ADEMCO 659EN Line Fault Monitor Instruction Manual

June 9, 2024
Ademco

INSTALLATION
INSTRUCTIONS
No. 659EN LINE FAULT

MONITOR

GENERAL INFORMATION

The No. 659EN Line Fault Monitor is designed for connection across incoming telephone lines on systems using telephone dialers (e.g., Nos. 6012 or 758) or digital communicators (e.g., Nos. 669, 570, 678, 67dUL-3, O73UL-F, 693, 693EN, S94EN), or Control/Communicators (such as Nos. 4150, 4160, 4160-12 or 4180-12). It will cause a signal to be generated if the telephone line between dialer or communicator and the central station is cut or shorted, or if incoming service is otherwise interrupted. The signal can be in the form of sounding the on-premises protective system’s alarm bell (when the system is ON), or the lighting of a trouble indication lamp on an accessory tester such as the No. 664. A built-in delay of approximately 25 seconds prevents false alarms in the event of momentary outages of telephone service.
Two No. 659ENs can also be used to control the selection of a trouble-free telephone line when two telephone lines are connected to the dialer or communicator via a No. 674 Select-A-Line. In the event that one of the lines should fail for any reason, the No. 659EN will cause an alarm signal to be sent to the central station over the functioning line to indicate that a problem has occurred.

OPERATION

The No. 659EN operates from 6 to 14 VDC. This voltage may be taken from the power supply for the dialer or communicator or from a separate power supply.

Definition of Fault:
The No. 659EN will recognize a fault condition when the DC voltage between tip: and ring (normally 48V) is less than 25 volts (approximately) and handset/ communicator current is 10 mA (approximately) or less.
Under certain conditions, some types of handsets (those using electro- mechanical bells) may prevent the voltage between tip and ring from rapidly decreasing to 25 volts after a line is cut. For example, the Type 500 telephone handset, because of its 2 microfarad bell circuit capacitor, will hold the tip-to-ring voltage above 25 volts for about 18 seconds, thus making the line appear to be intact during this period. This time (approximately 18 seconds) will double if two handsets are on line, triple if three are used, etc., before the line eut is detected and the 25 second delay is initiated.
If, however, the communicator is tripped subsequent to the line having been cut, either of the following events will take place:

a. If line seize is used, the handsets will be disconnected by the line seize relay.
b. If line seize is not used, the capacitor will be immediately discharged by the communicator’s internal signaling resistance and the monitor will sense the cut within its normal delay time after the communicator trip.
If it is desired that the monitor function without the extra delay (caused by the bell circuit capacitors used in handsets with electro-mechanical bells),
it is recommended that: ae Electronic telephones which do not contain the bell-ringing capacitors be used, or
b. Some handset bells be disabled, or Ce Some or all of the handsets be disconnected when the system is armed, or
d. A separate phone line without handsets be used for alarm communication only.

Output Relay:
Any fault condition which exists for a nominal 25 seconds will cause the relay to be energized.
The energizing of the relay can, at the option of the installer, be either:
a. Momentary, where the relay will be energized for only about one second and then be turned off. When the fault is cleared, the monitor circuit will automatically reset and be ready for another one-secom energization should a fault reappear. This option is normally used when the contacts of the relay are wired into the protective circuit of the control to sound the alarm.
or
b. Maintained, for as long as the telephone line fault persists. When the fault is cleared,the relay will automatically be de-energized. This option may be used for special applications such as to sound an electronic siren when no alarm control panel is used. If it is – desired to ring a bell, see the Output Relay caution note under SPECIFICATIONS.

Local Latching Indication:
If desired, a No. 664 Digital Communicator Tester can be used with the No. 659EN as a monitor lamp and reset switch to indicate whether the telephone line is, or has been,out of service. After approximately 25 seconds of the No. 659EN’s sensing of a line fault, the LED indicator in the No. 664 will light and remain lit until the line fault has cleared and the No. 664’s switch is depressed. This latching and reset action is independent of the output relay option chosen above.

Logic Level Signal:
This output is for use with the No. 674 Select-A-Line (which permits a dialer, digital communicator or control/communicator to be used with two telephone lines for increased reliability of transmission). Information as to its use is provided with the No. 674.

INSTALLATION

For ease of installation, the No. 659EN includes a housing which allows it to be conveniently mounted in a digital communicator (or other) cabinet. The No. 659EN’s upper edge is provided with a lip that can be slipped over the edge of the cabinet without interfering with the ability of the cabinet’s cover to close and lock. See Diagram 1.

WIRING (See Diagram 1)

  1. Grounds:
    Extend the GREEN FLYING LEAD provided and connect it to an earth ground (a cold water pipe or electrical box can often be used). Proper earth grounding provides protection against externally induced transient voltages in the telephone lines and must be connected to ensure reliable operation of the No. 659EN.

  2. Output Relay Contacts:
    The COM and N.C. terminals (4 and 6) are connected in series with the positive leg of the protective loop of an alarm control. If the contacts are to be connected across a protective loop, use the COM and N.O. terminals (4 and 5). See Diagram 1.
    Note: Upon sensing of a telephone line fault and completion of the built- in delay by the No. 659EN, the output relay’s COM and N.O. contacts will close and its COM and N.C. contacts will open, in accordance with the “Momentary” or “Maintained” Output Option Selected below:
    a. Momentary Output Option (output relay energized for about one second during line fault duration): CUT BLACK JUMPER that protrudes from front of circuit board.
    b. Maintained Output Option (output relay energized for duration of telephone line fault): LEAVE BLACK JUMPER UNCUT that protrudes from front of circuit board.

  3. Local Latching Indication:
    If such indication is desired, attach terminals 1, 2, and 3 of the No. 659EN to the WHITE, BLACK, and RED leads (respectively) of a No. 664% (Pushbutton Tester with Monitor Lamp) located where desired. Usually, the location will be next to the alarm control so that the No. 664’s lamp will be seen, if lit, when the alarm system is being turned ON.

  4. Telephone Line:
    Connect the incoming telephone line pair to terminals 7 and 8, disregarding polarity.

  5. Dialer or Digital Communicator:
    Connect the YELLOW and ORANGE leads of the No. 659EN to the incoming phone line terminals of the dialer or communicator.
    Diagram 1. INSTALLATION AND WIRING

  6. Handsets:
    Follow instructions provided with the dialer or digital communicator.

  7. Logic Level Signal Post:
    Information on the use of this post in connection with telephone line selector units (such as the No. 674 Select-A-Line) is given with the particular unit to be used.

  8. DC Power:
    Connect the RED (positive) and BLACK (negative) leads of the No. 659EN to any 6 to 14 VDC power supply such as: that of the digital communicator or dialer, a standard 6 or 12V lantern battery, or one of Ademco’s Recharge- A-Packs or other 6 or 12VDC power supplies.

SPECIFICATIONS

Physical:
Width: 2 1/2″ ( 6.4 cm)
Height: 6 (15.2 cm)
Depth: 1 1/2″ ( 3.8 cm)
Weight: 8 oz. (220.8 grams )

Power:
Operating Voltages: 6 to 14 VDO (from battery, Recharge-A-Pack or other 6 or 12-VDC rechargeable power Supply.
Current Drain:

  • Standby, Telephone Line Intact: 0.15 mA.
  • Telephone Line Fault, “Maintained” Output Option Selected: 30 mA.
  • Telephone Line Fault, “Momentary” Output Option Selected: 0.15 mA.
    * NOTE: If a No. 664 is used as a remote indicator, an additional 10 mA will flow when the indicator is illuminated.

Phone Line:
sensed Voltage and Current:
The No. 659EN defines a “good” line as one havings
a. a tip-to-ring voltage in excess of about 25 volts.
b. a tip-to-ring voltage less than about 25 volts but having a loop current (tip to-ring) in excess of about 10 mA.
The No. 659EN defines a “bad” line as one having a tip-to-ring voltage of less than about 25 volts and a loop current of less then approximately 10 mA.
Polarity:
Insensitive to phone line polarity.
Input Impedance at Phone Line Terminals: Greater than 10 Megohms between lines.
Impedance between Telephone Lines and Ground or Battery: Greater than 100 Megohms, 1500V breakdown.

Output Relays
SPDT Contacts, 1 amp, 28 VDC maximum
Caution: If it is desired to ring a bell with these contacts, an intermediate relay should be used between the No. 659EN and the bell so that the pulsating bell current does not pass through the No. 659EN and possibly cause interference with the latter’s operation. (The No. 559EN, in compliance with FCC Regulations, incorporates a very high input impedance circuit which can be affected by the bell electrical noise.)

TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular maintenance program to the user as well as acquainting the user with the proper operation and limitations of the alarm system and its component parts. Recommendations must be included for a specific program of frequent testing (at least weekly) to insure the system’s proper operation at all times.

LIMITED WARRANTY

Seller warrants fs products to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 18 months from the date stamp control on the product or for products not having an Ademco date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. Seller’s obligation shall be limited to repairing or replacing, at its option, free of charge for materials or labor, any part which is proved not in compliance with Seller’s specifications or proves defective in materials or workmanship under normal use and service. This warranty 1s void if the product is altered or improperly repaired or serviced by anyone other than Ademco factory service. For warranty service, return product transportation prepaid, to Ademco Factory Service, 165 Eileen Way, Syosset, New York 11791.
THERE ARE NO WARRANTIES. EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR
OTHERWISE, WHICH EXTENDS BEYOND THE DESCRIPTION ON TRE FACE HEREOF. In no case shall Seller be liable to anyone for any consequential or incidental damages for breach of this or any other warranty. expressed or implied, or upon any other basis of liability whatsoever, even if the loss or damage is caused by the Seller’s own negligence or fault.
Seller does not represent that its product may not be compromised or circumvented: that the product will prevent any personal injury or property loss by burglary, robbery, fire, or otherwise, or that the product will in all cases provide adequate warning or protection. Buyer understands that a properly installed and maintained alarm may only reduce the risk of a burglary, robbery, or fire without warning but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or property loss as a result. CONSEQUENTLY,
SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING. However, if Seller is held liable, whether directly or indirectly, for any loss or damage arising under this Limited Warranty or otherwise, regardless of cause or origin, Seller’s maximum liability shalt not, in any case, exceed the purchase
price of the product, which shall be fixed as liquidated damages and not as a penalty, and shall be the complete and exclusive remedy against Seiler. No increase or alteration, written or verbal, in this Limited Warranty is authorized.
This warranty replaces all previous warranties and is the only warranty made by Ademco on this product. No increase or alteration, written or verbal, of the obligation of this warranty, is authorized.
“Ademco” is a registered trademark of Alarm Device Manufacturing Company, Division of Pittway Corp.

P3516-1 6/85
ALARM DEVICE MANUFACTURING CO.
A DIVISION OF PITTWAY CORPORATION 165 Eileen Way, Syosset, New York 11791
Copyright © 1985 PITT WAY CORPORATION

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals