CERBERUS PYROTRONICS PS-35S Power Supply Owner’s Manual

June 9, 2024
CERBERUS PYROTRONICS

CERBERUS PYROTRONICS PS-35S Power Supply

Description

The Cerberus Pyrotronics Power Supply Model PS-35S is a step-down transformer and bridge designed for use with Control Panel Model CP-35 and to provide power for regulated pre-action releasing service. The units, which are modularized for System 3 enclosure mounting, are of deadfront construction and contain terminal strips, a circuit breaker with a reset switch on the AC input, protection fuses on the DC outputs and a receptacle for jumper plug connection directly into the control Panel Model CP-35. This equipment is approved for operation over the temperature range of 0°C to 49°C.

Operation

The Model PS-35S provides a rectified, full wave 24 VDC output from an input supply of 120 VAC, 50/60 Hz. The input consists of a main power phase and a trouble phase, each separately fused, and a common neutral. The 24 volt full wave output is rated at 10 Amps DC, full load. When the PS-35S is used to power the control panel system, the second output (terminals 5 and 6, rated at 24 VDC 2 Amps, bridge only) is used to power RM-30U/RU modules through a DC- 35S regulator and a TC-30U transfer module for releasing pre-action or deluge valves. This module combination is approved by FM for this application. Surge protection is provided across both the input phases as well as the DC output.

Engineer and Architect Specifications

The power supply for the alarm system shall be a Cerberus Pyrotronics Model PS-35S. This unit shall be Underwriters Laboratories Inc. listed. The unit shall provide a full wave of rectified 24 VDC output rated at 10 Amps full load. The PS-35S shall be capable of powering 100 detection zones (50 ZU-35 Zone Modules and 4 fully loaded Alarm Extender Modules Model AE-30U simultaneously.) The rated output, which shall be completely fused, shall be provided at a plug receptacle. A second output (terminals 5 and 6, rated at 24 VDC 2 Amps bridge only) is used to power modules internally housed and wired within the control unit enclosure. The power supply shall be of a deadfront construction and housed in a steel enclosure compatible with the modularized alarm system. Externally mounted 120 VAC/24 VDC transformers shall not meet the intent of this specification.

  • Multiple Usage
  • Deadfront Construction
  • Modularized
  • FM Approved for Pre-Action and Deluge Sprinklers
  • Listed, ULC Listed

Electrical Ratings

PS-35S Power Requirement: 120 VAC, 50/60Hz, three wire. 3.5A Max

The Model PS-35S with the CP-35 Control Panel occupies space normally taken by 8 modules. The power supply for the CP-35 must be mounted in the upper right- hand position of a System 3 enclosure. This should be considered when sizing the enclosure. Additional power supplies, if required, are mounted adjacent to the modules to be powered by them.

Ordering Information

Typical Wiring

CERBERUS-PYROTRONICS-PS-35S-Power-Supply-2

NOTICE: The use of other than Cerberus Pyrotronics detectors and bases with Cerberus Pyrotronics equipment will be considered a misapplication of Cerberus Pyrotronics equipment and as such voids all warranties either expressed or implied in regard to loss, damage, liabilities and/or service problems

Cerberus Pyrotronics
8 Ridgedale Avenue
Cedar Knolls, NJ 07927
Tel: 201-267-1300
FAX: 201-397-7008

Cerberus Pyrotronics
50 East Pearce Street
Richmond Hill, Ontario
L4B, 1B7 CN
Tel: 905-764-8384
FAX: 905-731-9182

firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CERBERUS PYROTRONICS User Manuals

Related Manuals