Solo100 4 Section Telescopic Fiberglass Pole Instruction Manual
- June 9, 2024
- Solo
Table of Contents
- Instructions
- Solo 100 and Solo 108 Telescopic Poles
- Solo 101 Extension Pole
- Solo 330 Aerosol Dispenser
- Solo A4 Detector Tester
- Solo CO* Aerosol C3
- Solo 200 Universal Removal Tool
- Solo 423/4 Heat Detector Tester*
- Solo 461 Cordless Heat Detector Tester
- Solo 461 Battery Charging Instructions and General Information
- Solo 610 Protective Carrying & Storage Bag
- Solo Series Kits
- Trutest
- Product Chart
- Documents / Resources
Instructions
Solo 100 and Solo 108 Telescopic Poles
- Extendable & non-conductive fibreglass pole
- Designed for use at varying heights – see product chart on page 11
- Accepts Solo 101 extensions and all Solo tools (including Trutest)
Instructions for use
2 OR 4 SECTIONS EXTEND & TWIST TO LOCK BUTTON
INSERT TOOL INTO POLE
Solo 101 Extension Pole
A 1.1m / 3ft 9″ addition to the Solo 100 telescopic pole*, or may be used by itself with the Solo range of tools.
Maintenance
The Solo poles can be cleaned with mild detergent in warm water and a soft,
lint-free cloth. Lubrication is not necessary.
Warning The use of Personal Protection Equipment is recommended when using tools at height.
*maximum of 3 extension poles recommended
Solo 330 Aerosol Dispenser
Instructions for use
A Unscrew and remove retainer cup
B Place aerosol canister into cup
C Replace retainer cup & screw upwards Adjust cup until aerosol activates
and unscrew slightly
D Insert the Solo 330 into Solo pole
Place Solo 330 over detector, ensuring a seal around smoke chamber.
Press upwards slightly to activate aerosol (no more than 1 second burst).
If the detector has not responded in 10 seconds repeat above every 10 seconds. Number of total sprays should not exceed 5.
If the detector fails to activate, check equipment and retest.
If the detector does not activate it will require further investigation.
Maintenance
Excess liquid deposits may be experienced following extended periods of use.
To clean, use a lint free cloth. Wash the cup with a mild detergent in warm
water and dry thoroughly.
- Solo 332 Aerosol Dispenser available for larger detectors
Warning To prevent the possibility of the aerosol discharging while in transit, loosen retainer cup by unscrewing 2 full turns.
Solo A4 Detector Tester
- Designed to be used only in conjunction with Solo 330 (332) dispenser
- Does not leave residue when used correctly with Solo 330 (332) Dispenser
- Activates detectors quickly
- Dissipates rapidly, enabling the detector to be quickly reset after successful activation
- Dispenser conserves aerosol, controls usage and reduces possibility of misuse
- Not using the recommended aerosol can cause problems and detector damage
Warning
Read CAUTION and Instructions before use.
Aerosols are pressurised containers.
Do not pierce, incinerate or expose to temperatures above 120°F/50°C, even
when empty.
Keep away from sources of heat (including sunlight).
Wear Personal Protection Equipment appropriate to the task and the
environment.
Material Safety Data Sheets available on request or online at
www.noclimb.com
Solo CO* Aerosol C3
- Suitable for use on CO Fire Detectors
- Designed for use in Solo 330(332) Dispenser
- See Solo 330(332) Instructions for use
Warning
Solo CO uses CO in a sufficiently low concentration to be of minimal risk when
used as directed.
CO is colourless and odourless and may be harmful.
Read CAUTION and instructions before use.
Solo 200 Universal Removal Tool
- Suitable for wide range of detector makes and sizes
- Adjustable colour coded tri-grips rotate to fit different sized detectors
- Universal joint ensures tool remains parallel with ceiling while in use
Adjusting the Tri-grips
PULL AND TWIST
Yellow 64 – 76mm / 2.5 – 3.0in diameter
Blue 86 – 98mm / 3.0 – 3.85in diameter
Red 98 – 112mm / 3.85 – 4.4in diameter
Red & Yellow 74 -93mm / 2.91- 3.66in diameter
Yellow & Blue 75 – 87mm / 2.95 – 3.43in diameter
Blue & Red 92 -105mm / 3.6- 4.13in diameter
Instructions for use
LOCATE LOWER BUTTON FOR DETECTORS AT ANGLES
LOCATE UPPER BUTTON FOR STANDARD FITTED DETECTORS
GRIP DETECTOR
TWIST AND PULL DOWN
Solo 423/4 Heat Detector Tester*
Instructions for use
ATTACH POWER CABLE & IF REQUIRED, ADD OPTIONAL EXTENSION CABLE
OPTIONAL EXTENSION CABLE
SECURE CLIP
INSERT 423/4 INTO POLE
CONNECT TO POWER AND PRESS ON SWITCH
PLACE OVER DETECTOR
- If detector does not activate within 1 minute it may be faulty
- Available in 110v and 230v versions
- Fitted with a thermal cut-out protection system
WARNING
DO NOT TOUCH METAL GRILL
DO NOT BLOCK AIR VENTS
NO USER SERVICABLE PARTS
Solo 461 Cordless Heat Detector Tester
Instructions for use
Insert a charged Battery Baton into tool & pole
Press the red switch to turn on LED illuminates green Flash at slow rate indicates normal STANDBY mode.
Position the latch & place over detector
- Tool will automatically start testing when infra-red beam in cup is broken
- Green LED will flash faster
- Hold in place until the alarm is activated*
- When the detector alarms, remove the tool from the detector
- It will revert to standby mode (slow flashing green LED) and the internal blower will cool the heating element for a few seconds
(*If the detector fails to activate it may be faulty. Insert a replacement detector and test again)
Notes
LED flashing red=warning battery nearly discharged – Normal
testing can continue
LED constantly red=battery fully discharged or error –
Testing cannot continue
LED flashing red/green=Tool automatically terminated test – Time exceeded
120 sec
After testing, switch off at red switch to preserve battery life
Useful Tips:
- Tool features an automatic power-saving feature, which will turn it off after five minutes if not used
- Only use with Solo™ Battery Baton™ and only charge the Battery Baton™ with the Solo™ Charger (see Page 9 for charging instructions)
- It is normal for the Battery Baton™ to get slightly warm during use
- Never block the ventilation hole in the side of the cup, which ensures correct airflow
Solo 461 Battery Charging Instructions and General Information
-
Connect charger to power outlet or lighter socket in vehicle using mains lead supplied or the umbilical DC connecting lead
-
Power LED will illuminate
-
Connect battery to charger
-
Fast Charge LED will illuminate
-
When battery is fully charged, fast charge LED will extinguish
-
Trickle charge LED will illuminate
-
Ideally fully discharge in normal use before recharge
-
International power outlet cables available from your supplier
Solo 610 Protective Carrying & Storage Bag
A bag is recommended for use both to carry and store the Solo equipment, and also to protect it from damage.
- Manufactured from woven polyester with PVC coating
- Reinforced to withstand wear and tear
- Specially designed compartments to take full range of products
- Separate pole bag included
- Convenient size and shape for storage and carrying
Solo Series Kits
- Most versatile and cost effective method of purchasing Solo tools
- Convenient and economical solution for professional detector testing
Trutest
Smoke detector sensitivity tester
- One genuine test
- Truly portable
- Instant result display
Product Chart
*not available in North America
SDi
1345 Campus Parkway
Neptune, NJ 07753-6815
U.S.A.
Tel: 732-751-9266
Fax: 732-751-9241
Email: sales@sdifire.com
Web: www.sdifire.com
For after sales service and any other information,
please call our customer service team on U.S.A.
732-751-9266
LI32091/1
Documents / Resources
| SOLO
Solo100 4 Section Telescopic Fiberglass
Pole
[pdf] Instruction Manual
Solo100 4 Section Telescopic Fiberglass Pole, Solo100, 4 Section Telescopic
Fiberglass Pole, Telescopic Fiberglass Pole, Fiberglass Pole, Pole
---|---
References
- Fire Alarm Resources | Download fire alarm documents
- Heat and Smoke Detector Testing Equipment | Detector Testers
- Home - SDi Fire