Fire-Lite Alarms W-SD355 Wireless Smoke Detector Instruction Manual

June 1, 2024
Fire-LITe Alarms

Fire-Lite-Alarms-logo

Fire-Lite Alarms W-SD355 Wireless Smoke Detector

Fire-Lite-Alarms-W-SD355-Wireless-Smoke-Detector-
product

Product Information

Specifications

  • Model: W-SD355 and W-SD355T Wireless Intelligent Photoelectric Smoke Sensor
  • Diameter: 4.0in. (102 mm) installed in B501W Base
  • Weight: 8.1 oz. (230 g) installed in B501W base with 4 batteries

FAQ

  • Q: How do I know when to replace the batteries in the wireless device?
    • A: Low battery levels are indicated by the message “TROUBLE BATTERY LOW” on the FACP. Replace the battery when this message is displayed.

SPECIFICATIONS

  • Operating Voltage Range: 3.3 VDC
  • Standby Current: 210μA @ 3.3 VDC (one communication every 23.8 seconds with LED blink enabled)
  • Maximum Alarm Current (LED on): 5 mA @ 3.3 VDC LED on
  • Maximum Transmit RF Power: 17dBm
  • Radio Frequency Range: 902-928 MHz
  • Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
  • Operating Temperature Range: 32°F to 120°F (0°C to 49°C),W-SD355; 32°F to 100°F (0°C to 38°C),W-SD355T
  • Battery Type: 4 Panasonic CR123A or 4 Duracell DL123A
  • Battery Life: 1 year minimum
  • Battery Replacement: Upon TROUBLE BATTERY LOW display and/or during annual maintenance
  • Height: 2.4in. (61 mm) installed in B501W Base
  • Diameter: 4.0in. (102 mm) installed in B501W Base
  • Weight: 8.1 oz. (230 g) installed in B501W base with 4 batteries

This sensor must be installed in compliance with the control panel system installation manual and the SLC Wireless Gateway Manual. The installation must meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when installed in compliance with the National Fire Protection Association (NFPA); see NFPA 72.

GENERAL DESCRIPTION

Fire-Lite-Alarms-W-SD355-Wireless-Smoke-Detector-fig-1

Model W-SD355 and W-SD355T are plug-in type smoke sensors that combine a photoelectronic sensing chamber with wireless communication. The sensors transmit a digital representation of smoke density through a wireless mesh to a gateway. The gateway will send the information to the panel when requested. Rotary decade switches are provided for setting the sensor’s address. (Figure

  1. Two LEDs on the sensor are controlled by the panel to indicate sensor status. Model W-SD355T combines a photoelectronic sensing chamber and 135°F (57.2°C) fixed temperature heat detector.

Fire-Lite panels offer different features sets across different models. As a result, certain features of the W-SD355 and W-SD355T may be available on some control panels, but not on others. The possible features available in the W-SD355 and W-SD355T, if supported by the control unit are:

  • The panel controls the LED operation on the sensor. Operational modes include red, green and amber colors in various solid or blink patterns.

Please refer to the operation manual for the UL listed control unit for specific operation of the W-SD355 and W-SD355T.
The W-SD355 and W-SD355T require compatible addressable communications to function properly. Connect these sensors to listed-compatible control panels only.

SPACING

Fire-Lite recommends spacing sensors in compliance with NFPA 72. In low air flow applications with smooth ceilings, space sensors 30 feet apart. For specific information regarding sensor spacing, placement, and special applications, refer to NFPA 72 or the System Smoke Detector Application Guide, available from Fire-Lite.

NOTE

Fire-Lite-Alarms-W-SD355-Wireless-Smoke-Detector-fig-2

Do not attach the base and detectors to temporary structures such as removable ceiling tiles such that the placement could be altered. To prevent changes in device placement, permanently secure the structure or mount the detector across the ceiling panel support as shown in Figure 2.

BATTERY REPLACEMENT

Low battery levels on the wireless devices are displayed as a trouble on the FACP. Therefore when the message “TROUBLE BATTERY LOW” is displayed, replace the battery in the device. This message is an indication that approximately one week of battery life remains.

To replace the batteries in a wireless device use the following steps:

  1. Have 4 CR123A (or DL123A) batteries available
  2. The system allows 200 seconds to replace the batteries before the device is noted as missing and will activate the Rescue Mode within the wireless system.
  3. Remove the detector from the base.Fire-Lite-Alarms-W-SD355-Wireless-Smoke-Detector-fig-3
  4. Open the battery compartment refer to Figure 3. Note: The battery compartment cover may be left attached at the hinges during battery replacement.
  5. Remove the used batteries and replace with new batteries. The battery compartment is designed such that the batteries can only align in the appropriate direction. Do not force the batteries into the openings.
  6. Replace the battery compartment cover.
  7. Return the device to its original location.

CAUTION

  • Dust covers provide limited protection against airborne dust particles during shipping.
  • Dust covers must be removed before the sensors can sense smoke. Remove sensors prior to heavy remodeling or construction.

TAMPER RESISTANCE

W-SD355 and W-SD355T include a tamper-resistant capability that prevents their removal from the base without the use of a tool. Refer to the base manual for details on making use of this capability. The base also includes a magnet for tamper resistance. The magnet activates a supervisory tamper fault at the panel if the detector is removed from the base.

TESTING

Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable the system to prevent unwanted alarms. All sensors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when tested and maintained in compliance with NFPA 72.

The sensor can be tested in the following ways:

Functional: Magnet Test (P/N M02-04-01 or M02-09-00)

This sensor can be functionally tested with a test magnet. The test magnet electronically simulates smoke in the sensing chamber, as well as tests the sensor electronics and connections to the control panel.

Fire-Lite-Alarms-W-SD355-Wireless-Smoke-Detector-fig-4

  1. Hold the test magnet in the magnet test area as shown in Figure 4.
  2. The sensor should alarm the panel.

Two LEDs on the sensor are controlled by the panel to indicate sensor status. Coded signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel technical documentation for sensor LED status operation and expected delay to alarm.

Smoke Entry

The GEMINI model 501 aerosol generator can be used for smoke entry testing. Set the generator to represent 4%/ft to 5%/ft obscuration as described in the GEMINI 501 manual. Using the bowl shaped applicator, apply aerosol until the panel alarms. Additionally, canned aerosol simulated smoke (canned smoke agent) may be used for smoke entry testing of the smoke detector. Tested and approved aerosol smoke products are:

MANUFACTURER MODEL
Home Safeguard Industries 25S and 30S
SDi CHEK02 and CHEK06
SDi SOLOA4
SDi SMOKESABRE-01

When used properly, the canned smoke agent will cause the smoke detector to go into alarm. Refer to the manufacturer’s published instructions for proper use of the canned smoke agent.

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by manufacturer. Misuse or overuse of these products may have long term adverse effects on the smoke detector. Consult the canned smoke agent manufacturer’s published instructions for any further warnings or caution statements.

Direct Heat Method (Hair dryer of 1000-1500 watts)

A hair dryer of 1000-1500 watts should be used to test the thermistors. Direct the heat toward either of the two thermistors, holding the heat source approximately 12 inches from the detector in order to avoid damaging the plastic housing. The detector will reset only after it has had sufficient time to cool. Make sure both thermistors are tested individually.

A sensor that fails any of these tests should be cleaned as described under CLEANING, and retested. If the sensor fails after cleaning, it must be replaced and returned for repair.
When testing is complete, restore the system to normal operation and notify the proper authorities that the system is back in operation.

CLEANING

Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of service.
Disable the zone or system undergoing maintenance to prevent unwanted alarms.

  1. Remove the sensor to be cleaned from the system.Fire-Lite-Alarms-W-SD355-Wireless-Smoke-Detector-fig-5
  2. Remove the sensor cover by pressing firmly on each of the four removal tabs that hold the cover in place. (refer to Figure 5).
  3. Vacuum the screen carefully without removing it. If further cleaning is required continue with Step 4, otherwise skip to Step 7.
  4. Remove the chamber cover/screen assembly by pulling it straight out.
  5. Use a vacuum cleaner or compressed air to remove dust and debris from the sensing chamber.
  6. Reinstall the chamber cover/screen assembly by sliding the edge over the sensing chamber. Turn until it is firmly in place.
  7. Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place. Make sure that the thermistors do not become bent under the cover on the W-SD355T.
  8. Reinstall the detector.
  9. Test the detector as described in TESTING.
  10. Reconnect disabled circuits.
  11. Notify the proper authorities that the system is back on line.

SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS

  • Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.

Please refer to insert for the Limitations of Fire Alarm Systems

FCC STATEMENT

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference
  2. This device must accept any interference received, including interference that may cause undesired operation.

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

One FireLite Place

  • Northford, CT 06472
  • Phone: 203.484.7161

©2014 Fire-Lite