Danfoss VXe Solo Indirect Fully Insulated District Heating Substation User Manual
- June 9, 2024
- Danfoss
Table of Contents
VXe Solo Indirect Fully Insulated District Heating Substation
Instructions for installation and use
Indirect, fully insulated district heating substation VXe Solo
District heating substation for indirect heating and connection pipes for
domestic hot water.
VXe Solo
Fully insulated for very low heat losses.
www.danfoss.com
Instructions for installation and use
VXe Solo
VXe Solo H ECL 310/A230
VXe Solo HWP ECL 310/A337
VXe Solo HWS ECL 310/A237
VXe Solo H OP ECL 310
1.0 Content
2.0 Installation instructions, safety and
handling……………………………………………………………………………………………………………………………………………3 3.0 Getting
started – Quick guide for easy start-
up…………………………………………………………………………………………………………………………………………5 4.0 Main components /
Connections ………………………………………………………………………………………………………………………………………………………………..7
5.0 Diagram, Dimensional sketch,
Example………………………………………………………………………………………………………………………………………………….. 10 6.0
General, Mounting of heat meter and safety
valves……………………………………………………………………………………………………………………………… 15 7.0 Filling the
system with water
……………………………………………………………………………………………………………………………………………………………………. 16 8.0
Electrical
connections…………………………………………………………………………………………………………………………………………………………………………………
17 9.0 Adjustmend and commissioning
…………………………………………………………………………………………………………………………………………………………….. 18 10.0 Heating
circuit, Danfoss ECL 310
automatics…………………………………………………………………………………………………………………………………………. 19 11.0
Control of heating
circuit…………………………………………………………………………………………………………………………………………………………………………… 20
12.0 Heating circuit, pump
………………………………………………………………………………………………………………………………………………………………………………… 22 13.0
Domestic hot water, Cylinder circuit
……………………………………………………………………………………………………………………………………………………….. 24 14.0
Maintenance / Supervision
……………………………………………………………………………………………………………………………………………………………………….. 27 15.0
Troubleshooting
…………………………………………………………………………………………………………………………………………………………………………………………. 29
16.0 EU Declaration of
conformity……………………………………………………………………………………………………………………………………………………………………. 32
17.0 Commissioning
Certificate………………………………………………………………………………………………………………………………………………………………………… 34
18.0 Guidelines for water quality in Danfoss brazed heat
exchangers……………………………………………………………………………………………………. 35
2 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
2. INSTALLATION INSTRUCTIONS, SAFETY AND HANDLING
Instructions Please read these instructions carefully before installing and
comissioning this substation. The manufacturer accepts no liability for loss
or damage resulting from failure to comply with these instructions for use.
Read and follow these instructions carefully to prevent the risk of physical
injury and/or damage to peroperty. Exceeding the recommended operating
parameters considerably increases the risk of personal injury and/or damage to
property. Installation, commissioning and maintenance must be carried out by
qualified and authorized personnel in compliance with the local safety
regulations.
Once the station has been installed and is operating, there is normally no
need to alter the settings or other functions. The district heating substation
is very reliable and easy to operate.
Energy source The substation is primarily designed for connection to district
heating. Alternative energy sources can be used if the operating conditions
are equivalent to district heating at all times.
Application The substation is designed only to operate with water and other
heating media may not be used. The substation is to be connected to the
household piping in a frost-free room, where the temperature does not exceed
50 °C and the relative humidity is not higher than 80%. The substation must no
be covered, bricked in or otherwise cut off from access.
Choise of materials Only use materials, that comply with local regulations.
Corrosion protection
The risk of equipment corrosion increases considerably if recommended
permissible chloride compounds are exceeded. All pipes are made of min. AISI
304 (heating) and min. AISI 316 (domestic water) stainless steel as well as
brass. Components for domestic water, however, primarily in dezincification-
resistant brass. Heat exchangers are made of stainless steel and are copper-
soldered or steel-soldered. Surfaces in contact with water can be subject to
two problems, limescale formation and corrosion. The nature of the water will
be of great importance in this context, where the pH value, chlorides, gases,
etc., have a decisive effect on how much lime is deposited and how aggressive
the water is. The temperature also has a great influence in this context. For
example the corrosion rate increases by a factor of 2 to 3 for every 10° C
temperature rise. With knowledge of the chemical water composition and
operating conditions of a heating system, the risk of scaling and corrosion
can be assessed. Based on that, recommendations can be made to avoid scaling
and/or corrosion problems in the components.
See item 18, page 35 for more detailed Guidelines for Water Quality in Danfoss
brazed heat exchangers and recommended Chloride concentration to avoid Stress
Corrosion Cracking.
Safety valve(s) Installation of safety valve(s) must always be in compliance
with local regulations.
Noise level. 55 dB.
Storage Before installation, the units must be stored in a dry, heated (i.e.
frostfree) room. (Relative humidity max. 80% and storage temperature 5-70 °C).
The units must not be stacked higher than the limit at the factory (max. 8
layers) Units supplied in cardboard packaging must be lifted using the handles
incorporated in the packaging. Units must be placed on pallets for
transport/moving across large distances.
As far as possible, do not lift the substation by the pipes. Lifting by the
pipes may cause leaks. REMEMBER to retighten.
Connection It must be possible to cut off all energy sources to the unit –
including electrical connections – at all times. The unit must be connected to
an electrical equalizer connection.
Warning! Hot surfaces Parts of the substation may be very hot and can cause
burn injuries. Be very careful when you are in the immediate vicinity of the
substation.
Warning of high pressure and high temperature The maximum supply temperature
in the district heating network can be up to 120°C and the operating pressure
can be up to 16 bar. This may result in a risk of scalding from touching the
substation and from outflow of the medium (water/steam). Exceeding the
substation design data and operating parameters for pressure and temperature
carries an appreciable risk of personal injury and/or damage to property.
Emergencies In the event of fire, leaks or other hazards, immediately shut off
all sources of energy to the substation, if possible and call for appropriate
assistance. If the domestic hot water is discoloured or malodorous, shut off
all ball valves on the substation, notify all users and call for professional
assistance immediately.
Warning of damage during transport On reception of the substation, and before
installing it, check for any evidence of damage during transport. The
substation must be handled and moved with the greatest care and attention.
IMPORTANT – Tightening of connections Before adding water to the system, ALL
pipe connections MUST be retightened, as vibrations during transport may have
caused leaks. Once the substation has been filled and the system has been put
into operation, ALL pipe connections MUST be tightened once more. (Do not
overtighten! – See page 15, Test and Connections)
Handling We recommend that you wear suitable safety footwear while handling
and installing the substation.
NOTE: Interventions/rework on our components results in loss of warranty.
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 3
Instructions for installation and use
VXe Solo
2. INSTALLATION INSTRUCTIONS, SAFETY AND HANDLING
Reach All products of the Akva Lux II Triiiple series comply with the
provisions of the REACH regulation. We are therefore obliged to inform our
customers about the presence of substances according to the SVHC candidate
list, if they are present. We hereby inform you: This product contains brass
parts containing lead (CAS 7439-92-1) in a concentration above 1% (w/w).
Potential equalization / grounding
Equipotential bonding is understood as all measures for eliminating electri-
cal potential differences (contact voltages), which can occur between eg two
pipelines. Equipotential bonding is an important measure for protec-tion
against electric shock. Equipotential bonding reduces corrosion in the heat
exchanger, instantaneous water heaters, district heating stations and plumbing
installations. Equipotential bonding should be in accordance with the
provisions 60364-4-41: 2007 and IEC 60364-5-54: 2011. Binding point is marked
with a grounding symbol on the bottom right corner of the mounting plate and
there is a hole in the mounting plate and a label with grounding symbol.
Disposal Dispose of the packaging in accordance with the local regulations for
disposal of used packaging materials.
The substation is made of materials that cannot be disposed of together with
household waste. Close all energy sources and disconnect all connection pipes.
Disconnect and dismantle the product for disposal in accordance with the
applicable local regulations for the disposal of the individual components.
4 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
3. GETTING STARTED – QUICK GUIDE FOR EASY START-UP
Mounting
Connect the substation to the household piping in accordance with the
labelling at the bottom and/or in accordance with the instructions in this
manual.
GETTING STARTED is a quick guide and some details in connection with
installation and commissioning may require additional information, which can
be found elsewhere in this instruction manual.
GETTING STARTED VXe Solo 1. Mount the substationon a solid wall using two
sturdy bolts (max. 8 mm), screws, expansion bolts or similar. 2. Tighten all
pipe connections, as they may have loosened during transport and handling. 3.
Mount the district heating meter (see page 15. 4. On systems that feature a
safety valve, establish a drain connection in compliance with the applicable
legislation. 5. Fill the heat exchanger / the system with water according to
the instructions on page 16. 6. Open the ball valve for the HE supply and
return flow and heat up the system. 7. Check the substation and the household
piping thoroughly for leaks. 8. Pressure test the entire system for leaks in
accordance with the applicable regulations. 9. Connect pump and automatic
components, if any, to the electricity supply, but do not switch on the power.
10. Heat the system and vent the radiator circuit/heating side thoroughly on
the radiators and the air valve, if any. 11. Connection Now switch on the pump
and automatic components, if any. 12. Finish by adjusting the substation in
accordance with the instruction manuals and remember to fill out the
Commissioning Certificate page 34.
Primary
Secondary
DHW
Note! Heating and cooling the substation may cause leaks. Therefore it may be
necessary to retighten the connections in the period after commissioning.
Note! Never lift the station by its front insulation cover!
DH supply DH return HE return HE supply Cylinder supply Cylinder return
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 5
Instructions for installation and use
VXe Solo
3. GETTING STARTED – QUICK GUIDE FOR EASY START-UP
Start-up: See page 5 ” Getting started”
Diagram examples: See page 11 – 14
Main components. See page 7 – 10
Mounting / Mounting of heat meter: See page 15
Safety valves: See page 15
Electrical connection: See page 17 Outdoor sensor: Connect to terminal block U
Filling the system with water: See page 16
Commissioning: See page 18-26
Reading of meter: Consumption and actual DH temperatures can be read on the
meter display, placed under the ECL controller.
Temperatures: To be read on thermometers (Pos. no. 13)
Pressure: To be read on manometer (Pos. no. 15)
Connections: Pos. no’s 7A (DH), 7B (HE), 7C (DHW)
U
Meter display
15
13
7A
7B
7C
6 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
4. MAIN COMPONENTS / CONNECTION- VXE H SOLO 310/A237
1 Plate heat exchanger HE, with insulation 5 Strainer 7 Ball valve 8 Circulation pump HE 11 Safety valve HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat meter ¾” x 110 mm 25 Controller Danfoss ECL310/A230 29 Danfoss actuator AMV 30 Flow controller with integrated control valve AVQM —————————————————————————Option: 54 Safety thermostat, Jumo AT
25 17
1 5
23 29
Accessories available as extra equipment (mounting on site)
KFE tap – Code No. 145H3717 For filling and draining 1/4″.
30 23
13
7
8 15 24 24
16
11 14
DH supply DH return HE return HE supply
Primary
Secondary
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 7
Instructions for installation and use
VXe Solo
4. MAIN COMPONENTS / CONNECTION- VXE SOLO HWP ECL 310/A337
1 Plate heat exchanger HE, with insulation
4 Differential pressure controller
and flow limiter AVPB-F
5 Strainer
7A Ball valve ¾ ET/ET 120 mm for
thermometer/manometer
7B Ball valve ¾ IT/ET 120 mm for
thermometer
8 Circulation pump, HE
11 Safety valve HE, 3 bar ½”
13 Thermometer
17
14 Pocket for pressure gauge
15 Manometer
16 Expansion vessel 12 l
23 Sensor pocket for heat meter
24 Fitting piece for heat meter
3/4″ x 110 mm
25 Controller Danfoss ECL310/A337
29 Danfoss actuator AMV
30 Two-way valve VS2
————————————————–
Option:
54 Safety thermostat, Jumo AT
24
Accessories available as extra equipment (mounting on site)
Thermostatic valve RAVK/VMA for DHW Code No. 144B2021
25
1
23
5 29 30 23 13
16
4
8 15 15 24
11
14
7B
7A
7B
DH supply DH return HE return HE supply Cylinder supply Cylinder return
Primary
Secondary
DHW
54
8 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
4. MAIN COMPONENTS / CONNECTION- VXE SOLO HWS ECL 310/A337
1 Plate heat exchanger HE, with insulation 5 Strainer 6 Non-return valve 7
Ball valve 8A Circulation pump, HE 8B Circulation pump, cylinder 11 Safety
valve HE, 3 bar ½” 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16
Expansion vessel 12 l 23 Sensor pocket for heat meter 24 Fitting piece for
heat meter
3/4″ x 110 mm 25 Controller Danfoss ECL310/A337 29 Danfoss actuator AMV 30
Danfoss flow controller with integrated control valve AVQM
————————————————————————————–Option: 54 Safety thermostat, Jumo AT
Accessories available as extra equipment (mounting on site)
KFE tap – Code No. 145H3717 For filling and draining 1/4″
Thermostatic valve RAVK/VMA for DHW Code No. 144B2021
16 17
25
1 54 1
5 29 15
6 30 8A 2323 24
13 7
6
8B 13
1114 5
DH supply DH return HE return HE supply Cylinder supply Cylinder return
PLEASE NOTE! As an option VXe Solo HWS can be supplied with Danfoss flow controller with integrated control valve AHQM instead of AVQM.
Primary
Secondary
DHW
16 25
54 1
5 29 15
6 8A 23 30 23 24
13 7
6
8B 13
11 5 14 14
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 9
Instructions for installation and use
VXe Solo
4. MAIN COMPONENTS / CONNECTION – VXE H OP ECL 310
1 Plate heat exchanger HE 5 Strainer 7 Ball valve 11 Safety valve HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Connection for expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat meter ¾” x 110 mm 25 Controller Danfoss ECL310/A230 26 Outdoor sensor, ESMT 27 Sensor, ESMC 29 Danfoss actuator AMV 30 Flow controller with integrated control valve AVQM
25 17
1
29 23 55
Accessories available as extra equipment (mounting on site)
KFE tap – Code No. 145H3717 For filling and draining 1/4″.
VXe Solo H OP
Code No.
Type 1, Cover
145F0620
Type 2, Cover
145F4438
Type 2, Cover, STW*
145F4454
*Safety function = AMV13 / Jumo Safety Thermostat
5
3023 23 13
7
30
248 24 16 24
11 11
14
DH supply DH return HE return HE supply
Primary
Secondary
10 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
5. DIAGRAM & DIMENSIONAL SKETCH, EXAMPLE – VXE SOLO H ECL310/A230
1 Plate heat exchanger HE 5 Strainer 7 Ball valve 8 Circulation pump HE 11 Safety valve HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat meter ¾” x 110 mm 25 Controller Danfoss ECL310/A230 26 Outdoor sensor , ESMT
27 Sensor, ESMC 29 Actuator AMV 30 Flow controller with integrated control
valve AVQM —————————————–Option:
Safety thermostat, Jumo AT
DH Supply
DH Return
1
2
3
4
A
B
785 660
C
D 65 100 80 80 550
E
Connections: 1. District heating (DH) supply 2. District heating (DH) return
3. Heating (HE) return 4. Heating (HE) supply
F
1
2
3
AQ373475147162en-010102
55 4
HE Supply
HE Return
5
6
7
8
POS.
1
2
A
3
4
5
6 7 8 9 10
B 11
12 13 14 15 16
17
18
C
19 20
21
22 23
24 25
315
26 27
D
28 29
30 31 32
33
34
E
35
36
General tolerance accuracy, measurements without tolerance:
Projection
Scale
Size
Material
37
ISO 2768 – mK
38
Weight
58.006 kg
1:6
A3
Danfoss Standard
39
Replace
Design
17-09-2020
JJ
Designation
40
VXe Solo
41
Approval
42
Danfoss Redan A/S
F 43
Confidential: Property of Danfoss Redan A/S, Nordborg, Denmark. Not to be handed over to, copied or used by third party. Two- or three dimensional reproduction of contents to be authorized by Danfoss Redan A/S.
No. 145F4440 Rev.
44
Sheet 1 / 1
45
5
6
7
8
46
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 11 47 48
49
50 51
Instructions for installation and use
VXe Solo
5. DIAGRAM & DIMENSIONAL SKETCH, EXAMPLE – VXE SOLO HWP ECL 310/A337
Cylinder
Supply limit Cylinder Supply
1 Plate heat exchanger HE, with insulation
4 Differential pressure controller and flow limiter AVPB-F
5 Strainer 7A Ball valve ¾ ET/ET 120 mm for
thermometer/manometer 7B Ball valve ¾ IT/ET 120 mm for
thermometer 8 Circulation pump, HE
11 Safety valve HE, 3 bar ½”
13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel
12 l 23 Sensor pocket for heat meter 24 Fitting piece for heat meter
3/4″ x 110 mm 25 Controller Danfoss ECL310/A337 26 Outdoor sensor, ESMT 27
Sensor Danfoss, ESMC 29 Danfoss actuator AMV 30 Two-way valve VS2
—————————————–Option: 54 Safety thermostat, Jumo AT
Cylinder Return
DH Supply
DH Return
HE Supply
HE Return
1
2
3
4
A
B
C
D 65 100 80 80 80 80 550
E
Connections:
1. District heating (DH) supply
2. District heating (DH) return
3. Heating (HE) return
4. Heating (HE) supply
F
5. Cylinder supply 6. Cylinder return
1
2
3
4
12 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
785 660
5
6
7
8
POS.
Q
1
2
A
3
4
5
6 7 8 9 10
B 11
12
13
14 15 16
17 18
C 19
20 21 22 23
24
25 26
55 315
27
D 28
29
30
31
3
32
33 34 35
E 36
General tolerance accuracy, measurements without tolerance:
ISO 2768 – mK
Weight
61.068 kg
Replace
Design
02-11-2016
JJ
Approval
Projection
Confidential: Property of Danfoss Redan A/S, Nordborg, Denmark. Not to be handed over to, copied or used by third party. Two- or three dimensional reproduction of contents to be authorized by Danfoss Redan A/S.
5
6
37
Scale
Size
Material
38
1:6
A3
Danfoss Standard
39
Designation
40
VXe Solo
41
42
Danfoss Redan A/S
No. 145F4445
F
43
44
Rev.
Sheet 1 / 1
45
7
8
46
AQ373475147162en-010102
47 48
49
50
51
Instructions for installation and use
VXe Solo
5. DIAGRAM & DIMENSIONAL SKETCH, EXAMPLE – VXE SOLO HWS 310/A337
1 Plate heat exchanger HE,
25 Controller Danfoss
with insulation
ECL310/A237
5 Strainer
26 Outdoor sensor, ESMT
6 Non-return valve
27 Sensor Danfoss, ESMC
7 Ball valve
28 Immersion sensor ESMB
8A Circulation pump, HE
29 Danfoss actuator AMV
8B Circulation pump, cylinder 30 Danfoss flow controller with
11 Safety valve HE, 3 bar ½”
integrated control valve
13 Thermometer
AVQM
14 Pocket for pressure gauge
15 Manometer
16 Expansion vessel 12 l
23 Sensor pocket for heat meter
24 Fitting piece for heat meter
3/4″ x 110 mm
Supply limit
Cylinder Return
Cylinder Supply
Cylinder
DH Supply
HE Supply
DH Return
HE Return
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
A
A
B
B
C
C
D
D
912
E
E
F
F
G
G
55
H
65
100
80
80
80
80
315
H
550
J
J
Connections:
1. District heating (DH) supply
K
2. District heating (DH) return
K
3. Heating (HE) return
4. Heating (HE) supply
L
5. Cylinder supply
6. Cylinder return
L
General tolerance accuracy, measurements without tolerance:
ISO 2768 – mK
Weight
73.118 kg
Replace
Projection
Scale
1:3
Size
Material
A1
Danfoss Standard Designation
Design
30-10-2018
JJ
Approval
M
Danfoss Redan A/S
M
Confidential: Property of Danfoss Redan A/S, Nordborg, Denmark. Not to be handed over to, copied or used by third party. Two- or three dimensional reproduction of contents to be authorized by Danfoss Redan A/S.
No. PROTO 897 Rev.
Sheet 1 / 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 13
Instructions for installation and use
VXe Solo
5. DIAGRAM & DIMENSIONAL SKETCH, EXAMPLE – VXE SOLO H OP ECL 310
1 Plate heat exchanger HE 5 Strainer 7 Ball valve 11 Safety valve HE 13
Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Connection for
expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat
meter ¾” x 110 mm 25 Controller Danfoss ECL310/A230 26 Outdoor sensor, ESMT
DH Supply
27 Sensor, ESMC 29 Danfoss actuator AMV 30 Flow controller with integrated control valve AVQM
HE Supply
DH Return
HE Return
1
2
3
4
5
6
7
8
9
10
11
12
A
A
B
B
C
C
660 125
D
D
E
65 100 80 80 F
550
315 55
G
Anschlüsse:
1. Fernwärme (FW) Vorlauf
2 Fernwärme (FW) Rücklauf
3. Heizung (HE) Rücklauf
4. Heizung (HE) Vorlauf
H
1
2
3
4
5
6
7
14 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
E
F
G
General tolerance accuracy, measurements without tolerance:
ISO 2768 – mK
Weight
64,398 kg
Replace
Design
07-12-2016
JJ
Projection
Scale
1:5
Size
Material
A2
Danfoss Standard
Designation
VXe Solo
Approval
Danfoss Redan A/S
H
Confidential: Property of Danfoss Redan A/S, Nordborg, Denmark. Not to be handed over to, copied or used by third party. Two- or three dimensional reproduction of contents to be authorized by Danfoss Redan A/S.
No. 145F4439 Rev.
Sheet 1 / 1
8
9
10
11
12
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
6. GENERAL, MOUNTING OF HEAT METER AND SAFETY VALVES
General
The installation, connection and maintenance of the substation must be
performed by qualified and authorised personnel. Installation must always be
performed in accordance with the applicable legislation and in compliance with
these instructions. The substation must be installed so that it is freely
accessible and can be maintained without unnecessary disruption. Lift the
substation by its mounting plate/rear section and secure it to a solid wall
using 4 sturdy bolts (max. 8 mm), screws or expansion bolts positioned in the
four keyholes. Before commissioning, rinse all the pipes in the household
piping system thoroughly to remove any impurities, and check and clean the
dirt strainers in the substation. Connect the substation to the household
piping in accordance with the labelling at the bottom and/or in accordance
with the instructions in this manual.
For fully insulated systems
The insulation front panel on the VXe Solo substations can be removed without
using tools. Take hold of the air duct in the top and bottom of the front
insulation section and pull carefully forward until the front insulation
section releases from the rear section. Then pull gently until the front
section is free from the components.
