INTRODUCTION
The Model PMI-S from Siemens Industry, Inc., is a user interface for the
Siemens E100 system. From the PMI-S the operator can acknowledge events,
control the system notification appliance circuits and reset the system.
Detailed information about the nature and location of events can also be
displayed.
The PMI-S contains the site specific program as developed in Zeus. All system
logic and supervision is provided by the controller in the PMI-S. The PMI-S
contains a ¼ VGA mono-chrome LCD, Touch Screen and LEDs for displaying system
status. An audible sounds when there are unacknowl-edged events on the PMI-S.
The display is surrounded by keys that are used to control the displayed
information and to navigate through these screens. Keys are also provided to
obtain help and to enter into the menu features of the PMI-S. (Refer to Figure
1.) On the back of the PMI-S there are additional diagnostic displays to aid
in system troubleshooting. This is also where the PMI-S address is set and
where the connection is made to Zeus for programming. (Refer to Figure 2.) A
contrast pot is provided on the back of the PMI-S to adjust the LCD for the
best visibility.
DESCRIPTION OF PMI-S DIAGNOSTICS
HNET | LED glows steady when a failure on the HNET network is detected. |
---|---|
XNET | LED glows steady when a failure on the XNET network is detected. |
PMI-DAC | For future use. |
PMI | LED flashes when a main processor failure occures in the PMI. |
ADDRESS SWITCHES | Set to 253 by turning the pointers on each of the three |
dials to 2 – 5 – 3.
OPTIONS| For future use.
STATUS LED| Walking segments light to indicate normal operation. Error code is
displayed if an internal error is detected.
RESET SWITCH| Press to re-initialize the PMI.
CONTRAST POT| Turn to adjust the LCD for the best visibility.
DEBUG PORT| Factory use only.
HNET| HNET connection to laptop PC for network diagnostics.
UPLOAD| Connection to Zeus tool for transferring system configuration data.
NIM-1M| For future use.
INSTALLATION
Remove ELECTRICAL POWER prior to installing the PMI-S in the enclosure. Remove the PMI-S from its anti static bag. Set the three-digit network address using the 10-position rotary switches located on the back of the PMI-S. Set the PMI-S to 253. Make sure that the PMI is configured at this address in the Zeus physical view. Note the location of the contrast pot. Although the PMI-S comes from the factory with the LCD contrast adjusted, this adjustment may not be proper for the viewing angle of the LCD once it is installed in the enclosure. If the contrast appears poor with the system powered, open the inner door and locate the contrast pot on the lower edge of the PMI-S printed circuit board. Adjust this pot until the LCD contrast is acceptable. The PMI-S mounts to the rear of the inner door in the enclosure. Select the location of the PMI-S. It can be mounted either in the center or on the left side of the inner door, when viewed from the outside of the enclosure. Place the PMI-S onto the inner door from the rear, over the four mounting studs in the desired location. Secure the PMI-S to the inner door with the four nuts provided. (Refer to Figure 3.) A 73 inch long 60 wire cable connects the PMI-S to the CC-5. The CC-5 is located in the back of the enclosure on the left hand side. Connect one end of the cable to JP3 on the PMI-S. JP3 is marked with “CC-5” on the PMI-S printed circuit board. Connect the other end of the cable to P1 on the CC-5. (Refer to Figure 4.) Make sure that all cables snap fully into their connectors and close the locking levers over the top of each cable connector. Secure the cable in the back box using cable ties and the tie down points in the enclosure. The cable must have sufficient slack to allow the inner door to open fully without putting stress on the cable.
OPERATION
In the normal standby condition the PMI-S displays the site specific custom message, the time and date, and a synopsis of the system status. The CPU LED will light when the CPU is not working properly or the system is resetting. When an alarm occurs in the system, the display enters the Alarm mode. The event is displayed, the local audible sounds and the appropriate LED blinks. If the event caused notification appliances to sound the LED lights. A reset button is available in the lower right side of the display. If notification appliances were active, two additional buttons appear at the bottom of the screen. These allow the operator to silence or unsilence the notification appliances. When the notification appliances are silenced the LED lights. The system can only be reset with the notification appliances silenced. If more events are present in the system than can be displayed on a single screen a scroll bar appears to the right of the event list. Pressing the up and down navigation buttons to the right of the LCD allows the operator to move through the list. The selected event is highlighted in the display. Pressing the INFO+ button will display a screen showing details relating to the selected event. Other buttons also appear at the bottom of this screen. There is an expanded text message available and a selection to show all of the devices associated with the event that are active. The operator can return to the previous screen by pressing the ESC (-) button, which is adjacent to the INFO+ button. [For more details on PMI operation, refer to the Operating Instructions Siemens E100, Order No.: A24205-A334-B845 (English) or Bedienungsanleitung Siemens E100, Best. Nr.: A24205-A334-A845 (German)..
ELECTRICAL RATINGS
- 24V Back Plane Current 230mA
- Screw Terminal 24V Curren t 0
- 6.2V Back Plane Current 0
- 24V Standby Current 230mA
For CE applications in Siemens E100 systems refer to Installation Instruction
A24205-A334-B844 (English) or A24205-A334-A844 (German). Siemens AG I BT FS
SYS 2003-2011 Siemens Industry, Inc. Florham Park, NJ Siemens Canada Limited,
Brampton, Ontario L6T 5E4 Canada Issued by Siemens AG
I BT FS SYS MCH D-81379 München Delivery subject to availability; right of
technical modifications reserved. P/N 315-035860-3 A24205-A334-B814 (Edition