POTTER RA-7630-RA-7692 Annunciators Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER RA-7630-RA-7692 Annunciators
RA-7630
Feature
- Both Annunciator and Programmer
- 32 Character LCD Display
- Power On LED
- Backlit key pad
- Passcode protection or key operated
- Simplistic wiring connections
- User menu
- Zone messages
Description
The RA-7630 LCD Annunicator offers a 32-character full text LCD readout that
displays system events and menu prompts, making it efficient and easy-to-use.
The backbox and trim frame provide an attractive installation. The keypad can
either be flush-mounted or surface-mounted. The RA-7630 Fire Command Center has
a factory installed keyswitch that enables the four function buttons—Alarm
Silence, System Reset,
Stock number: 3003007
System Test, and Fire Drill. The user can also access these four functions and
many more through the User Menu by entering a valid user code. An internal
diagnostics program lets installers and service technicians test the operation
of the keypad at any time without disabling the system.
RA-7692
Feature
- Green LED for “Power On”
- 5 Red Alarm LED’s
- 5 Amber Trouble LED’s
- Mounts on door of cabinet or remotely
- Simplistic wiring connections
- Internal buzzer
- Trouble LED for Communication failure or Phone line problem.
Description
The RA-7692 keypad annunciator provides LED notification of the system status
for the PFC-7500 series communicators. The panel has five sets of LEDs to
indicate alarm and trouble conditions. In addition, the panel has a Power ON
LED and a Trouble LED that will indicate a communication and phone line
failure. There is a piezo sounder that will activate momentarily anytime a key
is pressed, sounds intermittently during a trouble condition and sounds steady
when an alarm condition is present.
Stock number: 3003002
The keypad is powered directly from the PFC-7500 series panel. The keypad has
a wire harness that readily connects to the panel. The keypad efficiently
operates on 30mA and up to 500mA worth of the RA-7692 can be connected to a
single panel. The keypad has a removable back for ease in mounting.