3.53| 4.4| 11.0| 2.3| 5.3| 1200| 43.1| 28.3| 0.66| 1.49| 48.2| 29.0| –
1800| 49.6| 4.01| 35.9| 95.5| 3.62| 3.9| 1400| 44.1| 30.9| 0.70| 1.56| 49.4| 28.4| –



50

| 9.0| 1.7| 3.9| 1600| 48.2| 3.94| 34.8| 97.9| 3.59| 4.4| ****


50

| 6.0| 0.9| 2.0| 1200| 45.1| 29.6| 0.66| 2.04| 52.1| 22.1| –
1800| 49.7| 3.94| 36.3| 95.6| 3.70| 4.0| 1400| 46.5| 35.0| 0.75| 2.13| 53.8| 21.9| –
12.0| 3.2| 7.4| 1600| 51.9| 4.06| 38.1| 100.1| 3.75| 4.8| 8.5| 1.5| 3.5| 1200| 46.1| 29.8| 0.65| 1.77| 52.1| 26.1| –
1800| 53.9| 4.04| 40.2| 97.7| 3.91| 4.4| 1400| 47.5| 35.1| 0.74| 1.85| 53.8| 25.6| –
15.0| 4.6| 10.6| 1600| 53.9| 4.09| 40.0| 101.2| 3.86| 5.1| 11.0| 2.2| 5.2| 1200| 46.4| 29.8| 0.64| 1.66| 52.1| 27.9| –
1800| 55.7| 4.09| 41.7| 98.7| 3.99| 4.6| 1400| 47.8| 35.1| 0.73| 1.75| 53.8| 27.3| –



60

| 9.0| 1.7| 3.8| 1600| 53.3| 4.09| 39.4| 100.8| 3.82| 5.2| ****


60

| 6.0| 0.8| 1.9| 1200| 43.4| 28.8| 0.66| 2.25| 51.1| 19.3| 2.6
1800| 55.2| 4.06| 41.4| 98.4| 3.98| 4.7| 1400| 44.7| 34.0| 0.76| 2.35| 52.8| 19.0| 2.7
12.0| 3.1| 7.2| 1600| 57.7| 4.19| 43.4| 103.4| 4.04| 5.6| 8.5| 1.4| 3.3| 1200| 44.1| 29.0| 0.66| 2.00| 50.9| 22.1| 2.4
1800| 59.9| 4.14| 45.8| 100.8| 4.24| 5.1| 1400| 45.5| 34.2| 0.75| 2.09| 52.6| 21.8| 2.6
15.0| 4.4| 10.3| 1600| 60.1| 4.23| 45.7| 104.8| 4.17| 6.0| 11.0| 2.2| 5.0| 1200| 44.6| 29.1| 0.65| 1.90| 51.1| 23.5| 2.2
1800| 62.3| 4.18| 48.0| 102.0| 4.37| 5.4| 1400| 46.0| 34.3| 0.75| 1.98| 52.7| 23.2| 2.4



70

| 9.0| 1.6| 3.7| 1600| 58.4| 4.24| 44.0| 103.8| 4.04| 6.0| ****


70

| 6.0| 0.8| 1.8| 1200| 41.6| 28.0| 0.67| 2.46| 50.0| 16.9| 3.4
1800| 65.4| 4.20| 51.1| 103.6| 4.56| 5.5| 1400| 44.0| 33.1| 0.75| 2.42| 52.3| 18.2| 3.6
12.0| 3.0| 6.9| 1600| 63.4| 4.31| 48.7| 106.7| 4.31| 6.5| 8.5| 1.4| 3.2| 1200| 42.1| 28.3| 0.67| 2.23| 49.7| 18.9| 3.1
1800| 65.9| 4.24| 51.4| 103.9| 4.56| 6.0| 1400| 43.4| 33.3| 0.77| 2.33| 51.3| 18.7| 3.4
15.0| 4.3| 9.9| 1600| 63.7| 4.28| 49.1| 106.9| 4.36| 6.9| 11.0| 2.5| 4.9| 1200| 42.8| 28.4| 0.66| 2.13| 50.0| 20.1| 2.8
1800| 68.8| 4.26| 54.3| 105.4| 4.73| 7.2| 1400| 44.1| 33.4| 0.76| 2.21| 51.6| 20.0| 3.2



80

| 9.0| 1.5| 3.6| 1600| 61.8| 4.38| 46.8| 105.8| 4.13| 7.1| ****


80

| 6.0| 0.8| 1.8| 1200| 38.4| 27.1| 0.70| 2.73| 47.7| 14.1| 4.5
1800| 64.2| 4.31| 49.5| 103.0| 4.37| 6.5| 1400| 39.6| 31.8| 0.80| 2.85| 49.3| 13.9| 4.8
12.0| 2.9| 6.7| 1600| 67.1| 4.43| 52.0| 108.8| 4.44| 7.6| 8.5| 1.4| 3.1| 1200| 38.6| 27.4| 0.71| 2.53| 47.3| 15.2| 4.1
1800| 69.8| 4.32| 55.1| 105.9| 4.73| 7.0| 1400| 39.8| 32.2| 0.81| 2.63| 48.8| 15.1| 4.4
15.0| 4.2| 9.6| 1600| 70.5| 4.48| 55.2| 110.8| 4.61| 8.1| 11.0| 2.0| 4.7| 1200| 39.5| 27.6| 0.70| 2.42| 47.8| 16.3| 3.8
1800| 73.4| 4.36| 58.5| 107.7| 4.93| 7.5| 1400| 40.7| 32.4| 0.80| 2.53| 49.3| 16.1| 4.2



90

| 9.0| 1.5| 3.4| 1600| 65.2| 4.53| 49.7| 107.7| 4.21| 8.4| ****


90

| 6.0| 0.7| 1.7| 1200| 35.2| 26.1| 0.74| 2.99| 45.4| 11.8| 6.0
1800| 67.7| 4.44| 52.6| 104.8| 4.48| 7.7| 1400| 36.3| 30.7| 0.84| 3.12| 46.9| 11.7| 6.3
12.0| 2.8| 6.5| 1600| 70.9| 4.56| 55.3| 111.0| 4.55| 8.9| 8.5| 1.3| 3.0| 1200| 35.2| 26.4| 0.75| 2.84| 44.9| 12.4| 5.3
1800| 73.8| 4.41| 58.7| 108.0| 4.90| 8.2| 1400| 36.2| 31.1| 0.86| 2.94| 46.2| 12.3| 5.8
15.0| 4.0| 9.3| 1600| 74.8| 4.61| 59.0| 113.3| 4.75| 9.5| 11.0| 2.0| 4.5| 1200| 36.1| 29.2| 0.81| 2.79| 45.6| 12.9| 5.0
1800| 77.9| 4.46| 62.7| 110.1| 5.12| 8.7| 1400| 37.3| 31.4| 0.84| 2.84| 47.0| 13.1| 6.3



100

| 9.0| 1.4| 3.3| ****







Operation not recommended

| ****


100

| 6.0| 0.7| 1.7| 1200| 32.6| 24.4| 0.75| 3.32| 43.9| 9.8| 7.0
1400| 33.6| 28.7| 0.85| 3.46| 45.4| 9.7| 7.5
12.0| 2.7| 6.2| 8.5| 1.3| 2.9| 1200| 32.4| 24.7| 0.76| 3.23| 43.4| 10.0| 6.7
1400| 33.4| 29.1| 0.87| 3.36| 44.8| 9.9| 7.3
15.0| 3.9| 8.9| 11.0| 1.9| 4.4| 1200| 33.6| 25.1| 0.75| 3.11| 44.2| 10.8| 6.3
1400| 34.6| 29.5| 0.85| 3.25| 45.6| 10.6| 7.1



110

| 9.0| 1.4| 3.2| ****


110

| 6.0| 0.7| 1.6| 1200| 30.0| 22.7| 0.76| 3.64| 42.4| 8.2| 9.0
1400| 30.8| 26.7| 0.87| 3.79| 43.7| 8.1| 9.8
12.0| 2.6| 6.0| 8.5| 1.2| 2.8| 1200| 29.5| 23.0| 0.78| 3.62| 41.9| 8.2| 8.6
1400| 30.5| 27.1| 0.89| 3.77| 43.4| 8.1| 9.4
15.0| 3.7| 8.6| 11.0| 1.8| 4.2| 1200| 30.9| 23.4| 0.76| 3.51| 42.9| 8.8| 8.2
1400| 31.8| 27.5| 0.86| 3.66| 44.3| 8.7| 9.2



120

| 9.0| 1.3| 3.1| ****


120

| 6.0| 0.7| 1.5| 1200| 26.7| 23.9| 0.90| 4.35| 41.5| 6.1| 11.9
1400| 27.2| 26.1| 0.96| 4.45| 42.4| 6.1| 12.4
12.0| 2.5| 5.8| 8.5| 1.2| 2.7| 1200| 27.0| 24.1| 0.89| 4.11| 41.0| 6.6| 11.1
1400| 27.5| 26.2| 0.95| 4.21| 41.9| 6.5| 12.0
15.0| 3.6| 8.2| 11.0| 1.7| 4.0| 1200| 27.2| 24.1| 0.89| 3.97| 40.8| 6.8| 10.2
1400| 27.8| 26.2| 0.94| 4.10| 41.8| 6.8| 11.4

NVZ050 – 50% Part Load


EWT

°F

| ****

Flow gpm

| WPD| HEATING – EAT 70°F| ****

EWT

°F

| ****

Flow gpm

| WPD| COOLING EAT 80/67 °F
---|---|---|---|---|---|---|---
PSI| FT| Airflow cfm| HC

MBtuh

| Power kW| HE

MBtuh

| LAT

°F

| COP| HWC

MBtuh

| PSI| FT| Airflow cfm| TC

MBtuh

| SC

MBtuh

| S/T Ratio| Power kW| HR

MBtuh

| EER| HWC

MBtuh


20

| 3.7| 0.1| 0.3| Operation not recommended| ****

20

| 3.2| 0.1| 0.3| ****

Operation not recommended

5.1| 0.6| 1.4| 4.6| 0.5| 1.1
7.5| 1.2| 2.7| 850| 21.5| 2.29| 14.0| 93.7| 2.78| 3.9| 6.0| 0.8| 1.9
980| 21.6| 2.20| 14.1| 90.4| 2.88| 3.7



30

| 3.7| 0.1| 0.3| 850| 23.8| 2.32| 15.0| 95.0| 2.90| 4.0| ****


30

| 3.2| 0.1| 0.3| 750| 23.2| 15.5| 0.67| 0.64| 24.3| 34.6| –
980| 24.7| 2.35| 15.7| 92.4| 2.96| 3.6| 850| 23.7| 17.0| 0.72| 0.67| 24.8| 33.8| –
5.1| 0.6| 1.3| 850| 23.7| 2.35| 14.8| 94.8| 2.84| 4.1| 4.6| 0.5| 1.1| 750| 23.6| 15.7| 0.66| 0.61| 24.5| 36.8| –
980| 24.6| 2.38| 15.5| 92.3| 2.90| 3.7| 850| 23.9| 17.1| 0.72| 0.64| 25.0| 35.5| –
7.5| 1.1| 2.6| 850| 25.3| 2.48| 16.1| 96.8| 2.91| 4.1| 6.0| 0.8| 1.8| 750| 23.7| 15.7| 0.66| 0.59| 24.6| 38.2| –
980| 25.4| 2.38| 16.3| 93.1| 3.00| 3.5| 850| 24.3| 17.1| 0.71| 0.62| 25.2| 37.3| –



40

| 3.7| 0.1| 0.3| 850| 28.2| 2.39| 19.1| 99.7| 3.35| 4.2| ****


40

| 3.2| 0.1| 0.3| 750| 27.0| 18.4| 0.68| 0.86| 28.6| 30.0| –
980| 29.1| 2.40| 19.9| 96.5| 3.43| 3.8| 850| 27.5| 20.1| 0.73| 0.89| 29.3| 29.4| –
5.1| 0.6| 1.3| 850| 28.4| 2.42| 19.2| 99.9| 3.32| 4.3| 4.6| 0.4| 1.0| 750| 27.3| 18.6| 0.68| 0.81| 28.8| 32.0| –
980| 29.2| 2.43| 19.9| 96.7| 3.40| 3.9| 850| 27.8| 20.3| 0.73| 0.85| 29.4| 31.1| –
7.5| 1.1| 2.5| 850| 29.4| 2.43| 20.0| 100.9| 3.41| 4.4| 6.0| 0.8| 1.8| 750| 27.5| 18.6| 0.67| 0.79| 28.9| 33.2| –
980| 30.2| 2.44| 20.8| 97.5| 3.50| 4.0| 850| 28.1| 20.3| 0.72| 0.83| 29.6| 32.5| –



50

| 3.7| 0.1| 0.2| 850| 32.6| 2.45| 23.2| 104.4| 3.77| 4.5| ****


50

| 3.2| 0.1| 0.2| 750| 31.0| 20.5| 0.66| 1.04| 33.0| 28.4| –
980| 33.5| 2.45| 24.1| 100.7| 3.88| 4.2| 850| 31.9| 23.2| 0.73| 1.10| 34.1| 27.7| –
5.1| 0.5| 1.2| 850| 33.1| 2.50| 23.6| 105.0| 3.76| 4.7| 4.6| 0.4| 1.0| 750| 31.0| 20.6| 0.67| 1.00| 33.0| 29.5| –
980| 33.9| 2.48| 24.3| 101.0| 3.87| 4.3| 850| 31.9| 23.4| 0.73| 1.05| 34.0| 29.0| –
7.5| 1.1| 2.5| 850| 34.1| 2.52| 24.5| 106.0| 3.85| 4.8| 6.0| 0.7| 1.7| 750| 31.1| 20.6| 0.66| 0.98| 33.0| 30.2| –
980| 34.9| 2.50| 25.3| 101.9| 3.96| 4.4| 850| 32.0| 23.4| 0.73| 1.03| 34.0| 29.6| –



60

| 3.7| 0.1| 0.2| 850| 36.4| 2.53| 26.6| 108.4| 4.08| 4.3| ****


60

| 3.2| 0.1| 0.2| 750| 30.0| 20.0| 0.67| 1.26| 32.9| 22.7| 2.4
980| 37.2| 2.51| 27.5| 104.0| 4.21| 3.9| 850| 30.9| 22.6| 0.73| 1.32| 34.0| 22.3| 2.6
5.1| 0.5| 1.2| 850| 37.5| 2.57| 27.6| 109.6| 4.14| 4.4| 4.6| 0.4| 1.0| 750| 30.2| 20.2| 0.67| 1.22| 32.9| 23.5| 2.3
980| 38.1| 2.54| 28.3| 104.9| 4.27| 4.0| 850| 31.1| 22.8| 0.73| 1.27| 33.9| 23.2| 2.5
7.5| 1.0| 2.4| 850| 38.4| 2.60| 28.4| 110.5| 4.20| 4.6| 6.0| 0.7| 1.7| 750| 30.3| 20.2| 0.67| 1.20| 32.9| 24.1| 2.2
980| 39.0| 2.56| 29.1| 105.7| 4.33| 4.1| 850| 31.2| 22.8| 0.73| 1.25| 34.0| 23.8| 2.4



70

| 3.7| 0.1| 0.2| 850| 40.1| 2.61| 30.0| 112.4| 4.38| 4.8| ****


70

| 3.2| 0.1| 0.2| 750| 29.1| 19.5| 0.67| 1.48| 32.8| 18.7| 3.3
980| 39.4| 2.57| 29.3| 106.0| 4.34| 4.4| 850| 29.6| 22.1| 0.74| 1.66| 33.9| 17.0| 3.4
5.1| 0.5| 1.2| 850| 41.8| 2.65| 31.5| 114.2| 4.49| 5.0| 4.6| 0.4| 0.9| 750| 29.3| 19.7| 0.67| 1.44| 32.8| 19.4| 3.1
980| 42.3| 2.59| 32.2| 108.8| 4.64| 4.6| 850| 30.2| 22.2| 0.74| 1.50| 33.9| 19.1| 3.3
7.5| 1.0| 2.3| 850| 42.6| 2.68| 32.2| 115.1| 4.53| 5.2| 6.0| 0.7| 1.6| 750| 29.4| 19.8| 0.67| 1.41| 32.8| 19.9| 2.9
980| 43.1| 2.62| 32.9| 109.5| 4.68| 4.8| 850| 30.3| 22.3| 0.73| 1.47| 33.9| 19.7| 3.1



80

| 3.7| 0.1| 0.2| 850| 43.5| 2.68| 30.1| 112.7| 4.29| 5.7| ****


80

| 3.2| 0.1| 0.2| 750| 27.2| 19.5| 0.68| 1.75| 31.9| 14.8| 3.4
980| 43.9| 2.62| 30.6| 107.4| 4.43| 5.2| 850| 28.0| 21.7| 0.74| 1.81| 32.9| 14.7| 3.7
5.1| 0.5| 1.1| 850| 46.0| 2.72| 32.2| 115.2| 4.46| 5.9| 4.6| 0.4| 0.9| 750| 27.5| 19.7| 0.68| 1.71| 32.0| 15.3| 3.1
980| 46.2| 2.64| 32.6| 109.4| 4.62| 5.4| 850| 28.3| 22.0| 0.74| 1.77| 33.0| 15.2| 3.5
7.5| 1.0| 2.2| 850| 46.5| 2.76| 32.5| 115.7| 4.45| 6.1| 6.0| 0.7| 1.6| 750| 27.6| 19.8| 0.68| 1.68| 32.1| 15.7| 2.9
980| 46.7| 2.68| 33.0| 109.8| 4.60| 5.6| 850| 28.5| 22.2| 0.74| 1.74| 33.1| 15.6| 3.3



90

| 3.7| 0.1| 0.2| 850| 46.9| 2.75| 30.2| 113.1| 4.21| 6.6| ****


90

| 3.2| 0.1| 0.2| 750| 25.4| 19.4| 0.69| 2.02| 31.0| 11.9| 4.8
980| 47.0| 2.68| 30.5| 107.5| 4.33| 6.1| 850| 26.1| 21.6| 0.74| 2.08| 32.0| 12.0| 5.1
5.1| 0.5| 1.1| 850| 50.1| 2.80| 32.7| 116.0| 4.42| 6.9| 4.6| 0.4| 0.9| 750| 25.6| 19.6| 0.69| 1.98| 31.2| 12.4| 4.4
980| 50.1| 2.70| 33.0| 109.9| 4.59| 6.3| 850| 26.4| 21.9| 0.75| 2.04| 32.1| 12.3| 4.9
7.5| 0.9| 2.2| 850| 50.4| 2.84| 32.8| 116.3| 4.38| 7.1| 6.0| 0.7| 1.5| 750| 25.9| 19.7| 0.76| 1.97| 31.4| 12.5| 4.1
980| 50.3| 2.74| 33.1| 110.1| 4.54| 6.5| 850| 26.7| 22.1| 0.74| 2.01| 32.3| 12.6| 4.6



100

| 3.7| 0.1| 0.2| ****







Operation not recommended

| ****


100

| 3.2| 0.1| 0.2| 750| 24.1| 18.5| 0.73| 2.32| 30.9| 9.9| 6.2
850| 24.8| 20.4| 0.78| 2.38| 31.7| 9.9| 6.8
5.1| 0.4| 1.0| 4.6| 0.4| 0.8| 750| 24.4| 18.7| 0.72| 2.29| 31.0| 10.2| 5.8
850| 25.1| 20.7| 0.78| 2.35| 31.9| 10.2| 6.4
7.5| 0.9| 2.1| 6.0| 0.6| 1.5| 750| 24.6| 18.9| 0.73| 2.26| 31.1| 10.4| 5.4
850| 25.4| 20.9| 0.78| 2.31| 32.1| 10.5| 6.0



110

| 3.7| 0.1| 0.2| ****


110

| 3.2| 0.1| 0.2| 750| 22.8| 17.5| 0.77| 2.62| 30.7| 8.3| 8.4
850| 23.5| 19.3| 0.82| 2.67| 31.5| 8.4| 8.9
5.1| 0.4| 1.0| 4.6| 0.3| 0.8| 750| 23.1| 17.7| 0.77| 2.60| 30.9| 8.5| 7.9
850| 23.8| 19.5| 0.82| 2.65| 31.7| 8.6| 8.6
7.5| 0.9| 2.0| 6.0| 0.6| 1.4| 750| 23.4| 18.0| 0.77| 2.56| 31.0| 8.7| 7.3
850| 24.2| 19.7| 0.82| 2.61| 31.9| 8.8| 8.1



120

| 3.7| 0.1| 0.2| ****


120

| 3.2| 0.1| 0.2| 750| 21.4| 17.4| 0.81| 3.18| 31.3| 6.4| 11.5
850| 21.9| 18.9| 0.87| 3.25| 32.0| 6.4| 12.0
5.1| 0.4| 1.0| 4.6| 0.3| 0.8| 750| 21.7| 17.5| 0.81| 3.01| 30.9| 6.9| 10.4
850| 22.1| 19.0| 0.86| 3.08| 31.6| 6.8| 11.1
7.5| 0.8| 1.9| 6.0| 0.6| 1.3| 750| 21.9| 17.5| 0.80| 2.91| 30.8| 7.2| 9.1
850| 22.4| 19.0| 0.85| 3.00| 31.5| 7.1| 10.2

NVZ050 – 100% Full Load


EWT

°F

| ****

Flow gpm

| WPD| HEATING – EAT 70°F| ****

EWT

°F

| ****

Flow gpm

| WPD| COOLING EAT 80/67 °F
---|---|---|---|---|---|---|---
PSI| FT| Airflow

cfm

| HC

MBtuh

| Power

kW

| HE

MBtuh

| LAT

°F

| COP| HWC

MBtuh

| PSI| FT| Airflow

cfm

| TC

MBtuh

| SC

MBtuh

| S/T

Ratio

| Power

kW

| HR

MBtuh

| EER| HWC

MBtuh


20

| 9.0| 2.0| 4.6| Operation not recommended| ****

20

| 9.0| 0.8| 1.9| ****

Operation not recommended

13.5| 4.6| 10.5| 11.5| 2.0| 4.6
18.0| 7.2| 16.7| 1800| 47.3| 5.16| 29.6| 94.3| 2.68| 5.5| 14.0| 3.2| 7.3
2200| 49.6| 5.21| 31.8| 90.9| 2.79| 5.0



