FLEXIHEAT FH50ECP and FH100ECP Wood Warm Air Heaters Instruction Manual
- June 8, 2024
- Flexiheat
Table of Contents
Wood Warm Air Heaters
FH50ECP and FH100ECP
INSTALLATION INSTRUCTIONS
FH50ECP and FH100ECP Wood Warm Air Heaters
Please read carefully the precautions for use and the instructions for use before any installation andcommissioning.
TECHNICAL CHARACTERISTICS:
| | FH5OECP| FH100ECP
---|---|---|---
Nominal thermal power| kW| 50| 100
TREATED AIR| Flow at + 20°C| m3/ h| 1700| 3,400
Static pressure useful| mm.ca| 5| 5
Thermal jump| ° C| 45| 45
Number of fans| N°| 1| 1
rpm| 900| 900
Electric tension| V| 230| 230
Weight| Kg.| 240| 440
Maximum load (dry wood)| Kg.| 10| 20
Hearth Dimensions (Long, Wide, High)| cm| 83x50x60| 115x70x65
Hatches Dimensions (Long, Wide)| cm| 64×28| 89.2×28
Heating power dry wood = 4000 kcal / kg
• Recommendations
- Carefully read the warnings that appear in the instructions, knowing that they contain important indications relating to the safety of the installations, their use and maintenance.
- Use wood as a priority to ensure good combustion of Heater.
- The installation must be carried out according to the standards in force in the country where it will be used, according to the manufacturer’s instructions, by professionally qualified personnel or by a technical platform approved by the manufacturer. An error during installation can cause damage and risks to people and equipment, for which the manufacturer cannot be held responsible.
- Check the packaging and the integrity of the contents. If in doubt, do not use the device and contact the distributor or the manufacturer.
- Do not leave the packaging elements within the reach of children, as they represent a source of danger.
- Keep the suction grilles free.
- In the event of a breakdown or malfunction of the appliance, unplug it, refraining from any attempt to repair it, and contact your distributor.
- As soon as you decide to stop using the appliance, you must not use parts that could constitute a source of danger.
- This appliance must be used for the use for which it is intended. Any other use will be considered inadequate and, if necessary, dangerous, relieving the manufacturer of responsibility and thereby voiding the manufacturer’s warranty.
- Make sure that these instructions are always included with the device.
- The regulatory protection of the device must be ensured in accordance with the classification standards for the professional premises where it is installed.
If the appliance is installed in a place where there are disabled people and /
or accompanied by children, it must be installed with protections in
accordance with the regulations in force.
Never load more than 10 kg of log wood or briquettes for FH50ECP and 20Kg for
FH100ECP, i.e. 50 and 100 kW.
In the event of overloading: Risk of deformation of the floor crosspieces and
cracks in the brickwork Damage to the exchanger tubes, temperature rise,
general deformation and damage to the device.
1.1 PRINCIPLE OF FOOPERATION:
This hot air generator works with solid vegetable fuels; it is a device whose
operating principle is the production of direct heat through the use of
thermal energy produced by combustion.
Heat exchange is produced when a flow of air generated by a fan is passed
through the internal surfaces of the heat exchanger, without the aid of any
intermediate fluid so called direct exchange. In addition, part of the thermal
energy is produced by the low temperature radiation of the machine.
The gaseous residues resulting from the combustion (fumes), when the heat
exchange is carried out, are expelled outside through the flue gas pipe at a
temperature of approximately 280 ° C at maximum developed power.
The solid residues of gasoline combustion (ash) fall naturally thanks to a
stainless steel grate in an ashtray drawer in the lower part.
This appliance is used for heating industrial environments and meets these
standards. It can also be used for any other application, in this case, refer
to the specific standards.
It cannot be installed in direct contact with explosive agents or in a
flammable environment.
CONSTRUCTION OF THE APPLIANCE:
The heater is made of carbon steel sheet, developed according to European
standards. Easy to access for normal cleaning and maintenance operations. It
is composed of:
To) A rectangular-shaped combustion chamber briquetted by refractory elements.
b) A tilting hatch for loading solid fuels.
vs) A tubular heat exchanger with a large surface area with natural
ventilation fairing.
d) A perforated ash collection drawer with adjustable primary combustion air
intake ruler.
e) A chimney nozzle fitted with a draft key through which the combustion
residues pass to be expelled through the smoke duct outside the heated
enclosure.
