Description
The BG-12LPSP pull station is a non-coded, dual-action manual pull station with a key-lock reset feature, and dual language (Spanish/English) labeling and operating instructions. It provides Fire•Lite control panels with two (2) normally open (N/O) alarm initiating input signals. “Presignal” input is activated by pushing in, then pulling down the dual action handle. A “General” alarm input signal can be manually activated via a momentary rocker switch mountedinside the unit. This general alarm switch can only be accessed by opening the cover with the supplied key/lock.
The BG-12LPSP meets the ADAAG controls and operating mechanisms guidelines(section 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate the pullstation. Molded Terminal numbers are also present.
Ratings
Switch contacts (N/O) are gold plated for reliability and rated at 0.25 A at 30 volts (AC or DC).
Installation
The BG-12LPSP pull station can be surface mounted to an SB-10 or SB-I/O surface backbox or semi-flush mounted on a standard double-gang or 4″ (10.16 cm) square electrical box. The optional BG-TR trim ring can be used if the BG- 12LPSP is to be semi-flush mounted
Operation
To activate the dual-action pull station, push in and pull down on the handle. The word ‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull station is reset.
The pull station includes two independently operated Single Pole, Single Throw (SPST) Normally Open (N/O) Switches for pre-signal/ general alarm applications
Resetting the Pull Station
- Insert the key into the lock and rotate 1/4 turn counterclockwise.
- Open the door until the handle returns to normal.
- Close and lock the door.
NOTE: Closing the door automatically resets the switch to the ‘Normal’ position. Opening the door will not activate or deactivate the pre-signal toggle switch.
Wiring
WARNING! Do not loop wiring under any terminals. Break wire run to maintain IDC supervision.
CAUTION!
Do not detach the door of the pull station during installation. The door of
the pull station cannot be reattached to the backplate after the backplate has
already been installed onto an electrical box.
CAUTION!
Install the Fire•Lite BG-12LPSP pull sta – tion in accordance with these instructions, applicable NFPA standards, national and local Fire and Electrical codes and the requirements of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be conducted in accordance with the appropriate NFPA standards. Failure to follow these directions may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for devices that have been improperly installed, tested or maintained
ADA Compliance
For ADA compliance, if the clear floor space only allows forward approach to an object, the maximum forwardreach height allowed is 48 inches (121.92 cm). If the clear floor space allows parallel approach by a person in a wheelchair, the maximum side reach allowed is 54 inches (137.16 cm)