Test and connections
Before filling the system with water, retighten all the pipe connections
because vibrations and shocks during transport and handling may have caused
leaks. Once the system has been filled with water, tighten all the pipe
connections once more before performing pressure test for leaks. After heating
of the system, check all the connections and retighten if necessary. Please
note that the connections may feature EPDM rubber gaskets! Therefore, it is
important that you DO NOT OVERTIGHTEN the union nuts. Overtightening may
result in leaks. Leaks caused by overtightening or failure to retighten
connections are not covered by the warranty.
Meter display
Heat meter, fitting pieces.
The substation is equipped with fitting pieces for heat meter on the district
heating return line. (Measurement: 3/4″ x 110 mm).
Fitting of heat meters
– Close the four ball valves on the district heating and the heating sides.
– Loosen the union nuts at both ends of the fitting piece (A + B) and remove
it.
– Fit the heat meter, – remember to insert gaskets. – Mount sensor, – remember
to insert gaskets. – Mount temperature sensors in sensorpockets (according to
heat meter instructions. – After mounting of heat meter remember to check and
tighten
all pipe connections before commissioning the substation.
A
B
Meter display (reading unit)
The meter reading unit is placed on the console together with the ECL
regulator, as shown in the photo to the right, so that reading of the meter
can be done without removing the insulation cover.
Safety valve(s) Always lead the blow-off pipe from the safety valve to a drain
in accordance with applicable legislation.
The insulation cover is be prepared for this and blow-off pipe from the safety
valves are led through the slit in the insulating cover as shown in the photo
to the right.
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 15
Instructions for installation and use
VXe Solo
7. FILLING THE SYSTEM WITH WATER
Test and connections Before filling the system with water, retighten all the
pipe connections because vibrations and shocks during transport and handling
may have caused leaks. Once the system has been filled with water, tighten all
the pipe connections once more before performing pressure test for leaks.
After heating of the system, check all the connections and retighten if
necessary. Please note that the connections feature EPDM rubber gaskets!
Therefore, it is important that you DO NOT OVERTIGHTEN the union nuts. Over-
tightening may result in leaks. Leaks caused by overtightening or failure to
retighten connections are not covered by the warranty.
Filling, start-up Before filling the system with water, retighten all the pipe
connections. Once the system has been filled with water, tighten all the pipe
connections once more before performing pressure test for leaks. Before
filling the system with water and starting-up, check if:
– pipes are connected according to the circuit diagram, – expansion vessel is
connected, – heat meter is mounted, – shut-off valves are closed, – threaded
and flanged connections are tightened, – recirculation, if any, has been
established.
Filling the heat exchanger / the system with water: · The pump must be
switched off when filling the system with
water.
· Open the ball valves for the HE supply and return flow and fill the system
with water and at the same time venting the system.
· Fill the heat exchanger / the system with water until the manometer shows a
working pressure, which corresponds to the system height + approx. 5 m
(approx. 1.2 – 1.5 bar).
· Finally open the remaining ball valves and heat up the system.
· After filling and heat-up of the system it should be vented by means of the
air vents on the substation, if any and on the radiators.
· Then switch on the pump.
- Note: There is no filling valve inside the station. For refilling use a refill hose, customary for heating systems. Filling of water to the heating system must be done outside the substation, typically by connection to a cold water supply in the household installation.
NOTE: Accessories available as extra equipment (mounting on site) KFE tap – code No. 145H3717 For filling and draining 1/4″
16 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
Manometer AQ373475147162en-010102
Instructions for installation and use
VXe Solo
8. ELECTRICAL CONNECTION
Electrical connection The electrical connection of the substation must be
performed by a qualified and authorised electrician in compliance with all
applicable rules and regulations. The station should be connected to a 230 V
AC power supply. The power supply / connection must be carried out in
accordance with the applicable regulations and instructions.
The station must be wired and connected to an external main switch so that it
can be disconnected during maintenance, cleaning and repairs or in the event
of an emergency.
Do not forget to establish potential equalization.
The VXe Solo are delivered with Danfoss ECL Comfort 310 controllers from
factory. The actuator and sensors are mounted in the station. The controller
is built into the console at the top of the station.
The station is wired and tested in the factory. Electrical connections between
the controller, pump(s), sensor and actuator(s) are made.
Mounting of outdoor temperature sensor (ESMT) The outdoor temperature sensor
is delivered separately and must be mounted on site according to the enclosed
illustrations.
The outdoor sensor is always to be mounted on the coldest side of the
property, where it is less likely o exposed to direct sunshine (normally the
north side of the property). The sensor must not be exposed to the morning
sun, and should not be placed above windows, doors, air vents or other heat
sources, and not under balconies and roof eaves.
Mounting height approx. 2.5 m above ground.
Temperature range: -50 to 50° C.
Electrical connections The cables can be connected to the sensor in any order.
Connection cable: 2 x 0.4 – 1.5 mm²
For ECL 310: Connect the cable ends to ECL controller in common ground
terminal and in terminal 29.
Access to ECL base part Access to the base part for connection of outdoor
sensor or the like is obtained by pulling the lock (pin) down with a
screwdriver until a yellow line is visible on the lock. Then, the front piece
can easily be removed. Lock by pressing the lock (pin) up.
Controller ECL Comfort 310
Supply voltage:
230 V a.c. – 50 Hz
Voltage range:
207 to 244 V a.c. (IEC 60038)
Power consumption:
5 VA
Load on relay outputs:
4(2) A – 230 V a.c
Load on triac outputs:
0,2 A – 230 V a.c.
Actuator AMV 150
Supply voltage:
230 V a.c. – 50 Hz
Power consumption:
2 / 8 VA
For further information please see enclosed instruction manual.
Pumpe UPM3 AUTO Supply voltage: Protection class: Power consumption:
230 V a.c. – 50 Hz IP44 Max. 52 Watt
For further information please refer to the enclosed instructions for the circulation pumps.
Lock / pin
AQ373475147162en-010102
Common ground terminal
ECL Comfort 210 bundpart
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 17
Instructions for installation and use
VXe Solo
9. ADJUSTMENT AND COMMISSIONING
General information PLEASE NOTE! Some models may have a slightly different
appearance, but the control function is in principle the same as described
below.
Commissioning Commission the substation in accordance with the instruction
manual.
Filling the system / operating pressure Fill the unit with water according to
the instructions on page 16. If the pressure drops below 1 bar, water must be
added to the system. The operating pressure should never exceed 1.5 bar. (The
safety valve opens at 2,5 bar).
The pressure is read on the manometer.
If system pressure drops dramatically within a short time, heating system
should be examined for leakage, – this includes checking the factory set
pressure of the expansion vessel, which is normally 0,5 bar.
Fig. 1
Differential pressure controller
The differential pressure controller reduces the high, fluctuating pressure in
the district heating network to a constant operating pressure.
Fig. 2
VXe Solo H (Fig. 1)
For VXe Solo H the differential pressure controller is installed in the AVQM
self-acting flow controller with integrated control valve. Please see page 20
and relevant instruction manual.
VXe Solo HWP (Fig. 2) VXe Solo HWP is supplied with a AVPB-F differential
pressure controller, which is preset from factory and should not be adjusted
afterwards. The controller has a control valve with adjustable flow restrictor
and flow setting is being done by the adjustment of the flow restrictor
position. We suggest that you contact your local plumber for assistance.
Please see page 20 and relevant instruction manual.
VXe Solo HWS (Fig. 3) For VXe Solo HWS the differential pressure controller is
installed in the AVQM self-acting flow controller with integrated control
valve. Please see page 20 and relevant instruction manual.
Fig. 3
AVQM Manometer
AVPB-F Manometer
18 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AVQM Manometer
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
10. HEATING CIRCUIT, DANFOSS ECL 310 AUTOMATICS
Weather-compensated control of the heating circuit
Danfoss ECL 310
The temperature for the heating circuit is controlled electronically by the
Danfoss ECL controller. The supply temperature ist calculated by the
controller on basis of the outdoor temperature. The ECL Comfort controller is
loaded with a selected application by means of an ECL Application Key
(Plug-&-Play). The Application Key contains information about application,
languages and factory settings. Various applications can be loaded by means of
the ECL Application Key, and it is possible to update the controller with new
application software. The controller is factory preset to turn off the heating
automatically in the summer period. The controller settings can be changed in
accordance with the enclosed producer instructions for the mounted controller.
The controller is pre-programmed (normally) with the following factory settings: · Language = English, · Operating mode of the controller = Comfort “Sun” Symbol, · Application type = A230 / A337 / A237 Motor speed and motor protection is set and the controller is functional is functionally tested, so it’s ready for use.
Start-up of ECL 310 (easy start-up)
When the outside temperature sensor is properly installed and electrically
connected to the controller as described in the instructions on page 15,
proceed as follows: 1. Connect the controller and switch it on, 2. Choose
MENU’ in any circuit – Confirm and turn the dial and choose
Common controller settings’ in the circuit selector at the top right
corner in the display,
(You navigate in the controller by turning the dial left or right to the
desired position.
The position indicator in the display ( ) will always show you where you are).
3. Turn dial to select time and date, Push the dial to confirm the selection
4. Select time and date, 5. The controller is now ready for use. Set heat
curve and
temp. max. according to the procedure described below.
Setting / change of factory settings:
6. Choose MENU’ in any circuit – Confirm and turn the dial and choose
Heating circuit’in the circuit selector at the top right corner in the display
(radiator symbol),
7. Then turn the diall and choose Settings’ and confirm by pushing the dial. Then choose
Flow temperature’ and here you set `Heat curve'(value), according
to the actual system type, including”Temp. max.”,
8. Typical setting ranges:
Heating circuit one-string two-string Floor heating
Temp. max.
70-90°C
55-65°C
35-40°C
Heat curve
1,0 – 1,75
0,8 – 1,0
0,1 – 0,5
Note; in systems that feature only floor heating the max. supply temperature must be changed according to the above mentioned information.
If increased heat demand occurs during the heating period, the controller settings can be changed
See ECL Application Key Box with ECL Comfort 210/310 user guide and mounting guide, for further information.
Turn the dial to choose ‘MENU’ and press to confirm selection
Circuit selector Choose this symbol to enter `Common controller settings”
Circuit selector Heating circuit
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 19
5 5
Instructions for installation and use
VXe Solo
11. CONTROL OF HEATING CIRCUIT
Actuator and valve, VXe Solo H For controlling the heating circuit
the
VXe
Solo
H,
VXe
Solo
HWS
and –
VXe Solo H OP are supplied with a self-acting flow controller with
integrated control valve Danfoss AVQM and a Danfoss AMV actuator
placed in the primary return flow line. The AMV actuator is electrically
wired to the controller from the plant.
The control valve closes on rising differential pressure and opens on
falling differential pressure to control max flow. The controller closes
when set max. flow is exceeded.
In the combination with the electrical actuator AMV and ECL electronic controller the flow and temperature can be controlled to achieve highest energy savings. The AVQM is equipped with excess pressure safety valve, which protects control diaphragm for flow control from too high differential pressure.
AMV 150 The actuator has undergone a functional test and is preset from
factory. In the event of operating disturbances the actuator can be shut off
manually by turning the manual override knob on top of the actuator clockwise.
Please note that the knob can be “tight” to turn.
AMV 13 The actuator has undergone a functional test and is preset from
factory. Depending on the selected setting of the safety function, the AMV 13
valve is fully opened or closed when the voltage supply is switched off.
For additional information see manuals for: Self-acting flow controller with integrated control valve and actuator AVQM Electronic actuator AMV 150 Electronic actuator AMV 13
Actuator and valve, VXe Solo HWP For controlling the heating circuit the VXe
Solo HWP is supplied with a Danfoss AMV 150 / AMV 13 actuator and a Danfoss
two-way motorized contral valve VS 2, placed on the primary return flow line.
The AMV actuator is electrically wired to the controller from factory.
The actuator has undergone a functional test and is preset from factory.
In the event of operating disturbances the AMV 150 actuator can be shut off
manually by turning the manual override knob on top of the actuator clockwise.
Please note that the knob can be “tight” to turn.
Depending on the selected setting of the safety function, the AMV 13 valve is
fully opened or closed when the voltage supply is switched off.
AVQM
AMV 150 Manual override
AMV 13
Press and hold the button (on the bottom side of the actuator) during manual operation.
Instructions AVQM, AVQMT PN 16, 25 / DN 15-50
AVQM (PN 16)
AVQM (PN 25)
AVQMT (PN 25)
AVQMT/AVT (PN 25)
DN 15-32 p = 0.2
DN 15-50 p = 0.2
DN 32-50 p = 0.2
DN 15-50 p = 0.2
DN 32-50 p = 0.2
DN 15-50 p = 0.2
DN 32-50 p = 0.2
ENglIsh DANsK DEUTsCh EsPAÑOl slOVENSCINA POlsKI MAgyAr srPsKI
Flow (and temperature) controller with integrated control valve AVQM, AVQMT
Flow- (og temperatur-)regulator med indbygget motorventil AVQM, AVQMT
Volumenstrom (und Temperatur-) Regler mit Motorstellventil AVQM, AVQMT
Regulador de caudal (y temperatura) con válvula de control integrada AVQM,
AVQMT
Regulator pretoka (in temperature) z regulacijskim ventilom AVQM, AVQMT
Regulator przeplywu (i temperatury) z zaworem regulacyjnym AVQM, AVQMT
Térfogatáram(és hmérséklet) szabályozó, motoros szabályozó-szeleppel
egybeépítve AVQM, AVQMT
www.danfoss.com www.danfoss.dk www.danfoss.de www.danfoss.es www.danfoss.si www.danfoss.pl www.danfoss.hu
Page 7 Side 9 Seite 11 Página 13 Stran 15 Strona 17 Oldal 19
Uputstvo AVQM, AVQMT-PN 16, 25/DN 15-50
grejanje.danfoss.com Strana 21
Instructions AMV 150
ENglIsh DANsK DEUTsCh sVENsKA NEDERlANDs lIETUVI K. lATVIsKI MAgYAR CEsKY POlsKI
AMV 150 + VS2 (DN 15)
AMV 150 + VMV
AMV 150 + AVQM (DN 15)
Actuators for three point control AMV 150 Motorer til 3-punkts styring AMV 150 Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 Motor för 3-punktsreglering AMV 150 Servomotor met 3-puntssturing AMV 150 Pavaros trij padci valdymui AMV 150 Motori trs punktu kontrolei AMV 150 Szelepmozgatók hárompontos szabályozáshoz AMV 150 Servopohony s tíbodovým regulacním signálem AMV 150 Silowniki sterowane sygnalem 3-punktowym AMV 150 AMV 150
www.danfoss.com
Page 2
www.danfoss.dk
Side 3
www.danfoss.de
Seite 3
varme.danfoss.se
Sida 4
www.danfoss.nl
Pagina 4
www.danfoss.lt 5 puslapis
www.danfoss.com
Lpp. 5
www.danfoss.com
6. oldal
www.danfoss.cz
Strana 6
www.danfoss.pl
Strona 7
www.danfoss.ru 7
,QVWUXFWLRQV $09
$099096
$09$940
$099%
‘+6076,
(,+ ‘DQIRVV
1 1
VS 2
AMV 150
Manual override
AMV 13
Press and hold the button (on the bottom side of the actuator) during manual operation.
For additional information see manuals for: Electronic Actuator AMV 150 Electronic Actuator AMV 13 Danfoss Valve VS 2
,QVWUXFWLRQV $09
$099096
$09$940
$099%
5 5
‘+6076,
(,+ ‘DQIRVV
1 1
20 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
11. CONTROL OF HEATING CIRCUIT
Safety function, Jumo AT The heating circuit(s) can be supplied with a safety
thermostat Jumo AT for protection against overheating.
From factory the Jumo AT safety thermostat is pre-wired to the Danfoss ECL
controller with a 2 m cable, enabling the thermostat housing to be mounted in
any mounting position on the household piping (HE supply) on site.
For additional information see the enclosed manuals for: Jumo AT
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 21
Instructions for installation and use
VXe Solo
12. HEATING CIRCUIT, PUMP
Grundfos Pump UPM3 AUTO
Grundfos UPM3 Auto has 12 optional settings, which can be selected with the
push-botton. See fig. 1 – User interface.
The pump is set from factory to Proportionaldruck Pressure 2 .
The user interface shows: performance view (during operation)
– operation status – alarm status settings view (after pressing the button)
During operation, the display shows the performance of the pump. By pressing
the button, the display changes status or you can change settings.
Abb. 1. Bedienfeld mit einer Drucktaste und fünf LED´s
The LEDs show the power consumption for the pump. When the pump is running,
LED 1 is green. The four yellow LEDs indicate the current power consumption.
See fig. 2 – Performance view.
Fig. 2. Performance view
Performance % of P1 max. 0% (standby) 0 – 25% 25 – 50% 50 – 75% 75 – 100 %
22 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
12. HEATING CIRCUIT, PUMP
Check the pump setting by pressing the button once (one constant pessure). The
LEDs will briefly (2 sec.) show the pump setting before changing back to
showing the power consumption. See fig. 3 – Pump setting view.
If the pump setting does not give the desired distribution of heat in the
rooms of the house, change the pump setting. See fig. 3 – Pump setting view.
Before starting the setting, make clear what the display should show for the
new setting (see fig. 3).
To change the pump setting, choose the setting you want (see fig. 3), press
the button down for more than 2 seconds (less than 10) and the pump switches
to setting selection, the LEDs start flashing and display the current setting.
Then press the button until the LEDs shows the desired setting. The LEDs flash
and when they stop the new setting is saved. The LEDs return to show power
cunstumption.
Please note that if the LEDs do not flash after 2 seconds, possibly the pump
setting is locked. To unlock, press the button down for more than 10 seconds.
LEDs will flash and the pump is unlocked. To lock the pump, repeat the
procedure.
For more information, se enclosed Grundfos instructions.
Fig. 3. Pump setting view
Funktion Application
PROPORTIONAL PRESSURE AUTO ADAPT
– Two-pipe systems
CONSTANT PRESSURE AUTO ADAPT
– One-pipe systems – Floor heating
PROPORTIONAL – Two-pipe systems
PRESSURE 1
small systems
PROPORTIONAL – Two-pipe systems
PRESSURE 2
middle-sized system
PROPORTIONAL – Two-pipe systems
PRESSURE 3
large systems
CONSTANT PRESSURE 1
CONSTANT PRESSURE 2
CONSTANT PRESSURE 3 MAX.
CONSTANT CURVE 1
CONSTANT CURVE 2
CONSTANT CURVE 3 – MAX.
– One-pipe systems – Floor heating small systems
– One-pipe systems – Floor heating middlesized- systems
– Floor heating – One-pipe systems large systems
– One-pipe systems – Charging systems
small systems
– One-pipe systems – Charging systems middle-sized systems
– One-pipe systems – Charging systems – Venting of installation large systems
Pump mode
Alarm status In case the 1st LED is red the pump has detected one or more
alarms. See fig. 4 – Alarm status.
When there is no active alarm anymore the user interface switches back to
operation mode shortly and then showing power consumption.
AQ373475147162en-010102
Fig. 4. Alarm status Function Blocked Supply voltage low Electrical error
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 23
Instructions for installation and use
VXe Solo
13. DOMESTIC HOT WATER
General information PLEASE NOTE! Some models may have a slightly different
appearance, but the control function is in principle the same as described
below.
General The VXe Solo HWP (Fig. 1) is supplied with connection pipes for
cylinder on the primary side and the VXe Solo HWS (Fig. 2) is supplied with
connection pipes for cylinder on the secondary side.
Fig. 1 – VXe Solo HWP
VXe Solo HWP Please note that domestic hot water cylinder control is not
included in the standard delivery. For temperature regulation of the DHW
cylinder the VXe Solo
HWP can, as an option, be equipped with a RAVK self-acting thermostat and a
2-way valve VMA – for installation outside the system. The controller closes
when the temperature rises.
Instructions rAVK (25-65 °C)
ENglIsh
RAVK
POlsKI
RAVK
Installation Guide VMA DN 15
www.danfoss.com
Page 4
www.danfoss.pl
Strona 4
VMA
VMA / RAVI / RAVK / RAVV
VMA/ABV
69
G 3/4A 65
131 139
District Energy
VI.52.V4.00
DEN-SMT/SI 1
VXe Solo HWS
For VXe Solo HWS the temperature in the cylinder is controlled by the Danfoss
ECL controller in combination with the self-acting flow controller with
integrated control valve Danfoss AVQM and actuator AMV 150, according to the
cylinder temperature, measured by the cylinder sensor.
Fig. 2 – VXe Solo HWS
Danfoss ECL Comfort 310 The application Key contains information about
application, language and factory settings, adapted to the type of system, for
which it is ordered.
Note! Various applications can be loaded.
The controller is factory-set for local language and the running time for the
actuator (DHW circuit) is preset for the actual application. General
controller settings such as”Time and Date”must be entered during commissioning
of the controller. And also the desired DHW temperature must be set. (Make
sure that the immersion sensor is placed correctly before making adjustment of
the temperature). Please refer to the enclosed manufacturer instructions for
the ECL 210/310 controller in order to set the required domestic hot water
temperature in the DHW cylinder circuit: ECL Application Key Box with ECL
Comfort 210/310 user guide and mounting guide, for further information.
We recommend that your order commissioning of the controller with your local
Danfoss Sales Company.
24 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
Cylinder supply Cylinder return
Cylinder supply Cylinder return
DHW
DHW
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
13. DOMESTIC HOT WATER
Below schedule states whether the VXe Solo is supplied with connection pipes for DHW cylinder on the primary side or the secondary side, and whether the DHW temperature in the cylinder is controlled by the electronic controller and also states the controller application and the actuator/valve combination.
Type
VXe Solo HWP (ECL310/337)
VXe Solo HWS (ECL310/A337)
Primary Connection for Cylinder Secondary Connection for Cylinder Pump for cylinder circuit
Control not part of delivery
Danfoss ECL 310, Application A337 (AVQM / AMV 150)
Grundfoss UPM3 Auto
VXe Solo HWP with primary connection for cylinder
Cylinder
Supply limit
Cylinder Supply
Cylinder Return
DH Supply DH Return
VXe Solo HWS with secondary connection for cylinder
DH Supply DH Return
HE Supply
HE Return
Supply limit
Cylinder Return
Cylinder Supply
Cylinder
HE Supply
HE Return
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 25
Instructions for installation and use
VXe Solo
13. DOMESTIC HOT WATER
For VXe Solo HWS (ECL 310/A237) the temperature in the DHW cylinder is
controlled by the electronic controller in combination with the self-acting
flow controller with integrated control valve Danfoss AVQM and actuator AMV
13, according to the cylinder temperature, measured by the cylinder sensor.
The AMV actuator is electrically wired to the controller from the plant.
The actuator has undergone a functional test and is preset from factory.
Depending on the selected setting of the safety function, the AMV 13 valve is
fully opened or closed when the voltage supply is switched off.
For additional information see manuals for: Self-acting flow controller with
integrated control valve and actuator AVQM Electronic actuator AMV 13
AVQM
AMV 13
PUMP, DHW CYLINDER CIRCUIT
Domestic hot water circulation pump VXe Solo HWS with connection pipes for
domestic hot water cylinder on the secondary side is fitted with a circulation
pump Grundfos UPM3 Auto from factory. The pump is controlled by the cylinder
sensor and ECL controller in combination.
For more information, see Grundfos pump instructions and Danfoss ECL
application key instructions.
26 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
14. MAINTENANCE
Maintenance work Is only to be carried out by qualified and authorised
personnel.
Inspection The water heater should be checked regularly by authorised
personnel. Any necessary maintenance must be performed in accordance with the
instructions in this manual and other sets of instructions. During service the
dirt strainers are to be cleaned including the filter on the controller, all
pipe connections must be tightened and the safety valve must be function
tested by turning the lever.
Rinsing/cleaning of plate heat exchanger To clean the plate heat exchanger,
rinse it by running clean water through the exchanger at high speed and in the
opposite direction to the normal flow. This will remove any dirt deposits that
may have built up in the exchanger. If rinsing with clean water is not
sufficient, the exchanger can also be cleaned by circulating a cleaning agent
approved by Danfoss (e.g. Kaloxi or Radiner Fl cleaning fluid) through the
exchanger. Both these cleaning fluids are environmentally friendly and can be
disposed off through the standard sewer system. After use of a cleaning fluid,
the plate heat exchanger must be rinsed thoroughly with clean water.
Acidification of brazed plate heat exchanger As a starting point, we do not
recommend acidification of the exchanger. Deposits of limescale may build up
in plate heat exchangers for domestic hot water on account of the large
temperature fluctuations, and because aerated water is used on the secondary
side. If it becomes necessary to clean the exchanger with acid, this can be
done as shown on the drawing to the right. Brazed plate heat exchangers can
withstand rinsing with a dilute acid solution – e.g. 5% formic, acetic or
phosphoric acid).
Measures after maintenance work After maintenance work and before
commissioning: Check that all screwed connections are tight. Check that
all safety features, covers, that were removed, have
been replaced properly. Clean the working area and remove any spilled
materials. Clear all tools, materials and other equipment from the working
area. Connect to energy supply and check for leaks. Vent the system.
Carry out any necessary adjustment again. Make sure that all safety features
on the device and the system
work properly.
Meter reading The caretaker/owner must perform visual checking and reading of
the district heating meter at short, regular intervals. (The meter is not a
part of the delivery from Danfoss). Service procedures must only be performed
by trained, authorised personnel. NB! Excessive consumption for whatever
reason is not covered by the Danfoss warranty.
Cooling / Return temperature reading Cooling i.e. the difference between the
supply and return temperature of the district heating water has a
significant effect on overall energy economy. Therefore, it is important to
focus on the supply and return temperature in the heating system. The
difference should typically be 3035°C. Please note that a low district
heating return temperature is directly related to the return temperature from
the heating circuit and the return temperature of the circulation water. It is
therefore important to focus on these return temperatures.
Please note Use of other types of packaging, than the ones, with which the unit is delivered, will lead to the loss of warranty.
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 27
Instructions for installation and use
VXe Solo
14. MAINTENANCE SCHEDULE (recommendations)
Interval At least once per month
At least once a year
Maintenance work
Comments
Read the meter and check the system and all connections for leaks
Check the pipes and exchanger for signs of corrosion. Check for visible signs
of coatings (typically white coatings or green irises) on the surface of the
exchanger or pipes
Check all connections for leaks
Check all connections for leaks
Check that the safety valve on the cold water supply is functioning correctly.
Check that all components are intact and functioning as intended
Enter the measured readings in the control book – contact qualified and
authorised personnel in the event of leaks or other irregularities Visuel
control In the event of coatings or green irises on the surface of the
exchanger, the exchanger must be replaced immediately by qualified and
authorised personnel
If you identify a leak, replace the gaskets and retighten the pipe connections
If you identify a leak, replace the gaskets and retighten the pipe connections
Check the functionality by turning the lever on the safety valves
In the event of irregularities, lack of functionality or visible faults and
defects in a component, replace the component in questionn
Clean all dirt filters/strainers in the substation
Replace any filters that are not intact
Check that any electrical cables are in serviceable condition and that it is possible to disconnect the electrical power supply to the substation
Visual check. Check whether it is possible to disconnect the current to the substation.
Check the pipes and exchanger for signs of corrosion
Visual check
Check that the insulation cover is intact
Make sure that the insulation cover encloses the substation tightly
Check that the temperature regulators are set in accordance with the instructions in this manual
Follow the instructions in the present manual
Check the functions of all shut-off valves
Check that the ball valves open and close as they should
*)Enduser/caretaker. Note! After maintenance work has been carried out all gaskets HAVE to be replaced.
28 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
15. TROUBLESHOOTING HE
Fundamental
In the event of disruptions to operation, you should fundamentally – before commencing the actual troubleshooting – check whether:
· check the pipesand exchanger for signs of corrosion. check for visible signs
of coatings (typically white coatings or green irises) on the surface of the
exchanger or pipes
· the system is correctly connected · the district heating supply temperature
is at its normal level · the differential pressure is at its normal level. Ask
your district
heating supplier if necessary
· there is a power supply to the system – pump and automatics · the dirt strainer in the district heating supply pipe is clean · there is air in the system (if the system is vented)
Problem Too little or no heat.
Possible cause Strainer clogged in DH or HE circuit (radiator circuit). The
filter in the energy meter on DH circuit clogged. Defective or improperly
adjusted differential pressure controller
Sensor defective.
Automatic controls wrongly set or defective – possibly power failure.
Pump out of operation.
Solution
Clean gate/strainer(s).
Clean the filter (after consulting the DH plant operator).
Check the operation of the differential pressure controller clean the valve
seat if required.
Check the operation of the thermostat clean the valve seat if required.
Check if the setting of the controller is correct see separate instructions.
Check the power supply. Temporary setting of motor to “manual” control see
instructions on automatic controls.
Check if the pump is receiving power and that it turns. Check if there is air
trapped in the pump housing see pump manual.
Uneven heat distribution. DH supply temperature too high.
DH supply temperature too low.
The pump is set at too low speed of rotation.
Set the pump at higher speed of rotation.
Air pockets in the system.
Limiting of the return temperature adjusted too low.
Vent the installation thoroughly. Adjust according to instructions.
Defective radiator valves.
Check replace.
Uneven heat distribution in building because of incorrectly set balancing
valves, or because there are no balancing valves.
Diameter of pipe to flat station too small or branch pipe too long.
Air pockets in the system.
Adjust/install balancing valves.
Check pipe dimensions. Vent the installation thoroughly.
Defective controller. The controller does not react as it should according to
the instructions.
Defective control valve.
Set the automatic controls according to the instructions.
Replace control valve .
Defective controller. The controller does not react as it should according to
the instructions.
Strainer clogged.
Set the automatic controls according to the instructions.
Clean gate/strainer.
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 29
Instructions for installation and use
15. TROUBLESHOOTING HE
VXe Solo
Too high DH return temperature.
Noise in system. Heat load too high.
Too small heating surface/too small Increase total heating surface. radiators compared to the total heating requirement of the building.
Poor utilization of existing heating surface. Defective sensor on self-acting thermostat.
Make sure the heat is distributed evenly across the full heating surface open all radiators and keep the radiators in the system from heating up at the bottom. It is extremely important to keep the supply temperature to the radiators as low as possible, while maintaining a reasonable level of comfort.
The system is single pipe loop.
Das System sollte mit elektronischen Reglern und Rücklauffühlern ausgestattet sein.
Pump pressure too high.
Pumpe niedriger einstellen.
Air in system.
System entlüften.
Defective or incorrectly set radiator Check set/replace. valve(s). Single pipe loop systems require special one-pipe radiator valves.
Dirt in the differential pressure controller.
Check clean out.
Defective motorized valve, sensor or Check replace. automatic controller.
Pump pressure too high. Noice from Adjust pump to a lower level. Check
radiator valves.
flow direction.
Defective motorized valve, sensor or Check replace. electronic controller.
Disposal This product should be dismantled and its components sorted, if possible, in various groups before recycling or disposal. Always follow the local disposal regulations.
30 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
15. TROUBLE SHOOTING – DOMESTIC HOT WATER
Fundamental
In the event of disruptions to operation, you should fundamentally – before commencing the actual troubleshooting – check whether:
· the system is correctly connected · the district heating supply temperature
is at its normal level · the differential pressure is at its normal level. Ask
your district
heating supplier if necessary
· there is a power supply to the system – pump and automatics · the dirt strainer in the district heating supply pipe is clean · there is air in the system (if the system is vented)
Problem
Possible cause
Too little or no domestic hot water Dirt strainer in the district heating
supply line clogged.
Charging pump pump out of operation or set too low.
Defective actuator – or possibly dirt in the valve housing.
No power
Automatic controls wrongly set or defective – possibly power failure.
Calified plate heat exchanger
Defective actuator or thermostat Defective or clogged non-return valve.
Defective immersion sensor. Inadequate cylinder capacity.
Hot water is available only at some Cold and warm drinking water mix, e.g. in a
taps
defective thermostatic mixing valve.
Solution
Clean the dirt strainer.
Check whether the pump is running – whether the pump is receiving power.
Control that there is no air in the pump housing – see pump manual. Check the
functions of the actuator – clean valve seat if required. Check
Check if the setting of the controller is correct, – see separate
instructions. Check the power supply; Temporary setting of actuator to
“manual” control – see instructions on heating circuit, manual control.
Replace
Check according to encl. manual – replace Replace or clean Replace sensor.
Wait for heating / loading of the cylinder. You may check the specifications
of the manufacturer conc. cylinder capacity. Check – replace
DHW temperature too high
Non-return valve on the circulation line defective (leads to mixing – and the
circulation water pipes become cold during tapping).
Thermostatic valve RAVK/VMA set to high
Replace the non-return valve Check – adjust
Declining temperature during tapping
Temperature control valve does not close
Poor cooling
Calified heat exchanger
Replace
The temperature difference between the supply Choose a lower DHW setpoint or increase the
flow and the DHW setpoint is too low.
supply water temperature.
Calified heating element
Clean DHW cylinder with acid solution or replace heating element.
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 31
Instructions for installation and use
VXe Solo
15. TROUBLE SHOOTING – DOMESTIC HOT WATER
Temperature falls during tapping Controller incorrectly adjusted or defective.
(lack of capacity)
The immersion thermostat sensor incorrectly fitted in the cylinder.
Calified heating element.
Check that the setting of the controller is correct. – see the controller
instruction manual.
Place sensor correctly according to the specifictions of the manufacturer. You
may contact Danfoss Redan A/S for further information.
Descale the heat exchanger or replace it.
Temperature too high No DHW
Defective actuator – possibly dirt in the valve housing. Automatic controls
wrongly set or defective.
Defective immersion sensor. Calified heating element. Insufficient cylinder
capacity
Check the functions of the actuator – clean valve seat if required.
Check if the setting of the controller is correct, see separate instructions.
Replace immersion sensor.
Clean DHW cylinder with acid solution or replace heating element.
32 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
16. EU DECLARATION OF CONFORMITY
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 33
Instructions for installation and use
VXe Solo
17. COMMISSIONING CERTIFICATE
The substation is the direct link between the district heating supply network
and the household piping system. All supply pipes and the pipes in the
household piping system must be checked and rinsed before commissioning. Once
the system has been filled with water, all pipe connections must be
retightened before performing pressure test for leaks. The dirt strainers must
be cleaned and the substation must be adjusted in accordance with the
instructions in this manual.
It is important to comply with all technical regulations and the applicable
legislation in every respect.
Installation and commissioning must only be performed by trained, authorised
personnel.
The substation is checked in the factory for leaks before delivery. Leaks are
however possible due to vibrations caused by transport, handling and heating
of the system and therefore it is important to check all connections and to
retighten if necessarys before commissioning. Please note that the connections
may feature EPDM gaskets! Therefore it is important that you DO NOT OVER-
TIGHTEN the connections. Over-tightening may result in leaks. Leaks caused by
ove-rtightening or failure to retighten connections are not covered by the
warranty.
To be filled-out by the installer This substation has been retightened, adjusted and commissioned
on the:
Date/Year
by installer:
Company name (stamp)
34 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
AQ373475147162en-010102
Instructions for installation and use
VXe Solo
18. GUIDELINES FOR WATER QUALITY IN DANFOSS BRAZED HEAT EXCHANGERS
Parameter
pH
Conductivity
Free Chlorine
Ammonia (NH3, NH4+) Alkalinity (HCO3-) Sulphate (SO42-) HCO3- / SO42Nitrate
(NO3) Manganese (Mn) Iron (Fe) * Hardness ratio [Ca2+, Mg2+]/[HCO3-]
Unit
µS/cm
mg/l mg/l mg/l mg/l mg/l mg/l mg/l mg/l
/
Value or concentration
< 6.0 6,0 7.5 7.5 10.5
10.5 <10 10 500 500 1000 >1000 <0.5 0.5 1 1 5 >5 <2 2 20 >20 <60 60 300 >300 <100 100 300 >300 >1.5 <1.5 <100 >100 <0.1 >0.1 <0.2 >0.2 0 0.3 0.3 0.5 >0.5
Plate AISI 316L W.Nr. 1.4404
o + + + + + + + + o + + + + + + + + + + + + + + + + + + + +
+ Good corrosion resistance o **Corrosion could happen when more parameters are evaluated with o o/- Risk of corrosion – Use is not recommended
- Hardness ration limits defined per experience and internal tests in Danfoss laboratory ** In case of three or more parameters evaluated with o consultancy is needed with Consultant for Corrosion & Microbiology or BU HHE Representative
Brazing material
Cu
CuNi
StS
–
–
o
o/-
o
o
o
o
–
o
o
o
o
–
–
–
o
o
–
–
o
o/-
o
–
–
o/-
o
o
o
o
o
–
–
o/-
Recommended Chloride concentration to avoid Stress Corrosion Cracking (SCC) in the stainless-steel plates:
Application temperature
at T 20°C at T 50°C at T 80°C at T 100°C
Chloride concentration max 1000 mg/l max 400 mg/l max 200 mg/l max 100 mg/l
For more information please follow this link: https://assets.danfoss.com/documents/192075/
AQ373475147162en-010102
© Danfoss | Produced by Danfoss Redan A/S | 2023.02 | 35
36 | © Danfoss | Produced by Danfoss Redan A/S | 2023.02
145X2044
AQ373475147162en-010102
References
- Danfoss Srbija | Danfoss
- Danfoss värmelösningar | Effektiva lösningar för överlägsen komfort | Danfoss
- Engineering Tomorrow | Danfoss
- Danfoss - Engineering Tomorrow | Danfoss
- Danfoss Deutschland | Klima | Kälte | Heizung | Antriebe | Hydraulik | Danfoss
- Danfoss Salg Danmark | Danfoss
- Danfoss España: Soluciones innovadoras y ahorro de energía | Danfoss
- Danfoss - Engineering tomorrow | Danfoss
- Pagrindinis puslapis | Danfoss
- Danfoss Engineering Tomorrow - ontdek energie-efficiënte en innovatieve oplossingen voor uw branche | Danfoss
- Danfoss – Engineering Tomorrow | Danfoss
- Engineering Tomorrow | Danfoss
- Danfoss Slovenija, Danfoss Trata, ogrevanje, hlajenje, ogrevalna tehnika, hladilna tehnika, frekvenčni pretvorniki | Danfoss
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>