30

| 9.0| 1.9| 4.5| 1800| 51.5| 4.97| 34.5| 96.5| 3.03| 5.6| ****


30

| 9.0| 0.8| 1.8| 1400| 46.9| 29.7| 0.63| 1.88| 53.4| 25.0| –
2200| 52.7| 5.23| 34.8| 92.2| 2.95| 5.0| 1600| 47.8| 32.5| 0.68| 1.96| 54.5| 24.4| –
13.5| 4.4| 10.2| 1800| 55.1| 5.02| 38.0| 98.3| 3.22| 5.7| 11.5| 1.9| 4.5| 1400| 47.6| 29.9| 0.63| 1.79| 53.7| 26.6| –
2200| 56.6| 5.34| 38.4| 93.8| 3.11| 5.2| 1600| 48.4| 32.7| 0.68| 1.88| 54.8| 25.7| –
18.0| 7.0| 16.2| 1800| 54.5| 5.34| 36.3| 98.0| 2.99| 5.9| 14.0| 3.1| 7.1| 1400| 47.8| 29.9| 0.63| 1.73| 53.7| 27.6| –
2200| 57.2| 5.39| 38.8| 94.1| 3.11| 5.3| 1600| 49.0| 32.7| 0.67| 1.82| 55.2| 26.9| –



40

| 9.0| 1.9| 4.3| 1800| 58.7| 5.23| 40.8| 100.2| 3.29| 6.0| ****


40

| 9.0| 0.8| 1.8| 1400| 51.0| 33.0| 0.65| 2.15| 58.4| 23.8| –
2200| 60.0| 5.44| 41.4| 95.2| 3.23| 5.6| 1600| 52.0| 36.1| 0.69| 2.24| 59.7| 23.3| –
13.5| 4.3| 9.9| 1800| 62.4| 5.31| 44.2| 102.1| 3.44| 6.3| 11.5| 1.9| 4.3| 1400| 51.6| 33.3| 0.65| 2.04| 58.6| 25.3| –
2200| 63.8| 5.54| 44.9| 96.8| 3.38| 5.8| 1600| 52.6| 36.4| 0.69| 2.14| 59.9| 24.6| –
18.0| 6.8| 15.7| 1800| 63.3| 5.40| 44.9| 102.6| 3.44| 6.5| 14.0| 3.0| 6.9| 1400| 52.0| 33.3| 0.64| 1.98| 58.8| 26.3| –
2200| 64.8| 5.59| 45.7| 97.3| 3.39| 5.9| 1600| 53.2| 36.4| 0.68| 2.07| 60.3| 25.7| –



50

| 9.0| 1.8| 4.2| 1800| 65.8| 5.48| 47.1| 103.9| 3.52| 6.8| ****


50

| 9.0| 0.7| 1.7| 1400| 55.2| 36.2| 0.66| 2.27| 62.9| 24.3| –
2200| 67.2| 5.65| 47.9| 98.3| 3.48| 6.3| 1600| 56.3| 39.4| 0.70| 2.41| 64.5| 23.3| –
13.5| 4.2| 9.6| 1800| 69.6| 5.59| 50.6| 105.8| 3.65| 7.0| 11.5| 1.8| 4.2| 1400| 55.7| 36.5| 0.66| 2.22| 63.3| 25.1| –
2200| 71.0| 5.73| 51.5| 99.9| 3.63| 6.4| 1600| 56.8| 39.8| 0.70| 2.36| 64.9| 24.1| –
18.0| 6.6| 15.2| 1800| 70.8| 5.65| 51.5| 106.4| 3.67| 7.2| 14.0| 2.9| 6.7| 1400| 56.3| 36.9| 0.66| 2.18| 63.7| 25.8| 1.7
2200| 72.3| 5.79| 52.5| 100.4| 3.66| 6.6| 1600| 57.4| 40.1| 0.70| 2.32| 65.3| 24.7| 1.9



60

| 9.0| 1.8| 4.1| 1800| 74.2| 5.77| 54.5| 108.2| 3.76| 7.6| ****


60

| 9.0| 0.7| 1.7| 1400| 52.7| 35.4| 0.67| 2.54| 61.3| 20.8| 3.0
2200| 75.8| 5.87| 55.8| 101.9| 3.78| 7.0| 1600| 54.0| 38.5| 0.71| 2.70| 63.2| 20.0| 3.1
13.5| 4.0| 9.3| 1800| 77.6| 5.87| 57.6| 109.9| 3.87| 7.8| 11.5| 1.8| 4.1| 1400| 53.2| 35.7| 0.67| 2.49| 61.7| 21.4| 2.8
2200| 79.3| 5.95| 59.0| 103.4| 3.91| 7.2| 1600| 54.6| 38.8| 0.71| 2.64| 63.6| 20.7| 3.0
18.0| 6.4| 14.7| 1800| 79.3| 5.94| 59.0| 110.8| 3.91| 8.1| 14.0| 2.8| 6.5| 1400| 53.7| 36.1| 0.67| 2.44| 62.1| 22.0| 2.6
2200| 81.1| 6.01| 60.6| 104.1| 3.96| 7.4| 1600| 55.1| 39.2| 0.71| 2.60| 64.0| 21.2| 2.8



70

| 9.0| 1.7| 3.9| 1800| 82.5| 6.06| 61.9| 112.5| 3.99| 8.5| ****


70

| 9.0| 1.6| 1.6| 1400| 50.2| 34.6| 0.69| 2.81| 59.8| 17.9| 3.8
2200| 83.4| 6.10| 62.6| 105.1| 4.01| 7.9| 1600| 52.3| 38.2| 0.73| 3.08| 62.8| 17.0| 4.0
13.5| 3.9| 9.0| 1800| 85.6| 6.15| 64.6| 114.0| 4.08| 8.8| 11.5| 2.6| 3.9| 1400| 50.7| 34.9| 0.69| 2.75| 60.1| 18.4| 3.5
2200| 87.5| 6.16| 66.5| 106.8| 4.16| 8.1| 1600| 52.3| 37.9| 0.72| 2.93| 62.3| 17.9| 3.8
18.0| 6.2| 14.3| 1800| 87.7| 6.22| 66.5| 115.1| 4.13| 9.1| 14.0| 3.6| 6.2| 1400| 51.2| 35.2| 0.69| 2.71| 60.4| 18.9| 3.2
2200| 89.8| 6.22| 68.6| 107.8| 4.23| 8.3| 1600| 52.8| 38.3| 0.73| 2.88| 62.6| 18.3| 3.6



80

| 9.0| 1.6| 3.8| 1800| 88.0| 6.19| 66.9| 115.3| 4.17| 9.6| ****


80

| 9.0| 0.7| 1.6| 1400| 47.2| 33.7| 0.71| 3.22| 58.2| 14.7| 4.9
2200| 90.0| 6.15| 69.0| 107.9| 4.29| 8.9| 1600| 48.9| 36.6| 0.75| 3.43| 60.7| 14.3| 5.2
13.5| 3.8| 8.7| 1800| 90.1| 6.27| 68.7| 116.3| 4.21| 9.9| 11.5| 1.6| 3.8| 1400| 47.7| 34.0| 0.71| 3.16| 58.5| 15.1| 4.5
2200| 92.2| 6.20| 71.1| 108.8| 4.36| 9.1| 1600| 49.4| 37.0| 0.75| 3.36| 60.9| 14.7| 4.8
18.0| 6.0| 13.8| 1800| 92.8| 6.34| 71.2| 117.8| 4.29| 10.2| 14.0| 2.6| 6.0| 1400| 48.2| 34.4| 0.71| 3.10| 58.7| 15.5| 4.2
2200| 95.2| 6.27| 73.8| 110.0| 4.45| 9.4| 1600| 50.0| 37.4| 0.75| 3.31| 61.2| 15.1| 4.6



90

| 9.0| 1.6| 3.7| 1800| 93.4| 6.31| 71.9| 118.1| 4.34| 10.7| ****


90

| 9.0| 0.7| 1.5| 1400| 44.2| 32.9| 0.74| 3.63| 56.6| 12.2| 6.4
2200| 95.7| 6.22| 74.5| 110.3| 4.51| 9.9| 1600| 46.2| 35.7| 0.77| 3.87| 59.4| 11.9| 6.7
13.5| 3.6| 8.4| 1800| 94.7| 6.38| 72.9| 118.7| 4.35| 11.1| 11.5| 1.6| 3.7| 1400| 44.7| 33.1| 0.74| 3.56| 56.9| 12.6| 5.7
2200| 97.0| 6.24| 75.7| 110.8| 4.55| 10.2| 1600| 46.6| 36.1| 0.77| 3.79| 59.5| 12.3| 6.2
18.0| 5.7| 13.3| 1800| 97.9| 6.46| 75.9| 120.4| 4.44| 11.4| 14.0| 2.5| 5.8| 1400| 45.7| 34.1| 0.75| 3.65| 58.2| 12.5| 5.4
2200| 100.5| 6.31| 79.0| 112.3| 4.67| 10.6| 1600| 47.1| 36.4| 0.77| 3.73| 59.8| 12.6| 6.5



100

| 9.0| 1.5| 3.5| ****







Operation not recommended

| ****


100

| 9.0| 0.6| 1.5| 1400| 41.3| 31.9| 0.77| 4.13| 55.4| 10.0| 8.1
1600| 43.3| 34.7| 0.80| 4.40| 58.3| 9.8| 8.6
13.5| 3.5| 8.1| 11.5| 1.5| 3.5| 1400| 41.7| 32.2| 0.77| 4.05| 55.5| 10.3| 7.8
1600| 43.7| 35.0| 0.80| 4.31| 58.4| 10.1| 8.4
18.0| 5.5| 12.8| 14.0| 2.4| 5.6| 1400| 42.1| 32.6| 0.77| 3.97| 55.7| 10.6| 7.4
1600| 44.2| 35.4| 0.80| 4.24| 58.6| 10.4| 8.2



110

| 9.0| 1.5| 3.4| ****


110

| 9.0| 0.6| 1.4| 1400| 38.3| 30.9| 0.81| 4.63| 54.1| 8.3| 10.1
1600| 40.4| 33.6| 0.83| 4.93| 57.2| 8.2| 10.9
13.5| 3.4| 7.8| 11.5| 1.5| 3.4| 1400| 38.8| 31.2| 0.81| 4.53| 54.2| 8.6| 9.7
1600| 40.8| 33.9| 0.83| 4.83| 57.3| 8.5| 10.5
18.0| 5.3| 12.3| 14.0| 2.3| 5.4| 1400| 39.1| 31.6| 0.81| 4.45| 54.3| 8.8| 9.3
1600| 41.2| 34.3| 0.83| 4.75| 57.4| 8.7| 10.3



120

| 9.0| 1.4| 3.3| ****


120

| 9.0| 0.6| 1.3| 1400| 33.6| 30.0| 0.90| 5.65| 52.8| 5.9| 13.0
1600| 34.3| 32.8| 0.96| 5.78| 54.0| 5.9| 13.5
13.5| 3.2| 7.5| 11.5| 1.4| 3.3| 1400| 34.0| 30.3| 0.89| 5.34| 52.2| 6.4| 12.2
1600| 34.6| 32.9| 0.95| 5.48| 53.3| 6.3| 13.1
18.0| 5.1| 11.8| 14.0| 2.2| 5.2| 1400| 34.3| 30.3| 0.88| 5.17| 51.9| 6.6| 11.3
1600| 35.0| 32.9| 0.94| 5.33| 53.2| 6.6| 12.5

3/27/2020

Compressor Section Wiring Schematics

Aurora Variable Speed Indoor Split

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
6

97P928-03A

Compressor Section Wiring Schematics cont.
Aurora Variable Speed Indoor Split

Notes

  1. Variable speed pump low voltage harness provided with Variable Speed Flow Center.
  2. Low voltage wiring CLASS 2.
  3. Communication cable routed through Ferrite Toroid four times.
  4. Compressor power cable routed through Ferrite Toroid three times.
  5. Variable speed pump power wires to connect the pump to L1 and L2 on the AXB board are provided with Variable Speed Flow Center.
  6. Wiring harness supplied with valve.

Legend

| Factory Low voltage wiring
---|---
| Factory Line voltage wiring
| Field low voltage wiring
| Field line voltage wiring
| Optional block
| DC Voltage PCB traces
| Field Installed Item
●| Junction
○| Quick connect terminal
| Wire nut
| Field wire lug
| Ground
| Relay Contacts- N.O., N.C.
| Fuse
| Color identification tape on wire.
| Thermistor
| Light  emitting diode – Green
| Relay coil
| Capacitor w/ bleed resistor
| Switch – Condensate overflow
| Switch – High pressure
| Switch – Low pressure
| Current Transducer (CT)
| Polarized connector
CC – Compressor Contactor
CO – Condensate overflow sensor
K5 – DHW pump relay
K6 – Loop pump relay
CR3 – PSC Fan Speed Relay
CR4 – PSC Fan Power Relay
CS – Compressor Solenoid
F1, F2 – Fuses
HE – Heater element
HP – High pressure switch
LP – Low pressure switch
ER1 to ER4 – Aux heat stage relays| PB1, PB2 – Power blocks
PS – Power strip
RV – Reversing Valve coil
SW1 – DIP Switch – 5 position AXB
SW1 – TEST MODE ABC Board
SW2 – DIP Switch – 8 position ABC Board
FP1, FP2 – Freeze Protection
TS – Thermal limit switch
SC – Start Contactor
SR – Start Relay
HWL – Hot water limit sensor
WCL – Water Coil Limit Sensor
---|---

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
8WaterFurnace 700R11 Indoor Split
Geothermal Heat Pump - Figure 9 Compressor Section Wiring Schematics cont.
Aurora Variable Speed Indoor Split
WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
10 Compressor Section Wiring Schematics cont.
Aurora Variable Speed Indoor Split

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
11

ABC SW2 Accessory Relay

DESCRIPTION| SW2-4| SW2-5
Cycle with Blower| ON| ON
Cycle with Compressor| OFF| OFF
Water Valve Slow Opening| ON| OFF
Cycle with Comm. T-stat Hum Cmd| OFF| ON
A X B A cc e ssory 2 D IP S e ƫ ngs

SW1-4| SW1-5| DESCRIPTION
ON| ON| Cycles with Blower
OFF| ON| Cycles with CC first stage compressor or compressor spd 1-12
ON| OFF| Cycles with CC2 second stage of compressor or comp spd 7-12
OFF| OFF| Cycles with DH from ABC board
Aurora LED Flash Codes

Slow Flash| 1 second on and 1 second off
Fast Flash| 100 miilllliseconds on and 100 miilllliseconds off
Flash Code| 100 millliiseconds on and 400 miilllliiseconds off wiith a 2 second pause before repeating
Fault LED (LED 1, Red)| Random Start Delay (Alternating Colors)
Norm al Mode| OFF| Status LED (LED1, Green)| F as t Flash
Input Fault Locko u t| Flash Code 1| Configur at ion LED (L E D 2, Yell ow )| Fast Flash
High P ress ur e Loc k out| Flash Code 2| Fault LED (LED 3, Red)| Fast Flash
Low Pressure Lockout| Flash Code 3| Configuration LED (LED 2, Yellow)
Freeze Protection- FP2| Flash Code 4| No Software O v e r id e| OF F
Freeze Protection – FP1| Flash Code 5| DIP Swiitch Overiide| Sl ow Flash
Loss of Charge| Flash Code 6| Status LED (LED 3, Green)
Condensa t e Overflow Lockout| Flash Code 7| Normall Mod e| O N
Over/Under Volltage Shutdown| Flash Code 8| Controll is Non – Functiion al| OFF
Future Use| Flash Code 9| Test Mode| Sl ow Flash
| | Lockout Actiive| Fast Flash
Fault- FP1 and FP2 Sensor Error| Flash Code 11| Dehumidifiication Mode| Flash Code 2
Future Use| Flash Code 12| Future Use| Flash Code 3
Non-Cri t i c all AXB Sen s or Error| Flash Code 13| Future Use| Flash Code 4
Critical AXB Se ns or Error| Flash Code 14| Load Shed| Flash Code 5
Ala rm – Hot Water| Flash Code 15| ESD| Flash C o de 6
Fault Variiable Spee d Pump| Flash Code 16| Future Use| Flash Code 7
Future Use| Flash Code 17| Fault LED (LED 1, Red) Cont.
Non-Criitiicall Communica t ion Er ro r| Flash Code 18| Safe Mode – Ambiient Temp Sensor| Flash Code 49
Fault – Critical Co mmunic a tion Error| Flash Code 19| Fault – Diischarge Temperature Sensor| Flash Co de 51
Allarm – Low Loop Pressure| Flash Code 21| Fault – Suction Pressure Sensor| Flash Code 52
Fault – Communication ECM Fan Motor Error| Flash Code 22| Faullt – Condensiin g Pre s sure Sen s o r| Flash Co de 53
Alarm – Home Automation 1| Flash Code 23| Fault – Low Supply Voltage| Flash Code 54
Allarm – Home Automation 2| Flash Code 24| Fault – Compre s sor Out of Envelope| F las h Code 55
Fault – EEV Error| Flash Code 25| Fault – Over Current| Flash Co de 56
Derate – Drive Temperature| Flash Code 41| Fault – Over/Under Volltage| Flash Co de 57
Derate – High Diischarge Temperature| Flash Code 42| Fault – Hiigh Drive Temperature| Flash Code 58
Derate – Low Suction Temperature| Flash Code 43| Fault – Drive Internal Error MOC/AO C| F lash C o de 59
Derate – Low Condensing Pressure| Flash Code 44| Fault – Multiiple Safe Modes| F las h Co de 61
Derate – High Condensing Pressure| Flash Code 45| EEV2 Fault – Loss of Charge| Flash Code 71
Derate – Outer Power Liimiit| Flash Code 46| EEV2 Safe Mode – Suc Temp Sensor| Flash Code 72
Safe Mode – EEV (Indoor) Communication| F las h Code 47| EEV2 Safe Mode – LAT Temp Sensor| Flash Code 73
Safe Mode – EEV (Outdoor) Communicatiion| Flash Code 48| EEV2 Safe Mode – Max Op Pressure| Flash Code 74
| EEV1 Fault – Loss of Charge| Flash Code 75
EEV1Safe Mode – Suctiion Temp Sensor| Flash Code 76
EEV1Safe Mode – LAT Temp Sensor| Flash Code 77
EEV1 Safe Mode – Max Op Pressure| Flash Code 78

Compressor Section Wiring Schematics cont.
Aurora Variable Speed Indoor Split with UPC

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
12

Compressor Section Wiring Schematics cont.
Aurora Variable Speed Indoor Split with UPC

Notes

  1. Variable speed pump low voltage harness provided with Variable Speed Flow Center.
  2. Low voltage wiring CLASS 2.
  3. Communication cable routed through Ferrite Toroid four times.
  4. Compressor power cable routed through Ferrite Toroid three times.
  5. Variable speed pump power wires to connect the pump to L1 and L2 on the AXB board are provided with Variable Speed Flow Center.
  6. Wiring harness supplied with valve.

| Factory Low voltage wiring
---|---
| Factory Line voltage wiring
| Field low voltage wiring
| Field line voltage wiring
| Optional block
| DC Voltage PCB traces
| Field Installed Item
●| Junction
○| Quick connect terminal
| Wire nut
| Field wire lug
| Ground
| Relay Contacts- N.O., N.C.
| Fuse
| Color identification tape on wire.
| Thermistor
| Light  emitting diode – Green
| Relay coil
| Capacitor w/ bleed resistor
| Switch – Condensate overflow
| Switch – High pressure
| Switch – Low pressure
| Current Transducer (CT)
| Polarized connector
CC – Compressor Contactor
CO – Condensate overflow sensor
K5 – DHW pump relay
K6 – Loop pump relay
CR3 – PSC Fan Speed Relay
CR4 – PSC Fan Power Relay
CS – Compressor Solenoid
F1, F2 – Fuses
HE – Heater element
HP – High pressure switch
LP – Low pressure switch
ER1 to ER4 – Aux heat stage relays| PB1, PB2 – Power blocks
PS – Power strip
RV – Reversing Valve coil
SW1 – DIP Switch – 5 position AXB
SW1 – TEST MODE ABC Board
SW2 – DIP Switch – 8 position ABC Board
FP1, FP2 – Freeze Protection
TS – Thermal limit switch
SC – Start Contactor
SR – Start Relay
HWL – Hot water limit sensor
WCL – Water Coil Limit Sensor
---|---

Air Handler Wiring Schematics

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
15

Air Handler Wiring Schematics cont.

7 SeriesAir Handler Air Flow

Model| Max ESP| Speed 1| Speed 2| Speed 3| Speed 4| Speed 5| Speed 6| Speed 7| Speed 8| Speed 9| Speed 10| Speed 11| Speed 12
033| 0.75| 250| 400 G| 550 L| 650| 750| 850| 1000| 1150| 1250 H| 1350 Aux| 1450| 1600
042| 0.75| 250| 450 G| 650 L| 800| 950| 1050| 1200| 1350| 1450| 1600 H| 1750 Aux| 1850
050| 0.75| 300| 550 G| 800 L| 1000| 1150| 1300| 1450| 1600| 1750| 1900 H| 2050 Aux| 2200
**VS Compressor Speed| | | | 1-2| 3-4| | 5-6| 7-8| | 9-10| 11-12| |

** VS Compressor speed is given for the factory default cfm se ngs. When the cfm default se ngs are changed it will change the rela onship to the compressor speed that is shown in the table. In cooling mode compressor speeds 10-12 are only available when SuperBoost mode is selected at the thermostat. Factory se ngs are at recommended G, L , H and Aux posi ons
“G” may be located anywhere within the air ow table.
“L” seng should be located within the boldface CFM range
“H” seng MUST be located within the shaded CFM range
“Aux” seng MUST be equal to or greater than “H” seng
CFM is controlled within 5% up to the maximum ESP

Communicating Thermostat will connect to the COMM STAT (C R + -)
power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.
Communicating Thermostat

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
16

Note: On the AID Tool Configure Aurora Screen, confirm the AHB is added and communicating.

Notes
1 – To operate in 208V mode replace the blue transformer wire connected to PB1-L2 with red transformer wire.
2 – Low voltage wiring CLASS 2.
3 – DIP switch 1 on SW1 must be set in the OFF position.
Air Handler Wiring Schematics cont.

