Description
Mircom’s FA-260 Series Remote Annunciators are designed to provide LED
annunication. The remote annunciators consist of the RTI-265 Remote
Trouble Indicator and the RAM-265 Remote LED Annunciator.
The RTI-265 Remote Trouble Indicator provides remote trouble annunciation for
the FA-260 Series fi re alarm control panels. The RTI-265 is equipped with an
AC On LED, Common Trouble LED and a Trouble Silence push button. The Remote
Trouble Indicator mounts in a single gang outlet box.
The RAM-265 Remote LED annunciator provides remote alarm and trouble
annunciation for the FA-260 Series fi re alarm control panels. The RAM-265 is
equipped with an AC On LED, Common Trouble LED, a Trouble Silence push button
and fi ve alarm and supervisory LED/zones. The Remote LED Annunciator mounts
in a double gang outlet box.
A maximum of four RTI-265 and four RAM-265 units can be connected to each
FA-260 Series fi re alarm control panel.
Features
- Green AC ON indicator
- Yellow Common Trouble indicator
- Trouble Silence pushbutton
- Lamp Test function
RTI-265 Remote Trouble Indicator
- Single gang mounting
- Alarm current: 25 mA max.
- Dimensions: 2¾” x 4½” (70 mm x 115 mm)
RAM-265 Remote LED Annunciator
- Alarm current: 40 mA max.
- Double gang mounting
- Dimensions: 4½ x 4½” (115 mm x 115 mm)
- Five Alarm & Supervisiory LED/Zones
Operation
The AC and Trouble LEDs on the remote units follow the control panel AC and
Trouble LEDs. Pressing the
Trouble Silence switch at the panel or at any remote unit will silence the
trouble buzzer at the panel and all remote units.
Zone indicators on the RAM-265 Remote LED Annunciator follow the zone
indicators of the control panel. The red LED will operate if the panel zone is
programmed for ‘ALARM’ and the yellow LED will operate if the panel zone is
programmed for ‘SUPERVISORY’.
The Lamp Test is initiated by pressing and holding the Trouble Silence push
button for ½ second. The LEDs will fl ash until the button is released.
Typical Wiring Diagram
Ordering Information
- Model Description
- RTI-265 Remote Trouble Indicator
- RAM-265 Five Zone Remote Annunciator
NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in
prices, colours, materials, components, equipment, specifications and models
and also to discontinue models.
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: 905-660-4655
Fax: 905-660-4113
U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: 888-660-4655
Fax Toll Free: 888-660-4113
Web page: http://www.mircom.com
Email: mail@mircom.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>