Fire LITe ES-200X FACP with Communicator User Manual
- May 15, 2024
- Fire-Lite
Table of Contents
Supplement to the
ES-200X Manual #
LS10131-000FL-E Revision F
dated 5/23/2022 for
ES-200XP Applications
Document LS10387-000FL-E Rev: A
2/23/2023 ECN:00029240
ES-200X FACP with Communicator
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute
for life and property insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat
detectors, manual pull stations, audible warning devices, and a fire alarm
control panel (FACP) with remote notification capability—can provide early
warning of a developing fire.
Such a system, however, does not assure protection against property damage or
loss of life resulting from a fire.
An emergency communication system—typically made up of an automatic fire alarm
system (as described above) and a life safety communication system that may
include an autonomous control unit (ACU), local operating console (LOC), voice
communication, and other various interoperable communication methods—can
broadcast a mass notification message. Such a system, however, does not assure
protection against property damage or loss of life resulting from a fire or
life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located
throughout a protected premises following the recommendations of the current
edition of the National Fire Protection Association Standard 72 (NFPA 72),
manufacturer’s recommendations, State and local codes, and the recommendations
contained in the Guide for Proper Use of System Smoke Detectors, which is made
available at no charge to all installing dealers. This document can be found
at http://www.systemsensor.com/appguides/.
A study by the Federal Emergency Management Agency (an agency of the United
States government) indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm systems are designed to provide early
warning against fire, they do not guarantee warning or protection against
fire. A fire alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in or behind walls, on roofs, or on the other side of closed
doors. Smoke detectors also may not sense a fire on another level or floor of
a building. A second-floor detector, for example, may not sense a first-floor
or basement fire.
Particles of combustion or “smoke” from a developing fire may notreach the
sensing chambers of smoke detectors because:
- Barriers such as closed or partially closed doors, walls, chimneys, even wet or humid areas may inhibit particle or smoke flow.
- Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
- Smoke particles may be blown away from detectors by air outlets, such as air conditioning vents.
- Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors.
Smoke detectors are designed to alarm at various levels of smoke density. If
such density levels are not created by a developing fire at the location of
detectors, the detectors will not go into alarm. Smoke detectors, even when
working properly, have sensing limitations. Detectors that have
photoelectronic sensing chambers tend to detect smoldering fires better than
flaming fires, which have little visible smoke. Detectors that have ionizing-
type sensing chambers tend to detect fast-flaming fires better than smoldering
fires. Because fires develop in different ways and are often unpredictable in
their growth, neither type of detector is necessarily best and a given type of
detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused
by arson, children playing with matches (especially in bedrooms), smoking in
bed, and violent explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat
on their sensors increases at a predetermined rate or reaches a predetermined
level. Rate-of-rise heat detectors may be subject to reduced sensitivity over
time. For this reason, the rate-ofrise feature of each detector should be
tested at least once per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the
control panel and in rooms used by the system for the connection of alarm
transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, compromising
its ability to report a fire.
Audible warning devices such as bells, horns, strobes, speakers and displays
may not alert people if these devices are located on the other side of closed
or partly open doors or are located on another floor of a building. Any
warning device may fail to alert people with a disability or those who have
recently consumed drugs, alcohol, or medication. Please note that:
- An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
- Voice messaging systems must be designed to meet intelligibility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
- Language and instructional requirements must be clearly disseminated on any local displays.
- Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
- Studies have shown that certain people, even when they hear a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner’s responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
- In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If AC
power fails, the system will operate from standby batteries only for a
specified time and only if the batteries have been properly maintained and
replaced regularly.
Equipment used in the system may not be technically compatible with the
control panel. It is essential to use only equipment listed for service with
your control panel.
Alarm Signaling Communications:
-
IP connections rely on available bandwidth, which could be lim- ited if the network is shared by multiple users or if ISP policies impose restrictions on the amount of data transmitted. Service packages must be carefully chosen to ensure that alarm signals
will always have available bandwidth. Outages by the ISP for maintenance and upgrades may also inhibit alarm signals. For added protection, a backup cellular connection is recommended. -
Cellular connections rely on a strong signal. Signal strength can be adversely affected by the network coverage of the cellular carrier, objects and structural barriers at the installation location. Utilize a cellular carrier that has reliable network coverage where the alarm system is installed. For added protection, utilize an external antenna to boost the signal.
-
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup alarm signaling connections are recommended.
The most common cause of life safety system malfunction is inadequate maintenance. To keep the entire life safety system in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt, or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer’s representative. Maintenance should be scheduled as required by National and/or local fire codes and should be performed by authorized professional life safety system installers only. Adequate written records of all inspections should be kept.
Installation Precautions
Adherence to the following will aid in problem-free installation with long- term reliability:
WARNING – Several different sources of power can be connected to the fire
alarm control panel. Disconnect all sources of power before servicing. Control
unit and associated equipment may be damaged by removing and/or inserting
cards, modules, or interconnecting cables while the unit is energized. Do not
attempt to install, service, or operate this unit until manuals are read and
understood.
CAUTION – System Re-acceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA
72 after any programming operation or change in site-specific software. Re-
acceptance testing is required after any change, addition or deletion of
system components, or after any modification, repair or adjustment to system
hardware or wiring. All components, circuits, system operations, or software
functions known to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected, at least 10%
of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, must also be tested and proper system operation
verified.
This system meets NFPA requirements for operation at 0-49º C/32120º F and at a
relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system’s standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a normal room temperature of 15-27º C/60-80º
F.
Verify that wire sizes are adequate for all initiating and indicating device
loops. Most devices cannot tolerate more than a 10% I.R. drop from the
specified device voltage.
Like all solid state electronic devices, this system may operate erratically
or can be damaged when subjected to lightning induced transients. Although no
system is completely immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial wiring is not
recommended, due to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any problems are anticipated
or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit
boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or
punching of the enclosure. When possible, make all cable entries from the
sides or rear. Before making modifications, verify that they will not
interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with
screw terminal removal.
This system contains static-sensitive components. Always ground yourself with
a proper wrist strap before handling any circuits so that static charges are
removed from the body. Use static suppressive packaging to protect electronic
assemblies removed from the unit. Units with a touchscreen display should be
cleaned with a dry, clean, lint free/microfiber cloth. If additional cleaning
is required, apply a small amount of Isopropyl alcohol to the cloth and wipe
clean. Do not use detergents, solvents, or water for cleaning. Do not spray
liquid directly onto the display.
Follow the instructions in the installation, operating, and programming
manuals. These instructions must be followed to avoid damage to the control
panel and associated equipment. FACP operation and reliability depend upon
proper installation.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual
may cause interference to radio communications. It has been tested and found
to comply with the limits for class A computing devices pur- suant to Subpart
B of Part 15 of FCC Rules, which is designed to provide reasonable protection
against such interference when devices are operated in a commercial
environment. Operation of this equipment in a residential area is likely to
cause interference, in which case the user will be required to correct the
interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations
of the Canadian Depart- ment of Communications.
LiteSpeed™ and Lite-Connect™ are trademarks; and Fire-Lite® Alarms,
Honeywell®, and SWIFT® are registered trademarks of Honeywell International
Inc.Microsoft® and Windows® are registered trademarks of the Microsoft
Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a
registered trademark of The Mozilla Foundation.
©2023 by Honeywell International Inc. All rights reserved. Unauthorized use of
this document is strictly prohibited.
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you
have any comments or suggestions about our online Help or printed manuals, you
can email us.
Please include the following information:
- Product name and version number (if applicable)
- Printed manual or online Help
- Topic Title (for online Help)
- Page number (for printed manual)
- Brief description of content you think should be improved or corrected
- Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have
any technical issues, please contact Technical Services.
This symbol (shown left) on the product(s) and / or accompanying documents
means that used electrical and electronic products should not be mixed with
general household waste. For proper treatment, recovery and recycling, contact
your local authorities or dealer and ask for the correct method of disposal.
Electrical and electronic equipment contains materials, parts and substances,
which can be dangerous to the environment and harmful to human health if the
waste of electrical and electronic equipment (WEEE) is not disposed of
correctly.
Use this text to update the ES-200X Series Manual for ES-200XP applications.
Fire-Lite Documents:
HW-AV-LTE-M-FL CLSS Pathway Pro
Document #LS10340-000HW-E Peripheral Devices and Their
Documents:
1.1 Features and Options
- Pre-installed CLSS Pathway Pro
1.4 Components
CLSS Pathway Pro Communicator
The pre-installed CLSS Pathway Pro is a dual-path cellular communicator which
runs on 24VDC power from the panel. It supports both AT&T and Verizon LTE
networks, and uses either of them with a stronger signal. It transmits Contact
ID data from the fire panel to the central monitoring station.The CLSS
communicator transmits system status (alarms, troubles, AC loss, etc.) via
ethernet or cellular network.
1.8.4 FCC Compliance
Contains FCC ID: RI7ME310G1WW
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference. (2) This device must accept any interference received,
including, an interference that may cause undesired operation.
- Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
- This device complies with FCC/ISED radiation exposure limits set forth for an uncontrolled environment and meets the FCC radio frequency (RF) Exposure Guidelines and RSS‐102 of the ISED radio frequency (RF) Exposure rules. This transmitter must not be colocated or operating in conjunction with any other antenna or transmitter.
The antenna should be installed and operated with minimum distance of 8” (20 cm) between the radiator and your body.
2.6 UL Power-limited Wiring Requirements
Power-limited and non-power-limited circuit wiring must remain separated in
the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35
mm) away from any non-power-limited circuit wiring and non-power-limited
circuit wiring must enter and exit the cabinet through different knockouts
and/or conduits. When connecting the ground cables, be sure that the AC mains
ground is the first one installed, closest to the backbox. The antenna must be
mounted 8 in (20cm) from the display/keypad. A typical wiring diagram for the
ES-200XP is shown below.
2.8 CLSS Communicator
The CLSS Pathway Pro comes pre-installed and wired in the cabinet. The antenna
must be mounted 8” (20cm) away from the display/keypad.
Refer to Figure 2.10 above.
2.8.1 Configuration
After programming the panel via FS-Tools or the keypad, a CLSS account must be
created and used to finalize communication from the Pathway Pro to the central
station. Use either the CLSS Site Manager or CLSS Mobile app to configure the
CLSS Pathway Pro.
Configuration must be done using a PC along with FS-Tools or the panel, and
CLSS Site Manager. Follow the steps below.
-
Configure the panel via the keypad or FS-Tools.
-
Request a CLSS account and sign in.
Navigate to www.fire.honeywell.com. Click Request Access and follow the on-screen instructions. -
Build the customer site in CLSS.
In the CLSS Site Manager, go to the Quick access Menu or Feature Activation Screen and click Install Pathway Pro. Follow the on- screen instructions to install the device. -
Configure the Central Station.
-
Activate the CLSS Pathway Pro.
-
Upload the device list from panel/FS-Tools and download the Central Station Report.
3.5.7 Communicator The communicator settings allow
the user to configure the settings for the pre-installed CLSS Pathway Pro.
Pressing 2 while viewing the Programming Screen #3 will cause the following
Communicator options to be displayed: Communicator
Installed
The pre-installed communicator provides communication to a central station.
Use of the communicator requires it be enabled in user programming. Pressing 1
while viewing the Communicator Screen #1 will change the display to Installed
Yes. Each press of the 1 key will cause the display to toggle between
Installed Yes and Installed No.
Primary Communication Path The Primary Communication Path
screen is used to configure the method for reporting to central station.
Pressing 1 for Pri will display the following screens.
Cellular
To configure the communication method to contact central station using the CLSS Communicator, select 3 for Cellular from the Comm Path Screen. The following screens will display.
Enable
To enable the Cellular connection, press 1 while viewing the Cellular Options
Screen #1 to change the display to Enabled Yes. Each press of the 1 key will
cause the display to toggle between Enabled Yes and Enabled No.
NOTE: When using the CLSS Pathway Pro, CS Account Options and Supervision
Settings are not configured at the panel. Use the CLSS Site Manager or the
mobile app to configure Central Station settings. Visit
www.fire.honeywell.com and refer to Section
2.8 for more information.
9.3.2 How to Calculate System Current Load
Use Table 9.3 on page 131 to calculate current load as follows:
- Enter the quantity of devices in all three columns.
- Enter the current draw where required. Refer to the Device Compatibility Document and SWIFT Manual for compatible devices and their current draws.
- Calculate the current draws for each in all columns.
- Sum the currents for each column. This is the total load.
- Verify that the total from Column 1 is less than or equal to the value specified in the note.
- Copy the totals from Column 2 and Column 3 to Table 9.4 on page 132.
Table 9.3 contains columns for calculating current load. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 9.4 on page 132. For maximum output current available per circuit and per panel, refer to Section 1.2, “Specifications”, on page 14.
Device Type| Calculation Column 1
Primary (AC) Power Source
Fire Alarm Current (amps)| Calculation Column 2
Secondary (Battery) Power Source
Fire Alarm Current (amps)| Calculation Column 3
Secondary (Battery) Power Source
Standby Current (amps)
---|---|---|---
| Qty X [current draw]= Total| Qty X [current draw]= Total| Qty X [current
draw]= Total
Main Circuit Board| | 1 X[0.257]=| 1 X[0.141]=
CLSS Pathway Pro| [ ] X[0.100]=| [ ] X[0.100]=| [ ] X[0.100]=
Table 9.3 System Current Load Calculations
- Main board with display only.
Appendix H: NFPA Requirements
The following is the minimum configuration to meet the NFPA requirements.
Module | Local | Aux | RS | CS | Proprietary | Process Management 1 |
---|---|---|---|---|---|---|
ES-200XP | Y | Y | Y | Y | N | Y |
HW-AV-LTE-M-FL
(pre-installed CLSS Pathway Pro)| Y| Y| Y| Y2| N| Y
Where Y = Yes, N = No, and O = Optional
- Non-Emergency
- Also required when devices for Carbon Monoxide signaling are employed
ES-200XP Fire Alarm Control Panel Operating Instructions
NORMAL – Only AC POWER is illuminated green.
All other indicators are off. LCD display will read SYSTEM NORMAL .
PANEL KEY – The key to open the panel can be found at the following location:
WHEN AUDIBLE DEVICES ARE SOUNDING –
FOR AN ALARM
-
Evacuate the protected area
-
Notify the monitoring service and/or the Fire Department immediately. Tell them briefly what happened and what your current status is.
Phones: ____
Fire Department
Monitoring Service -
If the Fire Department is responding, be prepared to provide directions to arriving firefighters.
FOR TROUBLE, SUPERVISORY, AND EMERGENCY ALARMS
- Notify the monitoring service and/or applicable first responders if this panel is connected to either one, and tell them what is happening.
- Silence audible devices by unlocking and opening the panel and pressing the ACKNOWLEDGE/STEP button. The applicable indicator will remain illuminated. Contact authorized service personnel immediately! (See Below).
WARNING!
DO NOT ALLOW TROUBLE CONDITIONS TO REMAIN LOGGED IN THE SYSTEM. THE PROTECTION
THE SYSTEM OFFERS HAS BEEN COMPROMISED OR ELIMINATED, WHEN A TROUBLE CONDITION
EXISTS.
To return to normal after an alarm
- Do not enter the protected area until safe to do so.
- Clear all initiating devices. Smoke detectors will not reset if there is still smoke in the area.
- Reset the control panel (PRESS the RESET button)
Power failure or brownout
If AC power drops too low or fails, AC POWER indicator will extinguish, the
system TROUBLE indicator will turn on yellow, and the panel buzzer and any
other audible trouble devices will sound. Contact authorized service personnel
immediately. See below.
In the event of trouble, contact the local Fire-Lite Service Representative
Name:
Company: ____
Address:
Telephone Number: __
Manual activation (Fire Drill or otherwise)
Notification Appliance Circuits (NACs) can be activated by pressing and
holding the DRILL button for at least two seconds.
NOTE: You may want to disconnect the municipal box by sliding the
DISCONNECT switch, located on the 4XTMF module, to its disconnect position (to
the right). If a DACT is connected, notify the monitoring service before
conducting any fire drills or tests.
Alarm Silencing
Notification Appliance Circuits may be silenced by pressing the ALARM SILENCE
button. ALARM SILENCED will turn on yellow. Subsequent alarms will reactivate
circuits. Press the RESET button to clear the “silenced” condition.
NOTE: Notification Appliance Circuits may be programmed as
nonsilenceable. Also, Signal Silence Inhibit, if enabled, will prevent
silencing of NACs for five minutes after an alarm (see manual).
To test the indicators, LCD display and piezo
Press and release the RESET button and check all indicators/LEDs.
Every indicator/LED should be on, LCD shows all pixels on, piezo sounder
beeps.
For more information, refer to the ES-200X Series Manual, Document
LS10131-000FL-E and ES-200XP Supplement #LS1087-000FL-E.
They are kept in the following location:
THIS SHEET SHALL BE FRAMED ADJACENT TO THE CONTROL PANEL
Document #LS10389-000FL-E
Rev. A
2/16/2023
ECN 00029240
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>