CERBERUS TL-30U System 3 Control Module Instruction Manual

June 9, 2024
CERBERUS

CERBERUS - logo TL-30U System 3 Control Module
Instruction Manual

TL-30U System 3 ™
Control Module

ENGINEER AND ARCHITECT SPECIFICATIONS

  • Precision Timing
  • LED Indicator
  • Delayed Signal Capability
  • Placement Supervised
  • Solid State Logic Circuitry
  •  Listed and ULC Listed
  • NYMEA, CSFM and FM Approved

Description

The Time Limit Module, TL-30U is designed to provide a controlled time interval from 6 seconds to 10 minutes, after which either a signal circuit is activated, (such as a municipal alarm) or a signal circuit is deactivated (such as alarm bells). The module is also capable of repeating the above operational sequence when a subsequent alarm signal is received in a system utilizing the Subsequent Alarm Feature.
The module, which is of solid state circuitry, is normally passive, drawing no power until an alarm signal is received. When this occurs, a binary counter is activated to control  precisely, the length of the desired time limit before continuing the pre-programmed sequence of system operation. This sequence could be for silencing audible alarm devices  so that the system could receive and annunciate subsequent alarms. An alternate use would be the sending of an alarm to municipal headquarters if the alarm source  had not been checked or controlled, or, it could involve the actuation of an extinguishing system.
This time interval is available in two ranges as follow:
a) 6 seconds to 20 seconds
b) 30 seconds to 10 minutes
Standard units are preset for a 5 minute, time-out sequence, but can be changed by field adjustment.
Note: : Underwriters Laboratories Inc. standards require that when time limit cutoffs are used with audible devices, they shall operate no less than 3 minutes and no more than 10 minutes.
The module contains a red LED indicator lamp that is illuminated at the end of the timing period. This lamp will remain on until the module has been reset.
The Model TL-30U module is placement supervised, providing a system trouble signal upon removal from the system.
The unit is Underwriters Laboratories Inc. listed.
Engineer and Architect Specifications
Capability for precise time control of an output signal either by delaying actuation or stopping actuation shall be provided by a Cerberus Piezotronics Time Limit Module, Model TL-30U. This module shall be system interconnected by a ten-wire jumper plug and harness assembly, and shall be operable with the system main control panel.
The time in/time out duration period shall be capable of being set at any precise interval between the time frames of 6 seconds to 20 seconds, and 30 seconds to 10 minutes.  This interval shall be controlled by a solid state 14-stage binary counter contained in the circuitry of the module. At the end of the time interval, a red LED indicator lamp  shall indicate completion of the time cycle, after which a subsequent alarm can be received and processed in an identical manner. The module shall be reset from the main  control panel.
The model TL-30U shall be Underwriters Laboratories, Inc. listed.
Electrical Information
Current Requirement:
Normal — None
Operated — 45 mA

Ordering Information

Model No. Description Shipping Wt.
TL-30U Time Limit Module 1 lb.

Typical Wiring

Programming the TL-30U
There are two jumpers and one potentiometer on the component board used to program the module.

TIME IN/TIME OUT JUMPER* LONG TIME/SHORT TIME JUMPER

Determines whether TL-30U will be time in or time out. Connect  jumper between common and TO or TI.| Determines timing period LT: 30 sec. — 10 min ST:6-20 sec. Connect jumper between  common and LT or ST.

Adjust potentiometer R13 (500K) for the exact time period desired. Cross- zoning may be accomplished without the use of zone operated relays. The two zone outputs are  fed directly into the TL-30U (terminals 1 and 2). After the second zone has activated, the TL-30U will time as programmed.
*Time in denotes delay time period before terminal 3 goes high (+).
NOTES:

  1. When SA-30 or cross zoning are not used, jumper terminal 2 to terminal 1.
  2. All input/output signals not supervised.

CERBERUS TL 30U System 3 Control Module - Typical
Wiring

NOTICE: The use of other than Cerberus Piezotronics detectors and bases with Cerberus Piezotronics control equipment will be considered a misapplication of Cerberus Piezotronics equipment and as such void all warranties either expressed or implied in regard to loss, damage, liabilities and/or service problems.

CERBERUS - logo Cerberus Piezotronics
8 Ridgedale Ave.
Cedar Knolls, NJ 07927
Tel: 201-267-1300
FAX: 201-397-7008
Cerberus Piezotronics
50 East Pearce Street
Richmond Hill, Ontario
L4B, 1B7 CN
Tel: 905-764-8384
FAX: 905-731-9182
10/95 10M CPY-IG
Printed in U.S.A.
firealarmresources.com
October 1995
Supersedes sheet dated 5/94