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
17

7 SeriesAir Handler Air Flow

Model| Max ESP| Speed 1| Speed 2| Speed 3| Speed 4| Speed 5| Speed 6| Speed 7| Speed 8| Speed 9| Speed 10| Speed 11| Speed 12
033| 0.75| 250| 400 G| 550 L| 650| 750| 850| 1000| 1150| 1250 H| 1350 Aux| 1450| 1600
042| 0.75| 250| 450 G| 650 L| 800| 950| 1050| 1200| 1350| 1450| 1600 H| 1750 Aux| 1850
050| 0.75| 300| 550 G| 800 L| 1000| 1150| 1300| 1450| 1600| 1750| 1900 H| 2050 Aux| 2200
**VS Compressor Speed| | | | 1-2| 3-4| | 5-6| 7-8| | 9-10| 11-12| |

11/29/2018

** VS Compressor speed is given for the factory default cfm sengs. When the cfm default sengs are changed it will change the relaonship to the compressor speed that is shown in the table. Incooling mode compressor speeds 10-12 are only available when SuperBoost mode is selected at the thermostat. Factory sengs are at recommended G, L , H and Aux posions
“G” may be located anywhere within the airow table.
“L” seng should be located within the boldface CFM range
“H” seng MUST be located within the shaded CFM range
“Aux” seng MUST be equal to or greater than
“H” seng CFM is controlled within 5% up to the maximum ESP

Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.
Communicating Thermostat

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
18

Note: On the AID Tool Configure Aurora Screen, confirm the AHB is added and communicating.
Notes
1 – To operate in 208V mode replace the blue transformer wire connected to PB1-L2 with red transformer wire.
2 – Low voltage wiring CLASS 2.
3 – DIP switch 1 on SW1 must be set in the OFF position.
Dual Power Supply Connections
If two separate circuits are used to supply power to the auxiliary heat kit, the Installer will need to verify that each leg of the auxiliary heat circuit breakers are wired from the power supply correctly in order for the electric heat kit to operate properly. This can be done by measuring the supply side voltage of the auxiliary heat circuit breakers. Put a voltmeter on the L2 side of Circuit Breaker One and on the L2 side of Circuit Breaker Two. The voltmeter should read approximately 0 volts. If the meter reads high voltage, the auxiliary heat breakers need to be rewired so that breakers in the auxiliary heat kit match the wiring of the Disconnect Panel breakers. Meaning, L1 and L2 from one breaker in the disconnect panel must L1 and L2 from one breaker in the disconnect panel must connect to L1 and L2 at one of the auxiliary heat circuit breakers and L1 and L2 from the other breaker in the disconnect panel must connect to L1 and L2 of the other auxiliary heat circuit breaker, making sure that the L1 and L2 from each disconnect breaker matches the L1 and L2 at each of the auxiliary heat breakers.
WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
19

7 SeriesAir Handler Air Flow

Model| Max ESP| Speed 1| Speed 2| Speed 3| Speed 4| Speed 5| Speed 6| Speed 7| Speed 8| Speed 9| Speed 10| Speed 11| Speed 12
033| 0.75| 250| 400 G| 550 L| 650| 750| 850| 1000| 1150| 1250 H| 1350 Aux| 1450| 1600
042| 0.75| 250| 450 G| 650 L| 800| 950| 1050| 1200| 1350| 1450| 1600 H| 1750 Aux| 1850
050| 0.75| 300| 550 G| 800 L| 1000| 1150| 1300| 1450| 1600| 1750| 1900 H| 2050 Aux| 2200
**VS Compressor Speed| | | | 1-2| 3-4| | 5-6| 7-8| | 9-10| 11-12| |

11/29/2018

** VS Compressor speed is given for the factory default cfm sengs. When the cfm default se ngs are changed it will change the rela onship to the compressor speed that is shown in the table. In cooling mode compressor speeds 10-12 are only available when SuperBoost mode is selected at the thermostat. Factory sengs are at recommended G, L , H and Aux posi ons
“G” may be located anywhere within the air ow table.
“L” seng should be located within the boldface CFM range
“H” seng MUST be located within the shaded CFM range
“Aux” seng MUST be equal to or greater than
“H” seng CFM is controlled within 5% up to the maximum ESP

Dual Power Supply Connections
If two separate circuits are used to supply power to the auxiliary heat kit, the Installer will need to verify that each leg of the auxiliary heat circuit breakers are wired from the power supply correctly in order for the electric heat kit to operate properly. This can be done by measuring the supply side voltage of the auxiliary heat circuit breakers. Put a voltmeter on the L2 side of Circuit Breaker One and on the L2 side of Circuit Breaker Two. The voltmeter should read approximately 0 volts. If the meter reads high voltage, the auxiliary heat breakers need to be rewired so that breakers in the auxiliary heat kit match the wiring of the Disconnect Panel breakers. Meaning, Ll and L2 from one breaker in the disconnect panel must connect to 1:1 and L2 at one of the auxiliary heat circuit breakers and Ll and L2 from the other breaker in the disconnect panel must connect to 1:1 and L2 of the other auxiliary heat circuit breaker, making sure that the Ll and L2 from each disconnect breaker matches the 12I and L2 at each of the auxiliary heat breakers.
Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.
Communicating Thermostat

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
20

Note: On the AID Tool Configure Aurora Screen, confirm the AHB is added and communicating.
Notes
1 – To operate in 208V mode replace the blue transformer wire connected to PB1-L2 with red transformer wire.
2 – Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.
3 – DIP switch 1 on SW1 must be set in the OFF position.
4- Low voltage wiring CLASS 2
Air Handler Wiring Schematics cont.
Variable Speed Pump (UPMXL 25-124)

Variable Speed Flow Center With
1 – UPMXL 25-124 Pump

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
23

Variable Speed Flow Center With 2 – UPMXL 25-124 Pumps

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
24

Compressor Section Wiring Schematics cont.
Aurora UPC

WaterFurnace 700R11 Indoor Split Geothermal Heat Pump - Figure
25

ZS Sensor Information
Zone Sensors can be wired in daisy chain as show or in a star or hybrid configuration. Maximum of 5 sensors per UPC. Maximum allowable load 210mA. See the UPC install manual for possible sensor combinations.
Each ZS sensor must have a unique address, but the addresses do not need to be sequential. Use the DIP switches on the back of the ZS sensor to set an address from 0 to 4. (0 is the factory default.) Each DIP switch has the value shown in the figure to the left. Turn on as many DIP switches as you need so that their total value equals the address.

Notes
1. Use DIP Switches 5 – 8 to change communication protocol and DIP switches 1 – 2 to change BACnet baud rate

Legend

Fact ory Lo w Vo lt age Wiring
Field Low V olta ge Wiring
RJ45 Connector

Engineering Guide Specifications

General
Furnish and install WaterFurnace Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow. The reverse cycle heating/cooling units shall be either suspended type with horizontal air inlet and discharge or floor mounted type with horizontal air inlet and vertical upflow, or downflow air discharge. Units shall be AHRI/ISO 13256-1 certified and listed by a nationally recognized safety-testing laboratory or agency, such as ETL Testing Laboratory. Each unit shall be computer runtested at the factory with conditioned water and operation verified to catalog data. Each unit shall be mounted on a pallet and shipped in a corrugated box or stretch-wrapped. The units shall be designed to operate with entering liquid temperature between 20°F and 120°F [-6.7°C and 48.9°C].
Casing and Cabinet
The cabinet shall be fabricated from heavy-gauge galvanized steel and finished with corrosion-resistant powder coating. This corrosion protection system shall meet the stringent 1000 hour salt spray test per ASTM B117. The interior shall be insulated with 1/2-inch thick, multi-density, cleanable aluminum foil coated glass fiber with edges sealed or tucked under flanges to prevent the introduction of glass fibers into the discharge air. Standard cabinet panel insulation must meet NFPA 90A requirements, air erosion and mold growth limits of UL- 181, stringent fungal resistance test per ASTM-C1071 and ASTM G21, and shall meet zero level bacteria growth per ASTM G22. Unit insulation must meet these stringent requirements or unit(s) will not be accepted.
Three compressor compartment access panels shall be ‘liftout’ removable. The front access panel shall be lift-out to provide easy access to the electrical/compressor section. The control box shall be hinged and removable to allow easy access to the compressor. The internal component layout shall provide for service access from the front side for restricted installations.
The air handler shall be provided with two large access panels and shall be removable with supply and return ductwork in place. The internal components layout shall provide for major service with the unit in-place for restricted access installations. The blower assembly access shall be slide-out serviceable via a ‘works-in-a-drawer’ design. The cabinet shall be convertible to horizontal or downfl ow applications by reconfi guring the cabinet using only a nut driver. The unit shall be ‘zero clearance’ approved on any of its external surfaces. A duct collar shall be provided for fi eld installation on the supply air opening. The air handler shall be supplied with an integral return air fi lter rack (air fi lter is fi eld supplied).

Refrigerant Circuit
All units shall contain a sealed refrigerant circuit including a hermetic motor-compressor, oil seperator, electronic expansion valve, reversing valve, coaxial tube water-torefrigerant heat exchanger, optional hot water generator coil, and service ports. Compressors shall be high-efficiency variable speed scroll type designed for heat pump duty and mounted on double vibration isolators. Compressor motors shall be permanent magnet type. All air handlers shall provide an electronic expansion valve, enhanced fi n and tube air-to- refrigerant heat exchanger of the “A” coil design. The fi nned tube coil shall be sized for low-face velocity and constructed of lanced aluminum fi ns bonded to aluminum tubes in a staggered pattern. The coil shall include a composite drain pan.
Both electronic expansion valves shall provide proper superheat over the entire liquid temperature range with minimal “hunting.”
Refrigerant to air heat exchangers shall utilize aluminum tube construction rated to withstand 600 psig (4135 kPa) refrigerant working pressure. Refrigerant to water heat exchangers shall be of copper (cupronickel optional) inner water tube and steel refrigerant outer tube design, rated to withstand 600 psig (4135 kPa) working refrigerant pressure and 450 psig (3101 kPa) working water pressure.
All units shall have the source coaxial tube refrigerant-to water heat exchanger and the optional hot water generator coil coated with ThermaShield insulation. Refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures.
Blower Motor and Assembly
The blower shall be an oversized direct drive centrifugal type with a dynamically balanced wheel. The housing and wheel shall be designed for quiet low outlet velocity operation and of galvanized or galvalume steel construction. Tight blower housing geometry shall not be permitted. The blower housing shall be removable from the cabinet without disconnecting the supply air ductwork for servicing of the blower motor through a ‘works-in-a-drawer’ design. The high effi ciency blower motor shall be a variable speed ECM type. The blower motor shall be isolated from the housing by rubber grommets. The motor shall be perma- nently lubricated ball bearings and have thermal overload protection.
Electrical
A control box shall be located within the compressor and air handler compartments (air handler shall contain a 100VA transformer) and the compressor compartment shall contain a 24 Volt activated, 2 pole compressor contactor, circuit breakers for protecting loop pumps and compressor drive, removable terminal block for thermostat wiring, variable speed compressor drive and solid-state controller for complete unit operation. Electromechanical operation WILL NOT be accepted. Units shall be name-plated for use with time delay fuses or HACR circuit breakers. Unit controls shall be communicating type and provide heating or cooling as required by the remote thermostat/sensor. An Aurora Advanced VS Control, a microprocessor based controller, interfaces with a digital communicating thermostat to monitor and control unit operation shall be provided. The control shall provide operational sequencing, blower speed

Engineering Guide Specifi cations cont.

control, blower failure, high and low pressure switch monitoring, freeze detection, hot water limit thermistor sensing, condensate overfl ow sensing, auxiliary heat staging, lockout mode control, hot water and loop pump control, LED status and fault indicators, fault memory, fi eld selectable options, compressor envelope management, energy consumption measurement, and accessory output. The fault signals shall be plain English text and displayed on the thermostat. The Aurora Advanced VS Control shall also feature an On Peak input signal for utility controlled demand programs, intelligent hot water generation with user adjustable temperature limit, loop pump linking for multiple units driving a common fl ow center and up to two optional home automation inputs to drive dedicated alarms for sump pump, security system, and smoke/CO2 or dirty air fi lter sensors. As standard, the energy, performance and refrigerant monitoring kits will provide real time data including total power consumption, entering and leaving water temperature, fl owrate and heat of extraction/rejection capacity data, refrigerant superheat and subcooling. The capability for communicating to advanced zoning packages with up to six zones shall also be provided with complete fault and information display on the zoning MasterStat.
A detachable terminal block with screw terminals will be provided for field control wiring. All units shall have knockouts for entrance of low and line voltage wiring. The blower motor and control box shall be harness plug wired for easy removal.
The air handler shall contain integral circuit breakers on all units employing 15 kW or 20 kW electric heat. The 100VA transformer shall be protected by internal circuit breaker.
An Aurora Interface Diagnostic (AID) Tool shall communicate with the Aurora control allowing quick and easy access to setup, monitoring, and troubleshooting of any Aurora control. The device shall include the features of ECM airflow setup, VS pump and modulating water valve setup, fault description and history, manual operation capability, sensor readings, timings, and other diagnostic tools.
Option: An Aurora Unitary Protocol Converter (UPC) shall be included that communicates directly with the Aurora Heat Pump Control and allows access/control of a variety of internal Aurora heat pump operations such as sensors, relay operation, faults and other information. In turn, the UPC shall convert the internal Aurora Modbus protocol to BACnet MS/TP protocol for communication over a HAS system. Additional individual unit configuration items such as ECM fan speeds or freeze detection settings shall be directly available over the HAS without the need for access to the actual heat pump.
Piping
Supply and return water connections shall be 1 in. [25.4 mm] FPT brass swivel fittings, which provide a union and eliminate the need for pipe wrenches and sealants when making field connections. The optional hot water generator shall have sweat type connections. All source water piping shall be insulated to prevent condensation at low liquid temperatures. Refrigeration connections shall be made using sweat copper joints. The air handler condensate connections shall be a 3/4 in. NPT.
Options and Accessories
Cupronickel Heat Exchanger
An optional cupronickel water-to-refrigerant heat exchanger shall be provided.
Hot Water Generator
An optional ThermaShield coated heat reclaiming hot water generator coil of vented double-wall copper construction suitable for potable water shall be provided. The coil and hot water circulating pump shall be factory mounted inside the unit with integral electronic high limit temperature monitoring and external on/off switch. Hot water set point is selectable through the AID Tool.
Thermostat (field-installed)
A communicating auto-changeover electronic digital thermostat shall be provided. The thermostat shall offer variable speed heating and cooling staging with precise temperature control. An OFF-HEAT-AUTO-COOL-EMERG system switch, OFF-AUTO-INTERMITTENT blower switch, and indicating display shall be provided. The thermostat shall display in °F or °C. The thermostat shall provide real time energy consumption data of the unit.
Color Touchscreen Thermostat (field-installed)
A color touchscreen communicating auto-changeover electronic digital thermostat shall be provided. The thermostat shall offer variable speed heating and cooling staging with precise temperature control. An OFF-HEAT- AUTOCOOL-EMERG system switch, OFF-AUTO-INTERMITTENT blower switch, and indicating display shall be provided. The thermostat shall display in °F or °C. The thermostat shall provide real time and historical energy consumption data of the unit.
Earth Loop Flow Center (field-installed)
A self-contained module shall provide all liquid flow, fill and connection requirements for ground source closed loop systems up to 20 gpm. The pumps shall be wired to a power block located in the nearest unit. The heat pump units shall contain low voltage pump linking control so that two units may share one flow center.

Revision Guide

Pages: Description: Date: By:
Misc. Remove EEV, new part number revision JM
10 Updated line set length 12-Dec-20 MA
All Document created 26-Feb-20 MA

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD2703SNA 01/23WaterFurnace Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals