ADEMCO 540 Isolating Relay Module For Fire Mini Modularm Instructions

June 9, 2024
Ademco

540 Isolating Relay Module For Fire Mini Modularm
Instructions

540 Isolating Relay Module For Fire Mini Modularm

,l’he No. 540 Isolating Relay Modulemust be wired between the No. 535 Control Cabinet and the No, 643 Junction Box on all Fire Mini-Modulat-m installations. It should be installed after all fifty lamp terminals plus terminals Xl, X2, X3, X4 and X7 of the junction box have been wired in parallel to like numbered terminals inside the control cabinet. ( See installation instructions supplied with Fire Mini-Modularm systems.) It  should be located in the lowerleft side of the control cabinet.

ADEMCO 540 Isolating Relay Module For Fire Mini Modularm - fig
1

  1. Connect No. 540 Module terminals X3, X4 and X5 to correspondingly marked terminals inside the No. 535 Control Cabinet. Note that terminals X3 and X4 of the control cabinet will now have three wires  ttached to them: one from the No. 540 Module and two from the junction box. Terminal X5 will be connected to the No. 540 by a single wire only.
  2. Connect two wires from terminal 6 of the No. 540 to the terminals marked X5 of the junction box, one wire to each terminal. Spare conductors inside the No. 543 cable  an be’used for this purpose. Note that no direct connection is made between the X5 terminal of the junction box and terminal X5 of the control cabinet.

TROUBLESHOOTING

FIRE MINI-MODUIARM

Before beginning to troubleshoot the Mini-Modularm System:‘

  1. Make sure the No. 644 Power Supply is wired properly. The white lead from the control cabinet should be wired to the “protective circuit +” terminal of the No. 644; the black lead to the “common” termina.1, and the red lead to the “6 volts 4 amps +‘I terminal. Terminals 1, 2 and 3 on the No. 644 MUST be wired to terminals 1, 2, and 3 of the No. 97LT or No. 96M Power Pack. Make sure that the No. 644 Power Supply
  2. is connected to a 24-hour outlet not controlled by a switch.
  3. Make sure that there are no wires “pinched” between the steel plate of ‘the wired panel and the mounting brackets inside the control cabinet. Since there are hundreds of connections behind the wired panel, it is possible that either during mounting or wiring, one of these wires has shorted to the cabinet.
  4. Inspect all solder connections made to each of the sockets on the back of the wired panel. Make certain thatnoneof the wiring tabs touch each other.
  5. Remove the housing of the display panel and inspect all solder connec- tions made to this unit. Also determine that no two solder lugs or com- ponents are shorting out.
  6. Check the wiring to the No. 540 Isolating Relay Module if it has been included with the unit. This module is located in the lower left hand corner of the control cabinet.
    The red, black, green, and white wires coming out from the bottom left hand corner of the wired panel in the control cabinet must be connected to terminals 2, 3, 4 and 6 ,respectively of the No. 540 Module. Detailed information on the wiring of the No. 540 can be found on page 86 of this section.

NOTE :
EARLY PRODUCTION RUNS OF THE MINI-MODULARM DID NOT INCLUDE THE 540.
IF IT IS NECESSARY TO ADD THIS TO YOUR SYSTEM, INSTRUCTIONS ARE SUPPLIED FOR HOOK-UP TO FIRE & BURGLARY MINI-MODULARM SYSTEMS. THEY CAN BE FOUND UNDER NO. 540 ISOLATING RELAY MODULE.

FIRE MINI-MODULARM SYSTEM
TROUBLE :
I. AC PtLOT LAMP NOT LIT.

PROBABLE CAUSE REMEDY

A. AC connection to the No. 644 has been disconnected.
B. Fuse in the No. 644 has burned out.
C. Fuse on chassis of No. 535 has burned out.
D. Lamp in AC pilot liqht assembly has burned out.
E. Control module is not pluqqed in properly.| A. Make’certain that the No. 644 Is connected to a 24 hour outlet.
B. Replace the fuse in the No. 644 with an Ademco No. 90-7 c.5 amp Slo-Blo).
C. Replace fuse with Ademco No. 90-5 (7 amp).
D. Replace lamp with an Ademco No. 765,
E. Since the AC lamp beinq–l-it depends. upon the control module, make certain, that the module is plugged in.

TROUBLE :
2. HORN WILL NOT RESET WHEN RESET BUT-TON BUTTON IS HELD IN. IS PUSHED BUT DOES STOP AS LONG AS RESET

PROBABLE CAUSE REMEDY

Dirty cancel relay contacts inside the pluq-in subscriber module (in older units).| Relay in subscriber-.moduI&must be cleaned. Request return authorization number and  return for repair.

TROUBLE :
3. HORN WILL NOT STOP EVEN THOUGH RESET SWITCH IS HELD DEPRESSED.

PROBABLE CAUSE REMEDY

A. Wire connectinq X2 in the control cabinet to X2 on the display is open.
B. Defective reset button
.
C. Open coil in cancel relay inside subscriber module (in older units).| A. Momentarily short X2 to X4 inside the control cabinet.
If the horn resets, look for an open in the wire from X2 in the control cabinet to X2 on the display.
B. Open the display cabinet and short across the back of the reset button to stop horn. If horn stops,
this indicates defective switch which must be rep I aced.
C. Obtain a return authorira 2 Ion number and return the plug-in subscribers module for repair.

TROUBLE :
4. ALARM CONDITION EXISTS AT CUSTOMER’S PREMISES BUT SIGNAL IS NOT RECEIVED.

PROBABLE CAUSE REMEDY

A. Siqnal i.sxineinq transmitted properIy at contra I instrument located in the protected premi ses.
B. The contacts of the sensitive relay inside the pluq-in subscriber module
are dirty. No. 536 control
C. module is defective.| A. Thorough1 y check t.he customer’s alarm system to make  certain that L a proper siqnal is beinq transmitted on the  telephone lines (reversal of current) durinq an alarm condition. If a No. 145 or No. 147 is being used, make certain that the polarity is correct on terminals I and 2. ‘Relay inside subscriber
B. module must be cleaned. Request return authori- zation  number and return plug-in  subscriberunit for repair.
C. Replace module.

TROUBLE:
5: A PARTICULAR DISPLAY LAMP COMES ON FOR EVERY ALARM SIGNAL RECEIVED AND GOES OUT COMPLETELY WHEN THE RESET BUTTON IS DEPRESSED.

PROBABLE CAUSE REMEDY
Shorted diode in individual sub- scriber module. Obtain a return

authorization num- ber a;l<,return the subscriber module for repair.

TROUBLE :
6. HORN SOUNDS FOR INCOMING ALARM BUT NONE OF THE DISPLAY LAMPS LIGHT.

PROBABLE CAUSE REMEDY

A. Individual lamp for the subscriber module in alarm condition
has burned out.
B. Wire connectinq the control cabi- net to the subscriber
lamp is open.
C. No. 536 Control Module is defective.| A. Usinq the test switch, deterrr,ine which lamp is inoperative and replace
it with an Ademco No. 542 Replacement Lamp.
B. Push the test button and determine which lamp circuit is inoperative.
Check the wiring for that lamp cir- cuit between the display panel and the control cabinet. Make certain, that all connections are proper.
C. Replace Control Module.

TROUBLE:
7. INDIVIDUAL SUBSCRIBER LIGHT COMES ON FOR INCOMING ALARM S IGNAL BUT HORN DOES NOT SOUND.

PROBABLE CAUSE REMEDY

A. Wire connectinq X5 in the control cabinet to X5 in the display is open.
B. Horns inoperative.
C. Short to ground on wire to X2 (reset).| A. Short terminal X5 to terminal X3 in the control cabinet. If horn does not sound, look for open in wire connecting X5 in the control cabinet to X5 in the display panel.
B. If pushing the test button does not sound horn, the horn unit  must be replaced with Ademco No. 375.
C. Momentarily remoye wire from X2 ter- minal. then cause an alarm condition If the indication 7-y is proper, check for qround on wire to X2. Also try removinq al I the other subscriber modules. Try causing another alarm condition. If horn blows, one of the other subscriber modules is defective. See NOTE that follows.

TROUBLE:
8. WHEN USlNG FIRE MINI-MODULARM SYSTEM, COMMON RED LAMP ON LEFT OF DISPLAY f’ANEL DOES NOT COME ON DURING AN ALARM SIGNAL.

A. Lamp is burned out.
B.  Improper subscriber unit has been used.
C. Trouble with printed circuit board in panel.| A. Replace with Ademco No.‘765.
B. For,fire alarm circuits, Ademco No. 641 Subscriber Units must be  sed.
If a standard No. 537 is used, the common red lamp will not light during
an alarm.
C. Contact factory.
---|---

TROUBLE:
9. ON FIRE MINI-MODULARM SYSTEM, COMMON RED AND WHITE LAMPS LOCATED ON THE LEFT HAND SIDE ARE ON CONTINUOUSLY.

PROBABLE CAUSE REMEDY

This indicates a possible prbblem in the logic circui.t inside the display panel.| Contact the factory for additional instructions.

TROUBLE:
1O. PUSHING TEST BUT-TON DOES NOT LIGHT LAMPS OR SOUND HORNS.

PROBABLE CAUSE REMEDY

A. Control module is not plugqed in properly.
B. Open in wire from Xl in control cabinet to Xl in di’splay panel.
C. Test button not operative.| A. Make certain that control module ‘is plugged in correctly.
B. Momentarily short terminal XI to X3 in control cabinet. If test function does not operate, look for open in wire going from Xl ‘in  controi cabinet to Xl in display panel.
C. If short inq across the back of the test button operates the test func- tion, replace the test switch with an Ademco No. 8064.

TROUBLE:
11. ONLY HORN SOUNDS FOR TEST. ,THE DISPLAY LIGHTS DO NOT LIGHT.

PROBABLE CAUSE REMEDY
Contacts of test relay in control module are dirty. Relay inside control

module must be cleaned. Request return
authoriza- tion number and send the contral module back for repair.

PRODUCT INFORMATION ABOUT FIRE MINI-MODULARM

NOTE : The following feature has been added to the No. 640 Fire Mini- Modularm Display panel manufactured after Oct. 15, IY79. A buzzer and diode have been added to supervise the horn reset feature in the mini-modularm plug- in receiving modules. Whenever an alarm is received, a buzzer will sound as long as the reset button on the display panel is held in. Should a failure occur in any module, which would prevent the horn from sounding on a subsequent alarm from any other subscriber, the new buzzer will stay on when the reset button is released. The buzzer will continue to sound until the faulted module is replaced or the source of the alarm is removed.
This supervisory feature can be added to any existing mini-modulann installation. Simply order P3730 (buzzer) and P460 (diode) and install them as shown below.

ADEMCO 540 Isolating Relay Module For Fire Mini Modularm - fig
2

Note : To si lence buzzer, if fault cannot be corrected immediately, .insert an SPST switch (e.g. Ademco No. 258) in series here (remote it to a convenient location). THIS IS NOT A RECOMMENDED PROCEDURE, since you will lose supervision if the switch is left in the open position.

www.PDF-Zoo.com
firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals