Low Voltage High/Low/Off PIR Fixture Integrated Outdoor Sensor
Catalog Number: FSP-201
Installation Instructions
DESCRIPTION AND OPERATION
The FSP-201 is a motion sensor that dims lighting from high to low based on
movement. This slim, low-profile sensor is designed for installation inside
the bottom of a light fixture body. The PIR lens module connects to the
FSP-201 through a 1.30” diameter hole in the bottom of the fixture.
The sensors use passive infrared (PIR) sensing technology that reacts to
changes in infrared energy (moving body heat) within the coverage area. Once
the sensor stops detecting movement and the time delay elapses, lights will go
from high to low mode and eventually to an OFF position if it is desired.
Sensors must directly “see” motion of a person or moving object to detect
them, therefore careful consideration must be given to sensor luminaire
placement and lens selection. Avoid placing the sensor where obstructions may
block the sensor’s line of sight.
The FSP-201 operates at 12–32 VDC. It is designed to be installed in indoor
and outdoor environments.
Once powering the device up, the FSP-201 will use factory default parameters to operate. If adjustments are needed, Wattstopper FSIR-100 Wireless IR Configuration Tool must be used.
SPECIFICATIONS
Voltage ………………………………………………………………12–32 VDC
Current Consumption
Normal Operation …………………………………………………. 15mA
IR Programming …………………………………………………… 45mA
Wiring Terminals
Primary Voltage ……………………………………. +VDC, Com, Ctrl
Control Output ……………………………………. 100 mA maximum
Dimming Voltage ………..Dim + (purple), Dim – (pink), Ground
Use Solid or Tinned Stranded Copper Conductor……. 18AWG–20AWG
Operating Temperature ……………….-40°F (-40°C) to 176°F (80°C)
Tightening Nut Torque ………………………………………….25–30 in-lbs
Dimensions
Collar ………………………………………..1.30” diameter (33.0mm)
Collar height ……………………………………………0.64” (16.3mm)
Body ………1.38” x 3.8” x 0.9” (35.1mm x 96.5mm x 22.9mm)
Weight ……………………………………………………………… 2.4 oz (70 g)
Coverage
FSP-L2 Lens @ 8’ height ………………………up to 44’ diameter
FSP-L3 Lens @ 20’ height …………………….up to 40’ diameter
FSP-L7 Lens @ 40’ height …………………..up to 100’ diameter
Adjustments and Features
High Mode ……………………………………………………. 0 V – 10 V
Low Mode ………………………………………. . . . . 0 V – 9.8 V, Off
Time Delay …………………………… 30 seconds, 1 min – 30 min
Cut Off ………………………. Disable, 1 min – 59 min ,1 hr – 5 hr
Sensitivity ……………………….. On-Fix, Off-Fix, Low, Med, Max
Hold Off Setpoint …………………………. Auto, Disable, 1–250 fc
Ramp Up ……………………………………. Disable, 1 sec – 60 sec
Fade Down …………………………………. Disable, 1 sec – 60 sec
Photocell Setpoint for On/Off ………………… Disable, 1–250 fc
Factory Defaults
High Mode ……………………………………………………………..10 V
Low Mode ……………………………………………………………….1 V
Time Delay ………………………………………………………….. 5 min
Cut Off …………………………………………………………………… 1 hr
Sensitivity…………………………………………………………….. Max
Hold Off Setpoint ………………………………………………. Disable
Ramp Up ………………………………………………………….. Disable
Fade Down ……………………………………………………….. Disable
Photocell Setpoint for On/Off ………………………………. Disable
OPEN DEVICE for installation in a Listed Enclosure per Installation
Instructions.
INSTALLATION
-
Determine an appropriate mounting location inside the light fixture minimizing the electric light contribution to the sensor’s photocell.
Allow a minimum distance of 0.2” (5.1mm) from the wiring end of the sensor to the wall of the fixture. -
Drill a hole 1.30” (33.0mm) in diameter through the sheet metal in the bottom of the fixture.
-
Add the rubber gasket to the threaded collar, and install the sensor face down, parallel to the mounting surface. Ensure the rubber gasket touches the inside surface of the fixture. Install the plastic nut (or optional collar) securely against the fixture to a torque of 25–30 in-lbs to ensure IP rating is maintained.
-
Align the locking features between the sensor and lens module and push the lens module forward until the o-ring seals firmly. Turn the lens module clockwise to ensure that it locks in place.
-
Connect wires as shown in the wiring diagram.
-
Restore power from the circuit breaker.
NOTE: An optional collar can be installed in place of the tightening nut. See the Ordering Information table on page 4 for details.
WARNING: TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE WIRING.
NOTE: The Outside Fixture Wall thickness should be no greater than 0.125” (3.18mm) for optimal sensor mounting and security.
LENS OPTIONS
Several lenses are available for use with the FSP-201. Lenses give coverage at
mounting heights between 8’–40’ for applications such as offices, warehouses,
and outdoor use. Density and range of the coverage is determined by the type
of lens and mounting height.
A lens with shroud option is also available. The shroud blocks light coming
from the fixture, to prevent interference with the photocell function of the
sensor. Lens modules are IP-66 rated when combined with an FSP-201 sensor
mounted to an IP-66 rated outdoor fixture. See the FSP-Lx Coverage Guide for
more information.
USING THE FSIR-100 CONFIGURATION TOOL
The configuration process establishes the appropriate parameters for the
FSP-201 operation. This is done through the FSIR-100 Wireless IR Configuration
Tool. If no configuration steps are taken, the sensor will use its default
parameter values. Use of the FSIR-100 is highly recommended for ease of
troubleshooting, and especially when the FSP-201 is mounted in a high
location.
The FSIR-100 is a handheld tool for changing the defaults and testing the
FSP-201.It provides wireless access to the FSP-201 sensors for parameter
changes and testing. The FSIR-100 display shows menus and prompts to lead you
through each process. The navigation pad provides a simple way to navigate
through the customization fields.
Within a certain mounting height of the sensor, the FSIR-100 allows
modification of the system without requiring ladders or tools, simply with a
touch of a few buttons.
OUTDOORS—USE AT THE EXPOSED SENSOR COLLAR PART ONLY WHEN INSTALLED AT THE SPECIFIC LOCATION PER INSTALLATION INSTRUCTIONS WITH A LISTED OUTDOOR ENCLOSURE.
WIRING
|
---|---
NOTE: The FSP-201 must be grounded to ensure signal integrity, not for
safety ground.| NOTE: Per UL, the 0-10V negative dimming wire color has
been changed from gray to pink.
BATTERIES
The FSIR-100 operates on three standard 1.5V AAA Alkaline batteries or three
rechargeable AAA NiMH batteries.
The battery status displays in the upper right corner of the display. Three
bars next to BAT= indicates a full battery charge. A warning appears on the
display when the battery level falls below a minimum acceptable level. To
conserve battery power, the FSIR-100 automatically shuts off 10 minutes after
the last key press.
If communication is not successful, move closer to the sensor (if possible).
If still not successful, there may be too much IR interference from other
sources. Programming the unit at night when there is no daylight available may
be the only way to communicate with the sensor.
NAVIGATION
Navigate from one field to another using (up) or (down) arrow keys. The
active field is indicated by flashing (alternates) between yellow text on
black background and black text on yellow background.
Once active, use the Select button to move to a menu or function within the
active field. Value fields are used to adjust parameter settings. They are
shown in “less-than/greater-than” symbols:
Moving away from the value field overwrites the original value. The Home
button takes you to the main menu. The Back button can be thought of as an
undo function.
It takes you back one screen. Changes that were in process prior to pressing
the key are lost.
IR COMMUNICATION
IR communication can be affected by the mounting height of the sensor and high
ambient lighting such as direct daylight or electric light such as
floodlights, fluorescent lamps, LED’s and some halogen.
When trying to communicate with the FSP-201, be sure to be positioned under
the sensor without any obstructions. Every time the commissionng tool
establishes communication with the FSP-201, the controlled load will cycle.
* Distance may vary depending on the lighting environment
TROUBLESHOOTING
Lights will not go to High Mode:
- Check all wire connections and verify the dimming wires are tightly secured.
- Make sure that the sensor is not obstructed.
- Check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor lens to simulate darkness in the room. If the lights come ON, the setpoint needs to be adjusted. If set for minimum, more than 1 fc at the sensor of ambient light will cause the lights to be held OFF. See the new settings section for instructions.
- If lights still do not turn ON, call 800.879.8585 for technical support.
Lights will not go into Low Mode:
- The time delay can be set from a minimum of 30 seconds to a maximum of 30 minutes. Ensure that the time delay is set to the desired delay and that there is no movement within the sensor’s view for that time period.
- To quickly test the unit operation, enable test mode and move out of the sensor’s view. Lights should fade to low mode after 5 seconds.
- If lights still do not fade to Low Mode, call 800.879.8585 for technical support.
Lights will not turn OFF:
-
Cut Off time may be set to “Disable.”
-
Ensure that the Cut Off is set to the desired time and that there is no movement within the sensor’s view for that time period when the lights are in Low Mode.
-
To quickly test the unit’s operation, enable test mode and move out of the sensor’s view. Lights should fade to low mode after 5 seconds and then turn OFF (if cut off is enabled) after 10 sec.
-
If lights still do not turn OFF, call 800.879.8585 for technical support
False Triggering may occur if the sensor is exposed to high ambient temperature conditions and the unit is set to maximum sensitivity for PIR detection. -
If this occurs, reduce the PIR sensitivity setting from maximum to a medium point and re-check unit operation.
-
If experiencing false triggering during fade down/Off, try increasing the fade time.
Lights do not turn ON:
Check for blinking red LED. If the LED blinks with long pulses, as opposed to
short pulses, the sensor has reached its Hold Off setpoint or Photocell Light
Level setpoint.
Lights suddenly turn off and will not come back on:
Check for blinking red LED. If the LED blinks with long pulses, as opposed to
short pulses, the sensor has reached its Hold Off setpoint or Photocell Light
Level setpoint.
There is no IR communication:
Perform a power cycle on the FSP-201.
OPERATION DURING POWER-UP
During the sensor warm-up period, which can last up to 5 seconds after initial power-up (or after a lengthy power outage), the load will remain ON until the selected time delay expires.
ORDERING INFORMATION
Catalog # | Description |
---|---|
FSP-201 | Digital High/Low PIR Fixture Integrated Sensor |
FSIR-100 | Configuration Tool |
FSP-L2 | 360° lens, up to 44′ diameter at 8′ height |
FSP-L2-S | 360° lens, up to 44′ diameter at 8′ height, with shroud |
FSP-L3 | 360° lens, up to 40′ diameter at 20′ height |
FSP-L3-S | 360° lens, up to 40′ diameter at 20′ height, with shroud |
FSP-L7 | 360° lens, up to 100′ diameter at 40′ height |
FSP-L7-S | 360° lens, up to 100′ diameter at 40′ height, with shroud |
FSP-C1 | Small collar, for use with FSP-L2 and FSP-L3 lenses |
FSP-C2 | Large collar, for use with FSP-L7 lens |
BZ-50 | Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent |
BZ-150 | Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent, with |
Hold-On and Hold-Off capability
BZ-200| Power Pack: 120/277VAC, 50/60 Hz, 20A
Ballast/ELV/MLV/Incandescent/LED, 16A, E-Ballast/CFUPIug Load
BZ-250| Power Pack: 120/277VAC, 50/60 Hz, 20A,
Ballast/ELV/MLV/Incandescent/LED, 16A E-Ballast/CFUPIug Load, with Hold-On
/Hold-Off capability
BZ-250-347| Power Pack: 120/347VAC, 50/60 Hz, 16A
Ballast/ELV/MLV/Incandescent/LED/ E-Ballast/CFL, 15A Plug Load, with Hold-On
/Hold-Off capability
Sensor is White.
No. 23937 – 06/22 rev.7
© Copyright 2022 Legrand All Rights Reserved.