-
Ventilation group
The device is equipped with a medium pressure centrifugal fan which allows the connection of a distribution duct. -
Chimney nozzle
The appliance is equipped with a circular outlet of a standard diameter where it is possible to connect and securely fix a metal flue (preferably insulated) to evacuate the gaseous residues resulting from the combustion to the outside. The draft key integrated into the nozzle allows the power to be regulated by limiting the natural depression.
This duct must have the following characteristics:
- Diameter equal to or greater than the nozzle of the device and without section reductions. (Ø 153 mm for FH50ECP and Ø 200 mm for FH100ECP)
- Do not add elbows with more than a 45 ° angle and raise the duct in this case by 1m per 45 ° elbow
- Have an end part of the duct fitted with a cap.
2.1 PACKAGING AND TRANSPORT:
Hot air generators are shipped with plastic bubble wrap. The accessories are
packed separately in cardboard packaging. Transport and unloading must be
carried out with great care to avoid possible damage. Before accepting the
packages, it is advisable to unpack the equipment in the presence of the
carrier in order to ascertain the condition of the goods and therefore to
avoid any dispute.
2.2 INSTALLATION INSTRUCTION:
The position of the wood heaters must be defined by considering the following
indications:
-
Installation protocol
– Position of the device level, stably installed on a slab made for this purpose.
– Provide a safety distance of at least 1 meter from any obstacle around the device.
– Do not obstruct the fan’s suction grilles.
– Check that no obstacle hinders the distribution of hot air.
– Make sure that maintenance and cleaning operations can be carried out easily. -
Electrical connection
This device has been manufactured according to the EEC 73/23 directive and operates under a current of 240V single phase 50Hz. -
Key and draft moderator
– To regulate the draft, it is essential to install a draft moderator on the flue gas pipe
– In order to regulate combustion, a regulation key is integrated on the flue gas nozzle which will limit combustion when the generator is fully loaded and reduce combustion in order to increase autonomy, particularly at night.
The device must be installed in accordance with all standards and laws in
force in the geographical area of use of the device.
2.3 COMBUSTION GAS EVACUATION:
The installed chimney will comply with the regulations relating to its use and
will have a draft regulator. This duct will be insulated as far as possible in
double skin to avoid the dew point. (1m after the discharge nozzle). We offer
an optional STAINLESS STEEL starter kit with buffer to facilitate maintenance
by relocating the duct.
Never horizontal part with 90 ° elbows DRAW
The draft of a chimney is determined by the following formula:
T = H (YA – YB)
T = Draft in mm.ca
H = Height of the vertical chimney in meters.
YA = Specific weight of the outside air in kg / m³.
YB = Specific weight of the combustion gases expelled in kg / m³.
SECTION
The section of the chimney for the two series is determined by the following
formula:
S = 8.61 Q / H½
S = Section of the chimney in cm²
Q = This is the power of the boiler in kW / h. H = The reduced height
expressed in meters.
The reduced height of the chimney is defined by the following formula:
Hr = H – (N. 0.5 + L + R)
Hr = Reduced height
H = Actual height of the chimney.
N = Number of elbows.
L = Horizontal length.
R = Generator back pressure.
R = 1mm up to 50,000 kcal / h.
R = 2mm up to 160,000 kcal / h.
NOTE: These values must be increased by 6% depending on the region for
every 500 meters of elevation above sea level.
DUCT DEPRESSION
During installation, at the time of commissioning, it is recommended to have a
draft measurement called “depression” carried out in order to check the water
column of the chimney’s depression.
This measurement is carried out while hot when the device is at its normal
output after approximately half an hour of operation.
This depression should be 2 mm WC after the pull key.
It is therefore recommended for this result a vertical height of 5m for an
FH50ECP and 6 to 7m for an FH100ECP.
In order to stabilize the draft, it is necessary to install at the outlet of
the Ø 153mm nozzle for FH50ECP and 200mm for FH100ECP, a tee fitted with a
regulator flap.
The draft measurement must be carried out under the shutter, which will allow
the shutter to be balanced during the measurement.
The flue gas pipe must never be reduced to a diameter smaller than that of the
outlet nozzle. However, there is no problem if the duct is of a larger
diameter. In the event of installation on an old masonry duct, it is essential
to pipe the duct.
If you notice after several hours of use that smoke is coming out of the the
sides of the loading hatch closed, the duct does not have enough draft. It
must therefore be enhanced. It is imperative that the duct exceeds at least 50
cm the highest point of the roof called “ridge” and in any case, higher than
50 cm of any obstacle around the duct. (building nearby)
The chimney will be insulated and will never have a horizontal part according
to the regulations in force.
Depending on the regulations in force in the geographical area concerned, it
may be necessary to install particle filtration on the smoke evacuation
network.
2.4 IRREGULARITIES IN OPERATION AND PRECAUTIONS
CAUSES AND SOLUTIONS
In the event of an electrical fault or fan malfunction, first make sure that:
- The power supply is correct.
- There are no voltage variations greater than + 10% or -15%.
- The fuses are in good condition.
- There is no shortage of solid fuel.
NOTE: Any repairs must be carried out by qualified technical personnel
using original spare parts. It is forbidden to open or manipulate the
components of the generator, with the exception of those provided for
maintenance.
** NEVER TURN ON THE GENERATOR WITHOUT CONNECTING THE ELECTRIC NETWORK FAN
NEVER DISCONNECT THE POWER WHEN THE APPLIANCE IS HOT
Since the thermal energy accumulated in the combustion chamber and the heat
exchanger can damage the electric fan unit and the heat exchanger.
** DO NOT TOUCH THE PARTS EXPOSED TO HEAT RADIATION in particular the
loading door, the nozzle and the uninsulated duct.
WARNING :
It is imperative to keep a respectable distance when opening the hatch to
avoid any risk of burns.
**** Any load greater than the maximum load corresponding to the power of the
device, i.e. 10 kg for FH50ECP and 20 kg for FH100ECP, irreparably implies
overheating of the device in the short term, which causes damage:
-
The crack in the refractory brickwork
-
Deformation of the floor cross members which support the INOX floor grid.
This deformation gradually causing the impossibility of opening the ash drawer.
Improper installation of the flue gas can cause the same damage caused by overheating of the lower part of the appliance due to the lack of draft. -
Deterioration of the steel or carbon heat exchanger tubes
-
Perforation of the walls or heat exchanger tubes
-
Deterioration of the high temperature coating
• Ventilation in summer
To obtain ventilation only from the generator, proceed as follows: Switch the
inverter to the summer position.
2.5 MAINTENANCE:
For normal operation and proper aging of the device over time, it is
regulatory that qualified technical personnel carry out, at least once a year
and preferably at the end of the season, annual maintenance operations,
including including the sweeping of the flue. In the event of a claim, the
insurance company will request the annual certificate of chimney sweeping
carried out by a professional.
Any work on the device must be carried out cold.
• Cleaning the exchanger at the end of the season Proceed as follows:
- Unscrew the exchanger / fireplace assembly bolts
- Remove the exchanger
- Clean the outside of the heat exchanger tubes, if necessary by steam washing using a high pressure cleaner.
- Empty and clean the ash drawer
- Vacuum the soot in the combustion chamber, clean the brickwork
- Periodically replace damaged bricks (see spare parts list).
• Maintenance of the flue gas pipe
Disassemble the duct components and carefully sweep the flammable deposit
film.
• Electric fan unit
Blow out the inside of the engine with compressed air.
Use a brush and compressed air to clean the fan blades
2.6 COMMISSIONING AND USE OF THE APPLIANCE:
-
Use
This device is intended for the heating of industrial buildings, or others in compliance with legislation, safety and fire.
It cannot be installed in direct environmental contact with explosive agents (paints, solvents, etc.).
The device must be installed in accordance with all standards and laws in force in the geographical area of use of the device. -
Firing refractory briquetting at first use
When using for the first time, it is essential to carry out the briquetting firing procedure so that it takes on its refractory characteristics.
To do this, during the first commissioning, Connect the fan to the 240V + T electrical network, load the fireplace to 30% of its capacity, i.e.
around 3 to 4 kg with low-density wood, but with rapid combustion of species (wood from pallets, poplars, offcuts, wooden logs …)
After the total combustion of this charge, repeat the operation with 50% of the charge (draft key open to the max.) -
Commissioning after briquetting
– Load the appliance with wood or any other non-polluting solid fuel (for FH50ECP with a maximum of 10kg, for wood, which represents a combustion of 50KW / for FH100ECP with a maximum of 20Kg, for wood, which represents a combustion of 100Kw)
– Connect the fan to the 240V + T electrical network.
– Light the selected wood or solid fuel.
– The fuel load must never exceed the rated power of the heater. Do not start the heater without connecting the fan to the electrical network.
After these 2 operations, the stove can be loaded normally.
Note: If these operations are not carried out, there is a risk of cracking certain elements of the brickwork.
CAUTION: never shock the briquetting at high temperature when filling (risk of cracking the briquetting elements). -
Device shutdown at the end of the season
Disconnect the device and carry out maintenance (Paragraph 9). -
Fuel (concerns FH50ECP)
The calorific value of dry wood is about 10 kg or (4.7 kW to 5.3kW per kg) 50 kW at 45/50° humidity.
The filling for 50 Kw is therefore 10Kg
Each time the wood heater is put into service, it must be lit with a first load of wood in order to obtain active embers
When reloading, it is possible to incorporate chips or chip brick. The compressed chip brick can be used for reloading. It is advisable to incorporate a briquette by validating the total load weight given the high calorific value of the reconstituted briquette.
10Kg of bricks = 50 Kw or 5 Kw per kg of bricks. A standard brick has an
average weight of 1.8 kg, or 9 kW of energy.
2.7 EXPLODED VIEW OF THE UNIT: 2.8 DIMENSIONS:
Model FH50ECP
Model FH100ECP 2.9 DESCRIPTION, CABINET OPERATION (OPTIONAL) AND DIAGRAM
The fan regulation allows the fan to be started up at the set temperature
(i.e. around 30 ° C). As soon as the thermal heating circuit is at this
temperature, the fan will start up (inverter in winter position). When the
appliance cools down, the fan will stop at the set temperature in order to
prevent the circulation of fresh air during the mass heating cycle. 2.10
POSITIONING OF THE ELECTRICAL CABINET AND THE PROBE 2.11 FAN CABLE
CONNECTION DIAGRAM 2.12 DESCRIPTION AND OPERATION OF THE VISUAL
THERMOCONTROLE (OPTION) The visual thermo-control is a thermometer which
allows to control the power produced according to the loading, that is to say
10 kg of wood for the model FH50ECP or 20 kg of wood for the model FH100ECP.
Indeed, at full power, the flue gas temperature is around 270 ° for a
compliant chimney installation (2mm / cc of depression)
Assembly
Position the thermometer in the housing provided for this purpose in the
chimney nozzle
Functioning
As soon as the vegetable fuel is burnt, the flue gas temperature is indicated
on the visual thermal control.
The maximum power can be viewed by the red zone of the thermometer dial at
280°
In the event of overheating, spread the fuel in the fireplace and allow the
temperature of the flue gases to drop below 270°
At 50% power, i.e. around 150 ° C, you can reload the wood heater with fuel to
develop the maximum power, i.e. 5 kg for the FH50ECP or 10 kg for the
FH100ECP, of additional fuel.
www.flexiheatuk.com
01202 822221
Documents / Resources
|
FLEXIHEAT FH50ECP and FH100ECP Wood Warm Air
Heaters
[pdf] Instruction Manual
FH50ECP and FH100ECP Wood Warm Air Heaters, FH50ECP, FH100ECP, FH50ECP Wood
Warm Air Heaters, FH100ECP Wood Warm Air Heaters, Wood Warm Air Heaters, Wood
Warm Heaters, Air Heaters, Heaters
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>