CERBERUS SR-32 System 3 Supplementary Relay Module Instruction Manual

June 9, 2024
CERBERUS

CERBERUS - logo SR-32 System 3 Supplementary Relay Module
Instruction Manual SR-32
System 3 Supplementary Relay

ENGINEER AND ARCHITECT SPECIFICATIONS

  • 6 Relays per Module
  • DPDT Configuration
  • Terminals for Two #12 Wires
  • Listed, FM, CSFM and NYMEA Approved

Description

The supplementary relay module, Model SR-32 is designed to activate or deactivate, as desired, external devices such as door releases, fan shut-down, extinguishing system  release, audible alarms, etc.  Actuation of the unit may come from the system control panel, a ZN or ZU zone module, an SM switching module, or any other module with  appropriate signal output.
The module is fitted with six (6) independent, 24 VDC relays, each of which provides a set of double pole, double throw (DPDT) contacts rated 3 Amp., 120 VAC or 30  VDC each. Power to operate the relays is provided from the 24 VDC system power supply. Actuation of each relay is from a high resistance transistor input circuit, requiring  a high going DC signal from between 12 and 24 volts above system common. All terminals are of the clamp type, accommodating 2 wires of up to 12 gauge.
The model SR-32 occupies 2 standard module positions and is Underwriters Laboratories, Inc. listed.

Engineer and Architect Specifications

For the control of external devices, there shall be provided a Cerberus Piezotronics supplementary relay module, model SR-32. This module shall contain six (6) independent  24 VDC relays, fitted with DPDT contacts with a rating of 3 Amp., 120 VAC or 30 VDC each. Power to operate the relays shall be 24 VDC furnished by the system power supply.
A separate terminal shall be provided for individual activation of each relay. All terminals shall be of the clamp type which shall accommodate two (2) wires of up to #12  gauge. Therefore, no spade type, ring type or special connectors shall be required to connect two (2) wires to each input (activating) or output (contacts) terminals.
The unit shall be Underwriters Laboratories, Inc. listed.

Electrical Information

Current Requirement: Relays de-energized – None Relays energized – 45mA each

Ordering Information

Model No. Description Shipping Weight
SR-32 Supplementary Relay Module 3 lb. (1.4 kg.)

Typical Wiring

CERBERUS SR 32 System 3 Supplementary Relay Module - Typical
Wiring

NOTICE: The use of other than Cerberus Piezotronics detectors and bases with Cerberus Piezotronics equipment will be considered a misapplication of Cerberus  emotronics  equipment and as such void all warranties either expressed or implied with regards to loss, damage, liabilities and/or service problems.

CERBERUS - logo Cerberus Piezotronics
8 Ridgedale Ave.
Cedar Knolls, NJ 07927
Tel: 201-267-1300
FAX: 201-397-7008
Cerberus Piezotronics
50 East Pearce Street
Richmond Hill, Ontario
L4B, 1B7 CN
Tel: 905-764-8384
FAX: 905-731-9182
9/96 10M CPY-IG
Printed in U.S.A.